National Fenestration Rating Council. Incorporated. NFRC [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values

Similar documents
Test Results: Results of the test period on 06/19/16 using the Equivalent CTS Method: Thermal transmittance at test conditions (U s ):

SIMULATION TEST REPORT NCTL E0A0

Report No: NCTL S NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 07/14/15. Test Specimen

Report No: NCTL NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 12/14/15

NFRC THERMAL TEST SUMMARY REPORT Expiration Date: 03/31/06

THERMAL PERFORMANCE TEST REPORT

Simulation Report (Revised) Rendered To: Showcase Custom Vinyl Windows 1002 Olde Towne Drive Irving, TX 75061

NFRC THERMAL TEST SUMMARY REPORT January 27, 1999 Test Specimen

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NORTH EAST WINDOWS USA, INC.

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

SHANGHAI MYLCH WINDOWS & DOORS THERMAL PERFORMANCE TEST REPORT

Winter Night. Thermos 6mm Outdoors # #

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: NU VISTA WD, INC. SERIES/MODEL: Malibu 250 T TYPE: Fixed

WINDOW SIMULATION REPORT

Standard Test Method for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Using Hot Box Methods 1

NFRC SOLAR HEAT GAIN COEFFICIENT TEST REPORT. Rendered to: CLEAR FOCUS IMAGING

ISO INTERNATIONAL STANDARD

CAE 463/524 Building Enclosure Design Fall 2012

Building Envelope Requirements Overview Page 3-4

Solar Radiation 230 BTU s per Hr/SF. Performance Glazing Coatings, Layers & Gases

TEST METHOD FOR THERMAL TRANSMITTANCE AND AIR INFILTRATION OF GARAGE DOORS

Introduction...COMB-2 Design Considerations and Examples...COMB-3

ISO INTERNATIONAL STANDARD. Thermal performance of windows, doors and shutters Calculation of thermal transmittance Part 1: Simplified method

INDIANA DEPARTMENT OF TRANSPORTATION OFFICE OF MATERIALS MANAGEMENT. VERIFYING THERMOMETERS ITM No T

Standard Guide for Determination of the Thermal Resistance of Low-Density Blanket-Type Mineral Fiber Insulation 1

NEMA MW (R2014) Dynamic Coefficient of Friction of Film-Insulated Magnet Wire

Avery Dennison LW Series Retroreflective Window Sticker Film Issued: July 2013

THE IMPLICATION OF ENERGY EFFICIENT BUILDING ENVELOPE DETAILS FOR ICE AND SNOW FORMATION PATTERNS ON BUILDINGS

Installation guide 862 MIT / MIR

ISO INTERNATIONAL STANDARD. Thermal insulation for building equipment and industrial installations Calculation rules

Standard Test Method for Flat Particles, Elongated Particles, or Flat and Elongated Particles in Coarse Aggregate 1

ESB-M3G76-B2: Tape, Polyester Two Sided Pressure Sensitive. Tape Polyester Two Sided Pressure Sensitive. Technical Bulletin November, 2016

Avery Dennison LV-0700 Series Retroreflective Validation Decal Film Issued: July 2013

Designation: NWI DIF Horizontal Hail impact Standard

Potential of Hollow Glass Microspheres (3M Glass Bubbles) for Thermal Insulation Dr. Friedrich Wolff

IMPROVED PRODUCT Z, Z (Z-Foil)

Temperature Profile for 36 Marker Spheres on 3M 788 ACCR Conductor 3M Company

Thermal Imaging Survey. Conducted at Nottingham

THE EFFECTS OF CALORIMETER TILT ON THE INWARD-FLOWING FRACTION OF ABSORBED SOLAR RADIATION IN A VENETIAN BLIND

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

Derating of the MOSFET Safe Operating Area Outline:

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: INTERNATIONAL ARCHITECTURAL PRODUCTS, INC. DBA: UNITED STATES ALUMINUM

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

CAE 331/513 Building Science Fall 2016

Standard Practice for Heat Aging of Plastics Without Load 1

Analog Technologies. High Stability Miniature Thermistor ATH10K0.1%1R25

Surface Mount Multilayer Ceramic Chip Capacitors for Safety Certified Applications

Lead (Pb)-Free Thick Film, Rectangular High Value Chip Resistor

TEST METHOD FOR DETERMINING BREAKAWAY FORCE OF A MAGNET

IPC-TM-650 TEST METHODS MANUAL

Glazing selection for solar design

IPC-TM-650 TEST METHODS MANUAL

INTERNATIONAL STANDARD

5 mm Square Surface Mount Miniature Trimmers Multi-Turn Cermet Sealed

Molded Metal Film High Stability (< 0.25 % after 1000 h) High Temperature (up to 175 C) Precision Resistors

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION. SERIES/MODEL: 4000 TYPE: Fixed

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½

FIELD GUIDE FOR HORUS SCOPES

Lead (Pb)-Bearing Thick Film, Rectangular High Value Chip Resistor

Integrated Circuits Thermal Test Method Environment Conditions - Natural Convection (Still Air)

φ φ0.2 Bare copper wire 2352 Walsh Ave., Santa Clara, CA 95051, U. S. A. Tel.: (408) , Fax: (408)

