INSTRUCTION MANUAL FOR MM10 Relay

Similar documents
MPR500 Motor Protection Relay User's Guide

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

XM1 Motor Protection Relay. Manual XM1 (Revision B)

CR10XTCR THERMOCOUPLE REFERENCE

3VT4 Molded Case Circuit Breakers up to 1000 A

CR10TCR THERMOCOUPLE REFERENCE

CR10XTCR THERMOCOUPLE REFERENCE

MODEL 107 TEMPERATURE PROBE INSTRUCTION MANUAL

VIBRATION METER. Instruction Manual.

Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

PTA-427 BAROMETRIC PRESSURE TRANSDUCER OPERATOR S MANUAL

Operating Instructions for Digital Manometer. Model: MAN-SD

MODELS Number WW4.x For Europe & Others V 50HZ

Instruction Manual SEFRAM Thermal Camera

CTC 155 / 350 / 660 Dry-block calibrator

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Mini Environmental Quality Meter

INSTRUCTION AND MAINTENANCE MANUAL FOR TECHTROL COUNTER CONTROLLER & TOTALISER (TCCT)

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

566/568. Infrared Thermometers. Getting Started

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

Digital Fluxmeter CYHT700SP

CAUTION: BEFORE YOU BEGIN, ALWAYS MAKE SURE THE WEAPON IS UNLOADED AND SAFE TO HANDLE.

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

SUBJECT TO CHANGE WITHOUT NOTICE

3WHB10K 3-WIRE HALF BRIDGE TERMINAL INPUT MODULE INSTRUCTION MANUAL

Bright Advance Corporation

TH2821B Portable LCR Meter

Instruction Manual. DTP Series DC Termination Panels

SkyScan EWS-PRO - Manual -

Low Pressure Sensor Amplified Analog Output SM6295-BCM-S

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

E6C-N. Ideal for Out-of-step Detection of Stepping Motors and Position Control of Rotors and Unloaders

Integrated Suppression Module

Impedance relay and protection assemblies

Small Absolute Pressure Sensor

Small, Gauge Pressure Sensor

Field Pro Operation and Installation Manual

product manual H-3220A Benkelman Beam

Hadrons Desktop U.S. Atomic Clock & Weather Station

XD1-L Cable Differential Protection Relay

DPR User Manual. LG Digital Protection Relays

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

user's manual nx frequency converters resolver option board opt-bc

Small Gage Pressure Sensor

Lamp and Control Panel (Lamp Panel)

WE RE HERE TO HELP: 1 (844) LIGHTCLOUD

VIBRATION METER Acceleration & Velocity Model : VB-8201HA

Minute Impulse Clock Controller I01DN

Medium Pressure Sensor Analog Output

INSTRUCTION MANUAL Milwaukee Refractometer MA881 Refractometer for Invert Sugar Measurements

NLSV2T Bit Dual-Supply Inverting Level Translator

BMXART0814 analog input module M340-8 inputs - temperature

INSTRUCTION MANUAL DTH Fax: (503)

NOVALYNX CORPORATION MODEL 110-WS-16BP BAROMETRIC PRESSURE SENSOR INSTRUCTION MANUAL

CALEFFI. Modulating digital controller for heating and cooling. 161 series 01122/08 GB. replaces dp 01122/05

Acceleration/Velocity/Displacement VIBRATION METER

NLSV22T244. Dual 2-Bit Dual-Supply Non-Inverting Level Translator

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

MARKING DIAGRAMS DIP PIN ASSIGNMENT ORDERING INFORMATION FUNCTION TABLE CDIP 16 L SUFFIX CASE 620 MC10136L AWLYYWW

5SJ4...-.HG Circuit Breakers to IEC and UL 489

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

Instruction Manual HI Refractometer for Sodium Chloride Measurements

FIELD GUIDE FOR HORUS SCOPES

User s Manual: MODEL 904-T CLINOMETER PAK

HS515G-M. PARALOW Circle Dot Sight. User's Manual. Holosun Technologies Inc. Phone: (909) Fax: (909)

Microcare LCD Solar MPPT User Documentation

SKELESCOPE REFLECTOR TELESCOPE WITH TABLE TOP TRIPOD SK-100 INSTRUCTION MANUAL

MARKING DIAGRAMS 16 LOGIC DIAGRAM DIP PIN ASSIGNMENT CLOCKED TRUTH TABLE ORDERING INFORMATION CDIP 16 L SUFFIX CASE 620

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

INSTRUCTION MANUAL Milwaukee Refractometer MA886 Refractometer for Sodium Chloride Measurements

Softstarter range type PSD & PSDH

VK2 volume flow controller Overview

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

Non-Contact Safety Systems CMS

The MC10107 is a triple 2 input exclusive OR/NOR gate. P D = 40 mw typ/gate (No Load) t pd = 2.8 ns typ t r, t f = 2.

