REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

Similar documents
REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

Testing Procedure: AS ISO

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

A L I O N Technical Center. Test Report

RIVERBANK ACOUSTICAL LABORATORIES

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

Consultancy Report Ref: 9383-R01

Measurement of Acoustic Properties of light weight concrete SL-Deck

Measurement of sound absorption coefficient for Fraster felt SpaceCover

RIVERBANK ACOUSTICAL LABORATORIES

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

Development of a small-scale reverberation room

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Fabric Dazzle 6086 Manufacturer Carnegie Fabrics

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

Renolit stretch ceilings

LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING

Fabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04

Fabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

Fabric XPRESS + PU-foam Manufacturer Gabriel A/S

Curtain fabric type Ace Manufacturer Kvadrat A/S

Laboratory for Acoustics

REPORT. Client. Test object. Date of testt. Results. Rönnåsgatan 5B Ulricehamn. (7 appendices) content of the

Fabric REFLECTACOUSTIC

Fabric TWIST MELANGE Manufacturer Gabriel A/S

Page 1 of 10 pages Appendix, 5 pages Report no.: P Glostrup, October 12th 2012 Project: Claimant:

Fabric Medley Manufacturer Gabriel A/S

Fabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09

Technical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.

Fabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02

Paseo Recoletos, nº Madrid TEST REPORT

stylegreen Iceland Moss / Reindeer Moss of the company FlowerArt

Fabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32

Fabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07

Roller blind fabric PRIMACOUSTIC R

Fabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16

Fabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

Determination of sound absorption coefficient in impedance tubes according to ISO (2 appendices)

TFI Report Sound Absorption Impact Sound Insulation

TFI Report Sound Absorption Impact Sound Insulation

TFI Report Sound Absorption Impact Sound Insulation

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV

The effect of an edge on the measured scattering coefficients in a reverberation chamber based on ISO

ISO INTERNATIONAL STANDARD

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

Using an ambisonic microphone for measurement of the diffuse state in a reverberant room

Calcul des coefficients d'absorption alpha sabine

Laboratory for Acoustics

Part 2: Methods for special reverberation test rooms

Evaluation of standards for transmission loss tests

TFI Report Sound Absorption Impact Sound Insulation

Report. P.O. Box 70 NL 5700 AB Deurne The Netherlands Report number: A E-RA Date: 12 februari 2014 TS/TS/JW/A E-RA

Report. Laboratory for Acoustics

Yalıtım Kontrol Koruma. Insulation Control Protection

Acoustic response in non-diffuse rooms

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

REPORT N CR

MAC Aura XB Acoustic Test Report

Study of Wenger Audience Seating Chair Absorption. Ron Freiheit

ON SOUND POWER MEASUREMENT OF THE ENGINE IN ANECHOIC ROOM WITH IMPERFECTIONS

Certificate of Calibration Sound Level Calibrator

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

Report. Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool

R & D AKUSTIKA * SIA. Test Report of laboratory Sound Insulation measurements Nr. 569 / 2011 AL 8.4. CUSTOMER: AEROC AS (Estonia)

Summary. The basic principles of the simulation technique SERT

INVESTIGATIONS INTO THE PERFORMANCE OF THE REVERBERATION CHAMBER OF THE INTEGRATED ACOUSTICS LABORATORY. A Thesis Presented to The Academic Faculty

Technical Note. Measurement of Sound Absorption for Flex Acoustics AqTube. Performed for Flex Acoustics. TC Project no.: T Page 1 of 7

Some issues in measurement of the random-incidence scattering coefficients in a reverberation room

ISO INTERNATIONAL STANDARD

Basic Study on a Laboratory Measurement Method of the Normal-Incidence Scattering Coefficient

Report. Laboratory for Acoustics

Laboratory and In Situ Sound Absorption Measurement under a Synthetized Diffuse Acoustic Field: a Case Study on Five Materials

Investigations on real-scale experiments for the measurement of the ISO scattering coefficient in the reverberation room