Standard Test Method for Thermal Conductivity of Refractories 1

Guide Specifications Section

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: April 22, 2016 REVISED DATE: NA. EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 7400 TYPE: Fixed

Lead (Pb)-free Thick Film, Rectangular Commodity Chip Resistors

Surface Mount Multilayer Ceramic Chip Capacitors with Integrated Resistor for High Pulse Current Applications

AO291 Issue date: Product Data FASSON Transfer Polyimide Matt White TC11 / S8088 / BG50 Wh

Metallized Polyester Film Capacitors MKT Radial Potted Types

STANDARD PROCEDURE: NWSP R2 (15) Polyacrylate Superabsorbent Powders Determination of the Particle Size Distribution by Sieve Fractionation

Shree Tirupati Polypack

Part 5: Total stations

Lead (Pb)-Free Thick Film, Rectangular, Trimmable Chip Resistors

Metallic materials Knoop hardness test. Part 1: Test method. Matériaux métalliques Essai de dureté Knoop Partie 1: Méthode d'essai

SAMPLE ASSESSMENT TASKS PHYSICS ATAR YEAR 11

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

CAUTION: BEFORE YOU BEGIN, ALWAYS MAKE SURE THE WEAPON IS UNLOADED AND SAFE TO HANDLE.

SMD Aluminum Solid Capacitors with Conductive Polymer

Aluminum Electrolytic Capacitors Power Long Life Snap-In

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

GUIDELINES FOR FILMING IN TOMBALL, TEXAS

Time Constant. φ φ0.2 Bare copper wire

WeatherHub2 Quick Start Guide

303139, FEATURES INTRODUCTION. TABLE 1 - TOLERANCE AND TCR VS. RESISTANCE VALUE (- 55 C to C, + 25 C ref.)

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions

Inside Wall Temperature Measurements of DSTs Using an Infrared Temperature Sensor

Metallized Polyester Film Capacitors MKT Radial Potted Type

Surface Mount Multilayer Ceramic Capacitors for Pulse Current Applications

2.1. Accuracy, n- how close the indication of the thermometer is to the true value.

Part Type differentiation Package 1N5550 V RRM = 200 V G-4 1N5551 V RRM = 400 V G-4 1N5552 V RRM = 600 V G-4

Standard Test Methods for Glass-Bonded Mica Used as Electrical Insulation 1

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

FEATURES. Note 138D 306 X0 006 C 2 E3 MODEL CAPACITANCE CAPACITANCE TOLERANCE DC VOLTAGE RATING AT +85 C

CNY17F-4. Pb Pb-free. Optocoupler, Phototransistor Output, No Base Connection. Vishay Semiconductors

Town of Enfield, CT Geographic Information Systems

MATERIAL AND EQUIPMENT STANDARD FOR. INHIBITOR FOR HYDROCHLORIC ACID AND HCl+HF DESCALING AND PICKLING SOLUTION FOR OIL AND GAS WELLS ORIGINAL EDITION

VPR221SZ (Z-Foil) Vishay Foil Resistors

Pulse Proof Thick Film Chip Resistors

Transcription:

National Fenestration Rating Council Incorporated NFRC 500-2010 [E0A1] Procedure for Determining Fenestration Product Condensation Resistance Values 2010 NATIONAL FENESTRATION RATING COUNCIL, INC. PREPARED BY: National Fenestration Rating Council 6305 Ivy Lane, Suite 140 Greenbelt, MD 20770 Voice: (301) 589-1776 Fax: (301) 589-3884 Email: info@nfrc.org Website: www.nfrc.org

FOREWORD The National Fenestration Rating Council, Incorporated ("NFRC") has developed and operates a uniform rating system for energy and energy-related performance of fenestration products. The Rating System determines the U-factor, Solar Heat Gain Coefficient (SHGC), and Visible Transmittance (VT) of a product, which are mandatory ratings for labeling NFRC certified products and are mandatory ratings for inclusion on label certificates, and are supplemented by procedures for voluntary ratings of products for Air Leakage (AL), and Condensation Resistance. Together, these rating procedures, as set forth in documents published by NFRC, are known as the NFRC Rating System. The Rating System employs computer simulation and physical testing by NFRC-accredited laboratories to establish energy and related performance ratings for fenestration product types. The Rating System is reinforced by a certification program under which NFRC-licensed responsible parties claiming NFRC product certification shall label and certify fenestration products to indicate those energy and related performance ratings, provided the ratings are authorized for certification by an NFRC-licensed certification and Inspection Agency (IA). The requirements of the rating, certification, and labeling program (the "Certification Program") are set forth in the most recent versions of the following as amended, updated or interpreted from time to time: NFRC 700 Product Certification Program (the "PCP") NFRC 705 Component Modeling Approach ("CMA") Product Certification Program (the "CMA-PCP"). Through the Certification Programs and the most recent versions of its companion programs as amended, updated or interpreted from time to time: The laboratory accreditation program (the "Accreditation Program"), set forth in the NFRC 701 Laboratory Accreditation Program (the "LAP") The IA licensing program (the "IA Program"), set forth in NFRC 702 Certification Agency Program (the "CAP") The CMA Approved Calculation Entity ("ACE") licensing program (the ACE Program ) as set forth in the NFRC 708 Calculation Entity Approval Program (the "CEAP"), NFRC intends to ensure the integrity and uniformity of NFRC ratings, certification, and labeling by ensuring that responsible parties, testing and simulation laboratories, and IAs adhere to strict NFRC NFRC 500-2010 [E0A1] page ii

