Levels of electric and magnetic fields inside 110/X kv substations

Similar documents
Magnetic Field in an Apartment Located above 10/0.4 kv Substation: Levels and Mitigation Techniques

MEASUREMENTS AND CALCULATIONS OF NON-IONIZING RADIATION LEVELS IN VICINITY OF 35 KV OVERHEAD POWER LINES

ELECTRIC AND MAGNETIC FIELD GUIDELINE EVALUATION AND MAGNETIC FIELD EXPOSURES FOR LIVE-LINE WORKERS

THE EFFECT OF UNBALANCED LOADS IN DISTRIBUTION TRANSFORMERS AND GROUND NETWORK ON ELECTROMAGNETIC FIELDS

ANALYSIS OF ELECTROMAGNETIC FIELDS IN INTERCONNECTING SUBSTATIONS BETWEEN WTG AND NATIONAL POWER SYSTEM

The Influence of Phase Transposing on Double Circuit Overhead Power Line Magnetic Field

Electric field and exposure time in a EHV substation near a bay-equipment: concerning ICNIRP guidelines

STUDY AND EVALUATION OF INDUCED CURRENT IN HUMAN BODY FROM EXPOSURE TO ELECTROMAGNETIC FIELDS AT LOW FREQUENCIES

Calculation of Electric and Magnetic Field under AC Transmission and Distribution Lines in Guwahati City

A Global Index of Acoustic Assessment of Machines Results of Experimental and Simulation Tests

A Study of Electromagnetic Field Generated by High Voltage Lines Using Comsol Multiphysics

Arrangement of conductors in 220 kv double circuit line to reduce E-fields in view of public exposure

COMPEL 27,1. The current issue and full text archive of this journal is available at

Test Report EN (2008)

Electro Transformación Industrial, S.A. Technical Department. José Ignacio Garreta José Leandro Leandro Boyano

Film Capacitors. EMI suppression capacitors. Date: June 2018

Measurements of electric and magnetic fields, in heavy vehicles parking space, in the vicinity of a power station with 150kv to 20kv transformers

Power-frequency magnetic field calculation around an indoor transformer substation

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

Computation of Electromagnetic Energy Absorption in the Human Body Tissues by High Frequency Structure Simulator

Investigation of the Electric Field of Metallic Fence under a High Voltage Transmission Line

Exposure of Workers to Electromagnetic Fields (EMF) Inside the Olive Mills: Preliminary Evaluations During the Oil Production 1

HIGH PERFORMANCE MAGNETIC SHIELDING SOLUTION FOR ELF SOURCES

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

Calculation of Electric and Magnetic Field Safety Limits Under UHV AC Transmission Lines

Overhead lines. 110 kv wood tower with guy wires

S.S. Şeker, F. Can Boğaziçi University, Dept. of Electrical- Electronics Engg Bebek, İstanbul, Turkey

11/25/2013 LET S TALK ABOUT TRAINING! WHEN AND HOW OFTEN? CHEMICAL SAFETY SERIES WITH KRISTY 2 Kristy Main December 4, 2013

The efficiency of Somavedic Medic on magnetic field disturbances due to geopathic stress

Ring Cores General Information

Three Axis Magnetic Field Transducer x-h3x-xx_e3d-2.5khz-1-0.2t

MAGNETIC FIELD OF ELECTRICAL RADIANT HEATING SYSTEM

Aluminum Electrolytic Capacitors Power Long Life Snap-In

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Sang Lee Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for True Infra Sauna Heaters

QUESTIONNAIRE: REACH INTRODUCTION

User Manual VX4750 Function Generator Module

Combined HTS Cable and Fault Current Limiter Project in Germany

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

Aluminum Capacitors Power Standard Miniature Snap-In

Operating Instructions for Digital Manometer. Model: MAN-SD

Interdisciplinary Physics Example Cognate Plans

3D Computation of the Power Lines Magnetic Field

Power Resistor for Mounting onto a Heatsink Thick Film Technology

COMMISSION REGULATION (EU)

DETECTION OF DANGEROUS MAGNETIC FIELD RANGES FROM TABLETS BY CLUSTERING ANALYSIS

AUTOMOTIVE CURRENT TRANSDUCER OPEN LOOP TECHNOLOGY HC6H 400-S/SP1

This document is meant purely as a documentation tool and the institutions do not assume any liability for its contents

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.


