DIAGNOSTIC OF OVERHEATING UNDERGROUND DISTRIBUTION CABLE JOINTS. Daniel Fournier and Normand Amyot IREQ, Institut de recherche d Hydro-Québec Canada

Similar documents
Infrared thermography as a tool to elaborate procedures for predictive maintenance of ball mills equipment

Characteristics Climatic Category 40/105/56 (IEC 61071)

Characteristics Climatic Category 40/85/56 (IEC 61071) Operating Temperature. 700 ~ 2000 VDC Capacitance Range 0,2 ~ 7,5 µf Capacitance Tolerance

Characteristics Climatic Category 40/105/56 (IEC 61071) Operating Temperature. 850 ~ 1200 VDC Capacitance Range 0,33 ~ 3,0 µf Capacitance Tolerance

Characteristics Climatic Category 40/105/56 (IEC 61071)

Temperature and Field Dependence of Field Grading Tubes for Medium Voltage XLPE Cable Joints

Advanced Technique for Dielectric Analyses

3M Pak 50 Boardmount Socket, P50 series P50-XXXS-XXX-EA. 3M Pak 50 Boardmount Plug, P50 series P50-XXXP-XXX-EA

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

An Introduction to Insulation Resistance Testing

DISTRIBUTION SYSTEM ELECTRIC INFRASTRUCTURE RELIABILITY PERFORMANCE INDICATORS

Qualification Test Report. Modular Plugs, Unshielded and Shielded

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

ELECTROMAGNETIC-ACOUSTIC TRANSDUCERS FOR IN-SERVICE MANUAL TESTING OF HEATED OBJECTS

Product Data Sheet PD-0053-A

SPECIFICATION AND PERFORMANCE CHARACTERISTICS OF SCA-2 CONNECTOR SERIES

3M Pak 10 Plug, PK10 series PK10-XXXPX-X-DA. 3M Pak 10 Socket, PK10 series PK10-XXXSX-X-DA

product manual H-4204 Proving Ring Penetrometer

Glossary Innovative Measurement Solutions

Latest Status of High Temperature Superconducting Cable Projects

Santhosh Kumar BVMP ABB GISL Chennai, India

HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION

Engineering Fracture Mechanics Prof. K. Ramesh Department of Applied Mechanics Indian Institute of Technology, Madras

PRODUCT SPECIFICATION

Available online at ScienceDirect. Procedia Engineering 133 (2015 ) th Fatigue Design conference, Fatigue Design 2015

Prosperity Dielectrics Co., Ltd. 1 ACS-1045 Rev15

Product Data Sheet PD-0037-B

ER2 Short-head Electric Chain Hoist

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

This specification covers the requirements for product performance, test methods and quality assurance provisions of FG Terminal.

Kinectrics North America Inc. Report No.: K RC-0001-R00 March 20, C.J. Pon, Z. Peter Transmission and Distribution Technologies Business

High-voltage Ceramic Capacitors (DC250V-6.3kV)

Technical Notes. Introduction. PCB (printed circuit board) Design. Issue 1 January 2010

The influence of thermal properties on power transmission characteristics of HVDC cables a factor analysis

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kv XLPE Cable

Page 2 of 14 Report Ref. No

Statics Principles. The laws of motion describe the interaction of forces acting on a body. Newton s First Law of Motion (law of inertia):

Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company

FL ballasts Electronic fixed output. PC TC PRO sr 1/2x11 42 W PC PRO compact

Jinzhou Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

Emissivity: Understanding the difference between apparent and actual infrared temperatures

CONNECTORS, ELECTRICAL, RECTANGULAR, MICROMINIATURE, NON-REMOVABLE GAUGE 26 PCB PIN CONTACTS BASED ON TYPE 8MCG

21. LECTURE 21: INTRODUCTION TO DIELECTRIC BREAKDOWN

MULTILAYER CERAMIC CAPACITORS Capacitor Arrays Series (10V to 100V) 4 x 0402, 4 x 0603 Sizes NP0, X7R & Y5V Dielectrics Halogen Free & RoHS Compliance

WIESON TECHNOLOGIES CO., LTD.