requirements. In order to participate in the Certification Programs, a manufacturer / responsible party shall rate a product whose energy and energy-related performance characteristics are to be certified in accordance with mandatory NFRC rating procedures. At present, a manufacturer/responsible party may elect to rate products for U-factor, SHGC, VT, Air Leakage, Condensation Resistance, or any other procedure adopted by NFRC, and to include those ratings on the NFRC temporary label affixed to its products, or on the NFRC Label Certificate. U-factor, SHGC and VT, AL, and Condensation Resistance rating reports shall be obtained from a laboratory, which has been accredited by NFRC in accordance with the requirements of the NFRC 701. The rating shall then be reviewed by an IA which has been licensed by NFRC in accordance with the requirements of the NFRC 702. NFRC-licensed IAs also review label format and content, conduct in-plant inspections for quality assurance in accordance with the requirements of the NFRC 702, and issue a product Certification Authorization Report (CAR), or approve for issuance an NFRC Label Certificate for site-built or CMA products and attachment products. The IA is also responsible for the investigation of potential violations (prohibited activities) as set forth in the NFRC 707 Compliance and Monitoring Program. Ratings for products that are labeled with the NFRC Temporary and Permanent Label, or products that are listed on an NFRC Label Certificate, in accordance with NFRC requirements, are considered to be NFRC-certified. NFRC maintains a Certified Products Directory (CPD), listing product lines and individual products selected by the manufacturer/responsible party for which certification authorization has been granted. NFRC manages the Rating System and regulates the Product Certification Program (PCP), Laboratory Accreditation Program (LAP) and Certification Agency Program (CAP) in accordance with the NFRC 700 (PCP), the NFRC 701 (LAP), the NFRC 702 (CAP), the NFRC 705 (CMA- PCP), and the NFRC 708 (CEAP) procedures, and conducts compliance activities under all these programs as well as the NFRC 707 Compliance and Monitoring Program (CAMP). NFRC continues to develop the Rating System and each of the programs. NFRC owns all rights in and to each of the NFRC 700, NFRC 701, NFRC 702, NFRC 705, NFRC 707, NFRC 708 and each procedure, which is a component of the Rating System, as well as each of its registration marks, trade names, and other intellectual property. The structure of the NFRC program and relationships among participants are shown in Figure 1, Figure 2, and Figure 3. For additional information on the roles of the IAs and laboratories and operation of the IA Program and Accreditation Program, see the NFRC 700 (PCP), NFRC 701 (LAP), and NFRC 702 (CAP) respectively. NFRC 500-2010 [E0A1] page iii

Figure 1 Figure 2 NFRC 500-2010 [E0A1] page iv

Figure 3 Questions on the use of this procedure should be addressed to: National Fenestration Rating Council 6305 Ivy Lane, Suite 140 Greenbelt, MD 20770 Voice: (301) 589-1776 Fax: (301) 589-3884 Email: info@nfrc.org Website: www.nfrc.org NFRC 500-2010 [E0A1] page v

DISCLAIMER NFRC certification is the authorized act of a manufacturer/responsible party in: (a) labeling a fenestration or related attachment product with an NFRC Permanent Label and NFRC Temporary Label, or (b) generating a site built or CMA label certificate, either of which bears one or more energy performance ratings reported by NFRC-accredited simulation and testing laboratories and authorized for certification by an NFRC-licensed IA. Each of these participants acts independently to report, authorize certification, and certify the energy-related ratings of fenestration and related attachment products. NFRC does not certify a product and certification does not constitute a warranty of NFRC regarding any characteristic of a fenestration or fenestration-related attachment product. Certification is not an endorsement of or recommendation for any product or product line or any attribute of a product or product line. NFRC is not a merchant in the business of selling fenestration products or fenestrationrelated products, and therefore cannot warrant products as to their merchantability or fitness for a particular use. NFRC THEREFORE DISCLAIMS ANY AND ALL LIABILITY THAT MAY ARISE FROM OR IN CONNECTION WITH SERVICES PROVIDED BY, DECISIONS MADE BY OR REPORTS OR CERTIFICATIONS ISSUED OR GRANTED BY ANY NFRC-ACCREDITED LABORATORY, NFRC-LICENSED IA OR ANY PRODUCT MANUFACTURER/ RESPONSIBLE PARTY; RELIANCE ON ANY NFRC PRODUCT DESCRIPTION, SPECIFICATION, RATING, TEST OR CERTIFICATION, WHETHER APPEARING IN A REPORT, A PRODUCT CERTIFICATION AUTHORIZATION OR A PRINTED OR ELECTRONIC DIRECTORY, OR ON A LABEL, OR ON A LABEL CERTIFICATE; OR THE SALE OR USE OF ANY NFRC-RATED OR CERTIFIED PRODUCT OR PRODUCT LINE; INCLUDING BUT NOT LIMITED TO DAMAGES FOR PERSONAL OR OTHER INJURY, LOST PROFITS, LOST SAVINGS OR OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES. NFRC program participants are required to indemnify NFRC from and against such liability. NFRC 500-2010 [E0A1] page vi

