Enhancement of Heat Transfer in Heat Exchanger using Punched and V-cut Twisted Tape Inserts

Similar documents
Experimental Investigation of Heat Transfer Enhancement by Using Clockwise and Counter -clockwise Corrugated Twisted Tape Inserts

Research Article. Kaustubh G. Kulkarni * and Mandar M. Lele. Abstract

SSRG International Journal of Mechanical Engineering ( SSRG IJME ) Volume 2 Issue 5 May 2015

Performance analysis of V-jagged twisted tape insert for heat transfer in a circular tube

Heat Transfer Enhancement Using a Rotating Twisted Tape Insert

International Journal of Advanced Engineering Research and Studies E-ISSN

Heat Augmentation Using Non-metallic Flow Divider Type Inserts in Forced Convection

Analysis of Heat Transfer in Pipe with Twisted Tape Inserts

Heat Transfer Enhancement with Different Square Jagged Twisted Tapes and CuO Nano fluid

Numerical investigation of heat transfer enhancement in a pipe heat exchanger by adding nano particle and twisted tape

AUGMENTATION OF HEAT TRANSFER USING COILED POROUS TWISTED TAPE INSERT

Experimental Validation of Heat Transfer Enhancement in plate Heat Exchanger with Non Conventional Shapes of Rib

Effect of V-Shape Twisted Jaw Turbulators on Thermal Performance of Tube heat exchanger: An Experimental Study

Experimental Investigation of Heat Transfer Enhancement with Different Square Jagged Twisted Tapes and CuO/water Nano fluid

Study of Compound Heat Transfer Enhancement of Horizontal Liquid-Solid Fluidized Bed Heat Exchanger with a Kenics Static Mixer

International Communications in Heat and Mass Transfer

Australian Journal of Basic and Applied Sciences. Heat transfer enhancement of laminar flow in a circular tube using Swirl / vortex generator

Experimental and Numerical Analysis of Turbulent Flow Heat Transfer Enhancement in a Horizontal Circular Tube Using Mesh Inserts

EFFECT OF STAGGERED RIB LENGTH ON PERFORMANCE OF SOLAR AIR HEATER USING V-RIB WITH SYMMETRICAL GAP AND STAGGERED RIB

Investigation of Heat Transfer Enhancement in Laminar Flow through Circular Tube Combined Wire Coil and Wavy Strip with Central Clearance

International Journal of Innovative Research in Science, Engineering and Technology

Australian Journal of Basic and Applied Sciences

Department of Mechanical Engineering, VTU, Basveshwar Engineering college, Bagalkot, Karnataka, India

Sami D. Salman, 1,2 Abdul Amir H. Kadhum, 1 Mohd S. Takriff, 1 and Abu Bakar Mohamad Introduction

Experimental Investigation of Forced Convection Heat Transfer Augmentation from a Dimpled Surface

Experimental investigation of heat transfer augmentation in triangular duct with rectangular wing

International Communications in Heat and Mass Transfer

Heat Transfer Analysis of Helical Strip Insert with Regularly Spaced Cut Sections Placed Inside a Circular Pipe

EFFECT OF BAFFLES GEOMETRY ON HEAT TRANSFER ENHANCEMENT INSIDE CORRUGATED DUCT

Performance evaluation of heat transfer enhancement for internal flow based on exergy analysis. S.A. Abdel-Moneim and R.K. Ali*

Heat transfer characteristics and friction of turbulent swirling air flow through abrupt expansion

Experimental Heat transfer study of Turbulent Square duct flow through V type turbulators

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 06, 2015 ISSN (online):

Exergy Analysis of Solar Air Collector Having W Shaped Artificial Roughness

Heat Transfer Enhancement of Shell and Tube Heat Exchanger Using Conical Tapes.

