SEISMIC PERFORMANCE OF CONCRETE COLUMNS WITH INADEQUATE TRANSVERSE REINFORCEMENT. Alistair Boys 1 Des K. Bull 2 Stefano Pampanin 3 ABSTRACT

Similar documents
Behavior and Modeling of Existing Reinforced Concrete Columns

Lap splice length and details of column longitudinal reinforcement at plastic hinge region

Appendix G Analytical Studies of Columns

CE5510 Advanced Structural Concrete Design - Design & Detailing of Openings in RC Flexural Members-

Mesh-sensitivity analysis of seismic damage index for reinforced concrete columns

AXIAL COLLAPSE OF REINFORCED CONCRETE COLUMNS

Sabah Shawkat Cabinet of Structural Engineering Walls carrying vertical loads should be designed as columns. Basically walls are designed in

Effect of eccentric moments on seismic ratcheting of single-degree-of-freedom structures

EUROCODE EN SEISMIC DESIGN OF BRIDGES

INELASTIC SEISMIC DISPLACEMENT RESPONSE PREDICTION OF MDOF SYSTEMS BY EQUIVALENT LINEARIZATION

Design of a Multi-Storied RC Building

Finite Element Modelling with Plastic Hinges

DEFORMATION CAPACITY OF OLDER RC SHEAR WALLS: EXPERIMENTAL ASSESSMENT AND COMPARISON WITH EUROCODE 8 - PART 3 PROVISIONS

Eurocode 8 Part 3: Assessment and retrofitting of buildings

Design of Reinforced Concrete Structures (II)

Coupling Beams of Shear Walls

EFFECT OF SHEAR REINFORCEMENT ON FAILURE MODE OF RC BRIDGE PIERS SUBJECTED TO STRONG EARTHQUAKE MOTIONS

Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design

Lecture-04 Design of RC Members for Shear and Torsion

Vertical acceleration and torsional effects on the dynamic stability and design of C-bent columns

COLUMN BASE WEAK AXIS ALIGNED ASYMMETRIC FRICTION CONNECTION CYCLIC PERFORMANCE

City, University of London Institutional Repository

EARTHQUAKE SIMULATION TESTS OF BRIDGE COLUMN MODELS DAMAGED DURING 1995 KOBE EARTHQUAKE

PEER/SSC Tall Building Design. Case study #2

OS MODELER - EXAMPLES OF APPLICATION Version 1.0. (Draft)

Shear Failure Model for Flexure-Shear Critical Reinforced Concrete Columns

DETERMINATION OF DUCTILITY CAPACITY AND OTHER SECTION PROPERTIES OF T-SHAPED RC WALLS IN DIRECT DISPLACEMENT-BASED DESIGN

A METHOD OF LOAD INCREMENTS FOR THE DETERMINATION OF SECOND-ORDER LIMIT LOAD AND COLLAPSE SAFETY OF REINFORCED CONCRETE FRAMED STRUCTURES

Earthquake-resistant design of indeterminate reinforced-concrete slender column elements

Seismic performance evaluation of existing RC buildings designed as per past codes of practice

A thesis submitted in partial fulfillment of the requirements for the degree of Master of Engineering endorsed in Earthquake Engineering

CAPACITY DESIGN FOR TALL BUILDINGS WITH MIXED SYSTEM

This Technical Note describes how the program checks column capacity or designs reinforced concrete columns when the ACI code is selected.

Inclusion of a Sacrificial Fuse to Limit Peak Base-Shear Forces During Extreme Seismic Events in Structures with Viscous Damping

Challenges in Collapse Prediction for Steel Moment Frame Structures

SHAKING TABLE COLLAPSE TESTS OF TWO SCALE MODELS OF A 4-STORY MOMENT RESISTING STEEL FRAME

ε t increases from the compressioncontrolled Figure 9.15: Adjusted interaction diagram

SHEAR CAPACITY OF REINFORCED CONCRETE COLUMNS RETROFITTED WITH VERY FLEXIBLE FIBER REINFORCED POLYMER WITH VERY LOW YOUNG S MODULUS

Chapter 4. Test results and discussion. 4.1 Introduction to Experimental Results

Earthquake Simulation Tests on a 1:5 Scale 10 - Story RC Residential Building Model

