A COMPARISON OF HEAT TRANSFER AROUND A SINGLE SERRATED FINNED TUBE AND A PLAIN FINNED TUBE

Similar documents
Basic Concepts: Drag. Education Community

Calculations on a heated cylinder case

SHELL-AND-TUBE TEST PROBLEMS

UNIT II CONVECTION HEAT TRANSFER

University of Huddersfield Repository

FLOW SIMULATION AND HEAT TRANSFER ANALYSIS USING COMPUTATIONAL FLUID DYNAMICS (CFD)

II. GOVERNING AND CFD EQUATION

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

Vertical Mantle Heat Exchangers for Solar Water Heaters

COMPUTATIONAL FLUID DYNAMICS ON DIFFERENT PASSAGES OVER A PLATE COIL EVAPORATOR FOR 40 LITER STORAGE TYPE WATER COOLER

Air Flow through Woven Stainless Steel Mesh

Numerical Analysis of Tube-Fin Heat Exchanger using Fluent

FLOW MALDISTRIBUTION IN A SIMPLIFIED PLATE HEAT EXCHANGER MODEL - A Numerical Study

Particles Removal from a Moving Tube by Blowing Systems: A CFD Analysis

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel

ENGR Heat Transfer II

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

Numerical and Experimental Study on the Effect of Guide Vane Insertion on the Flow Characteristics in a 90º Rectangular Elbow

CFD study for cross flow heat exchanger with integral finned tube

FLUID FLOW AND HEAT TRANSFER INVESTIGATION OF PERFORATED HEAT SINK UNDER MIXED CONVECTION 1 Mr. Shardul R Kulkarni, 2 Prof.S.Y.

Iran University of Science & Technology School of Mechanical Engineering Advance Fluid Mechanics

SIMULATION OF THERMAL CHARACTERISTICS OF RADIATORS USING A POROUS MODEL. YETSAN Auto Radiator Co. Inc Çorum, Turkey NOMENCLATURE

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

EFFECTIVENESS OF HEAT TRANSFER INTENSIFIERS IN A FLUID CHANNEL

Overall Heat Transfer Coefficient

NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS

Active Control of Separated Cascade Flow

CFD MODELLING OF A SUBSEA COOLER FOR CALCULATION OF EXTERNAL HEAT TRANSFER COEFFICIENT

Principles of Convection

Lecture 30 Review of Fluid Flow and Heat Transfer

Heat and Mass Transfer Unit-1 Conduction

Numerical study of battle damaged two-dimensional wings

Chapter 3 NATURAL CONVECTION

Numerical Simulation of Fluid Flow and Heat Transfer in a Plasma Cutting Torch

NUMERICAL SIMULATION OF FLOW THROUGH TURBINE BLADE INTERNAL COOLING CHANNEL USING COMSOL MULTIPHYSICS

arxiv: v1 [physics.app-ph] 25 Mar 2018

TUBE BANKS TEST PROBLEMS

Convection. forced convection when the flow is caused by external means, such as by a fan, a pump, or atmospheric winds.

Unit operations of chemical engineering

Optimization of Shell And -Tube Intercooler in Multistage Compressor System Using CFD Analysis

HEAT TRANSFER. Mechanisms of Heat Transfer: (1) Conduction

Analysis of the Cooling Design in Electrical Transformer

INTRODUCTION: Shell and tube heat exchangers are one of the most common equipment found in all plants. How it works?

CFDOFAIRFLOWINHYDROPOWERGENERATORS

A numerical study of heat transfer and fluid flow over an in-line tube bank

Experimental Verification of CFD Modeling of Turbulent Flow over Circular Cavities using FLUENT

The Effect of Solid and Perforated Pin Fin on the Heat Transfer Performance of Finned Tube Heat Exchanger

External Forced Convection. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

CONCENTRIC EXCHANGER TEST PROBLEMS

The effect of geometric parameters on the head loss factor in headers

External Flow and Boundary Layer Concepts

Heat Transfer F12-ENG Lab #4 Forced convection School of Engineering, UC Merced.