Convective Heat Transfer and Thermal Performance in a Circular Tube Heat Exchanger Inserted with U-Shaped Baffle

COMPUTATIONAL FLUID DYNAMICS ANALYSIS ON HEAT TRANSFER AND FRICTION FACTOR CHARACTERISTICS OF A TURBULENT FLOW FOR INTERNALLY GROOVED TUBES

CFD Investigation of Heat Transfer and Flow Patterns in Tube Side Laminar Flow and the Potential for Enhancement

Comparative Analysis of Heat Transfer and Friction Characteristics in a Corrugated Tube

Investigation of Heat Transfer on Smooth and Enhanced Tube in Heat Exchanger

Sarbendu Roy, Manvendra Tiwari and Sujoy Kumar Saha 1. Mechanical Engineering Department, IIEST, Shibpur, Howrah , West Bengal, INDIA

Experimental Investigation of Trapezoidal Duct using Delta Wing Vortex Generators

Thermo-Hydraulic Performance of a Roughened Square Duct Having Inclined Ribs with a Gap on Two Opposite Walls

Experimental Investigation of Single-Phase Friction Factor and Heat Transfer inside the Horizontal Internally Micro-Fin Tubes.

Thermo-Hydraulic performance of Internal finned tube Automobile Radiator

EFFECT OF TWISTED TAPE INSERTS IN DOUBLE PIPE HEAT EXCHANGER USING AL2O3/WATER NANO FLUIDS

AASCIT Journal of Nanoscience 2015; 1(4): Published online September 10, 2015 (

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

HEAT TRANSFER AND FRICTION FACTOR CHARACTERISTICS OF COMPOUND TURBULATORS IN RECTANGULAR DUCTS OF SOLAR AIR HEATER

Experimentation and Performance Evaluation of Heat Exchanger Using Z-Ribs

EXPERIMENTAL STUDIES ON HEAT TRANSFER AUGMENTATION USING TRIANGULAR WAVY TAPE (TWT) AS INSERTS FOR TUBE SIDE FLOW OF LIQUIDS

International Journal of Emerging Technologies in Engineering Research (IJETER)

International Journal of Engineering, Business and Enterprise Applications (IJEBEA)

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

Chapter 3 NATURAL CONVECTION

Heat Transfer F12-ENG Lab #4 Forced convection School of Engineering, UC Merced.

Experimental Investigation of Trapezoidal Duct using Delta Wing Vortex Generators

Heat Transfer Investigation in a Circular Tube Fabricated from Nano-composite Materials Under a Constant Heat Flux

Investigation of Heat Transfer and Friction Factor Characteristics of Two Phase Nano Fluids by Inserting Twisted Tape and Helical Inserts in the Tube

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

REFERENCES. 5. ANSI/ASME, Measurement uncertainty, PTC 19, Part I, , 1986.

This is the author s final accepted version.

EXPERIMENTAL AND CFD ANALYSIS OF TURBULENT FLOW HEAT TRANSFER IN TUBULAR HEAT EXCHANGER

Analysis, Design and Fabrication of Forced Convection Apparatus

EXPERIMENTAL AND CFD ANALYSIS OF TURBULENT FLOW HEAT TRANSFER IN TUBULAR EXCHANGER

Flow and Heat Transfer Profiles in a Square Channel with 45 V-Downstream Orifices

Amir Houshmand, Ahmad Sedaghat, Kia Golmohamadi and Mohamadreza Salimpour

EXPERIMENTAL STUDIES ON HEAT TRANSFER AUGMENATATION USING GALVANISED IRON WIRE INSERT WITH AND WITHOUT BAFFLES

Journal of Thermal Science and Technology

Computational Fluid Dynamics Based Analysis of Angled Rib Roughened Solar Air Heater Duct

Experimental Study of Heat Transfer Enhancement through a Tube with Wire-Coil Inserts at Low Turbulent Reynolds Number

Numerical Analysis of Fe 3 O 4 Nanofluid Flow in a Double Pipe U-Bend Heat Exchanger

Comparative study of Different Geometry of Ribs for roughness on absorber plate of Solar Air Heater -A Review