Cree XLamp XR-C LEDs. CLD-DS10 Rev 12H. Product family data sheet

The Globally Harmonized System (GHS) for Hazard Classification and Labelling. Development of a Worldwide System for Hazard Communication

DRAIN TRACING DYE RED E123

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Physical Structure of Matter Hall effect in p-germanium with Cobra3. Solid-state Physics, Plasma Physics.

Induced current density in the foetus of pregnant workers in high magnetic field environments *

GHS Classification CONCEPT OF GHS

PRODUCT SAFETY SUMMARY (GPS) SODIUM-HYDROXIDE

Training program for x-ray inspection film (RT)

Manual Railway Industry Substance List. Version: March 2011

2016 No. 410 (W. 128) WATER, ENGLAND AND WALES. The Water Supply (Water Quality) (Amendment) Regulations 2016

Compliance with occupational limit values by applying workplace measurements

a) head-on view b) side view c) side view Use the right hand rule for forces to confirm the direction of the force in each case.

Solid Tantalum Surface Mount Chip Capacitors TANTAMOUNT, Molded Case, for Medical Instruments

3B SCIENTIFIC PHYSICS

5-7 Ilia Mavromichali Street, Larnaca

THE USE OF IONISING RADIATION IN THE MANUFACTURE OF MEDICINAL PRODUCTS

Analogue Meters CQ2x07 series

VK2 volume flow controller Overview

Product family data sheet

Letter to non European Union customers

Materials Approach using the Toyograph CAS Number Approach

Information gathering

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Examples of magnetic field calculations in indoor distribution substations

DC/DC regulator Input V Output up to 16 A

CCQ-800 AutoFocimeter. CCQ-800 AutoFocimeter. Operating Instruction. R/No.: CCQ8.0ESM REV: 3.45

Definition and regulation in terms of mechanism of action and intended use

Through Hole Transformers, Pulse, Trigger Type

ARFTG 84th WORKSHOP The New Frontiers for Microwave Measurements

Finite Element Method Application in Analyzing Magnetic Fields of High Current Bus Duct

Fatima Michael College of Engineering & Technology

Lectures of ENVIRONMENTAL ELECTRICAL SCIENCE

OSHA PART 1: PREPARING FOR THE SESSION. 1. Training Booklet. 2. Why This Session Is Important. 3. Purpose and Objectives of the Session

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

Prepare for this experiment!

REACH: HOW IT AFFECTS PSA TAPES

Cree XLamp XR-C LED Data Sheet

Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer

PHYS 241 EXAM #2 November 9, 2006

Substance Name: 2,2-bis(4'-hydroxyphenyl)-4- methylpentane EC Number: CAS Number: SUPPORT DOCUMENT FOR IDENTIFICATION OF

Product family data sheet

Cree XLamp XR-E LED PRODUCT FAMILY DATA SHEET FEATURES PRODUCT DESCRIPTION TABLE OF CONTENTS CLD DS-05 REV11

TELUX LED FEATURES APPLICATIONS COORDINATE. FORWARD VOLTAGE (V) (ma) at I F (ma) (ma) MIN. TYP. MAX. MIN. TYP. MAX. MIN. TYP. MAX. 0.33, 0.