Foreword Disclaimer Table of Contents... ii... vi 1. Preface... 1 2. Scope... 1 2.1 FENESTRATION PRODUCTS COVERED BY NFRC 500... 1 2.2 FENESTRATION PRODUCTS AND EFFECTS NOT COVERED BY NFRC 500... 2 3. Terminology... 2 4. Simulation Method for Determining Fenestration Product Condensation Resistance Values... 3 4.1 SIGNIFICANCE AND USE... 3 4.2 SIMULATION METHOD... 4 4.2.1 Product Simulation Requirements... 4 4.2.2 Determination of Surface Segments... 4 4.2.3 Condensation Resistance Rating... 4 4.3 CONDENSATION RESISTANCE CALCULATIONS... 4 4.3.1 Determine Condensation Resistance of the Frame, CR f... 4 4.3.2 Determine Condensation Resistance of the Glazing portion, CR c and CR e.... 5 4.3.2.1 Center-of-Glazing... 5 4.3.2.2 Dividers... 6 4.3.2.3 Edge-of-Glazing... 8 4.3.3 Determine Condensation Resistance of the Total Product, CR.... 8 4.3.4 Condensation Resistance Variables... 9 4.4 SIMULATION REPORT... 10 5. Test Method for Determining Fenestration Product Condensation Resistance Values... 10 5.1 SIGNIFICANCE AND USE... 10 5.2 TEST METHOD... 11 NFRC 500-2010 [E0A1] page vii

5.2.1 Test Specimen Testing Requirements... 11 5.2.2 Determination of Total Exposed Surface Area... 11 5.2.3 Temperature Measurement... 11 5.3 TEST PROCEDURE CALCULATIONS... 12 General Calculations... 12 5.3.1 Determine Condensation Resistance of the Total Product, CR.... 13 5.3.2 Condensation Resistance Variables... 13 5.4 TEST REPORT... 14 6. Referenced Documents... 15 6.1 NFRC DOCUMENTS... 15 6.2 ASTM STANDARDS... 15 Appendix A Background on the NFRC Condensation Resistance Rating... 15 Appendix B Predetermined Temperature Measurement Locations... 16 Figure 6-1 Casement and Awning Thermocouple Placement (Awning - rotate 90 degrees)... 17 Figure 6-2 Fixed Window, Sidelite, and Transom Thermocouple Placement... 18 Figure 6-3 Swinging Patio Door Thermocouple Placement... 19 Figure 6-4 Horizontal Slider, Vertical Slider, and Sliding Patio Door Thermocouple Placement (Vertical Slider rotate 90 degrees)... 20 Figure 6-5 Glazed Wall and Sloped Glazing Thermocouple Placement... 21 Figure 6-6 Divider Thermocouple Placement... 22 Index... 23 NFRC 500-2010 [E0A1] page viii

1. PREFACE This edition of the NFRC Condensation Resistance procedure includes information from ASTM C 1199, ASTM E 1423, NFRC round robin testing data, and technical interpretations by NFRC. The Condensation Resistance procedure includes a Simulation Method and a Test Method. The NFRC Simulation Method is presented in Section 4. The Simulation Method is based upon the NFRC-approved software tools and is to be used in conjunction with NFRC 100 and the NFRC Simulation Manual. The Test Method references NFRC 102 which contains many aspect of ASTM C 1199, as well as modifications adopted by NFRC. The Test Method has been developed to be a supplement to the Simulation Method. Those products that cannot be simulated for Condensation Resistance shall use the test procedure to determine a Condensation Resistance rating. The Test Method replicates, as closely as possible, the Simulation Method for Condensation Resistance, but simulated and tested Condensation Resistance values may not be identical. The simulations are being validated with tested U-Factors, as obtained using the NFRC 100 procedure and not with tested Condensation Resistance values. This procedure may involve hazardous materials, operations and equipment. This procedure does not purport to address all of the safety problems associated with its use. It is the responsibility of the user of this procedure to establish appropriate health and safety practices and to determine the applicability of any regulatory limitations prior to use. The values stated in metric (SI) units are to be regarded as the standard. The inch-pound (IP) units shown in parenthesis are for reference only. 2. SCOPE 2.1 Fenestration Products Covered by NFRC 500 The following products and effects are within the scope of the NFRC 500 and shall be permitted to be rated in accordance with this procedure. A. This procedure provides a Condensation Resistance rating for windows, fully glazed doors, curtain wall systems, site-built products, sloped glazing systems, skylights, Dynamic Glazing Products, and other fenestration products. i. Dynamic Glazing Products that utilize a shading system between glazing layers can only be rated for Condensation Resistance by using the test method specified in Section 5; NFRC 500-2010 [E0A1] page 1