LOW POWER SCHOTTKY. GUARANTEED OPERATING RANGES ORDERING INFORMATION PLASTIC N SUFFIX CASE 648

Sealing possibility Electrical endurance (ops) Mechanical endurance (ops) Overvoltage category Standards

Single cam type. Double cam type. Grip force N. Type Model/size Stroke Screw type straight style. Screw type tee style

SPECIFICATION SHEET : FHS2-UNV-36L

MAGMA NOTE! 21+ USER MANUAL

IR F ( C) ENGLISH INSTRUCTION MANUAL. Thermometer

INSTRUCTION MANUAL Milwaukee Refractometer MA888 Refractometer for Ethylene Glycol Measurements

Instruction Sheet COOL SERIES DUCT COOL LISTED H NK O. PR D C FE - Re ove r fro e c sed rea. I Page 1 Rev A

WeatherHub2 Quick Start Guide

MC Bit Magnitude Comparator

SN74LS145MEL. 1 of 10 Decoder/Driver Open Collector LOW POWER SCHOTTKY

MET ONE RAIN GAGE MODELS 380, 385, 380M, 385M

Lightcloud Application

User s Guide. Waterproof Palm ph Meter Model PH220. Introduction

5 V 64K X 16 CMOS SRAM

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

MODEL HMP45C TEMPERATURE AND RELATIVE HUMIDITY PROBE INSTRUCTION MANUAL

MC74AC132, MC74ACT132. Quad 2 Input NAND Schmitt Trigger

SK Series BOX PLOW INSTALLATION & OWNER S MANUAL TABLE OF CONTENTS

INSTRUCTION MANUAL. Laser Diode Sarcomere Length. Aurora Scientific Inc. 360 Industrial Parkway South, Unit 4 Aurora, Ontario, Canada L4G 3V7

xlogic SuperRelay is a compact and expandable CPU replacing mini PLCs, multiple timers, relays and counters.

OEM Silicon Pressure Die

Transcription:

INSTRUCTION MANUAL FOR MM10 Relay Motor Protection Relay

Front Panel Overview V1 250614 MM10 Motor Protection Relay a I L1 b I L2 I L3 c h i d e I L1 Figure 1: Front panel overview f g I L2 a Run LED b Trip/Pickup LED c Thermal LED d Down key e Up key f Reset/Mode key g Test key h Function LED i Data LED 1. General Description MM10 is a motor protection relay that combines thermal overload, short circuit, undercurrent, unbalance, phase loss, phase sequence, lock/stall rotor and earth fault protections. MM10 incorporates a 4digit LED indicator which allows direct numerical readout of set values, actual measured value and system indication. MM10 has 2 relay outputs (R1 and R2). R1 is On under normal operating condition to allow motor running, and off during tripping. R2 is programmable to give signal in various conditions. A programmable binary input is provided to perform various operations upon binary input triggering. 2. Display Symbols t 6X Thermal overload constant I>> Short circuit/high set Overcurrent t>> Short circuit/high set Overcurrent delay I< Undercurrent t< Undercurrent delay t Unbalance Unbalance delay I 0 > Earth fault t 0 > Earth fault delay I S >> Prolonged starting/stall rotor t Start Prolonged starting delay t Stall Stall rotor delay I B Base/full load current CT External current transformer ratio SW Soft switch 2.1 Current and Thermal Capacity Display During power up, when the relay is not under tripping condition, the display shows current in ampere or thermal capacity %. The Function LED indicates which parameter is being displayed. The Data LED showing value. I L3 I 0 Thermal Figure 2: Current and thermal capacity display For current more than 1000A, a dot is shown behind least significant digit. Eg: 1.25. = 1.25kA I L1 Phase 1 current IL2 Phase 2 current I L3 Phase 3 current I 0 Zero sequence/earth fault current Thermal % Thermal capacity % (Thermal overload tripping at 100%) During Thermal capacity display, thermal capacity can be cleared to 0% by pressing "UP" and "DOWN" simultaneously for longer than 1.5 seconds. Warning: Clearing thermal capacity effectively reset to cold start condition, user is not encouraged to clear thermal capacity unless it is sure that motor is cool enough to run/start within its thermal limit. Press UP or DOWN to scroll through the parameters. 1