MULTILAYER CERAMIC CAPACITORS Low Inductance Series 0612 Size, 50V X7R Dielectric Halogen Free & RoHS Compliance

Applications: MCY 4C 3 B 103 K 500 C T. Two significant digits followed by no. of zeros. And R is in place of decimal point.

MR medium rating busbar

Damping resistor design consideration

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

Evaluation of Capacitance in Motor Circuit Analysis Findings. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

PRELIMINARY PRODUCT SPECIFICATION. Part Number Product Description Doc Number

Experiment Two (2) Torsional testing of Circular Shafts

URD Cable Fault Prediction Model

University of California at Santa Cruz Jack Baskin School of Engineering EE-80J: Renewable Energy Sources Greenhouse Effect Pre Questionnaire

E8EB-N0C2B E8EB-N0B2B

RS INDUSTRY LIMITED. RS Chip Array ESD Suppressor APPROVAL SHEET. Customer Information. Part No. : Model No. : COMPANY PURCHASE R&D

1. Introduction. 2. Use of COMSOL Multiphysics

METALLIZED POLYPROPYLENE AC FILTERING CAPACITORS

Product Data Sheet PD-0036-B. 3M PC Boardmount Plug and Receptacle, 2 mm 95X Series

Electromagnetic-Thermal Analysis Study Based on HFSS-ANSYS Link

Understanding Integrated Circuit Package Power Capabilities

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Boundary Condition Dependency

Blower Motor 3P Connector

Thermal Imaging Survey. Conducted at Nottingham

5. STRESS CONCENTRATIONS. and strains in shafts apply only to solid and hollow circular shafts while they are in the

Good Luck! Mlanie LaRoche-Boisvert - Electromagnetism Electromagnetism and Optics - Winter PH. Electromagnetism and Optics - Winter PH

Product Series Specification Document

Experimental Investigation of Contact Resistance of Slotted and Perforated Bolted Busbar Connections

AP Physics C - E & M

6 INCH W X 5-3/4 INCH D X 8-3/8 INCH H

PRODUCT SPECIFICATION

Understanding Integrated Circuit Package Power Capabilities

IPC-TM-650 TEST METHODS MANUAL

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT.LTD.

Power Resistors, for Mounting onto a Heatsink Thick Film Technology

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

Critical parameters of

Estimation of Current Transformer Insulation Life with an Effect of Environmental Variables

4. Objectives of Research work

No Item Code Description Series Reference. Thickness. M B min (mm) T (mm) code. See Thickness Specification Reference Table below

SolderSleeve Devices Specification For Commercial Wire Splices. Table of Contents

Thermal-Magnetic Circuit Breaker 2210-T2...

MULTILAYER CERAMIC CAPACITORS Open-Mode Series (50V to 630V) 0805 to 1812 Sizes X7R Dielectric Halogen Free & RoHS Compliance

FEATURES APPLICATIONS DESCRIPTION QUICK REFERENCE DATA. PILKOR components

Multilayer Ceramic Capacitors High Capacitance Series

Thermal-Magnetic Circuit Breaker 2210-S2..

Thermal-Magnetic Circuit Breaker 2210-S2..

High Ohmic/High Voltage Resistors

MODEL: MO Digital DC Milliohm Meter OPERATING INSTRUCTION

Part 2. Sensor and Transducer Instrument Selection Criteria (3 Hour)

Introduction to Blackbody Sources

The Impact of Metallized Electrodes on High Energy Density Pulse Power Capacitors

Detection of Defects in Thermal Barrier Coatings by Thermography Analyses

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

Thermal-Magnetic Circuit Breaker 2210-S2...

Thermal-Magnetic Circuit Breaker 2210-S2...