Experimental Study of Spiral Heat Exchanger Performance in V- Trough Tube Collector by using Mono and Hybrid Nanofluids

Cfd Simulation and Experimentalverification of Air Flow through Heated Pipe

A copy can be downloaded for personal non-commercial research or study, without prior permission or charge


Mechanism of Heat Transfer Enhancement in the Core Flow of a Tube and Its Numerical Simulation

ENERGY PERFORMANCE IMPROVEMENT, FLOW BEHAVIOR AND HEAT TRANSFER INVESTIGATION IN A CIRCULAR TUBE WITH V-DOWNSTREAM DISCRETE BAFFLES

Numerical Investigation on Turbulent Forced Convection in Heating Channel Inserted with Discrete V-Shaped Baffles

Heat transfer coefficient of near boiling single phase flow with propane in horizontal circular micro channel

Performance Investigation of Artificially Roughened Duct used in Solar Air Heaters

ME 331 Homework Assignment #6

International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:18 No:02 1

Numerical Heat Transfer Study of Turbulent Square Duct Flow through W-Type Turbulators

Fluid Flow and Heat Transfer Characteristics in Helical Tubes Cooperating with Spiral Corrugation

PERFORMANCE ANALYSIS OF PARABOLIC TROUGH COLLECTOR TUBE WITH INTERNAL INTERMITTENT FINS

Numerical Investigation of Heat Transfer Enhancement and Pressure Drop of a Double Tube Heat Exchanger with Rectangular Fins in the Annulus Side

Heat Transfer Enhancement in Fe3O4-water Nanofluid through a Finned Tube Counter Flow Heat Exchanger

DETERMINATION OF R134A S CONVECTIVE HEAT TRANSFER COEFFICIENT IN HORIZONTAL EVAPORATORS HAVING SMOOTH AND CORRUGATED TUBES

Heat Transfer Enhancement of Solar Air Heater By Using Artificial Roughness double inclined ribs

EXPERIMENTAL INVESTIGATION OF THE HEAT TRANSFER IN A HORIZONTAL MINI-TUBE WITH THREE DIFFERENT INLET CONFIGURATIONS

Numerical and Experimental Investigation of Heat Transfer Using Discrete Ribs

NUMERICAL ANALYSIS TO OPTIMIZE THE HEAT TRANSFER RATE OF TUBE-IN-TUBE HELICAL COIL HEAT EXCHANGER

Forced Convection Heat Transfer Augmentation from Ribbed Surface

Experimental Investigations on the Local Distribution of wall static pressure coefficient Due To an Impinging Slot Air Jet on a Confined Rough Surface

International Journal of Scientific & Engineering Research, Volume 5, Issue 11, November ISSN

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

Laminar Forced Convection and Heat Transfer Characteristics in a Square Channel Equipped with V-Wavy Surface

Transcription:

ISSN 2395-1621 Enhancement of Heat Transfer in Heat Exchanger using Punched and V-cut Twisted Tape Inserts #1 Imran Quazi, Prof. #2 V.R.Mohite, #3 Prof. J Bali 1 imranquazi1987@gmail.com 2 vrmohite@gmail.com 3 bali.jagadeesh@gmail.com #13 DPCOE-Mechanical Department, SPP University Pune, India #2 BSIOTR Wagholi, Pune, India. ABSTRACT The heat transfer enhancement is crucial factor in design of heat exchangers. Rise in heat transfer rate can be achieved using various inserts in the tubes of heat exchangers. In the present research work, the outcomes observed after conducting experiments including the amplification of turbulent flow heat transfer in a horizontal circular tube with the help of punched and v-cut twisted tape inserts in which air is used as the working fluid, are represented. The procedure was conducted for plain tube with and without punched and v-cut twisted tape insert keeping wall heat flux constant and mass flow rates are varied. The punched and v-cut twisted tapes are made of aluminium and copper, but with three different twist ratios as 9, 10 & 11. The range of Reynolds number used is between 5000 to 10500. Both heat transfer coefficient and pressure drop are calculated and the outcomes are compared with those of plain tube. It was found that the rise of heat transfer with punched and v-cut twisted tape inserts as compared to plain tube varied from 18% to 52 % for various inserts. This rise was observed due to extensive turbulence obtained as a result of the geometry of the inserts used. ARTICLE INFO Article History Received :18 th November 2015 Received in revised form : 19 th November 2015 Accepted : 21 st November, 2015 Published online : 22 nd November 2015 Keywords punched and v-cut twisted tape insert, heat transfer enhancement, twist ratio. I. INTRODUCTION Number of techniques (both passive and active) are investigated for increasing the heat transfer rates inside circular tubes and variety of inserts have been used, especially if it is a case of turbulent flow. Some of these means are applied to increase thermal performance of heat transfer devices such as treated surfaces, coarse surfaces, swirling flow devices, coiled tubes, and surface tension devices [1]. Twisted tape swirl tabulator is one of the widely used passive technique for heat transfer augmentation as they present advantages of stable performance, simple structure and ease of installation [2]. Sarma et al. [3] presented generalized correlations to predict friction factor and convective heat transfer coefficient for a tube equipped with twisted tapes over a wide range of Reynolds number and the Prandtl number. Optimized design of recurrently set apart short-length twisted tapes for a circular tube for turbulent heat transfer was conducted by Wang et al. [4] by using computational fluid dynamics (CFDs) modeling. Eiamsa-ard et al. [5] projected experimental study of convective heat transfer inside a circular tube hving shortlength twisted tapes inserted under uniform heat flux. Akhavan-Behabadi et al. [6] conducted similar experiments to analyze effects of twisted tapes on heat transfer enhancement and pressure drop in evaporators placed horizontally. The working fluid used was R-134a. Heat transfer and friction factor of CuO/water nanofluid and

