SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

Similar documents
POWER SYSTEM STABILITY

Examples of Applications of Potential Functions in Problem Solving (Web Appendix to the Paper)

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 7 - Transient Stability

Chapter 9: Transient Stability

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

The Effects of Machine Components on Bifurcation and Chaos as Applied to Multimachine System

ECE 585 Power System Stability

REAL-TIME TRANSIENT STABILITY ASSESSMENT

EE 451 Power System Stability

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

The synchronous machine (SM) in the power system (2) (Where does the electricity come from)?

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Power System Stability GENERATOR CONTROL AND PROTECTION

KINGS COLLEGE OF ENGINEERING Punalkulam

EE2351 POWER SYSTEM ANALYSIS

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

Power Angle & Time Domain Plots 1.0 The power-angle curves

ECEN 667 Power System Stability Lecture 25: FFT, Energy Methods

Dynamics of the synchronous machine

max clear Figure 1 below illustrates a stable case. P post (f) (g) (e) A 2 (d) (c)

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

Minimax Approximation Synthesis in PSS Design by Embedding

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

Generators. What its all about

Enhancement of transient stability analysis of multimachine power system

Comparative Study of Synchronous Machine, Model 1.0 and Model 1.1 in Transient Stability Studies with and without PSS

Power system modelling under the phasor approximation

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability

arxiv: v1 [cs.sy] 24 Mar 2016

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

Micro-grid to System Synchronization Based on Pre-Insertion Impedance Method (Version 1.0) By Peter Zhou University of Alberta Jan 30 th, 2015

JRE SCHOOL OF Engineering

Nonlinear Control Design of Series FACTS Devices for Damping Power System Oscillation

Open Conductor Faults and Dynamic Analysis of a Power System

Lesson 17: Synchronous Machines

BEE701 POWER SYSTEM ANALYSIS

1 Unified Power Flow Controller (UPFC)

SPEED-GRADIENT-BASED CONTROL OF POWER NETWORK: CASE STUDY

Self-Tuning Control for Synchronous Machine Stabilization

Torques 1.0 Two torques We have written the swing equation where speed is in rad/sec as:

ECE 422 Power System Operations & Planning 7 Transient Stability

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

Model of Induction Machine to Transient Stability Programs

θ α W Description of aero.m

The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line

Introduction to Synchronous. Machines. Kevin Gaughan

MODELING AND SIMULATION OF ENGINE DRIVEN INDUCTION GENERATOR USING HUNTING NETWORK METHOD

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

Robust Tuning of Power System Stabilizers Using Coefficient Diagram Method

CURENT Course Power System Coherency and Model Reduction

7. Transient stability

INDUCTION MOTOR MODEL AND PARAMETERS

EVALUATION OF THE IMPACT OF POWER SECTOR REFORM ON THE NIGERIA POWER SYSTEM TRANSIENT STABILITY

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

The Operation of a Generator on Infinite Busbars

Simulations and Control of Direct Driven Permanent Magnet Synchronous Generator

Research Paper ANALYSIS OF POWER SYSTEM STABILITY FOR MULTIMACHINE SYSTEM D. Sabapathi a and Dr. R. Anita b

University of Auckland Research Repository, ResearchSpace. The digital copy of this thesis is protected by the Copyright Act 1994 (New Zealand).

The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

CHAPTER 3 MATHEMATICAL MODELING OF HYDEL AND STEAM POWER SYSTEMS CONSIDERING GT DYNAMICS

Module 3 : Sequence Components and Fault Analysis

Determination of stability limits - Angle stability -

Critical clearing time evaluation of Nigerian 330kV transmission system

QFT Framework for Robust Tuning of Power System Stabilizers

Mechatronics Engineering. Li Wen

IJSER. 1. Introduction

A Decoupling Based Direct Method for Power System Transient Stability Analysis

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Frequency and Damping Characteristics of Generators in Power Systems

Transient Stability Assessment Using Energy Function Method

Part A: From (14.19) in your text (see notes Stability1 ), we have

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

A Power System Dynamic Simulation Program Using MATLAB/ Simulink

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

ECEN 667 Power System Stability Lecture 20: Oscillations, Small Signal Stability Analysis

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Unified Power Flow Controller (UPFC) Based Damping Controllers for Damping Low Frequency Oscillations in a Power System

A Spreadsheet Illustration of the Transient Stability Analysis of Power Systems

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

Multiple Swing Out-of-Step Relaying

Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

DAMPING OF SUBSYNCHRONOUS MODES OF OSCILLATIONS

Reliability of Bulk Power Systems (cont d)

A. P. Sakis Meliopoulos and George J. Cokkinides Power System Relaying, Theory and Applications. Chapter 8 2 Generator Protection 2

DESIGN OF POWER SYSTEM STABILIZER USING FUZZY BASED SLIDING MODE CONTROL TECHNIQUE

Delayed Feedback Controller for Stabilizing Subsynchronous Oscillations in Power Systems

AN EVOLUTIONARY PROGRAMMING APPROACH TO OPTIMIZE SYNCHRONOUS GENERATOR INPUT POWER USING AREA-BASED TRANSIENT STABILITY INDEXES