i.ii. Fenestration products containing fritted glazing, etched glazing, or sandblasted glazing shall be rated by computer simulation. B. This procedure refers to the Condensation Resistance rating of a fenestration system installed vertically in the absence of solar and air leakage effects. C. The Condensation Resistance rating is determined for a single set of environmental conditions. The Condensation Resistance value is a comparative rating that indicates a product's ability to resist the formation of condensation. Since the Condensation Resistance rating is a comparative rating, it may not be appropriate for the determination of the actual occurrence of condensation under a given set of environmental conditions. 2.2 Fenestration Products and Effects Not Covered by NFRC 500 The following products and effects are beyond the scope of NFRC 500 and shall not be rated in accordance with this procedure. A. Fenestration products with shading or diffusing systems other than those listed in Section 2.1; A.B. B.C. C.D. D.E. Exterior glazing condensation or between glazing layer condensation;. Thermal performance changes of a fenestration product over the course of time, i.e., long term energy performance;. The impact of air leakage and degradation in performance of fenestration products; and Condensation Resistance of non-fully glazed doors and products with attachments. 3. TERMINOLOGY Condensation Resistance (CR): a relative indicator of a fenestration product's ability to resist the formation of condensation at a specific set of environmental conditions. The higher the Condensation Resistance value the greater the resistance to the formation of condensation. Center-of-glazing Condensation Resistance (CR c ): the Condensation Resistance for the central portion of the glazing (i.e., part of glazing where 1-D heat transfer effects dominate). The CR c also includes divider and edge-of-divider portions of the product. Condensation reference point temperature (t dpp ): the dew point temperature plus 0.3ºC (0.5ºF). Dew point temperature (t dp ): temperature at which water vapor condenses to liquid water at a given relative humidity (RH). Edge-of-glazing Condensation Resistance (CR e ): the Condensation Resistance for the edge portion of the glazing (i.e., part of glazing where 2-D heat transfer effects dominate). NFRC 500-2010 [E0A1] page 2

Frame Condensation Resistance (CR f ): the Condensation Resistance for the frame portion of the fenestration product. Product Condensation Resistance (CR): the lower of the CR f, CR c, and CR e. [Note 1: The term CR is being used as an abbreviation for Condensation Resistance for simplification purposes in equations and reference to specific terms, and shall only be used in its abbreviated form in this document and in test and simulation reports. The term CR shall not be used as an acronym for the Condensation Resistance rating for certification and labeling purposes.] 4. SIMULATION METHOD FOR DETERMINING FENESTRATION PRODUCT CONDENSATION RESISTANCE VALUES 4.1 Significance and Use A. This simulation method shall consist of 2-D heat transfer simulation of the same cross-sections used for U-Factor determination as specified by NFRC 100, or the latest applicable procedures. B. Since both temperature and surface air film conditions affect results, this simulation method requires the use of standardized environmental conditions. The standardized NFRC simulation conditions for determining the Condensation Resistance of vertical fenestration systems are specified below. i. Interior ambient temperature of 21ºC (69.8ºF). ii. iii. iv. Exterior ambient temperature of 18ºC (-0.4ºF). Relative humidities of 30 percent, 50 percent, and 70 percent RH providing condensation reference point temperatures of approximately 2.9ºC, 10.3ºC and 15.4ºC (37.3ºF, 50.6ºF and 59.8ºF) Wind speed of 5.5 m/s (12.3 mph) v. Mean radiant temperature equal to the exterior ambient air temperature. [Note 2: The environmental simulation conditions stipulated above are for the purpose of comparative ratings between products.] C. The Condensation Resistance of a specimen shall be determined at the sizes specified in Table 4-3 of NFRC 100. D. This simulation method shall be used to determine the Condensation Resistance, provided the simulations have been validated under NFRC 100. If the product has been deemed a test only product under NFRC 100, Section 5 shall be used to determine the Condensation Resistance. NFRC 500-2010 [E0A1] page 3

E. If any grouping has been done under NFRC 100 to simplify the number of individual products in a product line, the same grouping shall be used to simplify the number of individual products for Condensation Resistance. 4.2 Simulation Method 4.2.1 Product Simulation Requirements The fenestration system shall be simulated in accordance with NFRC-approved software tools that include a detailed gray-body diffuse radiation model and detailed convection modeling inside all glazing cavities. 4.2.2 Determination of Surface Segments For each 2-D cross-section, the developed boundary at the interior surface shall be subdivided into smaller segments, no larger than the size of mesh or grid used by the simulation program. These segments shall be used to compute the product of segment lengths and temperature difference used in the Condensation Resistance rating calculations. In addition, the total length for each 2-D crosssection shall be calculated. 4.2.3 Condensation Resistance Rating The Condensation Resistance (CR) shall be determined for the total fenestration product from the lower of the Condensation Resistance rating for the frame (CR f ), edge-of-glazing (CR e ) and center-ofglazing (CR c ). 4.3 Condensation Resistance Calculations The following section defines the method of calculating the Condensation Resistance from simulation data. A. Determination of the resistance of the fenestration product to the formation of condensation in any form, referred to as the Condensation Resistance, shall be accomplished using the conditions listed in Section 4.1.B. B. The Condensation Resistance using this procedure shall be determined using Equation 4-1, Equation 4-2 and Equation 4-3. 4.3.1 Determine Condensation Resistance of the Frame, CR f Temperatures of the frame sections shall be determined for each subdivided segment (see Section 0.05.2.1), as an average for that segment, using the approved 2-D simulation program. For each condensation reference point temperature, the product of each segment length and the temperature difference (t dpp -t f ), shall be NFRC 500-2010 [E0A1] page 4