water were experimentally checked in circular tube fitted with modified twisted tapes as another substitute [7 9]. Eiamsa-ardet al. [10] carried research works on heat transfer and friction factor features in a double pipe heat exchanger equipped with twisted tape component. They executed their analysis for both continuously placed twisted tape and twisted tape placed with various free spaces inside a circular tube. The heat transfer increase and pressure drop through condensation of HFC-134a in a horizontal tube fitted with twisted tapes were experimentally studied [11]. Jaisankar et al. [12] experimentally examined the heat transfer, friction factor and thermal behaviour caused by twisted tape for solar water heater. Tape width, twist ratio, space ratio, rod-diameter and phase angle effects on heat transfer and pressure drop were analysed experimentally in a circular tube fitted with regularly spaced twisted tape elements [13]. Naphon [14] also conducted experiments by using conventional twisted tape inserts in horizontal double pipe. Ferroni et al.[15] conducted particular experiments in circular tube fitted with physically separated, multiple, short-length twisted tapes. Convective laminar heat transfer augmentation in twisted tape inserted tube was conferred experimentally by Sarma et al.[16]. In some of the studies, researchers concentrated the thermal effects of twisted tape inserts in modified tube instead of smooth tube, for example; Thianpong et al. [17] examined heat transfer enhancement in a dimpled tube with a twisted tape swirl generator inserted inside. They also suggested the empirical correlations based on the experimental data obtained from their study for predicting the Nusselt number and friction factor for Reynolds number variation from 12,000 to 44,000. Bharadwaj et al. [18] performed experiments by using conventional type of twisted tapes to define pressure drop and heat transfer characteristics of water in a spirally grooved tube 75-start. Some researchers[19] modified the conventional twisted tape geometries, for example; Murugesan et al. [20] conducted experiments with V-cut twisted tapes to understand change in heat transfer and pressure drop for a circular tube. II. EXPERIMENTAL SETUP three various twist ratios as 9, 10 and 11. They are fabricated from aluminium and copper. Following figure shows schematic diagram of test tube with tape inserted. Fig. 2.Schematic of test tube with tape inserted The punched and v-cut twisted copper tape used in this experimental study is shown in Fig.2. A 0.24 hp blower is used to forcefully send the air through the test tube. Uniform heat flux is applied to external surface of the test section with the help of heating coil by electrical winding and its output power is controlled by a variac transformer to supply constant heat flux along the whole section of the test tube. The outer surface of the test tube is well insulated with glass wool to reduce the convective heat loss to the surroundings. The external surface temperatures of the test tube wall are measured by 6 K-type thermocouples. These were placed on the outer wall of the test section. Also, the inlet and outlet temperatures of the bulk air are measured by 2 K-type thermocouples at specific points. For measurement of pressure drop an inclined manometer was used across the test tube to have accurate readings. After passing through the test tube, air then enters the orifice meter, which is used for finding the volumetric flow rates. For this purpose a separate U-tube manometer is placed across orifice meter. The volumetric flow rate of air supplied from the blower is controlled by controlling the position of the control valve. The experiments were conducted by varying the flow rate in terms of Reynolds numbers from 5000 to 10500 of the bulk air. The test tube is heated from the external surface during the experiments,and the information of temperature, volumetric flow rate, pressure drop of the bulk air and electrical output are noted once the system reaches to the steady state condition. The Nusselt number, Reynolds number, friction factor, heat transfer enhancement are calculated based on the average outer wall temperatures and the inlet and outlet temperatures of air. III. DATA COLLECTION & STUDY The data reduction of the obtained results is summarized in following ways: Fig. 1.Experimental setup block diagram Above figure shows block diagram of experimental setup used Figure 1. The experimental setup includes a blower, an orifice meter for measurement of the volumetric flow rate and the heat transfer test tube section (700 mm). A 26 mm inner diameter MS test tube (D1), with 26.4 mm outer diameter (D2), and a 2 mm thickness (t) was used. The punched and v-cut twisted tapes are tested in this trial; with A. Heat Transfer Calculations Avg. Surface Temp., T s = (T 2 +T 3 +T 4 +T 5 +T 6 +T 7 )/6 (1) Avg. Temp of air, T b = (T 1 +T 8 )/2 (2) Air head, ha= h w ρ w / ρ a (3) ρ w = Density of water = 1000 kg/m 3 Air volume flow rate, Q a = C d *A o (2 g h air ) (4) A 0 = cross sectional area of orifice. Mass flow rate, m = Q a *ρ a (5) Velocity of air, V= Q a /A (6)