TYPE. max. working voltage 250 V 350 V 500 V 750 V. max. overload voltage 500 V 700 V 1000 V 1500 V. basic specifications IEC B

Transcription:

DIAGNOSTIC OF OVERHEATING UNDERGROUND DISTRIBUTION CABLE JOINTS Daniel Fournier and Normand Amyot IREQ, Institut de recherche d Hydro-Québec Canada SUMMARY A large number of power failures occur at cable joints in Hydro-Québec underground conduit network. Many are due to degradation of the electrical connection inside these joints and the corresponding degradation of their electrical insulation. A few years ago, Hydro-Québec started an infrared thermography program for underground cable joints. This program was implemented to perform predictive maintenance and withdraw the defective joints before failure. So far, the withdrawal criteria have had no real scientific and experimental basis. Moreover, there are serious discussions as to whether a non routine measurement of the temperature of a cable joint can really represent the health of its electrical connection. Also, for how long a temperature measurement is valid and therefore what should be the best frequency of temperature measurement Experimental We first chose three types of cable joints which represent the variety of electrical connections found in the underground power distribution system: separable elbow connectors for their bolted Cu (tin-plated) to Cu electrical contact, straight joints for their crimped connector (Al to Al electrical contact) and T joints for their bolted Al to Al electrical contact. We then measured the normal operating temperatures of each type of cable joint described above. Temperatures were measured at critical locations both inside and outside the cable joints, using thermocouples. These temperatures were measured at different current loads, at constant ambient temperature (~20 C) and for a given cable gauge. We defined one reference temperature for each type of cable joint. The difference between these reference temperatures and the ambient one is called the normal delta of temperature ( T). The second step was to assemble cable joints with stable and well characterized electrical-contact defects. These defect temperatures were measured at different current loads, at constant ambient temperature (~20 C) and for a given cable gauge. We defined one reference temperature for each type of cable joint. The difference between these reference temperatures and the ambient one is called the normal delta of temperature ( T). The second step was to assemble cable joints with stable and well characterized electrical-contact defects. These defects were such as to generate a temperature ~ 2 C above normal T, for a current load of 50 A. Our cable joints with their defects were subjected to a 24-hour current cyclic load, under high voltage (14.4 kv). Cyclic loads were intended to simulate field conditions: daily peak demands, sudden demand, interruptions and low overnight current load. Tests ended at cable joint failure (dielectric breakdown or loss of electrical contact). Results and discussion We monitored two parameters, namely Tmin and Tmax, while our cable joints were subjected to current cyclic load. Tmin is the minimum (joint temperature minus ambient temperature) reached during the daily low current portion of the cycle. At this point of the cycle, the joint temperature has stabilized and it is possible to follow the evolution of the initial T anomaly (~2 C above normal). The Tmax is the maximum (joint temperature minus ambient temperature) reached during the 24-hour cycle. Our results show evidence of a self-healing phenomena in power connectors. Indeed, connectors had periods of resistance instabilities during which metallic contacts are repeatedly reduced and then renewed. The selfhealing phenomena is more apparent in the low-current portion of our cycle load. We believe that the appearance of self-healing is a valuable indication that the electrical contact has entered an accelerated-aging phase preceding the failure. This could be a good withdrawal criterion, since self-healing appears even at low current loads and seems to precede failure by a fair amount of time (several months). The presence of the self-healing phenomena might explain why a non routine temperature measurement with an infrared camera cannot assess the health of the electrical contact of a cable joint. Indeed, an unfortunate worker could measure a normal temperature (due to self-healing) when in fact the contact is severely damaged. We believe that it is detection of the temperature instabilities at low and high current loads which counts and which reveals the true state of the electrical contact. Continuous monitoring of joint temperatures should therefore be considered. A computer software has been developed to diagnose the state of health of the cable joint. It takes into account all the aforementioned considerations and also many factors such as critical T, current load, ambient temperature, cable size, type of cable joint, and historical data bank. It is also backed by live data from the field where defective cable joint are being monitored. This software gives a diagnostic with a maintenance action: normal condition with a data recording, anomaly, which necessitates a closer inspection schedule and, finally, an important anomaly with immediate withdrawal of the cable joint. It is being tested in the field and results so far are very encouraging.

