The Effect of the Over Voltage on the Stress Distribution at the Terminals of H.V. XLPE Cables. Professor

Similar documents
ELECTRICAL STRESS CONCENTRATION AT THE TERMINALS OF M.V. & H.V. XLPE CABLES

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

Fatima Michael College of Engineering & Technology

Experimental and Analytical Studies on Lightning Surge Response of 500kV Transmission Tower


INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

Modeling of Transmission Line and Substation for Insulation Coordination Studies

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

STUDIES ON LIGHTNING CHARACTERISTICS

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Some Aspects of Stress Distribution and Effect of Voids Having Different Gases in MV Power Cables

Physics 196 Final Test Point

Code No: RR Set No. 1

An Optimised High Current Impulse Source

Analysis of Very Fast Transients in EHV Gas Insulated Substations

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

A Novel Optimized Design for Busbar Structures using Finite Element Methods

UNIT I - INTRODUCTION SYLLABUS

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Wave Phenomena Physics 15c. Lecture 8 LC Transmission Line Wave Reflection

Electric Field and Thermal Properties of Dry Cable Using FEM

Tailoring of new Field Grading Materials for HVDC Systems. Dipl.-Ing. Maximilian Secklehner Rashid Hussain, M.Sc.

Chapter 1W Basic Electromagnetic Concepts

The Lightning Study of Overhead Transmission Lines

EPRI Lightning Protection Design Workstation

An Empirical Formula for the Surge Impedance of a Grounding Conductor along a Reinforced Concrete Pole in a Distribution Line

Temperature and Field Dependence of Field Grading Tubes for Medium Voltage XLPE Cable Joints

Modern Electrical Diagnostics for Metal Oxide Surge Arresters

BREAKDOWN STUDY OF WATER WITH DIFFERENT CONDUCTIVITIES

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

Three Core XLPE/LSF/SWA/LSF Power Cable

INSULATORS INSULATORS

EE 427 High Voltage Breakdown & Testing Model Answers. Level 4 Semester 2 Examination - February 2009 Answer 1. anode (+) 2 marks. 3 marks.

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

DETERMINATION OF THE DIELECTRIC STRENGTH OF LPS COMPONENTS BY APPLICATION OF THE CONSTANT-AREA-CRITERION

Simulation of Partial Discharge in Solid Dielectric Material

Film Capacitors. EMI suppression capacitors. Date: June 2018

Effect of High Voltage Impulses on Surface Discharge Characteristics of Polyethylene

Physics - Grade 12. Revision Sheet for the Final Exam / Second Term. Academic Year: 2018/2019. Student s Name:.. Date: /3/2018

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

Collation Studies of Sequence Impedances for Underground Cables with Different Layouts

Lightning Insulation Coordination Study

Parametric Study of Losses in Cross-Bonded Cables: Conductors Transposed Versus Conductors Nontransposed

NYY-J/-o 34 NYCWY 36 NYCY 37 NAYY 38

ELECTRIC FIELD CALCULATIONS FOR AC AND DC APPLICATIONS OF WATER CONTROLLED CABLE TERMINATION

Mechanisms for Degradation of TR-XLPE Impulse Strength During Service Aging

Keywords: HVDC cable, Analytical calculation, PMLTCT, PMITD.

Santhosh Kumar BVMP ABB GISL Chennai, India

ELECO'2001. Paper Submission Form

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

MODELING OF THE DIRECT LIGHTNING STRIKE ON A TOWERS CASCADE EQUIPPED WITH ITS PROTECTIONS

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Question 1. (Marks 16)

Comparison of Transient Simulations on Overhead Cables by EMTP and FDTD

To order, specify : Types Protection functions Current surge Asymmetry and loss of phase. Operating principle

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

Independent, accredited testing station Member laboratory of STL and LOVAG TEST CONFIRMATION. on the given range of performed tests

Gas Discharge Tube (GDT) Data Sheet

SIRCOVER Manual transfer switches from 125 to 3200 A

Stress Distribution In Two Layers Of H.V.D.C Cable Insulation For Cooling Outer Conductor

DIRECT STROKE LIGHTNING PROTECTION DESIGN

Capacitance and Dielectrics. Chapter 26 HW: P: 10,18,21,29,33,48, 51,53,54,68

Lightning overvoltages and compliance with the ITI (CBEMA) curve

EE Branch GATE Paper 2010

Breakdown of MV Cable Jackets under Impulse Conditions. Caryn Riley, Ray Hill, Nigel Hampton. Spring ICC Sub Committee A