2.2 Auto Scroll When auto scroll is enabled, the display scrolls between currents and thermal reading every 10 seconds. To toggle auto scroll mode, press "UP" and "DOWN" simultaneously. 2.3 LED Display a) Run LED Run LED shows the motor status. Refer to 3.2.1 Motor Starting. Off Blink On b) Trip LED Motor stopping Motor starting Motor running Trip LED is normally off. During tripping pickup, where tripping delay is counting down, Trip LED blinks. Trip LED on during tripping. Off Blink On Normal Pickup Tripping Current/Thermal Display Tripping History 1 t 6X Thermal overload constant 2 I>> Short circuit 3 t>> Short circuit delay 4 I<< Undercurrent 5 t<< Undercurrent delay 6 Unbalance 7 t Unbalance delay 8 I 0 >> Earth fault 9 t 0 >> Earth fault delay c) Thermal LED Thermal LED blinks when motor current is more than 105% of I B. Thermal LED on during thermal overload tripping, and when thermal capacity is more than 40% after overload tripping (in which R1 is off, motor not allowed to start) Off Blink On Normal Thermal overload warning Thermal overload tripping Thermal capacity high, R1 off A I S >> Prolonged starting / stalled rotor b t Start >> Prolonged starting delay c t Stall >> Stalled rotor delay d I B Base/full load current E External CT ratio 3. Settings and Protection Features 3.1 Setting Display When the relay is not under tripping condition, pressing "RESET/MODE" will scroll through various settings. Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3. Table 1 gives description of each setting. Tip: To quickly jump back to current/thermal display during setting display, press and hold "RESET/MODE" for 1.5 second. F1 Auto/Manual Reset F2 Binary input F3 Relay 2 function F4 Phase Sequence/ Phase Loss option F5 Frequency Figure 3: Display mode when pressing Reset/Mode 2

3.2 Programming Setting Step 1: Press "RESET/MODE" until the Function LED shows the required setting. Step 2: Press "UP" and "DOWN" simultaneously to enter programming mode. The Function LED blinks to indicate the relay is in programming mode. Step 3: Press "UP" or "DOWN" to change the value. Step 4: To save the new value, press "UP" and "DOWN" simultaneously again. Programming mode exits, function LED stop blinking. To exit programming mode without saving, press "RESET/MODE" once Setting Function Setting Range Description 1 t 6X Thermal overload constant 140s. In steps of 0.1s for 110s, in steps of 1s for 1040s. 2 I>> Short circuit off, 212 x I B. In steps of 1 x I B 3 t>> Short circuit delay 025s. In steps of 0.1s for 010s, in steps of 1s for 1025s 4 I<< Undercurrent off, 2090% of I B. In steps of 1% 5 t<< Undercurrent delay 060s. In steps of 0.1s for 010s, in steps of 1s in 1060s. 6 Unbalance off, 1050%. In steps of 1% 7 t Unbalance delay 025s. In steps of 0.1s for 010s, in steps of 1s for 1025s. 8 I 0 >> Earth fault off, 1060% of I B. In steps of 1% 9 t 0 >> Earth fault delay A b c I S >> Prolonged starting /stalled rotor t Start >> Prolonged starting delay t Stall >> Stalled rotor delay 025s. In steps of 0.1s for 010s, in steps of 1s for 1025s. off, 212 x I B. In steps of 0.1 x I B 060s. In steps of 0.1s for 010s, in steps of 1s for 1060s. 060s. In steps of 0.1s for 010s, in steps of 1s for 1060s. Time constant for thermal overload Short circuit setting in multiples of I B Delay for short circuit Undercurrent setting in % of IB Delay for undercurrent Phase unbalance setting in % Delay for phase unbalance Earth fault setting in % of I B Delay for earth fault Prolonged starting/stalled rotor setting in multiples of IB Delay for prolonged starting Delay for stalled rotor d I B Base/full load current 210A Base/full load current of motor E External CT ratio 1800:1 External CT ratio. 1=direct. F1 Auto/Manual Reset 0 Manual reset 1 Auto reset F2 Binary input 0 Block relay 1 1 Reset tripping 2 Instant tripping F3 Relay 2 function 0 On any tripping 1 On thermal tripping 2 On thermal warning F4 Phase sequence (PS)/ phase loss (PL) option 0 PS and PL off 1 PS on 2 PL on 3 PL and PS on Manual or auto reset of tripping Thermal overload is always auto reset Setting for binary input Relay 2 function Phase sequence and phase loss option F5 Frequency 50 or 60Hz Nominal value of network frequency Table 1: Description of settings 3

