DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT

Similar documents
HOW TO DEAL WITH ELECTROMAGNETIC DISTURBANCES CAUSED BY NEW INVERTER TECHNOLOGIES CONNECTED TO PUBLIC NETWORK

Novel Approach to Develop Behavioral Model Of 12-Pulse Converter

Centralized Supplementary Controller to Stabilize an Islanded AC Microgrid

DEVELOPING methods and techniques to quantify the

Adaptive Fuzzy Logic Power Filter for Nonlinear Systems

Managing Emergency Generators

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

Harmonic Modeling of Networks

Electromagnetic Modelling Process to Improve Cabling of Power Electronic Structures

Energy Conversion and Management

Chapter 2 Voltage-, Current-, and Z-source Converters

Analysis on the Operating Characteristic of UHVDC New Hierarchical Connection Mode to AC System

Power Quality. Guide for electrical design engineers. Power Quality. Mitigation of voltage unbalance

and cables for offshore wind connection

ELECTRICAL ENGINEERING

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

AN INDEPENDENT LOOPS SEARCH ALGORITHM FOR SOLVING INDUCTIVE PEEC LARGE PROBLEMS

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

The Existence of Multiple Power Flow Solutions in Unbalanced Three-Phase Circuits

FLEXIBLE ac transmission system (FACTS) devices give

Two-Layer Network Equivalent for Electromagnetic Transients

ET4119 Electronic Power Conversion 2011/2012 Solutions 27 January 2012

EREC G5 Stage 2 Sub-group. Meeting No. 5. Held at National Grid House, Warwick Technology Park, Gallows Hill, Warwick, United Kingdom CV34 6DA

Model M3484 Industrial Line Noise Filter Module Customer Reference Manual

Design and Control of a Buck Boost Charger-Discharger for DC-Bus Regulation in Microgrids

The Effects of Mutual Coupling and Transformer Connection Type on Frequency Response of Unbalanced Three Phases Electrical Distribution System

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

CAPACITOR PLACEMENT IN UNBALANCED POWER SYSTEMS

Study on Identification of Harmonic Contributions Between Utility and Customer

A simple model based control of self excited induction generators over a wide speed range

Lecture 05 Power in AC circuit

An Intelligent Control Strategy for Power Factor Compensation on Distorted Low Voltage Power Systems

Notes for course EE1.1 Circuit Analysis TOPIC 10 2-PORT CIRCUITS

Section 1: Introduction

KINGS COLLEGE OF ENGINEERING Punalkulam

An improved methodology for determining MV to LV voltage unbalance transfer coefficient

Module 3 : Sequence Components and Fault Analysis

Proceedings of the 13th WSEAS International Conference on CIRCUITS

State Estimation and Power Flow Analysis of Power Systems

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Predicting the risk of non-compliance to EMC requirements during the life-cycle

Inducing Chaos in the p/n Junction

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Modeling and Simulation of DIGSILENT-based Micro-grid System

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Chapter 15 Power And Harmonics in Nonsinusoidal Systems

Project Components. MC34063 or equivalent. Bread Board. Energy Systems Research Laboratory, FIU

Philippe Wendling

Utility Harmonic Impedance Measurement Based on Data Selection

Elevated Neutral to Earth Voltages Due to Harmonics A T&D Update

Power Electronics

SoC Balancing of Different Energy Storage Systems in DC Microgrids Using Modified Droop Control

Generalized Dynamic Phasor-Based Simulation for Power Systems

Fault Calculation Methods

Sensibility Analysis of Inductance Involving an E-core Magnetic Circuit for Non Homogeneous Material

Order Reduction of the Dynamic Model of a Linear Weakly Periodic System Part II: Frequency-Dependent Lines

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Technology Computer Aided Design (TCAD) Laboratory. Lecture 2, A simulation primer

Power efficiency and optimum load formulas on RF rectifiers featuring flow-angle equations

Modeling charge polarization voltage for large lithium-ion batteries in electric vehicles

Simple hardware implementation of voltage balancing in capacitor-clamped inverter

A Review and Modeling of Different Droop Control Based Methods for Battery State of the Charge Balancing in DC Microgrids

Hybrid Time Domain Simulation: Application to Fault Induced Delayed Voltage Recovery (FIDVR)