Chapter 10: Air Breakdown

HIGH VOLTAGE ENGINEERING. Electric discharges in electric power engineering

AN INVESTIGATION INTO PARTIAL DISCHARGE BEHAVIOUR IN IMPULSE AGED POLYMER INSULATION

Modeling and Simulation of Air Insulated and Gas Insulated Substations

Space charge fields in DC cables

ECE 325 Electric Energy System Components 5 Transmission Lines. Instructor: Kai Sun Fall 2015

NECESSARY SEPARATION DISTANCES FOR LIGHTNING PROTECTION SYSTEMS - IEC REVISITED

66kV & 220kV Substation Protection From Lightning by Fixed Angle, Rolling Sphere and Early Streamer Method

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

I n many cold-climate regions of the world, overhead

Keywords- Metal Oxide Surge Arrester, Model, Transient, Laboratory Experiment, Simulation.

The ESD5451R is available in DFP1006-2L package. Standard products are Pb-free and Halogen-free. Circuit diagram

Dynamics of streamer propagation in air

A Level Physics B (Advancing Physics) H557/03 Practical skills in physics Sample Question Paper SPECIMEN

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

IEC Type Test Report Report No. EU1527-H-00.1 PH3 Series Polymer-housed Arrester 10,000 A Line Discharge Class 3

Lightning Phenomenology Notes Note 23 8 Jan Lightning Responses on a Finite Cylindrical Enclosure

Partial discharge (PD) is well established as a diagnostic

Transmission-Line Essentials for Digital Electronics

and Ee = E ; 0 they are separated by a dielectric material having u = io-s S/m, µ, = µ, 0

The objective of a grounding system are: 1. To provide safety to personnel during normal and fault conditions by limiting step and touch potential.

In-process Measuring of Capacitance Per Unit Length for Single-core Electric Wires

Chapter 24 Capacitance and Dielectrics

ELECTROMANETIC PULSE PROPAGATION IN A COAXIAL CABLE

Technical Challenge of Lightning Protection for Wind Power Generation

A New Contribution in Reducing Electric Field Distribution Within/Around Medium Voltage Underground Cable Terminations

Investigation and Analysis of Inception Voltage and Field Distribution in Power Cables with Internal Cavities in Dielectric

Performance analysis of 1200 kv ceramic disc insulator string under normal and faulted conditions

On the Influence of Earth Conduction Effects on the Propagation Characteristics of Aerial and Buried Conductors

1. Introduction. 2. Use of COMSOL Multiphysics

Transcription:

The Effect of the Over Voltage on the Stress Distribution at the Terminals of H.V. XLPE Cables Saad S. Sheet / Ass. Lecturer Professor Farook k. Amouri / saad_msc@yahoo.com amouri_2006@yahoo.com Abstract The power cables are usually subjected to over voltages from lightning impulses and switching surges, such over- voltages effects are concentrated at terminals of the high voltage cables. The longitudinal and radial stresses through cable terminals are computed by using Schwarz christoffel transformation used for sketching the electrical fields. The investigated cables are of rated voltage 33Kv and 132Kv insulated by cross-linked polyethylene (XLPE). Electrical field sketching at the cable terminals is carried out theoretically by the aids of computer programs. The results give an indication of the maximum stresses occurs in the cables insulation at the terminals and the maximum longitudinal stresses along the cables screen at outer surface of the XLPE insulation. The results show that maximum stress occurred by lightning impulse is found much higher than that of switching operation but the later has longer period. And both are found depends on the polarity of the over voltages and the polarity of the (power/frequency) voltages. Keywords: stress distribution ofover voltage XLPE cables, termination of XLPE cables ﺗﺄﺛﯿﺮ اﻟﻔﻮﻟﺘﯿﺎت اﻟﻌﺎﻟﯿﺔ ﻋﻠﻰ ﺗﻮزﯾﻊ اﻻﺟﮭﺎدات ﻋﻨﺪ ﻣﻨﻄﻘﺔ اﻷطﺮاف ﻟﻘﺎﺑﻠﻮات اﻟﻔﻮﻟﺘﯿﺔ اﻟﻌﺎﻟﯿﺔ ذوات ﻋﻮازل اﻟﺒﻮﻟﻲ اﺛﯿﻠﯿﻦ ﻣﺘﻘﺎطﻊ اﻷواﺻﺮ