3.2.1 Motor Status Upon power on the relay, if there is no tripping, Relay 1 turns on. If motor current is more than 1.1 x I B, motor is considered starting. If motor current is less than 1.05 x IB, motor is running. Motor is stopping when motor current drops below 0.1 x I B. RUN LED shows the motor status. If motor starts for longer than 60s, Run LED stop blinking and off, Relay 1 also off. This condition persists until motor current drops below 0.1 x I B. 3.2.2 Thermal Overload where: I max is the maximum phase current among the 3 phases. I min is the minimum phase current among the 3 phases. Tripping takes place when unbalance value is more than unbalance setting % for longer than unbalance delay. It can be disabled by setting unbalance delay to 'off'. Figure 4: Thermal tripping curve 2hour 1hour The protection is based on mathematical model of motor thermal image. The thermal capacity is calculated continuously when motor is starting, overloading or even after tripping. Tripping takes place when the thermal capacity of the motor reaches 100%. This could happen when the motor current is higher than 1.05 x I B. After tripping a new start is not allowed until the motor cools down to less than 40% of thermal capacity. Thermal capacity can be cleared to 0% by pressing "UP" and "DOWN" simultaneously for longer than 1.5 seconds during thermal capacity display. Warning: Clearing thermal capacity effectively reset to cold start condition, user is not encouraged to clear thermal capacity until motor is cool enough to start/run within its thermal limit. 3.2.3 t 6X Thermal overload Time Constant t 6X sets the themal overload constant (heating constant), which is the maximum period of when motor current is allowed to reach a 6 x I B. Cooling constant is defined as 4 s of heating constant and is applicable when motor current is less than 0.2 x I B. Refer to the thermal tripping curve on Figure 4. 3.2.4 Short Circuit This protection is to trip the relay quickly when high current is detected due to short circuit. I>> is normally set higher than motor starting current to avoid false tripping during motor starting and t>> is set to very short duration. Tripping takes place when any phase of motor current is larger than I>> for longer than t>>. It can be disabled by setting t>> to 'off'. 3.2.5 Undercurrent Undercurrent protection is activated when average motor current is larger than 0.1 x I B. Tripping takes place when average motor current is smaller than I<< for longer than t<<. It can be disabled by setting t<< to 'off'. 3.2.6 Unbalance Unbalance is calculated as: 4 30min 20min 10min 5min 3min 2min 1min 40s 30s 20s 10s 5s 3s 2s 1s 2hour 1hour 30min 20min 10min 1 2 3 4 5 6 (a) With 0% thermal capacity (cold start) 5min 3min 2min 1min 40s 30s 20s 10s 5s 3s 2s 1s I max I min X 100 % 1 2 3 4 5 6 I min (b) With prior 50% thermal capacity 1.05 1.05 t6x 40s 30s 20s 10s 5s 2s 1s I/I B t6x 40s 30s 20s 10s 5s 2s 1s I/I B