Damping resistor design consideration

ECE2262 Electric Circuits. Chapter 6: Capacitance and Inductance

Implementation Possibilities of SMD Capacitors for High Power Applications

für for T5-Lampen fluorescent in Multi-Lamp-Technologie

POWER electronic converters contribute significantly to

Brief Steady of Power Factor Improvement

Chapter 8 VOLTAGE STABILITY

EN Power Electronics and Machines

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT

Introduction To Voltage Surge Immunity Testing

Review of Basic Electrical and Magnetic Circuit Concepts EE

LCR Series Circuits. AC Theory. Introduction to LCR Series Circuits. Module. What you'll learn in Module 9. Module 9 Introduction

Switched Mode Power Conversion Prof. L. Umanand Department of Electronics Systems Engineering Indian Institute of Science, Bangalore

EMC Standards. Samuel Burri 2013, EPFL

POWER QUALITY MEASUREMENT PROCEDURE. Version 4 October Power-Quality-Oct-2009-Version-4.doc Page 1 / 12

Harmonic Domain Periodic Steady State Modeling of Power Electronics Apparatus: SVC and TCSC

EE Branch GATE Paper 2010

A NEW GENERATION OF ECGs QUICKTRONIC MULTIWATT ONE FOR MANY THERE IS LIGHT. AND THERE IS OSRAM.

Introduction to AC Circuits (Capacitors and Inductors)

7. CONCLUSIONS & SCOPE

INSTRUMENTAL ENGINEERING

LED lamp driving technology using variable series-parallel charge pump

Wavelet Entropy Based Algorithm for Fault Detection and Classification in FACTS Compensated Transmission Line

Power Flow Analysis of Radial Distribution System using Backward/Forward Sweep Method

Solved Problems. Electric Circuits & Components. 1-1 Write the KVL equation for the circuit shown.

Nonlinear Electrical FEA Simulation of 1MW High Power. Synchronous Generator System

HAL501...HAL506, HAL508 Hall Effect Sensor ICs MICRONAS INTERMETALL MICRONAS. Edition May 5, DS

Multi-transmission Lines Loaded by Linear and Nonlinear Lumped Elements: FDTD Approach

Notes on Electric Circuits (Dr. Ramakant Srivastava)

Reactive Power Flow Control of a Dual Unified Power Quality Conditioner

The colpitts oscillator family

Application of Artificial Neural Networks in Evaluation and Identification of Electrical Loss in Transformers According to the Energy Consumption

APPLICATIONS OF CONTROLLABLE SERIES CAPACITORS FOR DAMPING OF POWER SWINGS *

An Optimised High Current Impulse Source

A simple electronic circuit to demonstrate bifurcation and chaos

= V I = Bus Admittance Matrix. Chapter 6: Power Flow. Constructing Ybus. Example. Network Solution. Triangular factorization. Let

Transcription:

DISTURBANCE LOAD MODELLING WITH EQUIVALENT VOLTAGE SOURCE METHOD IN GRID HARMONIC ASSESSMENT Xavier YANG Xingyan NIU Bruno PASZKIER EDF R&D France EDF R&D China EDF R&D - France xavier.yang@edf.fr xingyan.niu@edf.fr bruno.paszkier@edf.fr ABSTRACT The subject addressed in this paper is to recommend using equivalent multi-frequency voltage source method, instead of conventional current source method, in assessing harmonic aspect of some new nonlinear loads. In grid harmonic assessment, we suggest to model the disturbance load by multi-frequency voltage source. This approach can bring about some interaction between disturbance source and grid parameters such as impedance and background harmonics. In fact, new disturbance loads are mainly built with transistor-based converters, ie, voltage source converters. Another advantage of proposed method is to study power quality issues inside micro grid, even in island mode the equivalent multi-frequency voltage source can be used to study power quality behaviour when switched in to voltage/frequency control (VF) mode. In the end, two case studies have been carried out with acceptable results compared to on-site measurements. Keywords: Harmonic impedance, high frequency harmonics, voltage source converter, micro grid. INTRODUCTION In grid harmonic assessment, disturbance load was often modelled as constant multi-frequency current source. This simplified approach had resulted in acceptable result in the past. In fact, disturbance loads were mainly built with thyristor-based converters, ie, line-commuted converter with current source nature. Current harmonics at the input of this type of converter are mainly defined by DC bus filter, only a little bit influenced by grid voltage and impedance. For this reason, disturbance load could be modelled by constant multi-frequency current source in simplified harmonic assessment (Fig. 1). For recent utility and end-user power quality studies, some harmonic issues show that equivalent current injection is not suitable to reveal actual disturbance behaviours such as harmonic interaction. For instance, this type of equivalent model can t interact with the back ground voltage harmonics from upstream grid as the equivalent current source is modelled with infinite internal impedance. Furthermore, the load type changes today: more and more voltage source converters based on transistors are used in MV and LV equipment such as switching power supplies, Adjustable-Speed Drive (ASD), EV, PV, Voltage Source Converter (VSC)-HVDC, etc. The behaviour of these new nonlinear loads changes considerably: they act no more as current source, but as voltage source with input passive Electromagnetic Compatibility (EMC) filter. For example, a general LV switching power supply is composed of a rectifier with DC capacitor that acts with voltage source behaviour (Fig. 2). The input ac current harmonic is considerably influenced by grid voltage and impedance. Apparently, the harmonic injection of this device shouldn t be modelled by constant equivalent current source. Especially for transient response, some interaction with grid impedance or background harmonics should be taken into account. Therefore, we should change modelling methods according the nature of actual non linear loads. The subject addressed by this paper is to recommend using equivalent voltage source method in harmonic assessment of some new nonlinear loads. The following figure shows the voltage source method which may be used to model the new power electronic devices such as ASD. Fig. 1: Equivalent harmonic current injection method Fig. 2: Equivalent harmonic voltage source method CIRED2015 1/5

