Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method

Similar documents
ELECTRIC FIELD AND VOLTAGE DISTRIBUTION ALONG INSULATORS UNDER POLLUTION CONDITIONS. V T Kontargyri N C Ilia I F Gonos I A Stathopulos

Measurement and simulation of the electric field of high voltage suspension insulators

Measurement and simulation of the voltage distribution and the electric field on a glass insulator string

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators. Integrated Engineering Software - Website Links

Modeling of High Voltage Insulator Strings through Finite Element Method

Electric Field and Potential Distributions along Non-Ceramic Insulators with Water Droplets. Integrated Engineering Software - Website Links

3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator

Modeling Electric Field and Potential Distribution of an Model of Insulator in Two Dimensions by the Finite Element Method

SCIENCE & TECHNOLOGY

Analysis and Prediction of Electric Field Intensity and Potential Distribution along Insulator Strings by using 3D models

Simulation Studies of Composite Insulators used in High Voltage Transmission

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Winai Onchantuek, Boonruang Marungsri, Anant Oonsivilai, Thanatchai Kulworawanichpong. WSEAS TRANSACTIONS on POWER SYSTEMS

Transient analysis of the behaviour of grounding systems consisted by driven rods

Estimation of the Electric Field and Potential Distribution on Three Dimension Model of Polymeric Insulator Using Finite Element Method

VOLTAGE DISTRIBUTION ACROSS STRING INSULATORS BY SPHERE GAP METHOD

Comparison between artificial neural networks algorithms for the estimation of the flashover voltage on insulators

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

Modeling of Polluted High Voltage Insulators

Modeling Electric Fields in High Voltage Submersible Changeover Switch

CHAPTER 5 ANALYSIS OF ELECTRIC FIELD AND VOLTAGE DISTRIBUTION

Electric Field Analysis and Experimental Evaluation of 400 kv Silicone Composite Insulator

Performance analysis of 1200 kv ceramic disc insulator string under normal and faulted conditions

EFFECT OF DIELECTRIC BARRIERS TO THE ELECTRIC FIELD OF ROD-PLANE AIR GAP

The Distortion Influence Simulation and Experimental Study of Human Body to High Voltage Power Frequency Electric Field

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Degradation of Hydrophobic Properties of Composite Insulators in Simulated Arid Desert Environment

Finite Element Analysis on Post Type Silicon Rubber Insulator Using MATLAB

The influence of the Effect of Grounding and Corona Current to the Field Strength the Corona Onset and the Breakdown Voltage of Small Air Gaps

Magnetic and Thermal Analysis of Current Transformer in Normal and Abnormal Conditions

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Real-time Monitoring of Leakage Current on Insulating Cross-arms in Relation to Local Weather Conditions

Experimental Study of the Artificial Neural Network Solutions for Insulators Leakage Current Modeling in a Power Network

Electric Field Stress Calculation on High Voltage Insulator

Effect of High Voltage Impulses on Surface Discharge Characteristics of Polyethylene

Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot

World Academy of Science, Engineering and Technology

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

Measurement of the electric field at the near field radiating by electrostatic discharges

Excerpt from the Proceedings of the COMSOL Conference 2010 Paris

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

The phenomenon of Ground Effect in contradiction to the Polarity Effect in rod plate air gaps.

3D-model of an AC/DC Hybrid EHV Transmission Line to Analyze the Electrical Potential along Insulators

INVESTIGATING THE PROTECTION OF SHIP ELECTRIC GRIDS AGAINST LIGHTNING STRIKES THE DEFKALION-THALIS PROJECT

Finite Element Modeling and Examination of Axisymmetric Thermal State of the Overvoltage Suppressor

Some Aspects of Stress Distribution and Effect of Voids Having Different Gases in MV Power Cables

Prof. Dr. Magdi El-Saadawi

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

Measurement of wettability for polymer materials using non-contact surface resistivity

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

A New Contribution in Reducing Electric Field Distribution Within/Around Medium Voltage Underground Cable Terminations

ELECTRIC FIELD AND VOLTAGE DISTRIBUTIONS ALONG NON-CERAMIC INSULATORS DISSERTATION

I n many cold-climate regions of the world, overhead

Numerical Analyze of Corona Discharge on HVDC Transmission Lines

Reliability Enhancement of Line Insulator of a Transmission System using Artificial Neural Network Sumit Mathur #1, G.K. Joshi* 2

Extensions to the Finite Element Technique for the Magneto-Thermal Analysis of Aged Oil Cooled-Insulated Power Transformers

Electric Field and Thermal Properties of Dry Cable Using FEM

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

Parametric Study of Losses in Cross-Bonded Cables: Conductors Transposed Versus Conductors Nontransposed

Electric Field Stress Calculation for different spacer types in Bus Duct

COMPUTER METHODS FOR THE DETERMINATION OF THE CRITICAL PARAMETERS OF POLLUTED INSULATORS

Available online at ScienceDirect. Procedia Computer Science 83 (2016 )

EFFECT OF EARTH DISCONTINUED TO THE ELECTRICAL FIELD DISTRIBUTION IN ROD-PLANE AIR GAPS UNDER LIGHTNING IMPULSE. A. Khechekhouche and D.