The practical application of G and C 50 in classrooms

Acoustic design of lightweight cabin walls for cruise ships

CERTIFICATE OF CALIBRATION

Design and Acoustics Brought into Harmony

Ecophon Acoustic Calculator. Accurate values in advance

1. Introduction. 2. ISO 3745 and ISO standard comparison

Ecolibrium. All natural. A new style for supermarkets? THE OFFICIAL JOURNAL OF AIRAH AUGUST 2017 VOLUME 16.7 RRP $14.95

SIMPLE APPLICATION OF STI-METHOD IN PREDICTING SPEECH TRANSMISSION IN CLASSROOMS. Jukka Keränen, Petra Larm, Valtteri Hongisto

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

Technical Brief 003 Report on the Measurement of Sound Absorption of Planex Linea Storage Units

A suggested method to be used to measure scattering coefficients of full scale samples.

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

An examination of some aspects of the use of ISO 140 Part 4 and 7 in field measurements.

FIFTH INTERNATIONAL CONGRESS ON SOUND AND VIBRATION DECEMBER 15-18, 1997 ADELAIDE, SOUTH AUSTRALIA

Transcription:

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM. Testing Procedure: AS ISO 354-2006 Testing Laboratory: Client: Applied Acoustics Laboratory RMIT University, School of Applied Sciences Melbourne, Victoria 3000, Australia NATA Accreditation Number 1421 Woven Image Pty. Limited 37-39 Chard Road Brookvale NSW 2100 Australia Date of Test: 5 th August 2009 Date of Report: 6 th August 2009 Report Number: Testing Officer: 121I/09-134/PD Peter Dale Peter Dale Approved NATA Signatory This document issued in compliance with NATA s accreditation requirements. Accredited for compliance with ISO/IEC 17025 Page 1 of 6

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM. 1. INTRODUCTION The tests described in this report were carried out at the request of the Woven Image Pty. Limited to determine the sound absorption coefficients of a sample of Woven Image Echo Panel 7mm tested with a 20mm air gap. The tests were carried out using the reverberation room of the Applied Physics Discipline, The Royal Melbourne Institute of Technology Limited. Testing has been carried out in accordance with AS ISO 354 2006 Acoustics: Measurement of sound absorption in a reverberation room. At the request of the client the weighted sound absorption coefficient α w has been determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption. The equipment used to perform these tests has been calibrated at an accredited laboratory and is in current calibration. 2. TEST FACILITIES AND PROCEDURES 2.1 Facilities The reverberation room is of pentagonal plan with the ceiling inclined with respect to the floor. No two room dimensions are equal or in the ratio of small whole numbers. The volume of the room is 200.0 cubic metres. A sufficiently diffuse sound field is established by the inclusion of 17 stationary diffusing boards of panelboard, each of onesided area approximately one square metre and suspended with random orientation. The total two-sided area of the diffusing elements is 0.16 of the total boundary surface area of the room. Previous tests carried out in the room have established that diffusivity of the room sound field is acceptable. The total surface area of the room boundaries and diffusing elements is 235.6 square metres. 2.2 Generation of sound field The test signals is random noise, band limited to a frequency range of 40Hz to 6300Hz. Three individual loudspeaker positions are used to excite the sound field in the reverberation chamber. The signal is fed to each loudspeaker in turn. 2.3 Receipt of signals Four microphones each mounted in statistically independent locations in the reverberation room are used to measure the sound field decays in the room. Ten sound decays are obtained at each of the twelve loudspeaker/microphone combinations, thus representing 120 decays for each frequency band. The microphone signal is relayed via a microphone amplifier, to a Bruel & Kjaer 3560 Pulse Multi Analyser System. The Pulse analyser is interfaced to a personal computer. A program running on the personal computer allows the determination of the reverberation time from the sound decays in accordance with the standard. The measuring equipment has been calibrated by an external laboratory, and is in current calibration. Page 2 of 6