determined and summed for all positive values. This sum shall be divided by the product of total frame segment lengths, L f and the difference between the condensation reference point temperature and the outside temperature (t dpp -t o ) and calculated for the three relative humidities (i.e., condensation reference point temperatures) for each cross-section. The final CR f for each relative humidity shall be calculated by area weighting these non-dimensional numbers for the whole frame area as given in Equation 4-1. CR f 1/ 3 SS f A k f k k = 1 100 Af k=frame section Equation 4-1 Where for each frame cross-section, k: SS fk = ( S f ) = 30 50 70 j j RH @ %, %, % 3 Where for each relative humidity: S f = ( ) i i ( ) + dpp f fi t t L t t L dpp o f i=subdivided element + =positive values only 4.3.2 Determine Condensation Resistance of the Glazing Portion, CR c and CR e. The glazing Condensation Resistance shall be split into two components: the edge-of-glazing and the center-of-glazing. The center-of-glazing Condensation Resistance also includes the divider and edge-of-divider areas, if applicable. 4.3.2.1 Center-of-Glazing Determine if the interior glass surface of the center-ofglazing area is above or below the three prescribed condensation reference point temperatures at 30% (j=1), 50% (j=2) and 70% (j=3) relative humidity. If the interior glass surface is at or below the condensation reference point temperature, use the entire center-of-glazing area for A cog,j. If the interior NFRC 500-2010 [E0A1] page 5

4.3.2.2 Dividers glass surface temperature is above the condensation reference point temperature then use 0 for A cog,j. True divided lites, simulated divided lites and between glass dividers are included in the center-of-glazing Condensation Resistance, CR c. If the glazing system contains between glass dividers, and the space between the divider and glass is less than 3 mm (1/8 in.), divider and edge-of-divider values shall be calculated. Temperatures of the divider and edge-ofdivider sections shall be determined for each subdivided segment (see Section 0.05.2.1), as an average for that segment, using the approved 2-D simulation program. For each condensation reference point temperature, the product of segment length, L and the temperature difference (t dpp -t d ) and (t dpp -t deog ) shall be determined and summed for all positive values. This sum shall be divided by the product of the divider width, L d or edge-of-divider width, L deog (i.e., 63.5 mm [2.5 in.]) and difference between the condensation reference point temperature and the outside temperature (t dpp -t o ). These calculated quantities shall be reported for the three relative humidities (i.e., condensation reference point temperatures) for each unique divider cross-section. The final CR c shall be calculated by area weighting these non-dimensional numbers for the center-ofglazing, divider, and edge-of-divider areas as given in Equation 4-2. NFRC 500-2010 [E0A1] page 6

CR c 1/3 SSd A k d + SS k deog A k deog + SS k cog A k cogk k k k = 1 100 Ad + A k deog + A k cogk k k k Equation 4-2 k=center-of-glazing, divider, edge-of-divider sections, respectively Where for each frame cross-section, k: SS SS SS dk doegk cogk = = = j ( S ) = 30 50 70 d j RH @ %, %, % 3 ( Sdeog ) = 30 50 70 j j RH @ %, %, % 3 ( Scog ) = 30 50 70 j j RH @ %, %, % 3 where for each relative humidity, j S S deog d = ( ) i i ( ) + dpp d di t t L t t L dpp o d i=subdivided element + =positive values only = ( ) i i ( ) + dpp deog deogi t t L t t L dpp o deog i=subdivided element + =positive values only S cog = ( tdpp tcog i ) i ( tdpp to ) i=subdivided element + =positive values only + NFRC 500-2010 [E0A1] page 7

4.3.2.3 Edge-of-Glazing Temperatures of the edge-of-glazing sections shall be determined for each subdivided segment (see Section 0.05.2.1), as an average for that segment, using the approved 2-D simulation program. For each condensation reference point temperature, the product of segment length and temperature difference (t dpp -t eog ) shall be determined and summed for all positive values. This sum shall be divided by the product of total edge-of-glazing length (i.e., 63.5 mm [2.5 in.]) and difference between the condensation reference point temperature and the outside temperature (t dpp -t o ) and calculated for three relative humidities (i.e., condensation reference point temperatures) for each cross-section. The final CR e shall be calculated by area weighting these non-dimensional numbers for the edge-ofglazing areas as given in Equation 4-3. CR e 1/ 3 SSeog A k eogk k = 1 100 Aeogk k k=edge-of-glazing sections, respectively Equation 4-3 Where for each cross-section, k: SS eogk = ( Seog ) = 30 50 70 j j RH @ %, %, % 3 where for each relative humidity, j S eog = ( ) i i ( ) + dpp eog eogi t t L t t L dpp o eog i=subdivided element + =positive values only 4.3.3 Determine Condensation Resistance of the Total Product, CR. Condensation Resistance = Lower of the CR f, CR c, and CR e NFRC 500-2010 [E0A1] page 8