Tailoring of new Field Grading Materials for HVDC Systems. Dipl.-Ing. Maximilian Secklehner Rashid Hussain, M.Sc.

STUDIES ON LIGHTNING CHARACTERISTICS

A Study of Electromagnetic Field Generated by High Voltage Lines Using Comsol Multiphysics

A Review of the Dynamic Modelling of Pollution Flashover on High Voltage Outdoor Insulators

Effective Design of Large Grounding Systems

Optimum Corona Ring Design for High Voltage Compact Transmission Lines. Using Gaussian Process Model. Nihal Mohan

HIGH electric field strength ( ) may cause corona on nonceramic

EVALUATION OF FLASHOVER VOLTAGE ON POLLUTED INSULATORS WITH ARTIFICIAL NEURAL NETWORK

Magnetic Field Analysis

Numerical Simulation and Experimental Study of Electromagnetic Forming

Finite Element Analysis Method for Detection of the Corona Discharge Inception Voltage in a Wire-Cylinder Arrangement

SIMULATION OF HEAT TRANSFER AND ELECTROMAGNETIC FIELDS OF PROTECTED MICROCOMPUTERS

A Novel Optimized Design for Busbar Structures using Finite Element Methods

Ten years analysis of Tropospheric refractivity variations

Static Force Characteristic and Thermal Field for a Plunger-Type AC Electromagnet

HIGH VOLTAGE TECHNIQUES REVİEW: Electrostatics & Magnetostatics

Insulator Selection Tool IST 2018

Wilson Area School District Planned Course Guide

CONTRIBUTION TO CALCULATING THE IMPEDANCE OF GROUNDING ELECTRODES USING CIRCUIT EQUIVALENTS. Andrijana Kuhar, Leonid Grcev

HIGH VOLTAGE ENGINEERING. Electric discharges in electric power engineering

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

The Effects of Applied Voltage, Contamination Level and the Length of Dry-Bands on the Electric Field and Leakage Current of Polymeric Insulator

3D Thermal-Diffusion Analysis on a Moisture Loaded Epoxy Sample

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

COUPLED MAGNETO-MECHANICAL FINITE ELEMENT ANALYSIS OF A POWER TRANSFORMER IN SHORT CIRCUIT CONDITIONS

Philippe Wendling

Eddy Current Losses in the Tank Wall of Power Transformers

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

Network Methods for Electromagnetic Field. Multiphysics Modeling

Analysis of Very Fast Transients in EHV Gas Insulated Substations

Antennas and Propagation. Chapter 2: Basic Electromagnetic Analysis

Transcription:

Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method V.T. KONTARGYRI I.F. GONOS N.C. ILIA I.A. STATHOPULOS High Voltage Laboratory School of Electrical and Computer Engineering National Technical University of Athens 9, Iroon Politechniou Str., GR-157 80, Zografou Campus, Athens GREECE vkont@central.ntua.gr, igonos@ieee.org, leta@power.ece.ntua.gr, stathop@power.ece.ntua.gr http://www.ntua.gr/liaison/highvoltage Abstract: - In this paper the authors attempt to study the distribution of the electric field on composite insulators around and inside the insulator when it is stressed by power frequency voltage. The Finite Element Analysis (FEA) program OPERA was used to carry out the electromagnetic analysis on the This program uses the finite element method to solve the partial differential equations that describe the field. The OPERA-2d/ST & ADETEC programs return field parameters, including the electric field intensity distribution as well the distribution of the potential on the surface of the The aim of this work is to simplify the model of the simulated insulator in order to reduce the complexity and the calculation time of the simulation. First, the whole insulator model has been used to determine the potential distribution around and inside the Next, a simplified model is investigated. The results of the whole and of the simplified model have been compared. In addition, the simulation results before and after the simplification of the insulator model using the finite element method have been compared to the results of other researchers, which have used different method. Furthermore, the surface pollution influence on the dielectric behaviour of the insulators has been examined. Useful conclusions have been got out for the way that the polluted insulator model can be simplified. Key-Words: - Composite insulators, pollution, electric field, finite element method, simulation. 1 Introduction Composite insulators tend to replace porcelain and glass insulators because of the advantages that offer compared with the other categories of insulators. The most significant advantages are the light weight, the lower construction and installation cost and the better contamination performance than the porcelain and glass insulators [1]. The knowledge of the distribution of the electric field within and around high voltage equipment such as insulators, which are used for suspension of overhead transmission lines, is a very important aspect of the design and the development of such equipment. High levels of the electric field are possibly responsible for audible noise, electromagnetic pollution, partial discharge and premature aging of insulation. Electrical discharges may degrade the polymeric materials, which are used to the sheaths and the sheds of the HV composite insulators. Continuous discharges can lead to erosion of the material [2, 3]. The knowledge of the electric field is more useful when it refers to polluted insulators because under operation conditions a polluted layer on HV insulators is very frequent, especially in industrial and coastal regions. The flashover in polluted insulators occurs more frequently and can cause breakdown of the transmission network [4]. Numerical techniques have been developed for calculating the electric field and the potential within and around HV equipment. Boundary integral equations have solved in order to study the electric field and potential of polluted insulator [5]. Calculating the low frequency complex electric field in insulators a quasi-static approximation, which permits the decoupling of Maxwell s equations, has been presented [6]. A finite difference method to calculate the electric field in polluted insulator with asymmetric boundary conditions has been proposed [7]. Furthermore a finite element method to solve low frequency complex fields in insulators with rotational symmetry is commonly used [8]. An effort to simplify the geometry of the insulator without significantly impacting on the accuracy of the computations of the electric field