EQUIVALENT VOLTAGE HARMONIC SOURCE METHOD Why using voltage source method A frequency domain simulator can carry out power quality assessment in a large scale grid with a low computing burden; therefore, this approach has accuracy issues while dealing with time-varying and non-linear loads such as power electronic equipment with equivalent current injection method. As mentioned above, today, there are more and more new types of power electronic devices connected to the grid. Although harmonic injection level is under control by different international and national standards, the presence of some high frequency harmonic currents > 2kHz in these new devices is not yet limited efficiently by current standards and grid codes. In practice, the impact of high frequency harmonics should not be neglected. They may reduce lifespan of other electronic devices and even disturb grid communication based on PLC (Power Line Carrier). In other side, new electronic devices are also sensitive to grid back ground high frequency voltage harmonics. The figures 3 and 4 below show the current wave shapes of a PV inverter when it is powered by different voltage supplies. Fig. 3 is with sinusoidal voltage supply. Fig. 4 is with a grid voltage disturbed by harmonics (voltage THD=5.053%, < 9 khz). The measurements show that this inverter is very sensitive to the harmonic voltages. The input current THD changes from 5.225% to 24.75% in case of disturbed power supply voltage. The above laboratory tests indicate the necessity to represent by simulation the interaction between grid background voltage harmonics and the current harmonic emission from nonlinear load. Fig. 4. Current of PV inverter with non-sinusoidal power supply voltage It is possible to estimate the above phenomenon by the proposed voltage source method. In recent practical applications such as PV and energy storage system integration, the grid-connected converters are almost all voltage source type. Furthermore, in micro grid working mode, these converters may play a role of power supply as VF node. It is thus reasonable to model these devices by equivalent harmonic voltage sources. According to Thevenin/Norton transfer theory, a nonlinear load can be theoretically represented by either current source or voltage source method at each studied frequency in terms of external equivalent behaviour (Figure 5). But in practice, a pure current source was used as it is difficult to define the parallel admittance of the current source. When connecting these models to an electric power grid for power quality assessment, the results may be very different for these two equivalent methods such as in internal harmonic interaction and harmonic impedance assessment, etc. (a). Equivalent current source Gh Jh Load (b). Equivalent voltage source Load Fig. 3. Current of PV inverter with sinusoidal power supply voltage Fig. 5: Two reciprocal modelling methods of disturbance loads CIRED2015 2/5