3.2.7 Phase Loss Phase loss fault is detected when average motor current is larger than 0.28 x I B but any phase current is less than 0.1 x I B. Tripping takes place in less than 120ms when phase loss is detected. 3.2.8 Phase Sequence Phase sequence fault is detected when the phase sequence in any 2 or all the phases are reversed. Tripping takes place in less than 120ms when phase sequence fault is detected. Phase loss and phase sequence protection can be enabled and disabled separately. Refer to 3.2.16 Phase sequence / phase loss option 3.2.9 Prolonged Starting and Stalled Rotor For prolonged starting and stalled rotor there is one I S >> setting and separate delay setting for each protection. I S >> shall be set below the motor starting/ stalled current. These protections are useful when thermal overload protection is not fast enough to protect the motor during stalling. Delay for prolonged starting, t Start >> shall be set longer than specified motor starting. Tripping takes place when any phase current is larger than I S > for longer than t Start during motor starting. Delay for stalled rotor, t Stall >> is activated upon completing the motor starting. Tripping occurs when any phase current is larger than I S >> for longer than t Stall >> during motor running. Both protections can be disabled by setting I S >> to 'off'. To disable only one of the protection, set the respective delay for the protection to be disabled to much longer than specified. 3.2.10 Earth Fault Earth fault protection is based on zero sequence current calculation. Tripping takes place when the current is larger than earth fault setting in % of I B for longer than t 0 >. It can be disabled by setting t 0 >> to 'off'. 3.2.11 Base Current Base current is the motor full load current. The range of setting is model dependent. When external CT is used, the formula is: I B = Motor full load current 1 X CT ratio 3.2.12 External CT Ratio The CT ratio shall be set accordingly for the display to show primary current. For example when using 150/5 CT, set the value to: External CT ratio = 150 5 = 30 3.2.13 Manual or Auto Reset The relay can be set to manual or auto reset when the relay trips. Resetting of relay is allowed when the tripping condition cleared. Manual reset is performed by pressing the "RESET/MODE" (or using binary input if it is configured as 1 Reset trip). Thermal overload is always auto reset. 3.2.14 Binary Input The binary input is a dry contact input that can be configured to perform various functions. 0 Block relay 1 The input, when triggered, will force relay 1 off. 1 Reset tripping The input is used to manually reset a tripping. 2 Instant tripping The input will generate a tripping condition. Refer to 4.4 Binary Input Tripping. 3.2.15 Relay 2 The relay 2 output can be configured to turn on in these conditions: 0 On any tripping Relay 2 on during any tripping. 1 On thermal tripping Relay 2 on during thermal tripping only. 2 On thermal warning Relay 2 on when motor current is more than 1.05 x I B. 3.2.16 Phase sequence / phase loss option Phase sequence and phase loss detection can be on (enabled) and off (disabled) separately. 0 Phase sequence and phase loss off 1 Phase sequence on 2 Phase loss on 3 Phase sequence and phase loss on 3.2.17 Frequency Nominal value of the network frequency. Select either 50 or 60 Hz. For example to use the relay with motor that has full load current of 138A, using external CT of 150/5, I B = 5 138 X = 4.6A 150 5

4. Tripping 4.1 Tripping Display During tripping, Trip LED on, Thermal LED also on during thermal overload tripping. Function LED and Data LED blinks showing tripping current or source as shown below: Trip LED Thermal LED Function LED Data LED Description On On t ol Thermal Overload tripping On Off 2 tripping current Short circuit tripping On Off 4 tripping current Undercurrent tripping On Off 6 Ub Unbalance tripping On Off 6 PS Phase sequence error tripping On Off 6 PL Phase loss tripping On Off 8 tripping current Earth fault tripping On Off A tripping current Prolonged starting/stalled rotor tripping On On t ESt Trip Test On Off t rip Binary input tripping Table 2: Tripping display 4.2 Tripping Reset During tripping condition, press "RESET/MODE" to reset, the relay will reset if condition permits. If relay is set to auto reset, the relay will reset automatically if the tripping condition is cleared with a 5% hysteresis. 4.3 Tripping Test Press and hold "TEST" for 3.5 seconds to simulate a tripping condition, Trip LED blinks when "TEST" is pressed. During Test Tripping, "test" blinks, R1 off and R2 on if set to "On any tripping". Press "RESET/MODE" to reset. Tripping Test is disabled when motor is starting/running. 4.4 Binary Input Tripping When Binary input is set to 2 Instant tripping, binary input will generate a tripping condition. "trip" will blink, R1 off and R2 on if set to "On any tripping". Press "RESET/MODE" to reset. If relay is set to auto reset, the relay will reset after the input is normal for 1s. 4.5 Tripping History Display During Current/Thermal display, press "RESET/MODE" to jump to Tripping History Display. Display shows the previous tripping status with a 'dot' blinking at Function LED. To clear tripping history, press "UP" and "DOWN" simultaneously. 5. Typical Application Diagram L3 L2 L1 F1 F2 F3 F4 F1 L F2 MM10 9 10 11 Aux 1 2 3 L N NO MM10 9 10 11 Aux 1 2 3 L N NO M Binary input 12 13 14 15 16 Block R1/ Reset/ Trip R1 R2 4 5 6 7 8 NC COM COM NC NO Stop Start S2 S1 H1 N M Binary input 12 13 14 15 16 Block R1/ Reset/ Trip R1 R2 4 5 6 7 8 NC COM COM NC NO Stop Start S2 S1 H1 N 3Phase Motor Figure 5: Example of application SinglePhase Motor* * To use MM10 for singlephase protection, Io>> Earth fault, Phase sequence and phase loss protection should be set to off. 6