and voltage distribution around and inside the insulator has been attempted [2, 9]. In this paper an effort is made to simplify the model of composite polluted insulators in order to reduce the simulation demands of design time and computer memory. For the simulation of the environmental pollution a thin film of a pollutant has been added on the insulator surface. the ground is considered at the top end fitting. 2 Software OPERA-2d [10] is a suite of programs for 2- dimensional electromagnetic field ana1ysis. The programs use the finite element method to solve the partia1 differential equations (Poisson's, Helmholtz, and Diffusion equations) that describe the behaviour of fields. The ADETEC solver provides field solution modules that address designs with conducting - dielectric materials under steady state and transient conditions and is suitable for the design of electric insulating components [8,11]. The program solves a current flow problem and uses the results as an input to an electrostatic problem. The software determines the potential by solving the conduction (current flow) equation r J = σ V = 0 (1) in addition to the electrostatic equation (Poisson) ε V = ρ, (2) in case the model contains any materials of a nonzero conductivity σ [8,11]. Fig. 1: The Finite Element Model of the simulated It has been observed that the same simulation results ensued from a model, which consists of a small number of sheds near the ends; this remark facilitates in simplifying the used model. A simplified model for the investigated insulator using four sheds (two at each end of the insulator) is shown in Fig.2 [9]. 3 Parameters of the insulators Polymer suspension insulators consist of four parts: a core, polymer sheath (housing), polymer weathersheds and two end fittings. The core is usually made of fiberglass and the end fittings are made of steel or ductile iron. The sheath and the weathersheds of the investigated insulators are of the same material (silicon rubber). It is considered that the relative permittivity of the silicon rubber, respectively of the fiberglass is 4.3, respectively 7.2. Fig. 2: The simplified Finite Element Model of the simulated The potential distribution around and inside the insulator for the full and the simplified model is shown in Figs 3 and 4. 4 Simplified finite element model 4.1 Application 1: 34.5kV insulator First a 34.5kV insulator with 12 sheds is studied. The symmetry of the insulator was exploited when creating the Finite Element Model, resulting in an axi-symmetric two dimensional problem. The insulator, which is simulated, is shown in Figs. 1. For the simulation a steady voltage of 1000V is applied at the bottom end fitting of the insulator and Fig. 3: Potential contours around and inside the

Fig. 5 illustrates the voltage distribution along the leakage distance of the Fig. 6 indicates the electric field along the same distance. Good agreement was obtained between the results, which was ensued using the full and the simplified model. A difference in the electric field distribution has been observed along the sheds, which have missed out in the simplified model of the In spite of this difference the simplified model gives the same maximum values of the electric field with the full model near the skipped sheds. pollution all the sheds are covered with a thin polluted layer. The conductivity of the polluted layer has been considered equal with 40 µs. It has been observed that a pollutant layer has to be designed instead of the skipped sheds; this layer must be thicker in comparison to the layer along the sheds near the ends. It has to be about two times thicker. Figs. 7 and 8 illustrate the voltage distribution around and inside the polluted insulator for the full and the simplified polluted model respectively. A slight difference can be observed between the results of the full and the simplified method. The work needs to be focused on the way that the pollution will be simulated in the simplified model. Fig. 4: Potential contours around and inside the insulator (simplified model). Fig. 7: Potential distribution around and inside the polluted insulator (full model). Fig. 5: Voltage along the leakage path of the insulator (full and simplified model). Fig. 8: Potensial distribution around and inside the polluted insulator (simplified model). Fig. 6: Electric field along leakage path of the insulator (full and simplified model). Furthermore, in this paper, a polluted model of the insulator is presented. For the simulation of the 4.2 Application 2: 69kV insulator Using a simplified polluted model, based on the previous study, a 69kV insulator with 21 sheds is simulated. The dimensions of the insulator are shown in Fig. 9. For the simulation ten sheds (five at each end of the insulator) have been used. Potential and electric field distributions are shown in Figs. 10 and 11, respectively, for the investigated non-polluted