In comparing the above equivalent circuits, it is observed that in voltage source equivalent circuit (b), it is easier to model the disturbance source impedance, and the disturbance load acting as voltage source may become power supply in micro grid mode. That means, we can use the same source to carry out power quality assessment even in island mode. Relations in proposed modeling method In Fig. 5 (b), at each harmonic frequency, the harmonic injected into the grid is defined as follow: = + This formula indicates that the current injection of a nonlinear load has no more current source behaviour; it depends on the equivalent harmonic voltage source values and the impedance values. There are two cases to define harmonic source: If is known, the current injection can be assessed by the above formula. If is known by equipment supplier's information or by limited values, the internal voltage harmonic source can be computed by, and. impedance and background harmonic For simplifying actual case, it is possible to use grid short circuit power to define grid impedance, or for more accurate case to simulate frequency curve based on grid data base. The grid back ground harmonic may be also assessed by on-site measurement or by planning levels. Internal harmonic source impedance Generally, may be set by limited harmonic values or defined by manufacturer s data sheet. The difficulties are how to determine internal impedance and. By dynamic short-circuit power ratio For very simplifying actual case, we can set either constant ratio / according to short-circuit levels or use predefined impedance curves of and from manufacturer s data if available. This ratio is one of the key parameters to quantify the short-circuit power level when is used as power supply in island mode of micro grid. For example, the nonlinear load is 50kVA PV inverter with 150kVA dynamic short-circuit power. It is connected to 400V LV grid with short-circuit power of 3MVA at the PCC. The grid impedance is about Z1=0.031525 + j0.0441. For starting a frequency domain simulation, the harmonic source impedance can be estimated as: = *3000/150 = 0.631 + j0.882. This method is very simple approach, it may conduct some error compared to the reality, but it is more realist than equivalent constant current source method. It is also recommended to take into account input EMC filter for power quality assessment (Fig.6). EMC filter Fig. 6: Voltage source method with input EMC filter Generally, it is easy to get EMC filter s technical parameters. This filter has an important impact in HF harmonic study. It is suggested to deal with EMC filter as an independent added-in part on the impedance. This filter is normally designed for radio frequency attenuation, but it may contribute, especially its parallel capacitors, to the HF frequency harmonic magnification, from 2 to 150 khz for example. By harmonic measurement (island mode for example) In case of micro grid case, it is relatively easy to quantify frequency depended impedance of the nonlinear load. If the nonlinear load is served as power supply in island mode, it is recommended to connect a harmonic source to the circuit (Fig.7). Because the rated power is generally small in micro grid, it is possible to use a disturbance generator as the variable harmonic source. Harmonic current generator Vh Fig. 7: Harmonic source identification By varying frequency of harmonic generator, it is possible to identify the impedance by computing Vh/ at each measured frequency. If there exists same harmonic frequency from side, we can shift a little generator s frequency f h + f and f h - f in order to avoid the influence resulted from 's harmonics. The harmonic impedance can be defined by linear mean values of the impedances at these two frequencies: z z( fh ) z( f f ) fh fh ) f 2 h h h( h By time domain simulation In particular case if the power electronic structure of nonlinear load is known, it is also possible to define impedance =Vh/ by time domain simulation + FFT computation for each harmonic frequency. CIRED2015 3/5

Harmonic assessment by iteration As per above proposed method, the harmonic impedance is defined by simplified processes. For a concrete power quality simulation, voltage source should be finalized by iterations. With iteration algorithm in advanced power quality modelling, the source should be further modified in order to get accurate results. The iteration process is suggested as follow: Start load flow computation: the studied nonlinear load is modelled by its actual powers P and Q; Update the source at fundamental frequency by load flow result and the preset impedance ; Replace the equivalent load PQ by and ; Re-simulate the circuit by iteration until get correct and converged ; Launch frequency domain simulation to study power quality issues. CASE STUDIES Micro grid application The proposed equivalent voltage source method has been applied in micro grid power quality assessment. The energy storage system in this micro grid is served as either nonlinear load (charging mode) or power supply (discharging mode). It is modelled by multi frequency voltage source and its harmonic spectrum is set on basis of on-site measurement (Fig. 8). Even though the current spectra > 2kHz are not nominated as harmonic by IEC standards, here we still use the term harmonic for general representation of Fourier frequency components. Fig. 8: Equivalent voltage spectrum (magnitude in %) The impedance of source is approximately defined by the grid impedance and the ratio / set to 0.1. With this voltage harmonic source, two simulations have been carried out: the storage is controlled as PQ node in grid connected mode and as VF node in island mode. The voltage source model of this nonlinear load has been implanted into EDF's power quality simulation software and this application case study is focused on micro grid power quality study. Fig.9 shows the phase voltage and line current at the input of the energy storage model in two modes. In island mode, the harmonic source worked as voltage control mode and the power is defined by all loads of the micro grid. The result of this simulation is near the results from on-site measurements of micro grid powered by battery energy storage system. Fig. 9: Voltage and current at the input of energy storage unit of the micro grid Harmonic resonance between grid impedance and EMC filter This case study concerns a 21kW bidirectional EV charging system. Laboratory tests show the HF harmonic magnification phenomenon around 6kHz. This harmonic magnification is caused mainly by a resonance between LV grid impedance and the capacity of EMC filter of EV charger (Fig.10). The simulation result is very near that obtained from laboratory tests. Fig. 10: HF harmonic magnification (current harmonic values in %) CIRED2015 4/5