DIAGNOSTIC OF OVERHEATING UNDERGROUND DISTRIBUTION CABLE JOINTS Daniel Fournier and Normand Amyot IREQ, Institut de recherche d Hydro-Québec Canada, INTRODUCTION A great deal of power failures occur at cable joints in Hydro-Québec underground conduit network. Many failures are due to the degradation of the electrical connection inside these joints and the corresponding degradation of their electrical insulation. Hydro-Québec started a few years ago an infrared thermography program for underground cable joints. This program has been implemented to perform a predictive maintenance and withdraw the defective joints before failure. This program has very strict withdrawal criteria. Those criteria have until now no real scientific and experimental basis. Moreover, there are serious discussions as to whether a punctual measurement of the temperature of a cable joint can really represent the health state of its electrical connection. Also, for how long a temperature measurement is valid and therefore what should be the best frequency of temperature measurement? A computer program based on sound cable joint withdrawal criteria has been developed. It diagnoses defective cable joints by detecting signs of electrical connection degradation before their failure. EXPERIMENTAL We first choose three types of cable joints which represent the variety of electrical connections found in the underground power distribution field: elbow separable connectors for their bolted Cu (tin plated) to Cu electrical contact, straight joints for their crimped connector (Al to Al electrical contact) and T joints for their bolted Al to Al electrical contact. We then measured the normal operating temperatures of each type of cable joint described above. Temperatures were measured at critical locations both inside and outside cable joints, using thermocouples (see Fig. 1). These temperatures (once stabilized) were measured at different current loads, at constant ambient temperature (~20 C) and for a given cable gauge. We have defined one reference temperature for each type of cable joint. The difference between these reference temperatures and the ambient one is called the normal delta of temperature ( T). A complete description of the experimental set-up is given in (1). The second step was to assemble cable joints with stable and well characterized electrical contact defects. These defects were such as to generate a ~ 2 C above normal T, for a current load of 50 A. For the elbow connector, we created an electrical connection defect at the 90 change of direction where the tin plated Cu rod bolts into the Cu-Al lug. We managed to measure (in a indirect way) a resistance increased of ~ 500 mω at the defect location before testing under current load. Fig. 1 Typical straight cable joint assembly with thermocouple location (TC). Note the location of the reference temperature (TC3) used to compute the Tmin and the Tmax. For the straight cable joint category, defects were generated at the Al crimped connector. Defects consist in a low crimping pressure (3000 instead of 8000 psi) and only two crimps. The lower crimping pressure is intended to decrease the total metallic contact area and therefore, increase the constriction resistance, and the operating temperature. Before sliding the joint housing over the crimped connector, we measured the resistance of the electrical contact of defects. We measured ~ 30 µω which is twice as high as for a normal crimped connector. For the T cable joint, the bolted Al to Al electrical contact is a preferential location for hot spots. We created a defective electrical contact at this location by simply tightening it at a lower than recommended torque. Indeed, by using a torque of ~ 20 instead of 55 pounds-feet, we got a measured ~ 48 µω instead of 15 µω which represents the normal value for this electrical contact. Our cable joints with defect were submitted to a 24 hours current cyclic load (see Fig. 2), under high voltage (14.4 kv). Due to the high voltage applied to the cable conductor, only outside thermocouples were retained to measure the joint temperatures. Cyclic loads were intended to simulate field conditions : daily peak demands, sudden demand, interruptions and low overnight current load. This is not a truly accelerated aging test since we have always respected the manufacturer current load limits. The only acceleration is due to three peak demands (instead of two per days) and the initial higher than normal electrical contacts resistance. Tests ended at cable joint failure (dielectric breakdown or loss of electrical contact). RESULTS AND DISCUSSION One criteria of accelerated degradation of an Al-Al electrical contact is when the crimped connector reaches

