Case Study on Fault Analysis Using PMU

Similar documents
Performance Evaluation and Review of System Protection Scheme Design with the help of Synchrophasor Measurements

URTDSM Initiative in India and Controlled Islanding using PMU Measurements

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

PMU-Based Power System Real-Time Stability Monitoring. Chen-Ching Liu Boeing Distinguished Professor Director, ESI Center

Optimal PMU Placement

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

Adaptive under frequency load shedding using synchrophasor measurement

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2015

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Reliability of Bulk Power Systems (cont d)

Role of Synchronized Measurements In Operation of Smart Grids

7. Transient stability

PMU Data Based Post Disturbance Analysis for a Large Grid Using Wavelets and Lyapunov Exponent

'l:l1w m:q;n: government of India. ~~gtf'~ Central Electricity Authority. ~m~~

A STATIC AND DYNAMIC TECHNIQUE CONTINGENCY RANKING ANALYSIS IN VOLTAGE STABILITY ASSESSMENT

Determination of Fault Location in Shunt Capacitor Bank through Compensated Neutral Current

POWER SYSTEM STABILITY AND CONTROL

VKES. Contents. Page 2 No 213, 13th Main RBI Layout JP Nagar 7th Phase, Bangalore Vidyuth Kanti Engineering Services

ECE 422/522 Power System Operations & Planning/ Power Systems Analysis II 3 Load Modeling

Identification and Classification of High Impedance Faults using Wavelet Multiresolution Analysis

New Method of Capacitors Failure Detection and Location in Shunt Capacitor Banks

Cascading Outages in Power Systems. Rui Yao

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

ECE 585 Power System Stability

Fault Calculation Methods

EE 451 Power System Stability

By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

Multiple Swing Out-of-Step Relaying

CÁTEDRA ENDESA DE LA UNIVERSIDAD DE SEVILLA

Real Time Phasor Data Processing using Complex Number Analysis Methods R.A. DE CALLAFON 1, C.H. WELLS 2 USA

A Lyapunov Exponent based Method for Online Transient Stability Assessment

PDQ Tracker High Level Requirements

Chapter 8: Unsymmetrical Faults

Failure Analysis of Medium Voltage Capacitor Banks: The Egyptian Experience

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Transmission and Dispatching Operations Manual

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

Digital Power System Protection

Identification of Power Quality Disturbances in a Three- Phase Induction Motor using Fuzzy Logic

An Iterative Technique for Instrument Transformer Calibration and Line Parameter Estimation with Synchrophasor Measurements

ALPS. Advanced Line Protection System

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR)

Simulating a Power System

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

Peak Reliability Delivering near real-time phase angle deltas using Inter-Control Center Communication Protocol (ICCP)

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

Cyber-Physical Intrusion Detection Incorporating μpmu Measurements in Automated Distribution Systems

INSTRUCTION MANUAL FOR MM10 Relay

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

Enterprise GIS to Support ADMS ESRI GeoConx EGUG 2016 Parag Parikh

Fine Tuning Of State Estimator Using Phasor Values From Pmu s

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

URD Cable Fault Prediction Model

THIRD GENERATION SYSTEM PROTECTION SCHEME PROJECT FOR ZEYA HYDRO POWER PLANT

Impedance relay and protection assemblies

Superconducting Fault Current Limiter in DC Systems with MLI Fed to IM

INDUCTION MOTOR TORQUE DURING FAST BUS TRANSFERS

OUT-OF-STEP DETECTION BASED ON ZUBOV S APPROXIMATION BOUNDARY METHOD

EE Branch GATE Paper 2010

Analysis of Very Fast Transients in EHV Gas Insulated Substations

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

Adaptive Distance Relaying Scheme for Power Swing Tripping Prevention

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

ABSTRACT. residential Photovoltaic (PV) systems. The investigation is done on both conventional and

Figure 1-44: 4-Wire Wye PT Configurations

Modeling and Simulation of Air Insulated and Gas Insulated Substations

An improved voltage-collapse protection algorithm based on local phasors

NEW DESIGN OF GROUND FAULT PROTECTION

Enhanced Fault Location Method for Shunt Capacitor Banks

MPR500 Motor Protection Relay User's Guide

Secured Busbar Differential Protection Using A Computationally Efficient Dot Product Technique

