Pressure Drop Measurements in Rectangular Micro-Channel Using Gas Flow

Similar documents
Flow characteristics of ethanol-methanol mixture through a parallel micro-channels

technology, Nunna, Vijayawada, AP, 2 Assistant Professor, Department of Mechanical Engineering, Vikas Group Of Institutions, Nunna,

Piping Systems and Flow Analysis (Chapter 3)

CFD Analysis of Forced Convection Flow and Heat Transfer in Semi-Circular Cross-Sectioned Micro-Channel

LEAKLESS COOLING SYSTEM V.2 PRESSURE DROP CALCULATIONS AND ASSUMPTIONS

Experimental Study of Convective Heat Transfer and Thermal Performance in the Heat-Sink Channel with Various Geometrical Configurations Fins

NUMERICAL INVESTIGATION OF COUNTER FLOW ISOSCELES RIGHT TRIANGULAR MICROCHANNEL HEAT EXCHANGER

Fluid Flow, Heat Transfer and Boiling in Micro-Channels

A Comparative Second Law Analysis of Microchannel Evaporator with R-134A & R-22 Refrigerants

Numerical Study of Heat Transfer of Water Flow through Pipe with Property Variations. By Amjad Ali Pasha A. Mushtaq Khalid A.

Water Circuit Lab. The pressure drop along a straight pipe segment can be calculated using the following set of equations:

1 Nik Mohamad Sharif & Normah Mohd Ghazali / Jurnal Teknologi (Sciences & Engineering) 78: 10 2 (2016) 61 68

Heat transfer coefficient of near boiling single phase flow with propane in horizontal circular micro channel

Chapter 3 NATURAL CONVECTION

LECTURE 6- ENERGY LOSSES IN HYDRAULIC SYSTEMS SELF EVALUATION QUESTIONS AND ANSWERS

Experimental Study of Energy Efficiency of a Single Microtube

Numerical Investigation of Effects of Ramification Length and Angle on Pressure Drop and Heat Transfer in a Ramified Microchannel

A CFD Simulation Study on Pressure Drop and Velocity across Single Flow Microchannel Heat Sink

Chapter (3) Water Flow in Pipes

Lesson 6 Review of fundamentals: Fluid flow

Fluid Mechanics II 3 credit hour. Fluid flow through pipes-minor losses

Lesson 37 Transmission Of Air In Air Conditioning Ducts

Chapter 10 Flow in Conduits

Minhhung Doan, Thanhtrung Dang

TankExampleNov2016. Table of contents. Layout

Comparison of heat transfer characteristics of liquid coolants in forced convection cooling in a micro heat sink

FORCE FED BOILING AND CONDENSATION FOR HIGH HEAT FLUX APPLICATIONS

Constructal design: geometric optimization of micro-channel heat sinks

Pressure Losses for Fluid Flow Through Abrupt Area. Contraction in Compact Heat Exchangers

IHTC DRAFT MEASUREMENT OF LIQUID FILM THICKNESS IN MICRO TUBE ANNULAR FLOW

IEEE TRANSACTIONS ON COMPONENTS, PACKAGING, AND MANUFACTURING TECHNOLOGY PART A, VOL. 20, NO. 4, DECEMBER

APPLIED FLUID DYNAMICS HANDBOOK

Chapter 8: Flow in Pipes

Applied Gas Dynamics Flow With Friction and Heat Transfer

Microfluidics 1 Basics, Laminar flow, shear and flow profiles

FLUID MECHANICS PROF. DR. METİN GÜNER COMPILER

Chapter 6. Losses due to Fluid Friction

Experimental Investigation of Heat Transfer Characteristics on a Gas-to- Gas Parallel Flow Microchannel Heat Exchanger

1-Reynold s Experiment

Mathematical Modelling for Refrigerant Flow in Diabatic Capillary Tube

Mechanical Engineering Programme of Study

Exercise sheet 5 (Pipe flow)

Chapter 8: Flow in Pipes

Chapter 6. Losses due to Fluid Friction

FE Fluids Review March 23, 2012 Steve Burian (Civil & Environmental Engineering)

Applied Fluid Mechanics

Engineers Edge, LLC PDH & Professional Training

Theoretical and Experimental Studies on Transient Heat Transfer for Forced Convection Flow of Helium Gas over a Horizontal Cylinder

International Communications in Heat and Mass Transfer

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

Internal Forced Convection. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

FACULTY OF CHEMICAL & ENERGY ENGINEERING FLUID MECHANICS LABORATORY TITLE OF EXPERIMENT: MINOR LOSSES IN PIPE (E4)