4.3.4 Condensation Resistance Variables t dp = Dew point temperatures at the given relative humidity (RH); t dp, 1 = 2.9ºC (37.3ºF) @ RH = 30% t dp,2 = 10.3ºC (50.6ºF) @ RH = 50% t dp, 3 = 15.4ºC (59.8ºF) @ RH = 70% t dpp = condensation reference point temperatures t dpp = t dp +0.3ºC (t dpp = t dp +0.5ºF) t dpp,1 = 3.2ºC (37.8ºF) t dpp,2 = 10.6ºC (51.1ºF) t dpp,3 15.7ºC (60.3ºF) t o = exterior ambient temperature 18ºC(0ºF) t fi = average temperature of the frame segments i, subdivided as per Section 0.05.2.1 t eogi = average temperature of the edge-of-glazing segments i, subdivided as per Section 0.05.2.1 t cogi = average temperature of the center-of-glazing area i t deogi = average temperature of the edge-of-divider area i t di = average temperature of the divider area i L fi = length of subdivided segments on each modeled frame cross-section L eogi = length of subdivided segments on each modeled edge-of-glazing cross-section L deogi = length of subdivided segments on each modeled edge-of-divider cross-section L di = length of subdivided segments on each modeled divider cross-section L f = total (wetted) length of each modeled frame crosssection L eog = total length of each modeled edge-of-glazing crosssection L deog = total length of each modeled edge-of-divider crosssection L d = total length of each modeled divider cross-section A cogk = center-of-glazing area of section, k A fk = projected frame area of each modeled section on the interior surface A eogk = edge-of-glazing area of each modeled cross-section on the interior surface A cogk = center-of-glazing area of each modeled center-ofglazing section on the interior surface NFRC 500-2010 [E0A1] page 9

4.4 Simulation Report A dk = divider area of each modeled divider cross-section on the interior surface A deogk = edge-of-divider area of each modeled divider section on the interior surface A f = Total projected area of the frame on the interior surface i = Index denoting divided sub-segments on indoor boundary j = Index denoting relative humidity considered j = 1; RH=30% j = 2; RH=50% j = 3; RH=70% k = Index denoting edge-of-glazing, frame (i.e. jamb, sill, head, meeting rail, etc.), or center-of-glazing sections CR f = Condensation Resistance of the frame CR c = Condensation Resistance of the center-of-glazing area, including divider and edge-of-divider CR e = Condensation Resistance of the edge-of-glazing area CR = Condensation Resistance of the specimen The simulation report shall include all of the information specified in the NFRC LAP and subsequent NFRC LAP Bulletins. The report shall include the total product Condensation Resistance rating value, CR. The following statement shall be included in the simulation report directly after the above results are reported: The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. 5. TEST METHOD FOR DETERMINING FENESTRATION PRODUCT CONDENSATION RESISTANCE VALUES 5.1 Significance and Use A. This test method references the calibration and testing procedures as defined in the NFRC 102 and necessary additional temperature NFRC 500-2010 [E0A1] page 10

instrumentation required for the NFRC test procedure to measure the Condensation Resistance of vertical fenestration systems. B. Since both temperature and surface air film conditions affect results, this test method requires the use of standardized environmental conditions. The test conditions for the NFRC test procedure to measure Condensation Resistance shall be identical to those used in the NFRC 102. C. This test method does not include procedures to measure the Condensation Resistance due to either air movement through the test specimen or solar radiation effects. D. The Condensation Resistance of a test specimen may be affected by its size and three-dimensional geometry. If the test specimen size is nonstandard [± 12.7 mm (0.5 in)] in width and/or height from the model size referenced in Table 4-3 of NFRC 100, then the text "non-standard size" shall be indicated in the final report as per Section 5.4. E. This test method shall only be used when the product cannot have the Condensation Resistance simulated using an NFRC Condensation Resistance Simulation Method per Section 4 of this procedure. 5.2 Test Method 5.2.1 Test Specimen Testing Requirements The fenestration system shall be tested in accordance with Section 6 of the NFRC 102 with the additional thermocouples applied to the interior surface of the product as defined in Appendix B of this procedure. 5.2.2 Determination of Total Exposed Surface Area The fenestration total wetted surface area shall be used. The wetted surface area shall be the same as that used in NFRC 102. 5.2.3 Temperature Measurement The fenestration system is shall be instrumented in accordance with Section 6 of NFRC 102. A. All measurements specified in NFRC 102 shall be made. B. The attachment of thermocouples shall be performed using a nominal 25 mm wide by 100 mm long (4 in. by 1 in.) adhesivebacked aluminum foil tape, with a surface emittance equal to that of the base surface (± 0.1). The 100 mm (4 in.) dimension parallel to the thermocouple wire. B.C. For Dynamic Glazing Products that utilize a shading or diffusing system, thermocouples shall be applied to the most indoor glazing surface. They shall not be applied to any shade or blind NFRC 500-2010 [E0A1] page 11