NON-LINEAR MODELING OF FLAT-PLATE SYSTEMS UNDER CYCLIC LOADING

ENERGY DIAGRAM w/ HYSTERETIC

Nonlinear static analysis PUSHOVER

THREE-DIMENSIONAL NONLINEAR DEGRADING MODEL FOR EARTHQUAKE RESPONSE ANALYSES OF CONCRETE BRIDGES

Chapter 6 Seismic Design of Bridges. Kazuhiko Kawashima Tokyo Institute of Technology

New model for Shear Failure of R/C Beam-Column Joints. Hitoshi Shiohara

Design of Reinforced Concrete Beam for Shear

POST-PEAK BEHAVIOR OF FRP-JACKETED REINFORCED CONCRETE COLUMNS

Chord rotation demand for Effective Catenary Action under Monotonic. Loadings

P-Delta Effects in Limit State Design of Slender RC Bridge Columns

SEISMIC PERFORMANCE OF LARGE RC CIRCULAR HOLLOW COLUMNS

BI-DIRECTIONAL SEISMIC ANALYSIS AND DESIGN OF BRIDGE STEEL TRUSS PIERS ALLOWING A CONTROLLED ROCKING RESPONSE

Chapter 8. Shear and Diagonal Tension

PREDICTION OF THE CYCLIC BEHAVIOR OF MOMENT RESISTANT BEAM-TO-COLUMN JOINTS OF COMPOSITE STRUCTURAL ELEMENTS

Dynamic Analysis of a Reinforced Concrete Structure Using Plasticity and Interface Damage Models

APPLICATION OF INTENSIVE SHEAR REINFORCEMENT TO SPLICING SLEEVE JOINT OF PRE-FABRICATED REINFORCEMENT ASSEMBLY

Journey Through a Project: Shake-table Test of a Reinforced Masonry Structure

Flexure: Behavior and Nominal Strength of Beam Sections

Where and are the factored end moments of the column and >.

EFFECTS OF CONFINED CONCRETE MODELS ON SIMULATING RC COLUMNS UNDER LOW-CYCLIC LOADING

Comparison of Structural Models for Seismic Analysis of Multi-Storey Frame Buildings

INELASTIC RESPONSES OF LONG BRIDGES TO ASYNCHRONOUS SEISMIC INPUTS

COLUMN INTERACTION EFFECT ON PUSH OVER 3D ANALYSIS OF IRREGULAR STRUCTURES

Design of Reinforced Concrete Beam for Shear

twenty one concrete construction: shear & deflection ARCHITECTURAL STRUCTURES: FORM, BEHAVIOR, AND DESIGN DR. ANNE NICHOLS SUMMER 2014 lecture

Constitutive Modeling of Reinforced Concrete Panel Behavior under Cyclic Loading

Prediction of the Lateral Load Displacement Curves for RC Squat Walls Failing in Shear

CHAPTER 6: ULTIMATE LIMIT STATE

Seismic design of bridges

Department of Mechanics, Materials and Structures English courses Reinforced Concrete Structures Code: BMEEPSTK601. Lecture no. 6: SHEAR AND TORSION

Lecture-08 Gravity Load Analysis of RC Structures

VTU EDUSAT PROGRAMME Lecture Notes on Design of Columns

Nonlinear Analysis of Reinforced Concrete Bridges under Earthquakes

SEISMIC RESPONSE EVALUATION OF AN RC BEARING WALL BY DISPLACEMENT-BASED APPROACH

Effective stress analysis of pile foundations in liquefiable soil

CHAPTER 4. ANALYSIS AND DESIGN OF COLUMNS

Design of Beams (Unit - 8)

INFLUENCE OF LOADING RATIO ON QUANTIFIED VISIBLE DAMAGES OF R/C STRUCTURAL MEMBERS

Dynamic Stability and Design of Cantilever Bridge Columns

A Modified Response Spectrum Analysis Procedure (MRSA) to Determine the Nonlinear Seismic Demands of Tall Buildings

Lecture-09 Introduction to Earthquake Resistant Analysis & Design of RC Structures (Part I)

Centrifuge Shaking Table Tests and FEM Analyses of RC Pile Foundation and Underground Structure