3. SAMPLE FOR TESTING Sample: Woven Image Echo Panel 7mm Description: Material: 100% PET Std Board Size: 2700mm x 1200mm x 7mm thick. Nominal Surface density: 1400gsm Air Gap: 20mm The sample tested comprised of 3.5 panels arranged on the floor of the reverberation room floor to give a sample size of 2700mm wide x 4230mm long as depicted in Figure 1 below. The sample was tested with the perimeter edges enclosed by metal edges in accordance with the recommendations contained in AS ISO 354. The sample was tested with the sample mounted with 20mm air gap between the sample and the floor of the reverberation chamber. The total surface area of the sample was 11.42m2. Figure 1: Woven Image Echo Panel 7mm installed for testing in the reverberation chamber with a 20mm air gap. Page 3 of 6

LOCATION OF SAMPLE IN THE REVERBERATION ROOM Reverberation Chamber (Not to scale): X and Y co-ordinates of the sample location in the Reverberation Room Corner Ref. Number X co-ordinate (metres) Y co-ordinate (metres) 1-1.00 1.79 2-1.76 5.95 3-4.41 5.47 4-3.66 1.31 Descriptor Diagram Reference Length (m) Sample Length 1 to 2 Diagram Ref. A 4.23 Sample Length 1 to 4 Diagram Ref. B 2.70 Page 4 of 6

4. RESULTS The mean reverberation times at each frequency for the empty room, T60 e, the room with the sample installed, T60 e+s, the sound absorption coefficient and the 95% confidence interval are provided in Table 1. The results are rounded to 0.01. The 95% confidence interval for each frequency is determined from the standard deviation of the reverberation times of the empty room and the room with the sample. The k factor used to determine the 95% Confidence interval is 2.201. The results for the sample are detailed in Table 1 and Graph 1 of this report. Test conditions: Room Empty Air temperature 19.5 o C, Relative Humidity 47% Barometric Pressure 0.7656 metre of mercury. Room with Sample Air temperature 19.7 o C, Relative Humidity 48% Barometric Pressure 0.7645 metres of mercury Table 1: Reverberation times and Sound Absorption Coefficients of Woven Image Echo Panel 7mm tested with a 20mm air gap Octave Centre Frequency Bands, Hz Average RT s for empty room. T60 e Average RT s for room. with sample T60 e+s Sound Absorption Coefficient α s 95% Confidence Interval for α s 100 8.365 8.424 0.00 0.05 125 7.209 6.488 0.04 0.05 160 8.252 7.567 0.03 0.03 200 9.472 8.005 0.05 0.02 250 9.029 7.088 0.09 0.03 315 8.042 6.038 0.12 0.04 400 7.364 4.909 0.19 0.03 500 6.798 4.287 0.24 0.03 630 6.477 3.582 0.35 0.02 800 6.395 3.135 0.46 0.03 1000 5.879 2.619 0.60 0.04 1250 5.280 2.250 0.72 0.04 1600 4.721 1.964 0.84 0.03 2000 4.023 1.767 0.90 0.04 2500 3.441 1.577 0.97 0.05 3150 2.811 1.438 0.97 0.03 4000 2.277 1.274 0.99 0.05 5000 1.800 1.142 0.92 0.06 Page 5 of 6

The weighted sound absorption coefficient α w of the sample determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption is: α w = 0.30(M,H) The Practical Sound Absorption Coefficients are detailed below in Table 2. These values have been determined in accordance with AS ISO 11654-1997 Acoustics: Sound Absorbers for Use in Buildings - Rating of sound absorption. Table 2: Practical Sound Absorption Coefficients for the Sample Frequency (Hz) 125 250 500 1000 2000 4000 Practical Sound Absorption Coefficient, α p 0.00 0.10 0.25 0.60 0.90 0.95 NRC of the sample calculated in accordance with ASTM C423-90A is: 0.45 Graph 1: Sound Absorption Coefficients of Woven Image Echo Panel 7mm tested with a 20mm air gap Sound Absorption Coefficient Sound Absorption 1.00 0.90 0.80 0.70 0.60 0.50 0.40 0.30 0.20 0.10 0.00 Echo Panel 7mm, 20mm Air Gap 100 160 250 400 630 1000 1600 2500 4000 Frequency (Hz) Page 6 of 6