Effect of core balance current transformer errors on sensitive earth-fault protection in compensated MV networks

Cree XLamp XP-C LEDs Data Sheet

The Globally Harmonized System (GHS) for Hazard Classification and Labelling. Development of a Worldwide System for Hazard Communication

Resin-Molded, Radial-Lead Solid Tantalum Capacitors

The Calculation of Electromagnetic Fields (EMF) in Substations of Shopping Centers

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Transcription:

24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Levels of electric and magnetic fields inside 110/X kv substations Maja Grbi c, Aleksandar Pavlovi c, Dejan Hrvi c, Branislav Vulevi c Nikola Tesla Electrical Engineering Institute, Belgrade, Republic of Serbia E-mail: maja.grbic@ieent.org ISSN 2515-0855 doi: 10.1049/oap-cired.2017.1292 www.ietdl.org Abstract: Power frequency electric and magnetic field levels which occur inside 110/x kv substations are analysed in this paper in order to assess the exposure of workers to these fields. The analysis is based on the results of electric field strength and magnetic flux density measurements inside 110/x kv substations in Serbia. The measurements were performed along the transport routes, near the high-voltage/medium-voltage equipment and the power transformers, as well as inside and in the vicinity of the control buildings, with the purpose of estimating maximum field levels which can occur inside these substations. In order to estimate the exposure of workers to these fields, the obtained results were compared to the action levels (ALs) prescribed by Directive 2013/35/EU. The first objective of the analysis performed is to reach general conclusions about field levels which can occur inside substations of the mentioned voltage level. The second objective is to check whether these levels comply with the ALs prescribed by Directive 2013/ 35/EU. 1 Introduction The topic of non-ionising radiation has become very important in Serbia over the last several years, thus initiating comprehensive research and testing regarding exposure of the general public and workers to power frequency electric and magnetic fields and mitigation techniques. This paper presents an analysis of power frequency (50 Hz) electric and magnetic field levels inside 110/x kv substations. The analysis is based on the results of electric field strength and magnetic flux density measurements inside substations of the aforementioned voltage level in Serbia, with the aim of assessing the exposure of workers to these fields. The measurements were carried out with the purpose of estimating maximum field levels which can occur inside these substations. The measurements were performed inside a large number of 110/x kv substations in Serbia, whereas results obtained inside two typical substations are presented in this paper. In order to estimate the exposure of workers to these fields, the obtained results were compared to the action levels (ALs) prescribed by Directive 2013/35/EU [1]. The first objective of the analysis performed is to reach general conclusions about the field levels which can occur inside the substations of the mentioned voltage level. The second objective is to check whether these levels comply with the ALs prescribed by Directive [1]. 2 Overview of Directive 2013/35/EU The issue of exposure of workers to non-ionising radiation is addressed by Directive 2013/35/EU of the European Parliament and of the Council [1], which repealed Directive 2004/40/EC [2]. Directive [1] prescribes exposure limit values (ELVs) and ALs. ELVs represent values established on the basis of biophysical and biological considerations, in particular on the basis of scientifically well-established short-term and acute-direct effects, i.e. thermal effects and electrical stimulation of tissues. ALs correspond to calculated or measured electric and magnetic field values at the workplace in the absence of the worker, and are established for the purpose of simplifying the process of demonstrating the compliance with relevant ELVs. The method of exposure assessment based on ALs is conservative. If field values obtained by measurements and calculations are below ALs, automatic compliance with ELVs is implied. ALs prescribed by Directive [1] are given in Table 1. Directive [1] prescribes the minimum requirements, giving EU member states the option of maintaining or adopting more favourable provisions for the protection of workers, in particular by fixing lower values for the ALs or the ELVs for electromagnetic fields. Table 1 ALs for power frequency (50 Hz) electric field strength and magnetic flux density (rms) Electric field strength 3 Testing of electric and magnetic fields inside 110/X kv substations 3.1 Measured quantities The testing was based on measurements of rms values of electric field strength and magnetic flux density. The intensity of these vector quantities was measured isotropically, by performing simultaneous measurements of all three spatial components of field vectors. The field frequency was also measured simultaneously with electric field strength and magnetic flux density, and it amounted to 50 Hz at all measurement points. 3.2 Measurement equipment Magnetic flux density Low AL, kv/m High AL, kv/m Low AL, mt High AL, mt 10 20 1 6 The measurements were performed by using an electromagnetic field analyser connected to the isotropic probes for electric field strength and magnetic flux density measurements [3]. These probes insure simultaneous measurements of all three spatial components of field vectors, based on which the instrument shows their resultant values. 747