F L U I D S Y S T E M D Y N A M I C S

Numerical Investigation of Laminar Flow in Micro-tubes with Designed Surface Roughness

Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10

LIQUID FILM THICKNESS OF OSCILLATING FLOW IN A MICRO TUBE

C ONTENTS CHAPTER TWO HEAT CONDUCTION EQUATION 61 CHAPTER ONE BASICS OF HEAT TRANSFER 1 CHAPTER THREE STEADY HEAT CONDUCTION 127

Pipe Flow/Friction Factor Calculations using Excel Spreadsheets

Viscous Flow in Ducts

Macroscopic conservation equation based model for surface tension driven flow

CONVECTION HEAT TRANSFER

NUMERICAL STUDY OF MICROSCALE HEAT SINKS USING DIFFERENT SHAPES & FLUIDS. Vipender Singh Negi CSIR-CSIO Chandigarh Govt. Of INDIA

Convection Heat Transfer. Introduction

Principles of Convection

Lecture 30 Review of Fluid Flow and Heat Transfer

MECHANICAL CHARACTERISTICS OF STARCH BASED ELECTRORHEOLOGICAL FLUIDS

Lecture 22. Mechanical Energy Balance

Inherent benefits in microscale fractal-like devices for enhanced transport phenomena

Applied Fluid Mechanics

Hydraulics. B.E. (Civil), Year/Part: II/II. Tutorial solutions: Pipe flow. Tutorial 1

InterPACKICNMM

Development of cryogenic silicon detectors for the TOTEM Roman pots

Experimental Study on Port to Channel Flow Distribution of Plate Heat Exchangers

Thermal & Hydraulic Characteristics of Single phase flow in Mini-channel for Electronic cooling Review

Practical Analysis Of Turbulent Flow In A Pipe Using Computational Fluid Dynamics

Characterization of transition to turbulence in microchannels

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

Micro Cooling of SQUID Sensor

Analysis of Pressure Losses in Conditioned Air Distribution: Case Study of an Industrial Cafeteria

Two-Phase Refrigerant Distribution in a Micro- Channel Manifold

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

Chapter (3) Water Flow in Pipes

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

Analysis of Fully Developed Turbulent Flow in a AXI-Symmetric Pipe using ANSYS FLUENT Software

Hydroelectric Design

ME 305 Fluid Mechanics I. Chapter 8 Viscous Flow in Pipes and Ducts

Experimental Analysis of Heat Transfer Enhancement over Dimpled Surface on One Side of Plate

Heat Transfer Convection

EXPERIMENT No.1 FLOW MEASUREMENT BY ORIFICEMETER

EXPERIMENTAL AND NUMERICAL STUDIES OF A SPIRAL PLATE HEAT EXCHANGER

Russell B. Schweickart and Gary Mills

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

When water (fluid) flows in a pipe, for example from point A to point B, pressure drop will occur due to the energy losses (major and minor losses).

CFD Analysis on Flow Through Plate Fin Heat Exchangers with Perforations

Visualization of flow pattern over or around immersed objects in open channel flow.

Final 1. (25) 2. (10) 3. (10) 4. (10) 5. (10) 6. (10) TOTAL = HW = % MIDTERM = % FINAL = % COURSE GRADE =

Hydraulics and hydrology

vector H. If O is the point about which moments are desired, the angular moment about O is given:

Analysis of Heat Transfer Parameters in Microchannel Fluid Flow

Pressure drop during condensation of refrigerants in pipe minichannels

Transcription:

Pressure Drop Measurements in Rectangular Micro-Channel Using Gas Flow R. Kalaivanan 1 and R. Rathnasamy 2 1 Associate professor, Mechanical Engineering, Annamalai University, India 2 Professor, Mechanical Engineering, Annamalai University, India Abstract: Due to the need for practical cooling technologies which could dissipate high heat fluxes, an experimental study of pressure drop in micro-channel was performed. In this work, laminar flow friction factors were determined using gas (air) as flow medium. Pressure drop vs flow rate data were used to evaluate friction factors in two parallel microchannels, namely MCP1 and MCP2 (1.0 mm deep x 0.240 mm width and 0.9 mm deep x 0.2 mm width, respectively). Each channel of length 192 mm fabricated on a 304 Stainless Steel substrate by chemical milling Reynolds number was covered between 24 5398 for MCP1 and 26 6233 for MCP2. Transient pressure drops measured within the channel itself to exclude entrance and exit losses. Friction factor Reynolds number analyses show that the friction constant are identical as normal channels for gas flow in the laminar region. Transition region lies in Re > 500 and transition set off at lower Re ~ 500 in comparison to normal channel. The discontinuity in f Re data identified as transition. Further, it may be possible to identify transition (from laminar region) as the deviation of non-dimensional pressure drop (NDPD) values. Keywords: Experiments, friction factor, gas, micro-channels, NDPD. I. Introduction Rapid advances in microelectronics during the past three decades have brought about a surge of interest in identifying means to reject heat from small surfaces. Heat fluxes in excess of 100 W/cm 2 are often required and in some instance rates that are an order of magnitude higher and desirable. A number of studies have been performed on this topic where the authors concluded that single-phase micro-channel cooling can be used as an effective means of heat rejection [1]. Friction factors measured in laminar and in turbulent flow of gas by [2], using silicon and abraded into glass. It is reported that the friction factors be greater than the classical values, by comparison to the Moody chart for flow in round pipes, not to corresponding charts for rectangular channels. Several investigations ensued which dealt with flow of gases [3]. Fluid flow and heat transfer experiments conducted in rectangular micro-channels by and offered a friction factor correlation (f=56.9/re Deq ) close to theoretical value [4]. Based on previous studies and current experimental work was performed to establish transition from f-re characterisation. In addition, NDPD method is adopted to characterise the same. to be comparable to the size of a double Euro PCB so that eventually the results of the study can be applied therein. The two test sections MCP1 and MCP2 were manufactured first by photo chemical etching process as shown in Figure 1. Subsequent to etching of channel the channel header portions were deepened by EDM in order to have negligible pressure loss. MCP1 and MCP2 have 47 and 50 micro-channels of rectangular cross-section 1000 by 240 µm and 900 by 200 µm in width and depth, respectively. Both ends of channels are provided with common header for uniform flow distribution through each channel [5]. These header portions were deepened after etching by EDM in order to have negligible pressure. The channel top covered with another plate of 0.5 mm by vacuum brazing. III. Experimental set-up and procedure Figure 2 shows the set-up for the gaseous flow experiments. The experimental set-up for gas flow consists of compressed gas source and a storage reservoir to supply gas to the test section. A pressure regulator is mounted between the gas source and the reservoir to avoid over pressurisation in the circuit under any circumstance. The storage reservoir has capacity of 0.0564 m 3 (56.4 litre). The compressed gas was admitted through the pressure regulator into the storage reservoir to build up a known pressure of about 5 bar. A solenoid valve is connected between the reservoir and test section and it was closed while charging the reservoir. The charged reservoir was allowed to discharge by opening this valve resulting in decrease of the gas pressure in the reservoir. Transient pressure measurements were conducted at a time interval of 5 seconds for both MCP1 and MCP2 at room temperature (~30 o C). The reservoir pressure and the pressure drop through the channels between each instant are recorded using differential pressure transducers (make: KELLER Druckmesstechnik; piezoresistive pressure transmitter, PD- 23/ 5 bar / 8666.1). The experiment details are given in Table 1. Fluid Table 1. Details of experiments No. of experiments MCP MCP 1 2 MCP1 Air 16 13 24-5398 Re range MCP2 26-6233 II. Fabrication of MCP1 and MCP2 For the present experiments, two test sections were prepared having common features; each channel of length 192 mm were fabricated on a 304 stainless steel substrate of overall dimensions 230 mm x 160 mm x 1.6 mm. This size is chosen 2964 Page

Storage reservoir 230 160 All dimensions are in mm Fig.1 Layout of the parallel type rectangular micro-channel 3.1 Primary data for gas flow Experiments were conducted for flow of gas as described. The data recorded in the current experimental program are presented graphically. Typical transient pressure curves for gas flow through MCP1 and MCP2 are shown in Figs. 3 and 4 respectively. The transient cylinder pressure and the pressure drop across the test section form the primary data. IV. Gas flow - Data reduction/analysis The mass flow rate was calculated by numerical differentiation of the reservoir pressure transient. By differentiating the perfect gas relation, pv=m g RT (1) and the mass flow rate can be calculated as dm g /d = (dp/d ) V/RT (2) The use of perfect gas relation is valid as the compressibility effects under the conditions of experiments are negligible (compressibility factor is almost 1.0). PXD SV MF Display unit PXD V Test module PR V Compressed gas source Fig. 2 Gas flow experimental set-up schematic Legend: G- Pressure gauge; MF-Micro filter; PR-Pressure regulator; PXD-Pressure transducer, SV- Solenoid valve V-Valve Fig. 3 Transient pressure data for air flow in MCP1 2965 Page