Keywords: air-cooled condensers, heat transfer enhancement, oval tubes, vortex generators

Practical Analysis Of Turbulent Flow In A Pipe Using Computational Fluid Dynamics

WALL ROUGHNESS EFFECTS ON SHOCK BOUNDARY LAYER INTERACTION FLOWS

Applied Fluid Mechanics

Outlines. simple relations of fluid dynamics Boundary layer analysis. Important for basic understanding of convection heat transfer

Analyzing Mass and Heat Transfer Equipment

If there is convective heat transfer from outer surface to fluid maintained at T W.

CFD Simulation on Supercritical Fluid Extraction of Black Pepper's Bioactive Compounds: Single Particle Study

ME 431A/538A/538B Homework 22 October 2018 Advanced Fluid Mechanics

Numerical Investigation of Convective Heat Transfer in Pin Fin Type Heat Sink used for Led Application by using CFD

PERFORMANCE SCREENING OF A LOUVERED FIN AND VORTEX GENERATOR COMBINATION

Drag reduction in a class 8 truck - scaled down model

ESRL Module 8. Heat Transfer - Heat Recovery Steam Generator Numerical Analysis

A Computational Investigation of a Turbulent Flow Over a Backward Facing Step with OpenFOAM

CHAPTER 4 OPTIMIZATION OF COEFFICIENT OF LIFT, DRAG AND POWER - AN ITERATIVE APPROACH

Validation 3. Laminar Flow Around a Circular Cylinder

Numerical study of 2D heat transfer in a scraped surface heat exchanger

Heat Transfer Simulation by CFD from Fins of an Air Cooled Motorcycle Engine under Varying Climatic Conditions

CFD Investigation of Heat Transfer and Flow Patterns in Tube Side Laminar Flow and the Potential for Enhancement

Explicit algebraic Reynolds stress models for internal flows

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway

Design and study of pressure drop and temperature distribution characteristics in a shell and tube heat exchanger using Computational Fluid Dynamics.

International Conference on Energy Efficient Technologies For Automobiles (EETA 15) Journal of Chemical and Pharmaceutical Sciences ISSN:

Countercurrent heat exchanger

Axial profiles of heat transfer coefficients in a liquid film evaporator

Thermo-Hydraulic performance of Internal finned tube Automobile Radiator

Vortex Induced Vibrations

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

Numerical Investigation on Air Side Performance of Fin and Tube Heat Exchnagers with Different Types of Fins

Design of Test Section for Coriolis Rig and Numerical Simulation of Cooling Flow Through Test Section

Convection Heat Transfer. Introduction

Effective Heat Transfer Enhancement in Finned Tube Heat Exchanger with Different Fin Profiles

Wall treatments and wall functions

SIMULATION OF FLOW STRUCTURE AND HEAT TRANSFER ENHANCEMENT IN A TRIANGULAR DUCT WITH RECTANGULAR WING

Tutorial for the heated pipe with constant fluid properties in STAR-CCM+

Piping Systems and Flow Analysis (Chapter 3)

In Chapter 6 we considered the general and theoretical aspects of forced

Numerical Study of Convective Heat Transfer for Flat Unglazed Transpired Solar Collectors

INSTRUCTOR: PM DR MAZLAN ABDUL WAHID

Enhance the Efficiency of Heat Exchanger with Helical Baffle

Introduction to Turbulence AEEM Why study turbulent flows?