~100 C (2). This is the case when T c3 (see fig. 1) reaches ~ 15 C (or 35 C at joint housing surface for and ambient temperature of 20 C). For elbow connector, Stoneham (3) has specified that it should be replaced if its internal temperature (Cu rod) is above 70 C. It is also said that the internal temperature of a T joint should not exceed 90 C as there is a rapid degradation of its epoxy components at this temperature (4). Once our cable joints were submitted to current cyclic load, we monitored two parameters : the Tmin and the Tmax. Tmin is the minimum reached during the daily low current (50 A) portion of the cycle (~04:00) during the night. At this point of the cycle, the joint temperature has stabilized and it is possible to follow the evolution of the initial T anomaly (~2 C above normal). The Tmax is the maximum reached during the 24 hours cycle. Figure 3 shows the Tmax versus time for the elbow connector. Current (A) 600 500 400 300 200 100 0 Time (hour) 00:00 02:00 Fig. 2 04:00 06:00 08:00 Elbow connector Straight joint T joint 10:00 12:00 14:00 16:00 18:00 20:00 22:00 Typical current load cycle. It basically shows the aging behavior of the defective electrical joint. It is not exactly like the one described by Bergmann (5). Nevertheless, one can recognize more or less the three aging phases: the formation, the relative stability and accelerated aging. The formation phase is short (from day 0 to ~ 20). It is characterized by a rapid increase in the T which reflects a joint resistance increase. The formation phase might extend here from day 90 up to ~ 120. If we disregard the T fluctuations due to initial current load adjustment (at day 70), this phase is characterized by a gradual increase in the joint resistance. The accelerated aging phase extends from about day 120 until the loss of electrical contact at day 280. This phase does not show a monotonic rapid increase of the contact resistance. It is characterized by contact resistance instabilities where rapid and important increase (up to ~13 C) and diminution of the T can take place within a few days. Finally, at day 280, the T reaches its highest peak (~31 C above normal) and failure occurred by loss of the electrical contact which opened the electrical circuit of our test loop. Such circuit opening in the underground distribution network would result in an electrical power failure. This test has been going on for ~475 days. It should have normally ended after ~280 days when this joint failed. A common practice in the field is to re-tighten the Cu rod of elbow joints when they have a hot spot. We therefore re-tightened the tin plated Cu rod and restarted the test to see the consequences of such practice. The three aging phases are more readily apparent in this second portion of the test : formation from about days 281 to 290, relative stability from day ~ 290 to 390 and accelerated aging (characterized by contact resistance instabilities) from day 390 up to day 475 (loss of electrical contact). Figure 4 shows the Tmin versus time for the elbow connector ( Tmin is the minimum reached during the daily low current (50 A) portion of the cycle). Around day 90, contact resistance instabilities are observed. As opposed to figure 3, there is no gradual increase in the T anomaly until ~ 6 days before failure. Indeed, within a few days, rapid increases in T are followed by sudden returns to the initial T anomaly (~2 C). T( C) 35,00 3 25,00 2 15,00 1 5,00 Loss of electrical contact Loss of elec. contact Re-start of the test Fig. 3 Tmax versus time for the elbow joint : bolted Cu (tin plated) to Cu contact. In this second portion of the test, the contact resistance instabilities resumed around day 390 which corresponds to a rapid increase of the Tmax. The more important instabilities appeared at about day 425 and correspond to the important ones observed for the Tmax after day about 420. This means that the common practice in the field which consists at re-tightening the tin plated Cu rod of elbow joints when they have a hot spot is definitely not a solution. The contact resistance instabilities observed in figures 3 and 4 are probably caused by a self-healing phenomenon due to softening or melting of the contact regions (6). This phenomenon is probably enhanced by the cyclic current load. Indeed, cyclic loads generate micromovements caused by the dilatation and contraction during heating and cooling of the contact region. The micro-movements induced by the dilatation of the conductor associated with the softening in the contact region can lead to a significant increase in the contact area. This causes the resistance to decrease, and the supertemperature to fall.