A= cross sectional area of pipe. Heat carried out, q = m *C p *(T 8 -T 1 ) (7) h = Q/A(T s -T b ) (8) h = heat transfer coefficient. T s = surface temperature The Reynolds number for the fluid is defined by, Re = VD/υ (9) V= velocity of the fluid. ν = Kinematic viscosity of the fluid. For internal flow conditions, if Reynolds number (Re) is greater than 4000 then the flow is said to be turbulent. After the flow is decided i.e. laminar or turbulent then the Nusselt number can be calculated. The theoretical Nusselt number is calculated below without considering friction which is theoretical Nusselt number and then calculated by considering friction which is experimental Nusselt number. Nuth = 0.023*(Re)0.8*(Pr)0.4 (10) This equation is called Dittus-Boelter equation. f s = (1.82 log 10 Re -1.64 ) -2 (11) Above equation is used to find friction factor and is called as Petukhov equation for smooth surface. f s = Friction factor for smooth tube. Re= Reynolds number. The actual pressure drop & friction factor is calculated with the help of tappings provided on both the ends of test pipe connected to U-tube manometer and the friction factor is calculated from the formula given below: f = P/ (L/D) 2 (ρ a V 2 /2) (12) P= pressure difference at both ends of test pipe. L= length of test pipe. D= Inner diameter of pipe. The experimental Nusselt number are calculated as given below: Nu =hd/k (13) Nu= Nusselt number h = heat transfer coefficient k = thermal conductivity of fluid D = diameter of test section The overall enhancement efficiency is expressed as the ratio of the Nusselt number of an enhanced tube with corrugated twisted tape insert to that of a smooth tube, at a constant pumping power. This factor is introduced by Webb[19]. PEC= η = (Nu with / Nu w/o ) / (f with /f w/o ) 1/3 (14) B. Validation experiments of plain tube In this study, experimental results of Nusselt number and friction factor for the plain tube are obtained and compared with equations of Dittus Boelter(10) and Petukhov (11) as mentioned above. The comparisons of friction factor and Nusselt number for the current plain tube with existing correlations are shown in Fig. 4 and 5, respectively. These figures show that validation experiments of heat transfer in terms of Nusselt number and friction factor for the plain tube are in good agreement with the results obtained from Dittus-Boelter and Petukhov equations. The results of current plain tube and preceding equations are nearly the same. Thus, this accuracy provides dependable results for heat transfer and friction factor in a tube with twisted tape inserts in this current study. The Reynolds number for validation test were ranged from 4500 to 10500 i.e. the range of Reynolds number used is for turbulent flow. Turbulent flow means Reynolds number greater than 4000. The results of the tests carried for performance inspection of present punched and V-cut twisted tape are discussed next in results and discussion. IV. RESULT & DISCUSSION A. Heat Transfer and Overall Augmentation Characteristics The variation of Nusselt number with Reynolds number for various punched and v-cut inserts is shown in Figure 6. Uppermost Nusselt number was obtained for tape with twist ratio of11. The Nusselt number for punched and v-cut inserts ranges from 33% to 56% compared to plain tube. This is due to heavy-duty turbulence intensity caused by punches & cuts on inserts leading to quick mixing of the flow causing heat transfer augmentation. The variations of friction factor with Reynolds number for corrugated tape inserts are presented in Figure 7. It is observed that the friction factor gradually reduced with rise in Reynolds number. It is observed to be maximum, for insert having twist ratio of 11. It is clear from Figures 6, 7 and 8 that when a punched and v-cut twisted tape is inserted into a plain tube, then there is a significant growth in Nusselt number due to secondary flow, with greater augmentation being recognized at lower Reynolds numbers and higher twist ratio. This enhancement is largely due to the centrifugal forces resulting from the spiral motion of the fluid and partly because of the tape acting as fin. It is detected that the rise in twist ratio results in increment of Nusselt number as well as growth in pressure drop. From Figure 6, the percentage rise in Nusselt numbers for corrugated twisted tapes compared to plain tube are about 30-89%, 33-100% and 58-146% respectively for