Friction fator (f) Friction factor (f). 10 1 0.1 0.01 10 100 1000 10000 Fig. 5. Plot of f vs Re for flow in MCP1 Fig. 4 Transient pressure data for air flow in MCP2 It is assumed that the temperature is constant. The Reynolds number is defined in the conventional way ( vd eq / ) based on cross-sectionally averaged velocity (v) (evaluated using the mass flow rate) and hydraulic equivalent diameter (D eq ) which is defined for non-circular duct as follows: D eq 4WH/(2W + 2H) (3) For the present experiment with gas, Re can be written as follows: Re 2V(dp/d )/ μ RT(W H) (4) The values of viscosity used [6] is 1.82x10-5 Pa s, for air. The pressure drop across the channel for any time step was taken as the average value at the two instants. The Darcy-Weisbach formula was used for calculating the friction factor as below Δp/ρ f (L/D eq ) (v 2 / 2) (5) where, p is the pressure drop, is the density, f is the friction factor, L/D is length to diameter ratio and v is the velocity. eq Equation (5) can be rewritten as follows: 2WH f Δp W H 3 2 2ρ Re 2 μ L (6) The density used in the above equation was evaluated at the average pressure between the inlet and outlet of the channel. V. Gas flow results The values of friction factor (f) obtained in the present flow experiments are plotted as f vs Re and the line f=c theo /Re have also been drawn in for reference. The C theo is the theoretical value for fully developed laminar flow in a straight channel. It is evident, that there is a deviation between C theo for normal channel assumption and to the present micro-channel. The value of C theo, which depends on the aspect ratio, had been calculated for MCP1 and MCP2 using the data given in F.M.White. Legend: - Experimental, Solid line- Theory, Dashed line- Transition 10 1 0.1 0.01 10 100 1000 10000 Fig. 6. Plot of f vs Re for flow in MCP2 Legend: - Experimental, Solid line- Theory, Dashed line- Transition Fluid MCP 1: Air Table 2. Values of C 1 in eq. (7) C theo 73.5 6 Avg e. 90. 38 mi n. 81. 69 max. 98.7 7 Std Dev n. Re Tr ŧ 5.12 ~500 MCP 74.7 2: 3 Air 91. 86. 95.2 29 47 8 2.89 ~500 ŧ Note: Only perceived data are presented. Remar ks on eq. (7) Re< 500 Re< 500 and the values of C 1 are given in the Table 2. Also Table 2 (Column 2) gives the theoretical values for the two channels. Although, the aspect ratios for MCP1and MCP2 are of same order, the values of friction constant for MCP1 and MCP2 are more than C theo and are about 22% higher. Comparing the values of MCP1 and MCP2, it is seen that there is a deviation of about 1%. 5.1 Friction data Figures 5 and 6 shows the friction factor vs Reynolds number plots for MCP1 and MCP2 respectively. The laminar flow data were fitted using the following relation, f C1 /Re (7) 2966 Page