T( C) 16,00 14,00 12,00 1 Fig. 4 8,00 6,00 4,00 2,00 Loss of electrical contact Loss of elec. contact Re-start of the test Tmin versus time for the elbow joint : bolted Cu (tin plated) to Cu contact. It reverses the aging process [6]. On the other hand, these micro-movements could cause fretting corrosion at the contact area and destroy it. Also, the presence of tin plating at the metallic interface increases the chance of having fretting since tin is prone to fretting (7). Therefore a succession of higher contact resistance (caused by fretting corrosion) and self-healing phenomenon could explain the pattern illustrated in figures 3 and 4 where quiescent periods are interrupted by periods of intense interfacial activity during which the area of metallic contact is repeatedly reduced and then renewed. Figure 5 shows the Tmax versus time for the straight joint. In this case, the formation phase is not apparent. This contact seems to be in a relative stability phase (although short cycles of small T variations are observed) with a gradual increase in T. It is difficult to say from this figure when this contact enters the accelerated aging phase albeit one can observe a brief period of resistance instabilities (from days 170 to 210). Figure 6 shows Tmin versus time for the same straight joint. One can see that important and short periods of resistance instabilities showed up at ~ day 115, 140 and 180. The onset of the accelerated aging phase seems to appear at day 260 where continuous short cycle with high amplitude temperature variations are observed. It is interesting to note that the onset of the accelerated aging phase is much more obvious on the Tmin graph where a relatively low current load is used. The duration of this accelerated aging phase is still unknown since failure of the electrical contact has not occurred yet. Finally, concerning the T joint results, it is interesting to note that, to the contrary of the previous tested joints, no precursor sign (i.e. resistance instabilities) announced the contact failure. Indeed, only a steep increase in the Tmin occurred few hours before the failure. One explanation of this situation could be the lack of pressure at the contact interface of bolted or screw type connections [1]. DIAGNOSTIC USING A COMPUTER PROGRAM A computer program has been developed to diagnose the health state of medium voltage underground cable joint. It takes into account all the considerations mentioned in the previous section and also many factors such as critical T, current load, ambient temperature, cable size, and type of cable joint. T ( C) T ( C) 6 5 4 3 2 1 Fig. 5 Tmax versus time for the straight joint: crimped Al to Al contact. 15,00 1 5,00 Fig. 6 Tmin versus time for the straight joint: crimped Al to Al contact. It is also backed by live data from the field where defective cable joint are being monitored. All those information are stored in an extended data bank. It also contains all the parameters concerning the thermal signature for almost any combination of medium voltage cable joint (for the north American market) and cable size (Al or Cu) in function of the current load and ambient temperature. Finally, each diagnostic are stored in this data bank since one criteria of this program is based on the evolution with time of overheating cable joint. The following is a brief description of the computer program functioning. Pre-inspection for a safe access to underground structure. Figure 7 shows the main menu of the computer program named Thermo. The upper part is for the identification of the cable joint. The middle part specifies the accessory model and cable size (using a list box), the ambient and the accessory surface temperatures both measured with an infrared camera, before workers get in the underground structure. Note that the current load is not necessary at this stage. Once the pre-inspection button is pushed, the program estimates the inner temperature of the accessory. If the