PACIFIC EARTHQUAKE ENGINEERING RESEARCH CENTER

Rapid Earthquake Loss Assessment: Stochastic Modelling and an Example of Cyclic Fatigue Damage from Christchurch, New Zealand

EVALUATION OF CURRENT APPROACHES FOR THE ANALYSIS AND DESIGN OF MULTI-STOREY TORSIONALLY UNBALANCED FRAMES

VELOCITY EFFECTS ON THE BEHAVIOUR OF ASYMMETRICAL FRICTION CONNECTIONS (AFC)

CHAPTER 4: BENDING OF BEAMS

Collapse modes of structures under strong motions of earthquake

Influence of column web stiffening on the seismic behaviour of beam-tocolumn

Failure interaction curves for combined loading involving torsion, bending, and axial loading

CAPACITY SPECTRUM FOR STRUCTURES ASYMMETRIC IN PLAN

University of Sheffield The development of finite elements for 3D structural analysis in fire

A q u a b l u e a t t h e G o l d e n M i l e

A Nonlinear Static (Pushover) Procedure Consistent with New Zealand Standards

SYSTEM IDENTIFICATION & DAMAGE ASSESSMENT OF STRUCTURES USING OPTICAL TRACKER ARRAY DATA

Seismic Assessment of a RC Building according to FEMA 356 and Eurocode 8

Mechanics of Materials Primer

Non-Linear Modeling of Reinforced Concrete Structures for Seismic Applications

Seismic Performance of RC Building Using Spectrum Response and Pushover Analyses

Design of reinforced concrete sections according to EN and EN

Transcription:

SEISMIC PERFORMANCE OF CONCRETE COLUMNS WITH INADEQUATE TRANSVERSE REINFORCEMENT. Alistair Boys 1 Des K. Bull 2 Stefano Pampanin 3 ABSTRACT Existing New Zealand building stock contains a significant number of structures designed prior to 1995 with inadequate detailing of the internal or gravity reinforced concrete (RC) columns. Typically these columns have insufficient transverse reinforcement, lap-splices in the plastic hinge region, and longitudinal bars that are cranked at the end of the lap-splice. Columns with such details have been shown to perform poorly when subjected to seismic actions, losing shear and axial load carrying capacity at low levels of drift. A set of displacement based models are presented (and verified experimentally) for the shear failure and subsequent loss of axial capacity for these columns under both uni- and bi-directional bending. INTRODUCTION Existing New Zealand building stock contains a significant number of structures designed prior to the revision of NZS 311 in 1995 with inadequate detailing of the internal or gravity reinforced concrete (RC) columns. While the requirements for shear, anti-buckling and confinement lead to adequate transverse reinforcement detailing of the moment resisting frame (MRF) columns in NZS311 1982, the gravity columns did not have matching requirements. This is a considerable oversight as the gravity columns undergo the same displacement demands as the MRF columns. As illustrated by previous earthquakes (see Figure 1) these columns are subject to damage associated with the displacement history of the structure, and can potentially lose axial capacity, leading to incipient collapse of the structure. Previous studies in the United States have investigated the axial failure of similarly detailed columns. Lynn et al [1] tested eight columns (with a range of reinforcement details) uni-directionally in double curvature. These double curvature tests highlight the susceptibility of inadequately detailed columns to lose axial capacity at moderate levels of drift (~2-3%). Melek et al [2] performed six unidirectional tests on cantilever columns with lapsplices under a range of axial loads. Results from these tests are limited to information regarding cyclic deterioration of the force-displacement capacity of the columns as axial failure occurred as a result of P-δ failure as opposed to loss of axial capacity at the shear failure plane. Both of the previous investigations focus on unidirectional bending and further research is necessary into the additional demands imposed by bi-directional bending with regard to degradation of strength/stiffness and the applicability of the proposed shear and axial drift limits. a) Indian Hills Medical Centre (1994 Northridge Earthquake) b) Olive View Hospital (1994 Northridge Earthquake) Figure 1 Damage to inadequately reinforced columns during previous earthquake 1 AB, Postgraduate Student, University of Canterbury 2 DKB, Professor, University of Canterbury & Technical Director, Holmes Consulting Ltd 3 SP, Senior Lecturer, University of Canterbury