Impact of Model Detail of Synchronous Machines on Real-time Transient Stability Assessment

Chapter 8 VOLTAGE STABILITY

Lecture 1: Induction Motor

STUDY OF SMALL SIGNAL STABILITY WITH STATIC SYNCHRONOUS SERIESCOMPENSATOR FOR AN SMIB SYSTEM

LESSON 20 ALTERNATOR OPERATION OF SYNCHRONOUS MACHINES

ECEN 667 Power System Stability Lecture 15: PIDs, Governors, Transient Stability Solutions

Transcription:

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS LECTURE NOTES Transient Stability SPRING SEMESTER, 008 October 7, 008

Transient Stability Transient stability refers to the ability of a synchronous generator connected to the grid to maintain synchronism when subjected to severe disturbances due to heavy load changes, loss of generation in other units or faults in the system. When there is a sudden disturbance, the machine rotor starts to oscillate about its equilibrium position. These oscillations are modeled using swing equation. 1 Swing equation When there is an unbalance between mechanical torque (T m ) and electrical torque (T e ), it will cause the rotor to accelerate or decelerate. The difference in the torque (T a ) is given by, J dω m T a = T m T e = T m T e (1) where J is the moment of inertia of the rotor in kg.m and ω m is the angular velocity of the rotor in rad/s. Equation (1) can be normalised as follows: Defining inertia constant H as where T base = V A base ω 0m H = 1 Jω 0m V A base J = HV A base ω 0m = H ω 0m T base (). Combining (1) and () we get, H d ( ) ωm ω 0m H d ω r = T m T e T base = T m T e (3) = ωr ω 0 where the variables superscripted with indicates per unit quantities and ωm ω 0m ω r is the velocity of the rotor in electrical rad/s and ω 0 is its rated value. If δ is the angular position of the rotor with respect to the rotating reference frame, = ω r and δ = ω r t ω 0 t + δ 0 (4) where δ 0 = δ at t = 0. Differentiating (4) twice with respect to time, dδ = ω r ω 0 = ω r (5) = d ( ω r) = d (ω 0 ω r ω 0 ) (6) = ω 0 d ω r 1 (7)

Substituting in (3), H ω 0 = T m T e (8) To include the rotor damping effects, we include rotor damping constant K D and proportional to change in speed and we have, H ω 0 = T m T e K D ω r (9) Equation (9) is known as swing equation. In pu representation, torque and power are equal, so we can represent (9) as, H ω 0 = P m P e K D ω r (10) Single machine on infinite bus (SMIB) model Infinite bus is the one with constant frequency and voltage. Consider a generator G connected to infinite bus through a transformer and a transmission line as shown in Figure 1(a). The reactance of the line X line, transformer X trans and the transient reactance X d are indicated in Figure 1(b). E is the generator voltage behind X d and E bus is the infinite bus voltage. Generator voltage E leads the E bus by an angle δ. The given network can be reduced as shown in Figure 1(c) where X T = X d + X trans + X line. Let E be the reference vector, the current I t is given by, Apparent power behind X d is given by, I t = E 0 E bus δ jx T = E 0 E bus (cos δ j sin δ) jx T (11) S = P + jq = E I t = E E bus sin δ X T + j E (E E bus cos δ) X T (1) If we neglect the stator resistance loss, the airgap power will be the terminal power P e. P e = E E bus sin δ X T = P max sin δ (13) where P max = E E bus X T. Equation (13) is diagrammatically represented in Figure. Under steady

Figure 1: Single machine on infinite bus system state P m = P e, and let the corresponding rotor angle be δ. From (13), P max is inversely proportional to X T. With X T increased to X T 1, P max reduces to P max1 as shown in Figure and also the steady state angle δ increases to δ 1. Combining (8) and (13) we get, H ω 0 = P m P max sin δ (14).1 Rotor angle response to sudden change in P m When the mechanical power P m is increased to P m1 as shown in Figure 5, since P m1 > P e, rotor accelerates increasing rotor angle towards δ 1. At y, P m1 = P e, but the rotor speed is higher than the synchronous speed ω 0 and so the rotor angle continues to increase. This will increase P e, now since P m1 < P e, rotor will start decelerate. At z with δ, rotor speed reaches syn.speed but still P m1 < P e rotor continues to decelerate with speed falling below ω 0. The rotor retraces the path, after reaching x the rotor continues to oscillate about the new equilibrium point δ 1 3

Power Angle Figure : Power angle curve. Equivalent single machine system We can represent a system consisting of many generators operating in parallel by an equivalent single machine system. Find the equivalent single machine system of the following multimachine systems. 1. Each machine 30 kva, H = 6 s, xd = 0.5 pu. (Refer Figure 3).. G 1 = 30 kva, H 1 = 6 s, xd 1 = 0.5 pu and G = 60 kva, H = 4 s, xd = 0.3 pu (Refer Figure 4). 3 Stability based on equal area criterion Using SMIB model, the stability of rotor angle oscillations can be determined graphically without solving the swing equations. Even though this method cannot be applied to multimachine systems, it can provide basic understanding and information about critical clearing angle and stability limits. From equation (14) we have = ω 0 H (P m P e ) (15) 4