Numerical Heat Transfer Study of Turbulent Square Duct Flow through W-Type Turbulators

Chapter 8 COOLING AND HEAT TRANSFER. 8.1 Importance of thermal analysis. 8.2 Heat transfer modes

CHAPTER 3 MODELLING AND ANALYSIS OF THE PACKED COLUMN

Chapter 3 Lecture 8. Drag polar 3. Topics. Chapter-3

Lecture-4. Flow Past Immersed Bodies

Transcription:

IJRRAS 2 (2) February A COMPARISON OF HEAT TRANSFER AROUND A SINGLE SERRATED FINNED TUBE AND A PLAIN FINNED TUBE S. R. MCILWAIN School of Engineering, University of the West of Scotland, Hamilton, Scotland ABSTRACT With comparable bundle geometry, serrated fin finned tube heat exchangers transfer more heat than plain finned ones. There are believed to be many factors in this behaviour, and this investigation used CFD to examine the heat transfer and fluid flow patterns around the fins to try to understand the magnitude of the differences in the processes. The study is a first step in developing a new theory-based method to predict the performance of serrated fin tube bundles. Keywords: serrated fins, CFD, heat recovery, furnaces, finned tube, air cooling, performance prediction 1. INTRODUCTION Serrated, or cut fins, are commonly used in heat recovery applications and are generally regarded as having a higher heat transfer coefficient than plain fins. They are also credited with inducing a higher pressure drop across a tube bundle. This study is a first step into the characterisation of the flows around serrated finned tube in comparison to plain finned tube, investigating the heat flow through the fin, the heat transferred and the magnitude and effects of turbulence generated by the discontinuous fin shape. This is achieved using Computational Fluid Dynamics (CFD) to compare the flow and heat patterns using a like-for-like comparison at prescribed gas velocities. The finned tube considered in this study is based on the geometry of an industrial tube bundle as used in furnace heat recovery applications. The fin type is a partially cut serrated type; there is a plain portion of fin and then the serrated portion above it on the fin radius. To minimise computational requirements, and to provide a definite basis for comparison without complication from the row effect, only one tube row was modeled. 2. CFD MODELS 2.1 Bundle geometry To reduce cycle time and minimise computer resources a modeling approach previously designed by the author [1] was used. This maximises symmetry planes and meant that only a small slice of a heat exchanger need to be represented. The model s mesh was separated into four main blocks for both plain fin and serrated fin models; an entry, a tube section, an initial outlet and the final outlet to allow for wake renormalization. The layout of the model domain is shown in Figures 1 and 2. Table 1 describes the tube and fin geometry of the plain fin design. The serrated geometry was the same as the plain fin described in Table 1, but with the additional data of Table 2 describing the blade geometry. Figure 1: Layout of the CFD meshes (serrated fin shown, not to scale) 88

IJRRAS 2 (2) February Figure 2: The gasflow approach view to the model (not to scale) Dimensions mm D f 88.9 D o.7 D i 48.7 s f 1.2 n f 239 Table 1: Dimensions of plain finned tube Dimensions mm H sf 6.62 W b 4.7 n b 41 Table 2: Additional dimensions of serrated finned tube 2.2 Solver conditions The default air physical properties in the CFD package are single values, and hence are fixed regardless of temperature. Due to the temperature variations encountered in the simulation a set of fifth order temperature dependant polynomials were used. These allowed variation in density, thermal conductivity, viscosity and specific heat capacity at constant pressure. The k-ε Realizable turbulence model was used as per the author s previous experience. The near-wall model was used to ensure that the turbulent regions around the serrated fin s edges were computed using a turbulence model rather than using a laminar wall function approach, as is default. Second order methods of determining the pressure-velocity relation and pressure interpolation were used, as the mesh in some regions was not well aligned with the bulk flow direction, and this technique was found to aid the resolution of the values in the non-aligned cells. It had been found previously that by modifying the turbulent Prandtl number the heat transfer results were a better match for the experimental data; therefore the same modification was adopted for this study. 2.3 Boundary conditions The ranges of velocities used in the simulations were 1-5m/s in 1 m/s increments. These are typical gas velocity values for 2 inch tube diameter heat recovery bundles used in heat recovery and economizer operations. In heat recovery applications the gasflow over the tube should be a hot stream. As the difference in heat transfer performance is of interest the typical operation was reversed to a use a previously developed approach for modeling isothermally condensing air-coolers, as in like for like comparison this would be acceptable for examining the differences between the fin types. This also allowed the wide use of symmetry planes in the model, rather than accounting for cooling tubeside fluid. Hence the approach airflow temperature was set at 293 o K and the tube s inner wall set to 373 o K. 3. SIMULATION RESULTS As the fins cannot be considered in isolation, which is away from the tube section, the results were obtained in the form of mass-weighted average values on planes running tangential to the fin surface, as shown in Figure 3. These values are therefore more representative of the heat exchangers full performance than considering the fin on its own. 89