Test Case: Power System Voltage Stability

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

PREDICTION OF TEMPERATURE VARIATIONS FOR INDUSTRIAL BUS DUCT SYSTEM UNDER FORCED CONVECTION COOLING WITH VARIOUS ASPECT RATIOS USING MATLAB

Tab 18 - Apparent Power, Active Power, Reactive Power Distribution Systems Engineering - Course , Siemens Industry Inc., all rights reserved

Study of Transient Behaviour of the Capacitor Voltage Transformer

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 26, NO. 2, MAY

EE5250 TERM PROJECT. Report by: Akarsh Sheilendranath

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

CHAPTER 3 INFLUENCE OF STATOR SLOT-SHAPE ON THE ENERGY CONSERVATION ASSOCIATED WITH THE SUBMERSIBLE INDUCTION MOTORS

EN50160 Power Analysis Report PowerCET Corporation Santa Clara, CA

Faults on Electrical System. A Research

WIDE AREA CONTROL THROUGH AGGREGATION OF POWER SYSTEMS

About the Author: Abstract:

The Effect of the Harmonics, the Fault Location and the Fault Resistance on the Performance of the Impedance-Type Distance Relay

Transmission and Dispatching Operations Manual

Trajectory Sensitivity Analysis as a Means of Performing Dynamic Load Sensitivity Studies in Power System Planning

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

Transcription:

Case Study on Fault Analysis Using PMU Prithwish Mukhopadhyay General Manager, WRLDC prithwish.mukhopadhyay@posoco.in Abhimanyu Gartia Deputy General Manager, WRLDC agartia@posoco.in Pushpa Seshadri Chief Manager, WRLDC pushpa_seshadri@posoco.in Rajkumar Anumasula Senior Engineer, WRLDC rajkumar@posoco.in Chandan Kumar Engineer, WRLDC chandan.wrldc@posoco.in Sunil Patil Engineer, WRLDC skpatil@posoco.in Abstract Synchrophasors are used extensively in Indian Grid to detect and analyze faults occurring in the system. This paper majorly discusses the case studies of power system faults that occurred in the Indian grid and its identification and classification using data obtained from Synchrophasors. The types of faults identified include symmetrical and unsymmetrical faults in power system. Further in case of single phase to ground faults, the successful, unsuccessful and non - operation of autoreclosure has been verified. Data from Phasor measurement units (PMUs) helped in identifying the fault recovery time and operation of autoreclosure and provided a strong tool for monitoring the status of the protection system in the grid. A comparative analysis of the disturbance recorder files and the synchrophasor data has also been discussed in this paper. The comparative analysis is used for validation of the DR and Synchrophasor data. This paper has led to the development of disturbance analysis tool for fault analysis using both DR and Synchrophasor data which will ease the system operator decision making ability while taking decision during a contingency in the system. Index Terms Synchrophasor, Faults, Autoreclosure, Indian grid, Disturbance recorder. I. INTRODUCTION Power system operation in India is complex due to disparity in geographical distribution of resources and loads, network complexity with rapid changes in network configuration and increasing combination of UHV, EHV, HVDC lines and FACTS devices in the system. Synchrophasor measurement units also known as Phasor measurement units (PMUs) have become a very effective tool for system monitoring and analysis. The Indian Grid is a large synchronous grid which constitutes of Eastern, Northern, North-Eastern, Southern and Western grids. Synchrophasor measurement units have been deployed in each regional grid under the pilot projects for monitoring and development of analytics which will help in system operation [1-2]. This has proved to be a boon for understanding the behavior of Indian power system. The high resolution data obtained from PMUs (25 samples/sec) with accurate time stamping provides a continuous snapshot of the system. Among the various applications explored from this technology, fault analysis is used extensively for understanding the sequence of events and also for strengthening protection schemes. It has helped in post facto analysis and real time detection of faults occurring in the grid. In the Western regional grid,,pmus are placed strategically covering all types of buses like generator buses, intermediate pooling stations, load centers, HVDC substations etc. [2]. The potential transformer (PT) of the Bus and current transformer (CT) of the feeders have been used as analog inputs to the PMUs. Prior to Synchrophasor technology implementation in India, the identification, detection and classification of fault was confirmed from the Disturbance recorder (DR) files, Sequence of events (SOE) from the Relays and Sub-station SCADA. Obtaining these details from various substations resulted in delayed analysis and information about the power system phenomenon. With the PMU data available at control centers, the fault can be detected identified and classified in real time by observing the trends in various parameters of the system. This has saved a lot of time for analysis as the nature and type of fault can be confirmed at the control center itself although the DR and SOE are still used for its confirmation. This paper is focused on the fault analysis of EHV transmission lines and bus bar, their characterization using synchrophasor and their validation using disturbance recorder data. Section II illustrates the single phase fault in the Indian power system followed by the Sections III and IV where phase to phase and three phase fault have been discussed. Section V discusses the validation of observations from Synchrophasor data with DR for power system. Section VI concludes the paper. II. SINGLE PHASE TO GROUND FAULT Single phase to ground fault is the most common type of fault in power system. Such faults are very common in 978-1-4799-5141-3/14/$31. @ 214 IEEE