أ. ﻓﺎروق ﺧﻠﯿﻞ ﻋﻤﻮري / اﻟﻤﻮﺻﻞ ﺳﻌﺪ ﺻﺎﻣﻮﺋﯿﻞ ﺷﯿﺖ اﻟﻜﻠﯿﺔ اﻟﺘﻘﻨﯿﺔ اﻟﮭﻨﺪﺳﺔ اﻟﻜﮭﺮﺑﺎﺋﯿﺔ اﻟﺨﻼﺻﺔ. ﻣﺜﻞ ھﺬه اﻟﻔﻮﻟﺘﯿﺎت اﻟﻌﺎﻟﯿﺔ ﺗﺘﺮﻛﺰ ﺑﻤﻘﺎدﯾﺮ ﻋﺎﻟﯿﺔ ﻓﻲ ﻣﻨﻄﻘﺔ اﻷطﺮاف ﻟﻘﺎﺑﻮات اﻟﻔﻮﻟﺘﯿﺔ اﻟﻌﺎﻟﯿﺔ. اﻟﺘﻮاﻓﻖ )ﺗﺤﻮﯾﻠﺔ ﺷﻮارﺗﺰ ﻛﺮﺳﺘﻮﻓﻞ(. اﺧﺘﯿﺮ اﻟﻘﺎﺑﻠﻮ اﻟﻤﺴﺘﺨﺪم واﻟﺬي ﺗﻢ ﺗﻄﻮﯾﺮه ﺑﺘﻘﻨﯿﻦ اﻷول 33 ﻛﯿﻠﻮ ﻓﻮﻟﺖ أﻣﺎ اﻟﺜﺎﻧﻲ ﻓﮭﻮ 132 ﻛﯿﻠﻮ ﻓﻮﻟﺖ وذو ﻋﺎزل ﺻﻠﺐ ﻣﻦ ﻧﻮع اﻟﺒﻮﻟﻲ اﺛﯿﻠﯿﻦ ﻣﺘﻘﺎطﻊ اﻷواﺻﺮ. اﻟﺤﺎﺳﺒﺔ اﻻﻟﻜﺘﺮوﻧﯿﺔ. واﻟﻨﺘﺎﺋﺞ أﻋﻄﺖ ﻣﺆﺷﺮ ﻟﺤﺎﻟﺔ أﻋﻈﻢ إﺟﮭﺎد ﻛﮭﺮﺑﺎﺋﻲ ﯾﺤﺪث ﻓﻲ ﻋﺎزل اﻟﻘﺎﺑﻠﻮ ﻋﻨﺪ. ﻟﻨﺒﻀﺔ اﻻﻧﺪﻓﺎﻋﺔ وﺗﻜﻮن ﻗﯿﻤﺔ اﻻﺟﮭﺎدات اﻟﻜﮭﺮﺑﺎﺋﯿﺔ ﻋﺎﻟﯿﺔ ﺟﺪا وﺑﺼﻮرة ﻏﯿﺮ ﻗﺎﺑﻠﺔ ﻟﻠﻤﻘﺎرﻧﺔ ﻋﻨﺪ ﺣﺎﻟﺔ. ﻧﺒﻀﺎت اﻟﻔﺘﺢ واﻟﻐﻠﻖ. اﻻﻋﺘﯿﺎدﯾﺔ اﻟﺘﻲ ﯾﻌﻤﻞ ﻋﻨﺪھﺎ اﻟﻘﺎﺑﻠﻮ ﻗﺒﻞ ﺗﻌﺮﺿﮫ إﻟﻰ اﻟﻔﻮﻟﺘﯿﺎت اﻟﻌﺎﻟﯿﺔ. Received 22 March 2007 Accepted 13 June 2007 Introduction

The cross-linked high density polyethylene is used as the insulating material in medium voltage cables (3.3Kv, 6.6Kv, 11Kv, 33Kv, 66Kv), high voltage cables (110Kv, 132Kv, 220Kv, 400Kv), and at present time used for more than 400Kv. Joints and termination in such cables are the most risky parts in the cables system. This is because it is not easy to get a purely uniform electric field in such positions even at power frequency voltages. High voltage cables are often connected with over head transmission lines, and so such cables are subjected to over voltages from lightning impulse as well as the over voltages from switching operation of the power transmission system. High voltage cables in underground power systems usually tested with lightning impulses according to the applicable (IEC) standard to proof it's capability against lightning over voltage [1]. High voltage switching operation and discharge phenomena in the gas gap circuit breakers electrodes cause, electromagnetic transients and such transients produced high electromagnetic fields and cause an over lap and concentration of electric fields specially at cable terminations [2,3]. Contribution deals with maximum stresses and field concentration at cable termination and at over voltages are produced in this paper. The contribution involves a field sketching at cable termination using Schwarz Christoffel transformation. Theoretical Approach: At rated working A.C. voltages on a cable and at over voltages the stress can be given by the following equations [4]. The stress near conductor Er is: (1) Er = (V + Vo.v) / (r ln (R/r))