FF Nu Nu www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 2 Page 1579-1584, 2015, ISSN 2395-1621 tape with twist ratio 9,10 & 11 respectively. Fig. 4. Validation results for friction factor Enhancement 1.51 4000500060007000 Re Fig. 8. Variation of Enhancement for different insert configurations V.CONCLUSION Fig. 5. Validation results for Nusselt number The overall enhancement ratio is useful unit to assess the quality of heat transfer enhancement obtained over plain tube with constant pumping power. It is found to be more than unity for all the punched twisted tape inserts under consideration. Distinctions of overall enhancement ratio η against Reynolds number for different tapes are shown in figure 8. It is observed that overall enhancement tended to decrease gradually with the rise of Reynolds number for all twist ratios. The highest value of overall enhancement is 1.32 for punched and v-cut twisted tape insert having twist ratio 11. It is seen in figure 8 that, for tapes of twist ratios 9, 10 & 11 curves are of decreasing order for a given twist ratio in the range of Re from 5000 to 10000. Nu-vs Re All Inserts 55 50 45 40 35 30 25 20 15 4000 5000 Re 6000 7000 Al u TR 9 Fig. 6. Variation of Nusselt number for different insert configurations FF vs Re-All Al T R 9 0.22 4000 5000 6000 Re 7000 Fig. 7.Variation of friction factor for different insert configurations The study states an experimental investigation of the potential of punched and v-cut twisted tape inserts to improve the rate of heat transfer in a horizontal circular tube having inside diameter 26 mm using air as working fluid. The Reynolds number varied from 5000 to 10500. The effects of factors such as modified twist ratio, Reynolds number on the heat transfer and overall enhancement ratio are considered. The following deductions can be drawn. The enhancement of heat transfer with punched and v- cut twisted tape inserts as compared to plain tube varied from 3 to 16% for twist ratio 9 and from 15 to 32% for twist ratio of 11. This enhancement is chiefly due to the centrifugal forces resulting from the spiral motion of the fluid. Growth in twist ratio causes increase in Nusselt numbers as well as friction factors. The maximum friction factor rise was about 52% for twist ratio 9 and 66% for twist ratio 11 for punched and v-cut twisted tape inserts compared to plain tube. The overall enhancement for the tubes with punched and v-cut twisted tape inserts is 1.32 for twist ratio 9 and 1.16 for twist ratio 11 for punched and v-cut twisted tape insert. Thus the improved performance can be achieved using punched and v-cut twisted tapes as compared to plane tube. Thus, from the considerations of higher heat transfer and savings in pumping power punched and v- cut tape inserts are seen to be promising for improving turbulent flow heat transfer in a horizontal circular tube. Future work can include: A. Change tape material from Aluminium and Copper to brass. B. Compound enhancement techniques maybe used i.e., the tape inserts can be united with coil wire inserts for better augmentation. NOMENCLATURE H/D twist ratio f th friction factor(theoretical) for plain tube w width of corrugated tape insert,(mm) f friction factor(experimental) for plain tube