IJRRAS 2 (2) February Figure 3: Position of the planes used for analysis values 3.1 Air temperature rise and pressure The overall air temperature rise and pressure drop of the bundles is shown in Table 3. It can be seen that the pressure drop increases more rapidly for the serrated fins, whereas the difference in air temperature is nearly constant. In terms of duty this translates to an average raise of 7.9% across the approach velocity range but with an increasing pressure drop penalty varying between.5 to %. Airflow velocity (m/s) 1 2 3 4 5 Plain Fin (Pa) Pressure Drop Serrated Fin (Pa) Plain Fin ( o K) Temperature rise Serrated Fin ( o K) 2.98 2.99 17.36 19.3 8.25 8.41 13.1 13.74 16.22 17.16.49 11.22 26.62 28.86 8.89 9.72 38.94 43.24 7.78 8.7 Table 3: Bundle pressure drop and air temperature rise 3.2 Air temperature across fin/tube unit The temperatures on the planes shown in Figure 3 were plotted and the results are shown in Appendix A. It can be seen that the air temperature on all planes, except the initial one (9mm), is constantly higher for the serrated fins. 3.3 Overall turbulence Appendix B shows the % turbulence intensity on the planes. It can be seen that the turbulence intensity is generally higher in the serrated fin models, however in each case there is similarity in the values on the final plane. 4. FLOW PATTERNS 4.1 Heat flow The exposed surface area of the serrated fin was 95.2% that of the plain fin. Given that extended surface area is considered of paramount importance in a heat exchanger, and that the tube area is constant in both designs, the results indicate that the extra heat transfer must be due to the shape factor. Figures 4 and 5 show the temperature contours on the surface of the plain and serrated fins, respectively. 9

IJRRAS 2 (2) February Figure 4: Temperature contours on plain fin at 3 m/s (flow left to right, scale in o K) Figure 5: Temperature contours on serrated fin at 3 m/s (flow left to right, scale in o K) It can be seen that on the leading edge of the serrated fin that the temperature is higher at approximately 329 o K than on the same region on the plain fin, which is approximately 317 o K. The temperature in the wake region in Figure 5 and immediately around the tube can be seen to be noticeably higher than that of the plain fin case, indicating a higher heat flow through the fin. The blades in the wake region of Figure 5 show a significantly higher temperature, and given that this is over a reasonable proportion of surface area this region alone will contribute significantly to the improved heat transfer, even though the effect is partially created by recirculating flow. The comparisons for 1, 2, 4 and 5 m/s are similar, and hence are not shown. 4.2 Airflow characteristics The reduced surface area of the serrated fin will result in reduced skin friction drag, but with the irregular shape of the blade protrusions into the oncoming flow the results would indicate that this was overcome by an increase in excrescence drag. In investigations into the local velocities around the fin surface it was seen that separation on the blade at the front of the fin was pronounced when compared to the separation that occurs over the plain fin leading edge. This would promote increased drag, and hence overall pressure drop, as seen in Table 3. The flow simply entered the gaps between blades, and then separated. There was very little evidence of recirculation behind the fins around the middle of the tube and none of flow crossover between the opposite sides of the blade, rather the flow stagnated behind the blades. Due to the irregular shapes in the flow and the edges of the blades there are more contrasting flows local to the serrated fin surface and hence more turbulence was generated than by plain fins, as shown in Figure 5. Figure 5 also shows that there is significantly more turbulence over the middle section of the serrated fin than over the plain fin. This is due to the highly channeled flows between the blades on the front and the blades on the mid section of the fin causing separations, and therefore adding disturbances to the largely isotropic flow over the front of the tube region. At the rear of the tube the turbulence of both fin types is comparable, which indicates that the turbulence is almost reducing for the serrated case, rather than either maintaining the difference or increasing it. The reasons for this are 91