transmission lines and can be either temporary/transient or permanent in nature. The ground path provided by trees, fogs etc. are temporary in nature and these ground paths gets cleared immediately. The permanent nature fault appears in case the conductor breaks down (in case of transmission line), current or potential transformer bushing burst (in sub-station) or by some other permanent grounding path. To avoid permanent isolation of an element in case of a transient fault, auto-reclosure (A/R) for single phase faults is provided for 4 kv and higher level EHV transmission lines On the basis of that, four cases of phase to ground fault are discussed here which are: 1. Single phase to earth fault on transmission line with successful A/R 2. Single phase to earth fault on transmission line with unsuccessful A/R 3. Single phase to earth fault on transmission line with no A/R. 4. Single phase to earth fault on Bus bar. The first case of single phase to earth fault with successful autoreclosure is shown in figure 1 and figure 2 where a fault on B phase to earth occurred on 4 kv Jabalpur-Vindhyachal circuit 4. It can be observed that when a single phase fault occur on transmission line the voltage of faulty phase dips to a lower value while remaining phases will observe a smaller dip due to unbalance in the system as the fault is being fed by the bus whose voltage has been as shown in figure 1. Figure 2 shows how the fault current is increased in the faulty phase of the circuit indicating fault feeding from the affected phase. The line protection operated in zone 1 from both end and the faulty phase got isolated from both end resulting in recovery of voltage in faulty phase while current in the phase became zero. This has resulted in A/R initiation for the faulty phase and after 1 second, that phase got reclosed and further no fault was sensed resulting in successful auto reclosure. The line came back in service and the system again came to a balanced state. The voltage channel in PMU is obtained from the Bus PT so it will not become zero but due to the fault, the voltage of bus will get unbalanced and will observe a large dip in faulty phase. Second case is the single phase fault with unsuccessful auto re-closure of the line. In cases where the fault is not of transient nature, permanent tripping of the line is required. One such case was observed in 4 kv Solapur Parli circuit 1. Figure 3 shows the voltage of 4 kv Solapur Bus during the fault while figure 4 gives the current observed in the faulty circuit from Solapur end. Figure 3. Voltage of 4 kv Solapur bus during single phase to ground fault on 4 kv Solapur Parli 1 circuitfrom Synchrophasor data Figure 1. Voltage of 4 kv Jabalpur bus from Synchrophasor data during single phase to ground fault on 4 kv Vindhyachal-Jabalpur circuit 4. Figure 4. Current of 4 kv Solapur parli citcuit 1 observed from Solapur end from Synchrophasor data Figure 2. Current of Vindhyachal-Jabalpur circuit 4 observed from Jabalpur end from Synchrophasor data B phase to earth fault occurred in the 4 kv Solapur Parli circuit 1 due to the heavy rainfall in the area. As observed from the voltage of 4 kv Solapur in figure 3, the voltage of faulty phase dipped to a very low value due to feeding of the fault through the bus. The fault current as shown in figure 4