The stress near sheath ER is: (2) ER = (V + Vo.v) / (R ln (R/r)) Where V: Working voltage in Kv at real value. Vo.v: Over voltages at real value. r: Radius of conductor in meter. R: Radius of sheath in meter The above two equations at the peak value of the electrical stresses can be defined at the conductor and at the sheath in case of no-load and at full load. The peak value of the stress near the sheath is higher than that near the conductor. At the cable terminals the electric field or stress seems to be nonuniform and this is due to the presence of the longitudinal fields in addition to the radial fields. In order to declare the effect of the two electrical fields at cable terminal, the field sketching at cable terminal is carried out theoretically at over voltage imposed on the working power/frequency voltages. Sketching of the electric field at cable terminals is carried out by using Schwarz Christoffel transformation, such method was used in reference [3] and verified by experiments at (power/frequency) voltages [3]. The general form of this transformation is: 1 1 1 1 dz S (W a ) (W b) (W c ) (W d ) dw (3)

where: S: rotation constant. a, b, c, d: values on the real axis used to ensure transformation conditions. α, β, γ, δ: right or zero angle of the polygon. By using this method any polygon in Z-plane can be transformed to the upper half of W-plane. The polygon sides of Z-plane became the real axis of the W-plane as shown in figure(1). figure(1) Representation of Schwarz Christoffel transformation The values A, B, C, D shown in figure(1) are representing the vertices of the polygon. For a certain cable two angle are used, the first 2, and the second 0, as shown in figure(2) and the representation of Z-plane and W-plane both and c ', b '.

figure(2) Representation of Schwarz Christoffel transformation for cable termination The above equation will be: (4) 1 1 dz S (W a ) (W b) dw a, b represents the value of located to assure the transformation condition of (a = -1), and(b = 0), and the equation will be: (5) Z S (W InW ) K the two unknown values S & K, can be used as: S K h where h: conductor radius so that the equation will be: (6)

Z h (W InW 1) This equation represents the form of the equipotential lines. under transformation condition and the arrangement in the above form is a new form of equation wich can be developed as: Z h (7) (e jh) This equation represents the form of the flux lines. By representing the real and imaginary parts from the above equation and plotting, then the field distribution around the cable conductors can be defined. The field map representation for cable termination by using method of Schwartz Christoffel transformation given in figure (3). figure(3)

field map representation for cable termination Designed Program: The theoretical analysis is simulated by designing a computer program. The program used data of high voltage power cables rated at voltages of 33Kv, 132Kv. The simulation involve the use of lightning impulses of 1.2/50 μs and at peak values of 20 times that of working voltages and at both positive and negative impulses. For switching operation, the waveforms of the surges is at peak value of 4 times that of working voltage and at longer front and tail voltage 20/30 μs, this value is computed by varying the values of the impulse generator parameter (R1,R2,C1,C2). The designed computer programs is given by its flow chart is shown in figure (4). Results and Discussion: Over voltages subjected on high voltage power cables are usually of two main forms, the first one is the impulse produced form lightning strokes and these are either positive or negative. Simulation of the positive and negative impulse waveform which are chosen and applied in the present study are given in figure(5) for 33Kv. The positive impulse voltages imposed on the positive (power/frequency) cycle is given in figure(5) (case a) and the corresponding fields at cable terminal is given figure(5) (case e). similar simulation for positive impulse voltages imposed on negative (power/frequency) cycle is given in figure(5) (case b), and the corresponding field sketching at cable terminal is shown in figure(5) (case f). The negative impulse imposed on positive power cycle as given in figure(5) (case c) and it's corresponding field sketching at cable terminal is shown in figure(5) (case g). The negative impulse imposed on negative (power/frequency) cycle with it's field sketching are given in (case d) and

(case h). The calculated results from the field sketching in figure(5) indicate that maximum field concentration occurred at positive impulse imposed on negative (power/frequency) cycle, (case b) followed by the case negative impulse imposed on positive cycles, (case c), negative impulse imposed on negative (power/frequency) cycle, (case d) and positive impulse imposed on positive (power/frequency) cycle, figure (case a). Similar results are obtained in figure(6) were for 132Kv cable terminal and also at positive and negative imposed impulses on (power/frequency) voltages. As compared with 33Kv cable the only difference in found in the amplitude of the (power/frequency) voltages since it is higher in 132Kv cables, but for 33Kv the field concentration due impulse is more risky because the insulation thickness is less. As a result of this study the termination in 33Kv must be designed depending on the impulse withstand level. The design of lower level terminals in 33Kv is the main cause of the 33Kv termination failure. With switching operation at 33Kv cable termination, the surge voltage imposed on negative (power/frequency) voltage cycle (case b) results the most field concentration followed by (case d) of negative surge imposed on negative power cycle followed by (case c) of negative surge imposed on positive (power/frequency) and finally (case a) of positive surge imposed on positive power cycle. For 132Kv terminal at switching operation the results given in figure(7) and for the above four different cases are similar in form to that at 33Kv cable terminals.