IJRRAS 2 (2) February unclear, but may lie with the recirculation and wake effects developing over the rear of the tube being a much larger driving force, and that the extra turbulence generated by serrated fins becomes homogenised with the bulk flow, as with the plain fin example. 5. CONCLUSIONS Though the single row heat exchanger is a special case, it can be seen that serrated fins improve the heat transfer although the mechanism may not be as amenable to a straightforward treatment as reported by previous workers, such as Weierman [2,3] and Ganapathy [4]. The results suggest that the heat transfer increase due to increasing turbulence that is often attributed to serrated fins may only be effective in certain regions, and would suggest that the access of the airflow further into the fin material is a larger driver in the heat transfer process. A further study with differing geometries may answer this question more fully. NOMENCLATURE D f Fin tip diameter m D o Outer tube diameter m D i Inner tube diameter m H sf Height of solid component of fin m n b number of blades per fin - n f Fin frequency - P Pressure drop Pa s f Mean fin thickness m W b Width of blade m REFRENCES [1] S.R Mcilwain, Improved prediction methods for finned tube bundle heat exchangers in crossflow, Ph.D Thesis, University of Strathclyde, Glasgow, 3 [2] C. Weierman, Pressure drop data for heavy duty finned tubes, Chemical engineering progress, 73, pp 69-72, 1977 [3] C. Weierman, Correlations ease the selection of finned tubes, The Oil and Gas Journal, Vol.74, pp 94-, 1976 [4] V. Ganapathy, Design and evaluate finned tube bundles, Hydrocarbon processing, Vol.75, No.9, pp3-111, 1996 APPENDIX A - Comparison of air temperature on planes Average air temperature on planes (1 m/s) Average air temperature on planes (2 m/s) 3 1m/s Plain 1 m/s Serrated 3 2m/s Plain 2 m/s Serrated 5 5 a. b. 92

Turbulence intensity (%) Turbulence Intensity (%) IJRRAS 2 (2) February Average air temperature on planes (3 m/s) Average air temperature on planes (4 m/s) 3 3m/s Plain 3 m/s Serrated 3 4 m/s Plain 4 m/s Serrated 5 5 c. Average air temperature on planes (5 m/s) d. 3 5 m/s Plain 5 m/s Serrated 5 e. APPENDIX B - Comparison of flow turbulence on planes Average turbulence intensity on planes (1 m/s) 8 Average turbulence intensity on planes (2 m/s) 7 1m/s Plain 1 m/s Serrated 2m/s Plain 2 m/s Serrated a. b. 93

Turbulence Intensity (%) Turbulence Intensity (%) Turbulence Intensity (%) IJRRAS 2 (2) February 8 Average turbulence intensity on planes (3 m/s) Average turbulence intensity on planes (4 m/s) 7 9 8 7 3 m/s Plain 3 m/s Serrated 4 m/s Plain 4 m/s Serrated c. 9 Average turbulence intensity on planes (5 m/s) d. 8 7 5 m/s Plain 5 m/s Serrated e. BIOGRAPHY: Dr. Stuart Mcilwain received a B.Eng (Hons) degree in Automotive Engineering from the University of Hertfordshire. After a period working for the UK National Engineering Laboratory he received a Ph.D. in mechanical engineering from the University of Strathclyde. Currently, he is a lecturer at the University of the West of Scotland. His research interests include fluid mechanics and thermal engineering. He is also a retained consultant to a number of local and international companies on fluid and thermal design issues 94