NDPD NDPD VI. Non-dimensional pressure drop (NDPD) An alternative way of presenting friction data is to give a relation between non-dimensional pressure drop (NDPD=2 p [( D eq 3 )/( 2 L)]) and Re. Equation (7) re-written becomes NDPD Re C1 (8) From the flow measurement data, experimental NDPD was evaluated. Figures 7 and 8 show the plots of NDPD vs Reynolds number for flow of gas in MCP1 and MCP2 respectively. At low Reynolds number values a linear relationship between the NDPD and Reynolds number is evident, wherein experimental NDPD data fall along the solid line (in Fig. 7 for MCP1 and Fig. 8 for MCP2). The solid lines drawn in Figs. 7 and 8 represent the theoretical value of NDPD for laminar flow in straight macro-channels. The dashed lines drawn (in Figs. 7 and 8) represent the experimental value of NDPD based on the average value of C 1 for air (Column 3 in Table 2). 4.0E+06 3.0E+06 2.0E+06 1.0E+06 0.0E+00 0 1000 2000 3000 4000 5000 Fig. 7 Plot of NDPD vs Re for flow in MCP1 Legend: - Experimental, Solid line- C theo, Dashed line- C 1 (exp) 2.0E+06 1.0E+06 0.0E+00 0 500 1000 1500 2000 2500 3000 3500 4000 4500 Fig. 8 Plot of NDPD vs Re for flow in MCP2 Legend: - Experimental, Solid line- C theo, Dashed line- C 1 (exp) Both from the f-re and NDPD-Re plots, it is clear that in each of the two channels at low Re the pressure drop varies linearly with velocity as would be expected for laminar flow. However, the friction factor is higher than the respective theoretical values for MCP1 and MCP2 (Figs. 5 and 6). It may be mentioned here that other experiments in microchannels have shown both higher [2] and lower [8] values of friction factor than those obtained in macro-channels. Further, the Figs. 5 to 8 shown are for one set of experimental data for each fluid and channel. 6.1 Transition Reynolds number (Re Tr ) The transition from laminar to turbulent regime is traditionally visualized as a discontinuity in the f vs Re relation. These change(s) of slope as construed to be points of transition as suggested by [7]. Unlike in the conventional flow geometries where one can expect a discontinuity in f vs Re relation, in the case of micro-channels such a sharp discontinuity is absent. Gerlach [7] proposed identification of these mild discontinuities through a plot of normalized pressure drop ( pd 2 eq / 2 ) against Re. This is also analogous to NDPD vs Re (or f vs Re) which has been adopted in the present analysis. ` It can be noticed from the f-re and NDPD-Re plots, for each of the two channels at low Re the pressure drop varies linearly with velocity as would be expected for laminar flow. This feature is the change(s) in slope of NDPD at certain Reynolds number(s) for MCP1 and MCP2 is also evident. These Reynolds numbers in the present analysis are termed as transition Reynolds numbers (Re Tr ). For MCP1 and MCP2, large changes in slope occur at Re 500. This change in slope appears to be like the characteristic transition to turbulence observed in pipe and channel flows. The derived or identified transition point is marked in Figs. 5 and 6 with vertical dashed line. Further study is required to relate the deviations in the friction curve with different fluids and geometries. However, it is clear that accurate data of friction is required for design of micro-channels. Three important conclusions arise out of the experiments with gas, namely i) The friction factors in MCP1 and MCP2 are the same. ii) The friction factors in MCP1 and MCP2 are higher than theory for laminar region. iii) The transition was observed in MCP1 and MCP2 at Re Tr 500. VII. Conclusion Pressure drop, friction factor were measured and calculated for gas flow in rectangular micro-channels. The gas flow experiments have been conducted in MCP1 and MCP2 with Reynolds number range of the order of 24 6233, covering laminar and transition flow regimes. The following conclusions emerge from the investigation 1. The transition region in micro-channel flow cannot be described distinctly as in the case of normal channels. 2. Reynolds number alone is inadequate to explain the flow behaviour in micro-channels. 3. To identify the transition, as the deviation of NDPD values or from change in slope. 4. The friction factor values are comparable to conventional tube flow in laminar region. 5. To obtain a generalised correlation for friction factor there is a need for more experiments on various geometries and different gases. 2967 Page

Acknowledgements The test modules used in this paper are financially supported by Department of Mechanical Engineering, Indian Institute of Science (IISc), Bangalore from Centre for Air Borne Systems project. The authors are grateful to Liquid Propulsion Systems Centre, Indian Space Research Organisation, Bangalore for deploying their expertise in the fabrication of test sections. References [1] M.B. Kleiner, S.A. Kuhn, and K. Haberger, High performance forced air cooling scheme employing micro-channel heat exchangers. IEEE. Trans. On Components, Packaging and Manufacturing Technology. Part A 18(4), 1995, 795. [2] P. Wu and W.A. Little, Measurement of friction factors for the flow of gases in very fine channels used for Micro-miniature Joule-Thomson Refrigerators. J. Cryogenics. 23, 1983, 273. [3] G. Hetsroni A. Mosyak, E. Pogrebnyak and L.P. Yarin, Fluid flow in micro-channels. Int. J. Heat and Mass Transfer, 52, 2005, 1982-1998. [4] J.Y. Jung and H.Y. Kwak, Fluid flow and heat transfer in micro-channels with rectangular cross section. J. Heat and Mass Transfer, 44, 2008, 1041-1049. [5] R.H. Perry, D. W. Green, and Maloney, Perry s chemical engineer s hand book, 6 th edition, McGraw- Hill Book Company. 1984. [6] C. F. Beaton, and G. F. Hewitt, Physical property data for the design engineers. New York Hemisphere publishers, 1989. [7] T. Gerlach, Micro-diffusers as dynamic passive valves for micro-pump applications. Sensors and Actuators, - A physical 69, 1998, 181-191. [8] D. Yu, R. Warrington, R. Barron, and T. Ameel, An experimental and theoretical investigation of fluid flow and heat transfer in micro-tubes. ASME/ JSME Thermal Engineering Conf. 1, 1995, 523-530. 2968 Page