The probe for electric field strength measurements is cube shaped, with a 10 cm edge. During the measurements, this probe was placed on a wooden tripod and connected to the analyser by a several-metres-long optical cable. In this way, the influence of the operator on measurement results was avoided. The probe for magnetic flux density measurements is sphere shaped, with a cross-sectional area of 100 cm 2. During the measurements this probe was directly connected to the analyser. Throughout the measurements of electric field strength and magnetic flux density, a measurement mode with a 5 Hz 2 khz filter was used. 3.3 Measurement procedures The measurements were conducted in accordance with the measurement procedure described in [4], at a large number of measurement points. During measurements of magnetic flux density, load currents of the magnetic field sources were also monitored. Based on the ratio of maximum load currents and the currents at the time of measurements, as well as on the measured values of magnetic flux density, a conclusion was reached on compliance of maximum magnetic flux density levels, which would occur at the rated load, with ALs. The measurements were performed along the transport routes, near the high-voltage/medium-voltage (HV/MV) equipment and the power transformers, as well as inside and close to the control buildings. At all the measuring points outdoors, the measurements were carried out at a height of 1.7 m above ground, as workers in these zones are usually in the standing position and dominant field sources (busbars, HV/MV equipment) are located above them. In the vicinity of metal-enclosed cabinets with MV equipment, the measurements were also carried out at the heights of 0.5, 1 and 1.5 m. Fig. 1 Locations of measurement points 1 62 4 Results of electric and magnetic field measurements In this paper, measurements inside two 110/x kv substations in Serbia are presented. 4.1 110/10 kv Kraljevo 5 substation The measurements were performed at the measurement points shown in Figs. 1 and 2 [5]. At measurement points 1 104, located outdoors, the measurements of electric field strength and magnetic flux density were performed at the 1.7 m height. At points 105 110, near 110/ 10 kv power transformers T1 and T2, only magnetic flux density measurements at the 1.7 m height were performed in the vicinity of 10 kv enclosed busbars. Measurement points 111 127 are located inside the control building. Points 111 126 are positioned near 10 kv metal-enclosed equipment, at the heights of 0.5, 1, 1.5 and 1.7 m. Measurement point 127 is also positioned inside the control building at the 1 m height and represents the location where maximum magnetic flux density value of 0.35 µt was measured in the control room, where workers spend most of their time. The load currents of the magnetic field sources during magnetic flux density measurements as well as the maximum load currents of these sources are shown in Table 2. The marks in Table 2 signify the following: U (kv) voltage level of magnetic field source, I (A) load current of magnetic field source during measurements, I (%) percentage of maximum load current, and I max (A) maximum load current of magnetic field source. Fig. 2 Locations of measurement points 63 110 Table 2 Load currents of magnetic field sources Magnetic field source U, kv I, A I,% I max,a OHL No. 1167 B/1 110 0 0 880 OHL No. 1167 B/2 110 92 10.5 880 transformer T1 110 45 45.4 99.2 transformer T2 110 47 47.4 99.2 In the case of power transformers, the transformer rated loads specified by the manufacturer are adopted as the maximum loads. In the case of overhead power lines (OHL), maximum current allowed within the period of 20 min is adopted as the maximum load. 748