MODEL DEVELOPMENT The most significant failure mechanism inherent in the inadequately detailed gravity columns is the loss of axial load carrying capacity. Elwood and Moehle recently proposed an idealised drift based backbone model for the drift capacity of these columns [3]. The model developed is empirical in nature and as such is applicable only to columns with appropriate reinforcement details [4]. Figure 2 below illustrates the proposed backbone capacity model and experimental results. The model has a shear capacity equal to the plastic capacity of the column (as determined by moment-curvature analysis). Detail dependent drift levels are calculated for the yielding of the section, shear failure (indicated by a reduction of capacity to below 8% of maximum); and the loss of axial load carrying capacity subsequent to the shear-failure. For the purposes of the paper only relationships for drift at shear and axial failure will be illustrated. The drift at shear failure (δ s ) is obtained by evaluating the relationship given by Equation 1 using a shear stress (υ), corresponding to the plastic shear capacity of the section (V p ) [4]. failure of the columns is dependent on prior shear failure and force equilibrium at the shear failure plane as illustrated in Figure 3. Force equilibrium in conjunction with experimental data was used to derive the relationship for the drift at axial failure [5]: δ = a 4 1 1+ tan tan 65 + P A st 2 f 65 yt s d tan 65 c (2) Where; 65 is the assumed angle of the shear failure plane, A st = area of transverse reinforcement parallel to the applied shear and having spacing s, f yt = yield stress of transverse reinforcement, and d c = depth of column core measure parallel to the applied shear. 3 1 υ 1 P 1 δ s = + 4ρ" (1) 1 4 f ' 4 A f ' 1 c g c Where; ρ = transverse steel volumetric ratio, υ = nominal shear stress, f c = concrete compressive strength, P = column axial load, and A g = gross cross-sectional area. Figure 3 Free body diagram of the shear failure plane SPECIMEN DESIGN Figure 2 Backbone model with experimental data Design of the test columns was undertaken with consideration of the limitations imposed by the proposed models, the test apparatus, and with consultation with practising professional engineers to ensure realistic detailing. A significant detail (neglected in previous studies) is the practice in New Zealand of cranking the longitudinal bars at

the top of the lap-splice. These cranked bars are susceptible to buckling which may initiate early shear failure and loss of axial capacity. The resulting test specimens are 45mm square cantilever columns with a height (to the application of lateral load) of 1624 mm as illustrated in Figure 4. All specimens have four D25 Grade 3 reinforcing bars (longitudinal reinforcing ratio = 1%), R1 stirrups at 3mm spacing (minimum diameter and maximum spacing allowable, transverse reinforcing ratio =.12%), and cranked bars at the end of the lap-splice. Two lap-splice lengths are chosen; 6mm corresponding to the minimum allowable length of 24 longitudinal bar diameters (d b ) and 75mm to reflect a more conservative design. As a consequence of the lapsplice length and the configuration of the transverse reinforcement the specimens with 24 d b lap-splices also have inadequate restraint provided to the cranked longitudinal bars. Details of the lapsplice, cranked longitudinal bars and the location of the transverse reinforcement for the two test configurations are shown below in Figure 5. A concrete compressive strength (f c) of 32 MPa was targeted to reflect nominal design strength of 24 MPa and allowing for a 33% increase in longterm in-situ strength. Five of the specimens have an applied axial load of 2kN reflecting the likely upper bound of existing gravity columns. The sixth test has a reduced axial load of 1kN to enable the degradation in lateral capacity of the lap-splice to be calibrated. The experimental program with specimen designation, detailing provided, applied axial load and imposed displacement protocol is outlined in Table 1. Figure 4 Details of test specimens Table 1 Experimental program Designation Lap-Splice length Tie Details Load Loading Protocol 24L-3-2D 6mm (24 d b ) R1 @ 3mm 2kN (.3f c A g ) 2D Quasi-Static 24L-3-3D 6mm (24 d b ) R1 @ 3mm 2kN (.3f c A g ) 3D Quasi-Static 24L-3-3D-R 6mm (24 d b ) R1 @ 3mm 1kN (.15f c A g ) 3D Quasi-Static 3L-3-2D 75mm (3 d b ) R1 @ 3mm 2kN (.3f c A g ) 2D Quasi-Static 3L-3-3D 75mm (3 d b ) R1 @ 3mm 2kN (.3f c A g ) 3D Quasi-Static 24L-3-EQ 6mm (24 d b ) R1 @ 3mm 2kN (.3f c A g ) 3D Quasi-EQ