6. Techinical Data SETTING RANGES Thermal Overload constant, t 6X Short circuit, I>> Short circuit delay, t>> Undercurrent, I<< Undercurrent delay, t<< Unbalance, Unbalance delay, t Earth fault, I 0 >> Earth fault delay, t 0 >> Phass loss Phase sequence Prolonged starting/stalled rotor, I S Prolonged starting delay, t Start Stalled rotor delay, t Stall CT RATINGS : 1 40s. In steps of 0.1s for 110s, in steps of 1s for 1040s : off, 2 12 x I B. In steps of 1 x I B : 0 25s. In steps of 0.1s for 110s, in steps of 1s for 1025s : off, 20 90% of I B. In steps of 1% : 0 60s. In steps of 0.1s for 110s, in steps of 1s for 1060s : off, 10 50%. In steps of 1% : 0 25s. In steps of 0.1s for 110s, in steps of 1s for 1025s : off, 10 60% of I B. In steps of 1% : 0 25s. In steps of 0.1s for 110s, in steps of 1s for 1025s : <120ms : <120ms : off, 2 12 x I B. In steps of 0.1 x I B : 0 60s. In steps of 0.1s for 110s, in steps of 1s for 1060s : 0 60s. In steps of 0.1s for 110s, in steps of 1s for 1060s Rated current Rated frequency Burden Thermal withstand : 210A : 50 or 60Hz : <0.3VA at rated current : Continuous: 2 x maximum rated For 30s: 6 x maximum rated For 1s: 10 x maximum rated CASE DIMENSION BINARY INPUT Rated input voltage : 12V (Supplied internally) 96 mm AUXILIARY SUPPLY Model MM10 240X005 Model MM10 48X0005 Supply frequency Maximum power consumption : 85 ~ 265 V AC 110 ~ 370 V DC : 24 ~ 72 V DC : 50 or 60 Hz : 3 VA typical 96 mm Fr o n t CONTACTS Contact arrangement Contact rating Contact material Operating Expected electrical life Expected mechanical life : Changeover : 5A, 250V AC (cosφ = 1) : Silver alloy : 15ms max : 100,000 operations at rated current : 5 x 10 6 operations 110mm 100mm INDICATORS Run Trip/Pickup Thermal : Green indicator : 7segment display and red indicators : Yellow indicator 90mm ENVIRONMENTAL CONDITIONS Temperature Humidity MECHANICAL : 5ºC to +55ºC : 56 days at 93% RH and 40ºC noncondensing 90mm Mounting Front panel Approximate weight : Panel mounting : Standard DIN 96 mm x 96mm : 0.75kg Figure 6 7

Warranty: LARSEN & TOUBRO LIMITED (L&T) warrants that the Motor Protection Relay, MM10 will meet L&T's published specifications and will be free from defects in workmanship and materials for a period of 12 months from the date of Shipment. L&T's obligation under this warranty shall be limited to servicing or replacing defective parts provided that notice of such defects and satisfactory proof thereof is given to L&T by its customer within the warranty period. This warranty does not cover any defect in the product caused by accident, misuse, neglect, alteration, modification or substitution of any of the components or parts, or any attempt at internal adjustments by unauthorized service personnel. Under no circumstances shall L&T be liable for any consequential or resulting injury or for loss, damage or expense, directly or indirectly, arising from the use of this product. The forgoing warranty is in lieu of all other warranties, express or implied and is the sole and exclusive remedy for any claim arising from the defect in the product. Electrical Standard Products Larsen & Toubro Limited Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858 Fax : 022 6774 5859 Email : cic@lntebg.com Website : www.lntebg.com