f i H friction factor obtained using tape inserts pitch, (mm) h experimental convective heat transfer coefficient, (W/m 2 K) h w manometer level difference,(m) h air equivalent height of air column, (m) Q a air discharge through test section (m 3 /sec) D Inner diameter of test section, (m) k thermal conductivity, (W/m-K) A test section inner tube area, (π/4 D 2 ) (m 2 ) Cp specific heat of air, (J/kg K) A 0 area of orifice, (m 2 ) L m length of test section, (m) mass flow rate of air, (Kg/sec) Nu Nusselt number (experimental) for plain tube Nu th Nusselt number for plain tube (theoretical) Pr Prandtl number p pitch, (m) P Q Re pressure drop across the test section, (Pa) total heat transferred to air (W) Reynolds number, (ρ V D/μ) T 1 -T 8 - air temperature at inlet and outlet, ( K) T 2, T 3, T 4, T 5, T 6 - tube wall temperatures, ( K) Ts T b V avg Surface temperature of the working fluid, ( K) bulk temperature, ( K) air velocity through test section, (m/sec) Greek symbols ν Kinematic viscosity of air, (m 2 /sec) μ dynamic viscosity, (kg/m s) η Over all enhancement ρ w density of water, (kg/m 3 ) ρ a density of air (kg/m 3 ) REFERENCES [1] A.E. Bergles, ExHFT for fourth generation heat transfer technology, Experimental Thermal and Fluid Science 26 (2002) 335 344. [2] J. Guo, A. Fan, X. Zhang, W. Liu, A numerical study on heat transfer and friction factor characteristics of laminar flow in a circular tube fitted with centercleared twisted tape, International Journal of Thermal Sciences 50(2011) 1263 1270. [3] P.K. Sarma, P.S. Kishore, V. Dharma Rao, T. Subrahmanyam, A combined approach to predict friction coefficients and convective heat transfer characteristics in A tube with twisted tape inserts for a wide range of Re and Pr, International Journal of Thermal Sciences 44 (2005) 393 398. [4] Y. Wang, M. Hou, X. Deng, L. Li, C. Huang, H. Huang, G. Zhang, C. Chen, W. Huang, Configuration optimization of regularly spaced short-length twisted tape in a circular tube to enhance turbulent heat transfer using CFD modeling. [5] S. Eiamsa-ard, C. Thianpong, P. Eiamsa-ard, P. Promvonge, Convective heat transfer in a circular tube with short-length twisted tape insert, International Communications in Heat and Mass Transfer 36 (2009) 365 371. [6] M.A. Akhavan-Behabadi, R. Kumar, A. Mohammadpour, M. Jamali-Asthiani, Effect of twisted tape insert on heat transfer and pressure drop in horizontal evaporators for the flow of R-134a, International Journal of Refrigeration 32 (2009) 922 930. [7] K. Wongcharee, S. Eiamsa-ard, Enhancement of heat transfer using CuO/water nanofluid and twisted tape with alternate axis, International Communications in Heat and Mass Transfer 38 (2011) 742 748. [8] K. Wongcharee, S. Eiamsa-ard, Friction and heat transfer characteristics of laminar swirl flow through the round tubes inserted with alternate clockwise and counter-clockwise twisted-tapes, International Communications in Heat and Mass Transfer 38 (2011) 348 352. [9] S. Eiamsa-ard, P. Promvonge, Performance assessment in a heat exchanger tube with alternate clockwise and counter-clockwise twisted-tape inserts, International Journal of Heat and Mass Transfer 53 (2010) 1364 1372. [10] S. Eiamsa-ard, C. Thianpong, P. Promvonge, Experimental investigation of heat transfer and flow friction in a circular tube fitted with regularly spaced twisted tape elements, International Communications in Heat and Mass Transfer 33 (2006) 1225 1233. [11] V. Hejazi, M.A. Akhavan-Behabadi, A. Afshari, Experimental investigation of twisted tape inserts performance on condensation heat transfer enhancement and pressure drop, International Communications in Heat and Mass Transfer 37 (2010) 1376 1387. [12] S. Jaisankar, T.K. Radhakrishnan, K.N. Sheeba, Experimental studies on heat transfer and friction factor characteristics of forced circulation solar water heater system fitted with helical twisted tapes, Solar Energy 83 (2009) 1943 1952. [13] S.K. Saha, A. Dutta, S.K. Dhal, Friction and heat transfer characteristics of laminar swirl flow through a circular tube fitted with regularly spaced twisted-tape elements, International Journal of Heat and Mass Transfer 44 (2011) 4211 4223. [14] P. Naphon, Heat transfer and pressure drop in the horizontal double pipes with and without twisted tape insert, International Communications in Heat and Mass Transfer 33 (2006) 166 175. [15] P. Ferroni, R.E. Block, N.E. Todreas, A.E. Bergles, Experimental evaluation of pressure drop in round tubes provided with physically separated, multiple, short-length twisted tapes, Experimental Thermal and Fluid Science 35 (2011) 1357 1369. [16] P.K. Sarma, T. Subramanyam, P.S. Kishorea, V.D. Raoc, S. Kakac, Laminar convective heat transfer with twisted tape inserts in a tube,

International Journal of Thermal Sciences 42 (2003) 821 828. [17] C. Thianpong, P. Eiamsa-ard, K. Wongcharee, S. Eiamsa-ard, Compound heat transfer enhancement of a dimpled tube with a twisted tape swirl generator, International Communications in Heat and Mass Transfer 36 (2009) 698 704. [18] P. Bharadwaj, A.D. Khondge, A.W. Date, Heat transfer and pressure drop in a spirally grooved tube with twisted tape insert, International Journal of Heat and Mass Transfer 52 (2009) 1938 1944. [19] S. Eiamsa-ard, P. Seemawute, K. Wongcharee, Influences of peripherally-cut twisted tape insert on heat transfer and thermal performance characteristics in laminar and turbulent tube flows, Experimental Thermal and Fluid Science 34 (2010) 711 719. [20] P. Murugesan, K. Mayilsamy, S. Suresh, P.S.S. Srinivasan, Heat transfer and pressure drop characteristics in a circular tube fitted with and without V-cut twisted tape insert, International Communications in Heat and Mass Transfer 38 (2011) 329 334.