Figure 3: 3 M/C system Figure 4: M/C system Multiplying by dδ, Integrating (16) we get, dδ = ω 0 H (P m P e ) dδ ( ) d dδ = ω 0 H (P m P e ) dδ (16) ( ) dδ ω0 = H (P m P e ) dδ (17) Under steady state conditions dδ = 0, during disturbance δ will be changed, but after the removal of disturbance the system should regain steady state conditions without δ deviating unboundedly. For stability equation (17) should be equal to zero i.e, δ ω 0 δ 0 H (P m P e ) dδ = 0 (18) 5

Power Angle Figure 5: Rotor angle oscillations where δ 0 is the steady state rotor angle, δ is the maximum rotor angle (see Figure 5). For the equation (18) to be zero, the area described by the function P m P e must be zero. From Figure 5, the kinetic energy gained is given by area A 1 and is given by, A 1 = δ1 δ 0 (P m P e ) dδ (19) The energy lost during deceleration is given by the area A and is given by, for stability, A = δ δ 1 (P m P e ) dδ (0) Area A 1 = Area A (1) i.e, kinetic energy gained = energy lost during deceleration Equation (1) represents the principle of stability through equal area criterion. 3.1 Stability during sudden input power change For sudden change in input power stability can be found by using the stability criteria given by (1). Stability can be maintained only if we can find area A in the power angle curve such that (1) is satisfied. The maximum rotor angle δ max is given by the rotor angle corresponding to P m for which π < δ > π as shown in Figure 6. 6

Power Angle Figure 6: Power angle curve for sudden change in P m Using (13) and (1) we can write, P m (δ 1 δ 0 ) On simplification, δ1 δ 0 P max sin δ dδ = δmax δ 1 P max sin δ dδ P m (δ max δ 1 ) () ] P m (δ max δ 0 ) = P max [( cos δ) δ 1 δ 0 + ( cos δ) δmax δ 1 At stability limit P m = P max sin δ max, substituting in (3), = P max (cos δ 0 cos δ max ) (3) sin δ max (δ max δ 0 ) + cos δ max = cos δ 0 (4) Equation (4) is a nonlinear equation which can be solved by iterative technique to get δ max. With δ max known we can find δ 1 and P m as follows: 3. Stability during 3 phase fault δ 1 = π δ max and P m = P max sin δ 1 (5) Fault at sending end. When fault occurs near the sending end as in Figure 7, no power is send to the infinite bus. If we neglect the resistance of transformer and generator P e is zero during fault. Since P e is zero, P m is used to accelerate rotor and this increases rotor angle to δ 1. At 7

Figure 7: Fault at the sending end δ 1, the fault is cleared and P e takes the value corresponding to y as shown in Figure 8(a). At y since P e < P m, rotor decelerates to z and then returns back to x and starts to oscillate about δ 0. Critical clearing angle δ c is reached when area A becomes less than A 1 [see Figure 8(b)] and at z the rotor angle becomes δ max. Using (1) solving for δ c, P m (δ c δ 0 ) = δmax δ c (P max sin δ P m ) dδ = P max (cos δ c cos δ max ) P m (δ max δ c ) P m (δ max δ 0 ) = P max cos δ c P max cos δ max (6) [ δ c = cos 1 cos δ max + P ] m (δ max δ 0 ) P max To find the critical time t c, substitute P e = 0 in (15), Integrating both sides from time 0 to t we get, (7) = ω 0 H P m (8) dδ = ω 0 H P mt δ = ω 0 4H P mt + δ 0 (9) at δ = δ max, t = t c, substituting in (9), t c = 4H (δ max δ 0 ) ω 0 P m (30) 8

Power Power m m 1 1 0 1 Angle 0 c max Angle Figure 8: Power angle curve for fault at sending end 4 Numerical Example Let us consider a 50 Hz single machine on infinite bus system. The machine is connected to infinite bus through a transformer and a transmission line. The system data is included in the Figure 9. A temporary 3 phase fault occurs at sending end and the system is restored back to normal after fault clearance. Find the critical clearing angle and critical clearing time above which the system will become unstable. 9

Figure 9: Power system for numerical example. 0.9 j0.08 Generator Current I G = = 0.9 j0.08 pu 1 0 Total reactance X T 1 = 0.5 + 0.5 + 0.35 = 0.6750 pu Generator voltage behind x d, E q = V bus I G X T 1 = 1 0 + j0.6750 (0.9 j0.08) = 1.165 9.9581 pu ( ) Initial power angle δ 0 = sin 1 Pe X T 1 = 9.9581 0 E q V bus Maximum power angle δ max = 180 δ 0 = 150.0419 [ Critical clearing angle δ c = cos 1 cos δ max + P ] m (δ max δ 0 ) = 79.6180 0 P max 4H (δ max δ 0 ) Critical clearing time t c = = 0.71 s ω 0 P m 10

Figure 10: Power angle curve for the numerical example. 11