a) Lap-splice at base of column b) Cranked Longitudinal bars Figure 5 Photographs of lap-splice and cranked longitudinal bars with poorly placed stirrup TEST APPARATUS The test apparatus allows the cantilever columns to be loaded axially in addition to bi-axial bending. Figure 6 below illustrates the schematic of the lateral force application via a self-equilibrating frame and counterweight. Ball pivots are located at the top and base of the column allowing the reaction frame to rotate in both principal directions as the Lateral Rams extend (or contract) and induce bending in the column. load is applied using the DARTECH, which has an adjustable height reaction head and a ram extending from the floor. The experimental apparatus configured for bidirectional bending is shown below in Figure 7. The reaction frames with hydraulic rams for the two principal directions are shown. In the centre is the DARTEC, providing the axial load via a fixed reaction head upon 4 extendable legs and a 1,kN capacity hydraulic ram at the base. Partially obscured behind the near corner leg of the DARTEC is a test specimen (following testing). In the background the counterweights can be seen. Figure 6 Schematic of experimental apparatus Figure 7 Experimental Apparatus

MATERIAL TESTING Prior to testing each specimen, material tests were carried out to determine; the yield strength of the longitudinal and transverse steel, and the 28 day concrete compressive strength. These results are summarised in Table 2 below. The yield strength of the longitudinal steel (f y = 315 MPa) is very similar to the target capacity. However the yield strength of the transverse steel provided was significantly stronger (f yt = 439 MPa) than was specified, however this had minimal effect on the behaviour of the specimen due to the very low transverse reinforcement ratio. There was a moderate variability in the concrete compressive strength (f c ranges from 24.3 to 33.6 MPa), but all values lie within the expected range of in-situ columns. Table 2 Material testing Column Designation f c (MPa) f y (MPa) f u (MPa) f yt (MPa) 24L-3-2D 33.6 315 465 439 24L-3-3D 28.4 315 465 439 24L-3-3D-R 27.5 315 465 439 3L-3-2D 33.9 315 465 439 3L-3-3D 24.3 315 465 439 24L-3-EQ 25.3 315 465 439 UNI-DIRECTIONAL LOADING TESTS Two specimens were tested under uni-directional loading to confirm the validity of the proposed model. Specimens 24L-3-2D and 3L-3-2D were tested using a standard quasi-static drift protocol as used by Melek et al [2]. The protocol has three excursions to positive and negative peaks at increasing levels of drift (see Figure 8). Drift Level (%) 4 2-2 -4 Figure 8 Uni-directional quasi-static drift protocol The backbone model and associated drift limits for shear and subsequent axial failure were calculated for each of the specimens using the measured material strengths. Note that as the modelled axial failure is contingent on prior shear failure and the calculated drift at axial failure occurs at a lower drift than the shear failure for both specimens, the axial failure drift limit is increased to coincide with the shear failure limit. The experimental data and model comparisons for the two tests are shown in Figure 9. Both specimens had comparable material strengths and consequently very similar backbone models. failure of the two specimens occurred just prior to the modelled failure limit. failure of specimen 3L-3-2D occurs simultaneously with shear failure as the model suggests and while specimen 24L-3-2D undergoes the full excursion to the peak past the drift limit, failure occurs on the subsequent reverse cycle. Hysteretic degradation of the specimen with the minimum lap-splice length is markedly more pronounced than the more conservative specimen as Figure 9 shows. The tests also illustrate that the lack of effective restraint of the cranked longitudinal bar has no effect on the drift capacity of these columns which is perhaps counterintuitive.