temperature is above 70 or 100 C (according to the accessory model), the access of the underground is denied. A lower than 70 or 100 C allows free access to the structure. Full diagnostic using the current load. Current load is measured once the worker is in the structure. It is put in the main menu and by pushing the Diagnostic button, a full maintenance diagnostic is performed as can be seen in figure 8. Three different diagnostics can be obtained: green meaning that the accessory behaves normally and that no maintenance is required, yellow message meaning that we have a small overheating problem which requires a tighter maintenance schedule and finally, a red message meaning that the accessory has an important overheating problem and that it should be withdrawn as soon as possible. In the case of a yellow message, a Prediction curve (see figure 9) gives one the opportunity to visualize how close the actual situation is to the red area (where inner accessory temperatures are above 70 or 100 C ) in function of current load and ambient temperature. Historical data bank By pushing the History button on the main menu, we have access to the historical data bank where every diagnostic is stored (see fig. 10). This data bank is very important since every time a diagnostic is performed, the program compares the actual data with the previous one in order to detect any thermal instabilities as observed on figures 4 and 6. If any instability is detected, a message appears in the information box and a withdrawal of the accessory is recommended. Any data can be retrieved for examination or for another inspection. Fig. 8 Main menu of the thermo program. In this case a full diagnostic has been performed Fig. 9 Prediction curve showing the actual situation versus the critical area where inner temperature are above 100 C Fig. 10 Historical data bank Fig. 7 Main menu of the thermo program. In this case a pre-inspection has been performed CONCLUSION Our results have shown evidences of self-healing phenomena in power connector. Indeed, connectors had periods of resistance instabilities during which metallic contacts are repeatedly reduced and then renewed. The self-healing phenomena is more apparent at the low current portion of our cycle load. We believe that the appearance of self-healing is a valuable indication that

the electrical contact has entered an accelerated aging phase preceding the failure. This could be a good withdrawal criteria since self-healing appears even at low current loads and seems to precede the failure by a fair amount of time (several months). The presence of the self-healing phenomena might also explain why a punctual temperature measurement with a infrared camera cannot asses the health state of a cable joint electrical contact. Indeed, unfortunate worker could measure a normal temperature (due to self-healing) when in fact the contact is severely damaged. We believe that it is the detection of the temperature instabilities at low current and high current loads which counts and reveals the true electrical contact health state. Continuous monitoring of joint temperature should therefore be considered. Finally a computer software has been developed to diagnose the health state of cable joint. It takes into account all the aforementioned considerations and also many factors such as critical T, current load, ambient temperature, cable size, type of cable joint and historical data bank. It is also backed by data from the field where defective cable joint are being monitored. This software gives a diagnostic with a maintenance action: normal condition with a data recording, anomaly which necessitates a closer inspection schedule and finally an important anomaly with an immediate withdrawal of the cable joint. It is being used in the field and results are so far very good. 6. Williamson B. P., 1980, Self-Healing Effect : its Implications in the Accelerated Testing of Connectors, Proc. 10 th ICEC, Budapest, Hungary, p. 1089. 7. Braunovic M., 1994,, Aluminum connections : Legacies of the Past, Proceedings of the 40 th IEEE Holms Conference on Electrical Contacts, Raghar Holm Scientific Achievement Award. ACKNOWLEDGMENT Our special thanks to Daniel Lalancette and Richard L écuyer for their technical contribution and to Christian Langheit for the programming of the THERMO software. REFERENCES 1. Fournier D., 1998, Aging of Defective Electrical Joints in Underground Power Distribution Systems, Proceedings of the 44 th IEEE Holms Conference on Electrical Contacts, pp. 179-192, Arlington, USA,. 2. Dang C., 1992, Condition limites d utilisation des jonctions Elastimold, Hydro-Québec IREQ-92-067 report. 3. Stoneham M, 1990, Infrared Thermography for Distribution System, Canadian electrical association Report no. 168 D 391A, p. 73. 4. Dang C. and Trinh N.G., 1990, Dielectric Performance of Distribution XLPE-Cable Accessories at High Temperature, Canadian electrical association Report no. 139 D 505A. 5. Bergmann, Lobl H., Bohmeand., HGrosβmann S., 1996, Model to Asses the Reliability of Electrical Joints, Proc. of the 1996 IEEE Holm Conference on Electrical Contacts, Chicago, Il., September, p. 180.