increased and with carrier aided zone 1 protection, the line tripped in the faulty phase from both ends. A/R was initiated after one second. The faulty phase of the circuit got reclosed but due to permanent nature of fault, all the three phases tripped thus isolating the faulty line. There are cases in which the Auto-reclosure did not occur on the line in case of single phase to ground fault. This is mainly due to issue with the carrier communication or relay. Such cases are very much essential to be analyzed and informed to the concerned utility to rectify it at the earliest. One such case has been shown in figure 5 and 6 where the auto reclosure activity was not observed during single phase to earth fault on 4 kv Korba-Bhatapara. 22 kv level was observed by the synchrophasor unit installed at 4 kv nearby Bus is shown in figure 7. Figure 7. Voltage of 4 kv Boisar bus during single phase to ground fault on 22 kv Padghe Bus II from Synchrophasor data From Figure 7, it can be observed that Y phase to ground fault occurred at Padghe Sub-station on 22 kv Bus II due to bursting of Y phase Bus PT. This resulted in fault feeding by the nearby buses resulting in voltage dip as observed in figure 7. The fault got cleared in 16 ms with the operation of 22 kv Bus bar protection of Bus II. With this it can be understood that how easily single phase fault can be analyzed at control centre without any DR/EL from the sub-station with the help of synchrophasor data. Figure 5. Voltage of 4 kv Korba bus during single phase to ground fault on 4 kv Korba Bhatapar circuit from Synchrophasor data On 4 kv Korba Bhatapra circuit, Y phase to earth fault occurred on the circuit. As observed from the figure 5, the faulty phase voltage dipped at Korba and the fault got cleared with operation of line protection [2]. While figure 6 shows the current of the feeder from Korba end which confirms that the all the three phases of the line tripped rather than single phase with A/R initiation. This was informed to the concern utility and rectified. III. PHASE TO PHASE FAULT The second category of fault in the power system is phase to phase fault. In such cases, the fault may involve a ground path or may not. Such types of faults are rare in nature and generally found in transmission lines. The case as shown in figure 8 and 9 is for the R-Y Phase fault on 4 kv Dehgam-Gandhar circuit 2. It can be observed from figure 8 that the phase voltages of the faulty phases have dipped to a lower value till the fault got cleared with the tripping of line. The current observed from Dehgam for this line show that the fault current in the faulty phases has increased drastically and it got cleared with tripping of the line from both end on zone 2 protection. Figure 6. Current of 4 kv Korba Bhatapara citcuit observed from Korba end from Synchrophasor data The last case in the section of single phase to ground fault is associated with bus fault, which in general occur due to problem with CT/PT bursting. One such case of bus fault at Figure 8. Voltage of 4 kv Dehgam bus during Phase to Phase fault on 4 kv Dehgam-Gandhar circuit 2 from Synchrophasor data

Figure 9. Current of 4 kv Dehgam- Gandhar citcuit 2 observed from Dehgam end from Synchrophasor data It can be observed that how easily the phase to phase fault can be detected with the synchrophasor data. This has reduced the time taken for analysis of any complex fault in power system. IV. THREE PHASE FAULT One of the most severe and rare occurring fault in the power system is three phase fault. This fault may or may not involve ground. The severity is very high and may result in commutation failure of nearby HVDC and stalling of AC motor in the nearby area. Two cases are considered here for example, one at a bus and other on the transmission line. Figure 1 shows the voltage of nearby bus during a three phase fault on 22 kv Bus 1 at Padghe. Voltage has dipped in all the three phases as the fault was being fed by the nearby buses. Figure 11 shows the current in the transmission line connecting the two substations, which has increased as the Boisar Bus is feeding the fault at padghe. The fault got cleared after the operation of bus bar protection. Figure 11. Current of 4 kv Boisar-Padghe citcuit duing the three phase bus fault on 22 kv Padghe Bus 1 from Synchrophasor data The second case is of the three phase fault on a transmission line. Figure12 and 13 shows the synchorphasor data for the three phase fault on 4 kv Raipur Wardha circuit 1. From figure 13 it can be seen that during three phase fault on 4 kv Raipur wardha 1 circuit, the voltage of the Raipur bus I all the three phases dipped to a lower value and recoverd with tripping of circuit on zone 1 line protection. Figure 12. Voltage of 4 kv Raipur bus during three phase fault on 4 kv Raipur Wardha circuit 1 from Synchrophasor data. Figure 1. Voltage of 4 kv Boisar bus during three phase fault on 22 kv Dehgam-Gandhar circuit 2 from Synchrophasor data. Figure 13. Current of 4 kv Raipur Bhadrawati circuit 1 observed from Raipur end from Synchrophasor data