3 3 Lateral Force (kn) 2 1-1 δ s, δ a Lateral Force (kn) 2 1-1 + δ s, δ a -2-3 -5-25 25 5 Displacement (mm) a) Specimen 24L-3-2D -2-3 -5-25 25 5 Displacement (mm) b) Specimen 3L-3-2D Figure 9 Experimental results and empirical models for the uni-directional loading specimens A sequence of test photographs from specimen 24L-3-2D is shown in Figure 1 a) e) below. Comparing these with Figure 1 i) and j), the additional damage associated with the minimum splice length is apparent. Specimen 3L-3-2D exhibits minimal cracking prior to the formation of the shear failure plane and splice cover expulsion does not occur. Buckling of the longitudinal bars was isolated to the crank in specimen 24L-3-2D whereas specimen 3L-3-2D exhibited buckling in the longitudinal bar and the crank. a) Specimen 24L-3-2D 1.5% Drift b) Specimen 24L-3-2D 2.% Drift (1st Cycle) c) Specimen 24L-3-2D 2.% Drift (3 rd Cycle) d) Specimen 24L-3-2D +3.% Drift (shear failure) e) Specimen 24L-3-2D -3.% Drift (axial failure) f) Specimen 24L-3-2D Buckled cranked bar g) Specimen 24L-3-2D Burst stirrup h) Specimen 3L-3-2D Buckled crank + Splice i) Specimen 3L-3-2D j) Specimen 3L-3-2D +2% Drift (prior to failure ) 2++% Drift (axial failure ) Figure 1 Progression of damage and failure close-ups

BI-DIRECTIONAL LOADING TESTS The bi-directional loading is a modification of a cloverleaf protocol. For these three tests the leaves have been scaled such that the peak drift in each of the principal components is equivalent to the drift level associated with the uni-directional protocol. Each leaf is traversed once at each level of drift, and in addition, an excursion is undertaken to each of the four principal axes. Resolving the bi-directional protocol into the principal components illustrates the rationale; in each principal axes the drift protocol entails three peaks in the positive and negative directions, similar to the uni-directional protocols. As a consequence the expected increase in damage associated with bi-directional loading and the adequacy of the proposed drift based failure limits can be assessed. Figure 11 below shows the drift protocol and experimental results for specimen 24L-3-3D (the drift protocol is identical for all three bi-directional tests). The central graph of the figure shows the drift protocol in plan view, with the components in the N-S and E-W directions shown to the right and below respectively. In addition the shear and axial failures are noted on both the Force-Displacement and the drift protocol graphs. Lateral Force E-W (kn) 25 125-125 -25 2 1 Drift N-S (%) -1-2 25 125-125 Lateral Force N-S (kn) -25 25 25 5 75 1 125 Step No. Step No. 5 75 1 125-2 -1 1 2 Drift E-W (%) Figure 11 Specimen 24L-3-3D drift protocol and experimental results

The proposed backbone model calculates the shear and axial drift limits for unidirectional loading (for any loading angle) by assessing the section capacity (at a given loading angle) and the density and effectiveness of the transverse reinforcement. Hence for a loading angle of 45 the stirrups have a reduced effectiveness (factor of 1/ 2) due to geometry, affecting both the shear and axial drift limits. Bi-directional loading poses a difficulty for this model as the section capacity and the shear and axial drift limits will differ for each angle of loading. Conservatively, it is proposed that the drift limits are calculated for loading at a 45 angle (corresponds to the minimum effectiveness of the transverse reinforcement) and resolved into the inplane component. As the imposed loading protocol incorporates displacements through all 36, the backbone section capacity is increased from the capacity at 45 to the capacity at to include the full range of loading angles. An illustration of the backbone model for bi-directional loading (resolved to the in-plane component) is provided in Figure 12. As described previously for the uni-directional loading specimens the drift at axial failure is adjusted to coincide with the drift at shear failure. Lateral Force (kn) 3 2 Drift at shear failure calculated by evaluating the shear limit relationship at a shear stress corresponding to the section capacity for 45 loading 1 Section ( Loading) Section (45 Loading) Capacity (45 Loading) Drift Limit (45 Loading) Drift Limit (45 Loading) Backbone Model 1 2 Displacement (mm) δ s, δa Figure 12 Backbone for bi-directional loading (resolved to the in-plane component) Experimental results and comparison with the proposed model for the bi-directional loading tests are shown on the following page in Figure 13 to Figure 15. Looking at the relationships for specimens 24L-3-3D and 24L-3-3D-R it initially appears that the backbone model overestimates the capacity of the specimens as the force-displacement relationship does not reach the in-plane capacity. However if consideration is given to the path of the loading protocol and the high rate of degradation associated with the minimum splice length provided it is evident that full capacity is unlikely to occur. Specimen 3L-3-3D however sustains a shear force considerably closer to the backbone due to the additional capacity of the splice provided. Of greater importance to the applicability of the model is the accuracy to predict the drift level at shear and axial failure. Experimental results and the modelled backbone for specimen 24L-3-3D are shown in Figure 13. failure occurs at a level of drift slightly below the modelled level and as for the uni-directional specimen with this lapsplice length the axial failure occurs on the subsequent loop of the drift protocol. Figure 14 shows the comparisons for the second bi-directional specimen, 24L-3-3D-R (reduced axial load of 1kN). It is clear that the backbone model captures the shear failure and the forcedisplacement behaviour adequately. The notable point of departure is with regard to the drift at axial failure, which exceeds the modelled limit by approximately 5%. However if the performance of previous tests performed by Melek [2] is considered it is evident that cantilever column tests with axial load in this range lose axial capacity resulting from a flexural P-δ failure. Whereas the model developed by Elwood et al. [5] was calibrated using tests in double curvature and has shown to be valid for axial loads of this magnitude. Consequently, given the good fit of the experimental data at prior to the modelled axial failure, the performance of this model applied to real double curvature columns can be considered adequate for low axial loads. Comparisons for specimen 3L-3-3D are shown in Figure 15. failure of the specimen occurs during the first leaf to 1.5% drift, just prior to the modelled limit. The subsequent axial failure occurs during the third leaf of the drift protocol, slightly later than modelled limit but this could be explained by the additional restraint at the failure plane by the dowel effect of the longitudinal bars and the reduced damage associated with increased splice length. A photographic sequence of the damage sustained by each of the three columns is shown over-page in Figure 16 - Figure 19. Similar damage is evident for each of the three tests with splice cover expulsion, bar buckling and the formation of a shear failure cone being evident in all three tests. This is a result of the dependency of the modelled axial failure on the formation of a shear failure plane and the full bi-directional loading imposed on these specimens.