Figs. 12 and 13 indicate the same distributions for a polluted 1015 129 159 Units: mm Fig. 9: A 69kV Fig. 13: Electric field distribution around and inside the polluted Fig. 10: Potential distribution around and inside the Fig. 14 illustrates the voltage along a line running parallel to the axis of the non-polluted and the polluted Fig. 15 indicates the electric field distribution along the same line. The distribution of the voltage along the insulator is not uniform, the sheds nearer the conductor being more highly stressed. Furthermore, it is obvious that the polluted insulator is more highly stressed. Fig. 11: Electric field distribution around and inside the Figure 14: Voltage along the non-polluted and the polluted Fig. 12: Potential distribution around and inside the polluted Figure 15: Electric Field along the non-polluted and the polluted

5 Conclusions The studied approach is applicable to any insulator type, leading to reliable results in a very fast and economic way, helping the HV overhead line planners to the selection of the right insulator type, depending on the local pollution severity of the area crossed by the overhead line. The distribution of the voltage along the insulator is not uniform, the part of the insulator nearer the conductor being more highly stressed. Also, the insulator is higher stressed under pollution conditions. By comparing the results of the full to those of the simplified model of the insulator, a very good agreement has been stated. Although a good agreement was obtained between the results of the polluted full model and the polluted simplified model, more work is needed to achieve even better agreement. The work needs to be focused on the shape of the polluted layer at the missed out sheds. Also, it is very important to obtain accurate material data (permittivity and conductivity values) for the materials constituting the insulator and the pollutant. Acknowledgments: This project was funded under the Ministry of National Education and Religious Affairs of Greece and the EU. References: [1] H.M. Schneider, J.F. Hall, G. Karady, J. Rendowden, Nonceramic insulators for transmission lines, IEEE Transactions on Power Delivery, Vol. 4, No. 4, October 1989, pp. 2214-2221. [2] T.Zhao, M.G. Comber, Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towers, IEEE Transactions on Power Delivery, Vol. 15, No. 1, January 2000, pp. 313-318. [3] I. Sebestyé, Electric field calculation for HV insulators using domain decomposition method, IEEE Transactions on Magnetics, Vol. 38, No. 2, March 2002, pp. 1213-1216. [4] V.T. Kontargyri, I.F. Gonos, I.A. Stathopulos, A.M. Michaelides, Calculation of the electric field on an insulator string using the finite elements method, Proceedings of the 38th International Universities Power Engineering Conference (UPEC 2003), September 2003, Thessaloniki, Greece, pp. 65-68. [5] J.L. Rasolonjanahary, L. Krähenbühl, A. Nicolas, Computation of electric fields and potential on polluted insulators using a boundary element method, IEEE Transactions on Magnetics, Vol. 28, No. 2, March 1992, pp. 1473-1476. [6] E. Asenjo, N. Morales, A. Valdenegro, Solution of low frequency complex fields in polluted insulators by means of the finite element method, IEEE Transactions on Dielectics and Electrical Insulation, Vol. 4, No. 1, February 1997, pp. 10-16. [7] N. Morales, E. Asenjo, A. Valdenegro, Field solution in polluted insulators with nonsymetric boundary conditions, IEEE Transactions on Dielectics and Electrical Insulation, Vol. 8, No. 2, April 2001, pp. 168-172. [8] A. Michaelides, C.P. Riley, A.P. Jay, G Molinari, P. Alotto, A. Zubiani, A. D Souza, J. Madail Vaiga, Parametric FEA for the design of electric insulating components, EU Project ADETEC, MedPower 2002, November 2002, Athens, Greece. [9] W. Que, S.A. Sedo, Discussions of possible simplifications for the electric field and voltage distribution calculations along composite insulators, XIIIth International Symposium on High Voltage Engineering, August 2003, Delft, Netherlands. [10] Vector Fields, OPERA-2d User Guide, Vector Fields Limited, England, 1999. [11] P. Alotto, G Molinari, A. Michaelides, C.P. Riley, A.P. Jay, A. Zubiani, A. D Souza, J. Madail Vaiga, A transient formulation for the design of electric insulating/conducting components: EU Project ADETEC, 10th International IGTE Symposium on Numerical Field Calculation in Electrical Engineering, September 2002, Gratz, Austria.