CONCLUSION The proposed multi-frequency voltage source method in disturbance load modelling is naturally compatible with voltage source converter used in new power electronic equipment such as ASD, PV, EV, energy storage, etc. It is possible to simulate certain harmonic interaction between nonlinear loads and upstream grid. Another important advantage of this method is capable to represent nonlinear load both in grid connected and island modes. It is thus adaptable to represent distributed source simulation in micro grid as it works correctly as power supply in island mode as VF node. With proposed method, it is possible to enhance some commercial simulation tools in disturbance assessment as these tools still use equivalent constant harmonic current method in disturbance load modelling. FURTHER WORK AND PERSPECTIVES The key step in using proposed multi-frequency voltage source method is to define correctly internal source parameters. The method is not perfect yet, but it gives the possibility to deal with certain harmonic interaction with upstream grid and represent harmonic sources with voltage behaviours. In the future, other advanced harmonic methods should be taken into account in power quality studies: Hybrid approach between time & frequency domains For well-known structure of nonlinear load, it is recommended to create embedded time domain modeling unit [5] inside a frequency domain simulation tool. The non-linear load such as power electronic device can ban be modeled by time domain [5] or by crossed frequency admittance matrix extracted from steady-state differential equations [2][3][4] and the results will be exported to frequency domain power quality studies. This approach makes it available to deal with directly an actual distribution grid database including more than thousands of nodes. Frequency coupling admittance matrix by laboratory tests The crossed frequency admittance matrix proposed by [2][3][4][6] result from analytical resolution of wellknown steady-state differential equations. This approach gives very good result in harmonic assessment. Therefore, it is impossible to be used on unknown nonlinear load modeling. That is why we suggest building frequency coupling admittance matrix by laboratory tests. The modeling methods "linear" are quite unsuited to define the behavior of non linear devices like inverters. That's why we tested a model with a neural network method. A neural network can be seen as a function between its inputs and outputs that has several parameters set by a learning algorithm. It is then able to predict the value of the output variables whatever input values. As the figure below shows with laboratory tests, this method gives much better results than linear regression methods. In addition, the power delivered by the inverter can be counted as an input parameter. Fig. 11: Relative errors to the fundamental current obtained with the different modeling methods We will use this modelling method as part of our harmonic impact studies of new uses on the French DNO networks. REFERENCES [1] IEEE Harmonics Modeling and Simulation Task Force, Modeling and Simulation of the Propagation of Harmonics in Electric Power Networks: Part I, IEEE Trans. on Power Delivery, vol. 11, n 1, Jan 1996, pp. 466-474. [2] M. Fauri, Harmonic modeling of non-linear load by means of crossed frequency admittance matrix, IEEE transactions on Power Systems, Vol. 12, No. 4, November 2001, page 1632-1638. [3] K. L. Lian, B. K. Perkins and P. W. Lehn, Harmonic analysis of a three-phase diode bridge rectifier based on sampled-data model, IEEE Trans. Power Del., vol. 23, no. 2, April. 2008. [4] Jing Yong, Liang Chen, Alexandre B. Nassif, and Wilsun Xu, A Frequency-Domain Harmonic Model for Compact Fluorescent Lamps, IEEE Transactions On Power Delivery, v. 25, no. 2, 2010. [5] X. YANG, Y. XIAO, S. NGUEFEU, Power quality assessment when integrating an HVDC link into existing power grids, CIGRE 2010, B4_303. [6] J. G. Mayordomo, A. Carbonero, L. F. Beites, R. Asensi and W. Xu, A contribution towards a general and systematic procedure for modeling line commutated AC/DC converters in the harmonic domain, IEEE Trans. Power Del., vol. 24, no. 4, pp. 2415-2427, Oct. 2009. [7] V. Caliskan, D. Perreault, T. Jahns and J. Kassakian, Analysis of three-phase rectifiers with constantvoltage loads, IEEE Trans. Circuits Syst., vol. 50, no. 9, pp. 1220-1226, Sep. 2003. CIRED2015 5/5