Start Enter Data to select cable Rated Not Accepted Cable Rated Error Accepte d Enter exist information End VOLTAGE STATES Rated Voltage Switching Voltage Not Accepted Calculate Normal Power Cycle Voltage(Pc.) Calculate Radial Stresses of rated (Rs.) Calculate Flux Stresses of rated at (step=0) Error Switching Operation State Accept ed Enter exist information End Calculate Switch Voltage (Sw.) Calculate Normal Power Cycle Voltage(Pc.) Calculate The Value (Sw. + Pc.) Calculate Flux Stresses of rated at (step >0) Plot Radial Stresses and Flux Stresses of Rated State Impulse Voltage Calculate Radial Stresses (Rs.) Calculate (Sw. * Rs.) Calculate [(Sw. * Rs.) + Rs.] Not Accepted Error Impulse State Accepte d Enter exist information Calculate Impulse Voltage (Imp.) End Calculate Normal Power Cycle Voltage(Pc.) Calculate The Value (Imp. + Pc.) Calculate Radial Stresses (Rs.) Calculate (Imp. * Rs.) Calculate [(Imp. * Rs.) + Rs.] Calculate the Value of Switching current Calculate the value of Impulse current Calculate Flux Stresses of Calculate Flux Stresses of Impulse at (Step =0) Calculate Flux Stresses of Switch Calculate Flux Stresses of Impulse at (Step >0) Plot Radial Stresses of Switching Operation Plot the voltage (Imp. + Pc.) Plot the voltage (Sw. + Pc.) Plot Radial Stresses of Impulse Plot Flux Stresses of Switching Operation State Calculate Cable Boundary Plot the Cable Boundary End Plot Flux stresses of Impulse State

figure(4) flowchart of the designed program (a) (e) (b) (f)

(c) (g) (d) (h) figure(5) a, b, c, d, are wave forms of the imposed impulse waveforms on power/frequency voltage e, f, g, h are the field sketching for a, b, c, d cases in 33Kv power cable terminal (a) (e)

(b) (f) (c) (g) (d) (h) figure(6) a, b, c, d, are wave forms of the imposed impulse waveforms on power/frequency voltage e, f, g, h are the field sketching for a, b, c, d cases in 132Kv power cable terminal

(a) (e) (b) (f) (c) (g) (d) (h) figure(7) a, b, c, d, are wave forms of the imposed switching operation surges on power/frequency voltage e, f, g, h are the field sketching for a, b, c, d cases in 33Kv power cable terminal

(a) (e) (b) (f) (c) (g)

(d) figure(8) (h) a, b, c, d, are wave forms of the imposed switching operation surges on power/frequency voltage e, f, g, h are the field sketching for a, b, c, d cases in 132Kv power cable terminal Conclusion: Field concentration in high voltage cables subjected to over voltage imposed on power/frequency voltage indicates a very concentrated electrical field at cable terminals and this is found depends on the polarity of the (power/frequency) voltages. Such difference becomes very serious due to the variation in polarity of the (power/frequency) voltages specially in the cable insulators. In XLPE cable insulators the change in the space charge accumulation followed concentrated electrical field usually lag the variation in polarity and cause more space charge accumulation and more field concentration. Over voltage effect on 132Kv cable terminals is found to be nearly in the same manner as that for 33Kv cable. References:

1. Schwenk K. and Gamlin M. "Load range methods for lightning impulse testing with high voltage impulse generators", Haefly Test AG, Basel, Switzerland 2005. e-mail: schwenk.klaus@haefely.com 2. Akses A., Yazici M., Kalenderli O. and Baran E. "Electromagnetic interface from a lightning impulse generator", Turkey 2002. e-mail: aysam@uekae.tubitak.gov.tr 3. Sheet S. and Amouri F., "Electrical stress concentration at the terminals of M.V. and H.V. XLPE cables", Al-Rafidain Engineering Vo1.14, No.1, Iraq 2006. e-mail: saad_msc@yahoo.com 4. Weedy B.M., "Underground transmission", Handbook, John Wiley, England 1979. 5. Gallagher T. J. & Pearmain A. J., "High Voltage testing and design", Handbook, university of London, John Wiley, England, 1984.