25 25 E-W Lateral Force (kn) 15-15 N-S Lateral Force (kn) 15-15 -25-3 -15 15 3 E-W Displacement (mm) -25-3 -15 15 3 N-S Displacement (mm) Figure 13 Experimental results and empirical models for Specimen 24L-3-3D 2 2 E-W Lateral Force (kn) 1-1 N-S Lateral Force (kn) 1-1 -2-5 -25 25 5 E-W Displacement (mm) -2-5 -25 25 5 N-S Displacement (mm) Figure 14 Experimental results and empirical models for Specimen 24L-3-3D-R 25 25 E-W Lateral Force (kn) 125-125 N-S Lateral Force (kn) 125-125 -25-3 -15 15 3 E-W Displacement (mm) -25-3 -15 15 3 N-S Displacement (mm) Figure 15 Experimental results and empirical models for Specimen 3L-3-3D

a).5% Drift Loops b).75% Drift Loops c) 1.% Drift Loops d) 1.5% Loop 1 (shear) e) 1.5% Loop 2 (axial) Figure 16 Progression of damage for Specimen 24L-3-3D b).75% Drift Loops c) 1.% Drift Loops d) 1.5% Drift Loops e) 2.% Drift Loops f) 3.% Loop 3 (axial) Figure 17 Progression of damage for Specimen 24L-3-3D-R a).5% Drift Loops b).75% Drift Loops c) 1.% Drift Loops d) 1.5% Loop 2 (shear) e) 1.5% Loop 3 (axial) Figure 18 Progression of damage for Specimen 3L-3-3D a) Specimen 24L-3-3D Buckled crank b) Specimen 24L-3-3D cone c) Specimen 3L-3-3D Splice Cover Expulsion d) Specimen 3L-3-3D Cover Expulsion d) Specimen 3L-3-3D Buckled Bars Figure 19 Post failure damage photographs for bi-directional loading