With this all the three types of fault has been discussed with the help of synchrophasor data. This has shown the importance of synchrophasor measurement units in fault analysis and event detection at control centers. In the next section the validation of synchrophasor data with the disturbance recorder file is discussed for determining up to what extent it can be used and what are their limitations. IA/kA 15 1 5 IB/A 4 2 -.5 -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 -.5 -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 V. VALIDATION OF SYNCHROPHASOR DATA FOR FAULT ANALYSIS AND ITS LIMITATION Synchrophasor data has come out as a very effective tool for analyzing faults in power system in real time. But the synchorphasor data has its own limitation compared to the disturbance recorder file which has higher sampling rate (khz). Figure 14, 15, 16 shows the DR for the first three events discussed in section II in case of single phase to earth fault with successful A/R, unsuccessful A/R and no A/R respectively using SIGRA [3]. The synchorphasor are the fundamental frequency component calculated using Discrete Fourier Transform (DFT). So higher harmonic are being neglected which may result in different fault current observed from synchrophasor data and actual data from fault recorder. IA/A IC/A 4 2 15 1 5 -.5 -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 -.5 -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 Figure 16. Current from the DR of 4 kv Korba Bhatapara circuit 1 from Korba end for the single phase fault ( No A/R). The validation analysis of the three cases is shown in table 1. Here major two parameters i.e. fault current value and fault clearing time has been tabulated for all the three cases. TABLE I. VALIDATION OF DR AND SYNCHROPHASOR MEASUREMENT DURING FAULT 4 2 IB/A 3 2 1 IC/kA 1..75.5.25. Case No -.5..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 5. 5.5 Successful 3.5 A/R 4. 1.365 4.5 1.255.5 98 8 -.5..5 1. 1.5 2. 2.5 3. 5. Unsuccessful A/R Maximum fault current observed from DR (ka) Maximum fault current observed from PMU (ka) Fault clearing time from DR (ms) Fault recovery time from PMU (ms) 5.46 3.37 81 12 3.5 No A/R 4.518 145.5 94 12 -.5..5 1. 1.5 2. 2.5 3. 4. 5. 1..5. -.5..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 5. 5.5 Figure 14. Current from the DR of 4 kv Jabalpur -Vindhyachal circuit 4 from Jabalpur end for the single phase fault ( successful A/R). LINE_A_IL1/A 6 4 2 LINE_A_IL2/A 75 5 25 LINE_A_IL3/kA LINE_A_ 6 4 2 6 4 2 -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 This in general result in a ±4 ms error in the time for fault Also, when the fault -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 current is analyzed it can be observed -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 can be due to various reasons and out of these major two are: -.25..25.5.75 1. 1.25 1.5 1.75 2. 2.25 protection core of the CT also, but in India Figure 15. Current from the DR of 4 kv Solapur -Parli circuit 1 from Solapur end for the single phase fault ( unsuccessful A/R). It can be observed that fault clearing time from DR and PMU has slight difference which is attributed to mainly three factors: 1. Reporting rate of PMU (here at every 4 ms) 2. DFT Window length (generally varies from two cycles to 1 cycles). 3. Time stamping of phasor (time stamping at the starting/middle/end of DFT calculation window) [4]. recovery time [2]. This can be improved with increasing the reporting rate of the PMU. that there is a difference between the maximum fault current from synchrophasor measurement and disturbance recorder, both of which are taken from the same CT of the feeder. This 1. PMU uses measurement core while the DR uses the protection core of the CT which is having higher accuracy. (Although PMU can be made to use measurement core of the CT is used) 2. The second reason is the contribution of higher harmonics during faults.