The measurement results are shown in Figs. 3 6, where E and B signify the measured values of electric field strength and magnetic flux density, respectively, and n signifies the ordinal number of measurement points. The highest value of electric field strength is measured at point 96 and amounts to 6.75 kv/m. This value is measured close to 110 kv equipment, where workers spend little time. The highest value of magnetic flux density is measured at point 122 and amounts to 86.15 µt. This value is measured at the 1.7 m height, just below 10 kv busbars of the transformer T2. The load of this transformer during the measurements was about 47.4% of its rated load. Fig. 5 Results of magnetic flux density measurements at measurement points 1 74 Fig. 3 Results of electric field strength measurements at measurement points 1 62 Fig. 6 Results of magnetic flux density measurements at measurement points 75 127 Fig. 4 Results of electric field strength measurements at measurement points 63 104 4.2 110/35 kv Očaga substation The measurements were performed at the measurement points shown in Figs. 7 and 8 [6]. In Fig. 8, electric field strength and magnetic flux density measurement points are separated where maximum values of these fields are in fact spatially separated. In these instances, measurement points are marked with E and B followed by appropriate ordinal numbers. Fig. 7 Locations of measurement points 1 76 749

Fig. 8 Locations of measurement points 77 119 At points 1 118, located outdoors, the measurements are performed at the 1.7 m height. Point 119, positioned at the 1 m height, represents the location where maximum magnetic flux density value of 0.26 µt was measured inside the control building. The load currents of the magnetic field sources and their maximum load currents are shown in Table 3. The measurement results are shown in Figs. 9 12. The highest value of electric field strength is measured at point 46 and amounts to 5.67 kv/m. This value is measured at the height of 1.7 m, close to 110 kv equipment, where workers spend little time. The highest value of magnetic flux density is measured at point 114 and amounts to 16.03 µt. This value is measured at the height of 1.7 m, near the 35 kv equipment and busbars, at the transformer load of 33.3% of its rated load. Fig. 10 Results of electric field strength measurements at measurement points 77 118 Table 3 Load currents of magnetic field sources Magnetic field source U, kv I, A I,% I max,a OHL No. 120/1 110 30 4.6 650 OHL No. 120/2 110 100 15.4 650 transformer T1 110 65 33.3 195 transformer T2 110 65 33.3 195 Fig. 11 Results of magnetic flux density measurements at measurement points 1 76 Fig. 9 Results of electric field strength measurements at measurement points 1 76 Fig. 12 Results of magnetic flux density measurements at measurement points 77 119 750

5 Conclusion On the basis of results of detailed measurements conducted inside two 110/x kv substations, a general conclusion about the levels which can occur inside these substations can be made. It can be concluded that in both cases measured values of electric field strength are lower than the low AL of 10 kv/m. Measured values of magnetic flux density, as well as the maximum values of magnetic flux density, which would appear at the rated load, are significantly lower than the low AL of 1 mt. 6 References 1 Directive 2013/35/EU of the European Parliament and of the Council of 26 June 2013 on the minimum health and safety requirements regarding the exposure of workers to the risks arising from physical agents (electromagnetic fields) (20th individual Directive within the meaning of Article 16(1) of Directive 89/391/ EEC) and repealing Directive 2004/40/EC, Official Journal of the European Union, 29 June 2013 2 Directive 2004/40/EC of the European Parliament and of the Council of 29 April 2004 on the minimum health and safety requirements regarding the exposure of workers to the risks arising from physical agents (electromagnetic fields) (18th individual Directive within the meaning of Article 16(1) of Directive 89/391/EEC), Official Journal of the European Union, 24 May 2004 3 EN 61786-1:2014: Measurement of DC magnetic, AC magnetic and AC electric fields from 1 Hz to 100 khz with regard to exposure of human beings Part 1: Requirements for measuring instruments 4 EN 50499:2008: Procedure for the assessment of the exposure of workers to electromagnetic fields 5 Nikola Tesla Electrical Engineering Institute, report No. 315407-L: Testing of exposure of workers to non-ionizing radiation Measurements of low frequency electric field strength and magnetic flux density inside 110/10 kv Kraljevo 5 Substation, 28 December 2015 (in Serbian) 6 Nikola Tesla Electrical Engineering Institute, report No. 315307-L: Testing of exposure of workers to non-ionizing radiation Measurements of low frequency electric field strength and magnetic flux density inside 110/35 kv Ocǎga Substation, 28 December 2015 (in Serbian) 751