QUASI-EARTHQUAKE LOADING Development of the quasi-earthquake protocol was undertaken to determine the likely performance of these gravity columns under a realistic displacement history. Also, in place of the in-plane drift limits (for 45 ) used previously a full drift limit curve was derived in the NS-EW plane. The drift protocol was developed using the following steps: 1. and failure drift limits are calculated at and 45 for the specimen (material testing required) and a limit curve is fitted. 2. A SDOF model of a prototype column is created with appropriate section properties and a hysteresis rule calibrated to the previous bidirectional tests. 3. A mass is selected to obtain an appropriate period to ensure relevant excitation from the earthquake record. 4. Earthquake record selection was made using the GNS database records for Wellington, given a standard shallow earthquake, and ensuring that the demand was not too excessive in terms of a large number of peaks near the limit curve. To this end the two orthogonal components of the F7821Z2 record of the 1978 Tabas earthquake were selected. 5. The record components are scaled to obtain a displacement history that coincides with the calculated drift limits for axial failure. Figure 2 below illustrates the imposed displacement protocol for specimen 24L-3-EQ and the experimental results with the modelled inplane backbone limits. The central graph of the figure shows the protocol and limit curve, with the components in the N-S and E-W directions shown to the right and below respectively. 25 Lateral Force E-W (kn) 125-125 -25 Experimental F-d data Backbone for loading Backbone for 45 loading 4 Displacment N-S (mm) 2-2 -4 25 125-125 Lateral Force N-S (kn) -25 + Limit Surface 125 25 375 5 Step No. 125 Step No. 25 375 5-4 -2 2 4 Displacement E-W (mm) Figure 2 Specimen 24L-3-EQ experimental results and model comparison

The comparison between the experimental data and the backbone model with drift limit curve(s) (shear and axial drift limit curves coincide for this specimen) illustrates the necessity to assess the full bi-directional behaviour of these columns. failure occurs as the bi-directional drift reaches the limit curve, however if the in-plane representation of the backbone is considered failure occurs between the solid and dashed backbone lines correspond to drift capacity for inplane and 45 loading respectively. As is evident the angle at which the drift maxima occurs affects the drift capacity, thus assessing columns using the 45 limits is conservative and the full limit curve should be used. Several excursions to significant levels of drift beyond the shear failure are required for axial failure to occur. However as earthquake records generally follow this post-peak pattern (with the exception of near-field events) it is appropriate to accept the validity of the drift-based backbone model and associated limit curves. b) Specimen 24L-3-2D 1.5% Drift c) Specimen 24L-3-2D 2.% Drift (1st Cycle) d) Specimen 24L-3-2D 2.% Drift (3 rd Cycle) e) Specimen 24L-3-2D +3.% Drift (shear failure) f) Specimen 24L-3-2D -3.% Drift (axial failure) Figure 21 Progression of damage for Specimen 24L-3-EQ CONCLUSIONS This investigation into the performance of RC gravity columns under uni- and bi-directional loading leads to the following conclusions: 1. RC gravity columns with inadequate transverse reinforcement are extremely susceptible to loss of axial load carrying capacity at drift levels lower than allowable during a design level event. 2. The backbone model proposed by Elwood and Moehle [3] is confirmed to adequately capture the shear and axial failure drift limits of RC columns with inadequate transverse reinforcement, including the extension to bidirectional loading. 3. Bi-directional loading results in a significant reduction to the in-plane drift capacity, however if a pair of shear and axial failure limit curves are used when assessing these columns the drift capacity may be more accurately assessed. 4. Buckling of the poorly restrained cranked longitudinal bars is not a critical mechanism for loss of axial load capacity. 5. The lap-splice length provided does not affect the drift capacity of RC columns, but does affect the rate of degradation and damage. REFERENCES [1] A. C. Lynn, J. P. Moehle, S. A. Mahin, and W. T. Holmes, "Seismic Evaluation of Existing Reinforced Concrete Building Columns," Earthquake Spectra, vol. 12, pp. 715-739, 1996. [2] M. Melek, J. W. Wallace, and J. P. Conte, "Experimental Assessment of Columns with Short Lap Splices Subjected to Cyclic Loads," PEER Report, vol. 4, 23. [3] K. J. Elwood and J. P. Moehle, "Idealised Backbone Model For Existing Reinforced Concrete Columns and Comparisons With FEMA 356 Criteria," Struct. Design Tall Spec. Build., vol. 15, pp. 553-569, 26. [4] K. J. Elwood and J. P. Moehle, "Drift Capacity of Reinforced Concrete Columns with Light Transverse Reinforcement," Earthquake Spectra, vol. 21, pp. 71-89, 25. [5] K. J. Elwood and J. P. Moehle, " Capacity Model for -Damaged Columns," ACI Structural Journal, vol. 12, pp. 578-587, 25.