IA/A 2 15 1 1.% 275.84 16.3% 4.8% 45.4 52.68 48.73 8.4% 5.6% During 5 13.37 faults, the fault current is having DC, 23.19 Fundamental 15.38 frequency component and higher harmonic component. DR measured currents are having all these components. While synchrophasor is giving only the fundamental frequency component IB/A resulting 1.% in lower current values. Figure 17 shows 25 37.99 the 2 various components in the faulty phase current for the 15 2.5% three cases discussed for validation in this section. It can be 1 8.6%.6% 63.11 9.8% 2.7% 4.2% 26.43 3.3 5 observed 1.76 8.35 13.1 that the Current associated with fundamental component of the frequency are very close to what being observed by the synchrophasor units. IC/kA.8.6.4.2. LINE_A_IL3/kA IA/A 3 4. 2 3. 2. 2. 1 1.5 1...5. IB/kA 15. 1. 5.. 19.1% 17.7% DC 5 1 15 2 25 3 35 4 45 5 DC 5 1 15 2 25 3 35 4 45 5.9%.1 1.% 1.21 2.5%.3 2.5%.3.1%..7%.1 DC 5 1 15 2 25 3 35 4 45 5 1.% 1.% 379.9 3.93 1.% 13.9% 1.53 26.8% 5.7% 4.7% 1.5 3.8% 18.5% 52.87 11.7% 2.5% 1.3% 8.2%.73 3.3% 4.7%.4% 3.4% 1.1% 1.8% 1.% 1.1%.5% 21.65.19 14.58 9.63.46 4.92.32 5.44.13.19 1.48.13 4.1 4.9%.7 3.81 2.2% 3.8%.4 2.9.7% 2.9%.9% 1.2% 1.%.2.7.3.6.1.4.3.1.2.1 DC DC 5 5 1 1 15 15 2 2 25 25 3 3 35 35 4 4 45 45 5 5 DC 2. B Phase 5current for Unsuccessful 1 15 A/R Case 2 25 3 35 4 45 5 5.5% 7.35 1. B Phase current for Successful A/R Case 1.% 14.55 33.1% 4.82 19.4% 2.82 9.6% 1.4 6.7%.97 DC 5 1 15 2 25 3 35 4 45 5 3. Y Phase current for No A/R Case Figure 17. Various compoent of Current when maxium fault current appear IC/A in the three cases 1.% 1. Successfulr A/R 2. Unsuccesdful A/R and 3. No A/R. 58.1 4 3 2 1.6% 8.2% 5.% 3.5% Thus, it 61.31 can be inferred 1.% 2.6% 1 47.64 that, synchrophasor 28.95 data has given a 2.49 5.64 14.95 very good insight into the various aspect of fault observed in the power system. Synchrophasor data can be used for event detection engine at control centers in real time by setting various thresholds to detect the individual types of faults. It DC 5 1 15 2 25 3 35 4 45 5 1.% 14.77 also 15. helps 5.5% in quicker detection of A/R in case it has been 7.46 33.1% 1. 4.88 19.4% enabled during single/three phase fault 9.7% in 6.6% zone 6.9% 1 for 5. 2.86 1.43.98 1.3 transmission. line. The extent of fault current signifies the severity of fault to the real time operator in taking decision for DC 5 1 15 2 25 3 35 4 45 5 charging of the faulty line. Synchrophasor data in combination with field records will make fault analysis easier. VI. CONCLUSION This paper has discussed the various types of faults as observed from the synchrophasor measurements. This has helped in finding the various characteristic of different types of faults in power system. The paper has led the basis of disturbance analysis tool development for analysis of the fault in offline mode with the helped of Synchphasor and DR data. Also has set path to the course of event detection engine in real time using synchrophasor data stream. Such development will help real time system operator to access the severity of power system faults and take corrective action to reduce its after effects. 1.6%.2 6.9% 1.1 3.2% 3.3% 2.3% permitting 8.96 the 9.4 publication 6.22 of this paper. The authors are sincerely thankful to Shri. P.Pentayya, Ex General Manager, WRLDC for his guidance during Synchrophasor Pilot project implementation in western region. The authors are also thankful to WRLDC personnel for their support. The views expressed in this paper are of authors and not necessarily that of the organizations they represent. 3.4% 9.27 6.39 1.5%.2 5.8%.84 12.33 5.8%.85 4.25 2.%.2 4.1%.6 1.3% 7.55 4.1%.61 1.8% 5.46.4%.1.54 8.2.54 1.6% 5.7.4%..53 12.17.55 REFERENCES [1] Synchrophasors Initiative in India, POSOCO, New Delhi, Tech.Rep. July 212 [2] Synchrophasors Initiative in India, POSOCO, New Delhi, Tech.Rep. December 213 [3] User Manual Fault Record Analysis SIGRA 4, Siemens [4] IEEE Standard for Synchrophasor Measurements for Power Systems, IEEE Std C37.118.1-211,Dec.211 ACKNOWLEDGMENT The authors acknowledge the guidance and support given by managements of POSOCO as well as PGCIL and for