5.3 Test Procedure Calculations General Calculations component which may be present on the indoor side of the product. This section defines the method of calculating the Condensation Resistance from test data. A. Determination of the resistance of the fenestration product to the formation of condensation in any form, referred to as the Condensation Resistance, shall be accomplished using the conditions listed in Section 5.1.B. B. The Condensation Resistance using this procedure shall be determined as follows. i. Record interior surface temperature for each individual thermocouple location. ii. iii. Calculate the wetted area assigned to each individual surface thermocouple sensor. Calculate the total interior wetted area of frame and glazing. iv. Determine Condensation Resistance of the frame, CR f, center-of-glazing, CR c, and of the edge-of-glazing, CR e, using Equation 5-1, Equation 5-2 and Equation 5-3: CR f ( ), 1/3 + t 3 dpp t j f A i fi i j= 1 ( tdpp, j to ) Af j= RH @30%,50%,70% = 1 100 3 i=frame thermocouples Equation 5-1 NFRC 500-2010 [E0A1] page 12

CR e ( ), 1/3 + t 3 dpp t j eog A i eogi i j= 1 ( tdpp, j to ) Aeog j= RH @30%,50%,70% = 1 100 3 Equation 5-2 i=center-of-glazing, divider and edge-of-divider thermocouples CR e ( ), 1/3 + t 3 dpp t j eog A i eogi i j= 1 ( tdpp, j to ) Aeog j= RH @30%,50%,70% = 1 100 3 i= edge-of-glazing thermocouples Equation 5-3 5.3.1 Determine Condensation Resistance of the Total Product, CR. Condensation Resistance = Lower of the CR f, CR c, and CR e 5.3.2 Condensation Resistance Variables t dp,jv = Dew point temperatures at the given relative humidity (RH); t dp, 1 = 2.9ºC (37.3ºF) @ RH = 30% t dp,2 = 10.3ºC (50.6ºF) @ RH = 50% t dp, 3 = 15.4ºC (59.8ºF) @ RH = 70% t dpp, j = condensation reference point temperatures t dpp = t dp +0.3ºC (t dpp = t dp +0.5ºF) t dpp,1 = 3.2ºC (37.8ºF) t dpp,2 = 10.6ºC (51.1ºF) t dpp,3 = 15.7ºC (60.3ºF) t o = exterior ambient temperature [-18ºC (-0.4ºF)] t fi = individual frame thermocouple temperatures. t gi = individual glazing (center-of-glazing, divider, and edge-of-divider) thermocouple temperatures. NFRC 500-2010 [E0A1] page 13

5.4 Test Report t eogi = individual edge-of-glazing thermocouple temperatures. A fi = wetted interior area represented by the frame thermocouples A ci = interior area represented by the central part of glazing (i.e., center-of-glazing, divider, and edge-of-divider) thermocouples A eogi = interior area represented by the edge-of-glazing thermocouples A f = Total (wetted) area of the frame on the interior surface A c = Total area of the central part of glazing (i.e., centerof-glazing, divider, and edge-of-divider) on the interior surface A eog = Total area of the edge-of-glazing on the interior surface i = Index denoting frame, or glazing thermocouple section j = Index denoting relative humidity considered j = 1; RH=30% j = 2; RH=50% j = 3; RH=70% CR f = Condensation Resistance of the frame CR c = Condensation Resistance of the center-of-glazing area, including divider and edge-of-divider CR e = Condensation Resistance of the edge-of-glazing area CR = Condensation Resistance of the Specimen The report shall include all of the information specified in NFRC 102, and the NFRC LAP and subsequent NFRC LAP Bulletins. The test specimen size and design shall also be reported. If the test specimen size is non-standard [± 12.7 mm (0.5 in.)] in width and/or height from the model size referenced in Table 4-3 of NFRC 100, then the text "non-standard size" shall be inserted immediately following the size everywhere the size is listed, both in the full report and in any summary. The report shall include the total product Condensation Resistance rating value, CR; the frame Condensation Resistance, CR f ; the center-of-glazing Condensation Resistance, CR c and the edge-of-glazing Condensation Resistance, CR e, as determined using this test procedure. In addition, the report shall include, if applicable, information required in the Section 9 of NFRC 102. NFRC 500-2010 [E0A1] page 14

The following statement shall be included in the test report directly after the above results are reported: The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. 6. REFERENCED DOCUMENTS 6.1 NFRC Documents NFRC 100-2010 NFRC 102-2010 6.2 ASTM Standards C 1199 C 1363 E 1423 Procedures for Determining Fenestration Product U-Factors. Procedure for Measuring the Steady-State Thermal Transmittance of Fenestration Systems Standard Test Method for Measuring the Steady State Thermal Transmittance of Fenestration Systems Using Hot Box Methods Standard Method of Test for the Thermal Performance of Building Assemblies by Means of a Hot Box Apparatus Standard Practice for Determining the Steady-State Thermal Transmittance of Fenestration Systems APPENDIX A BACKGROUND ON THE NFRC CONDENSATION RESISTANCE RATING Reducing or eliminating condensation is one of many fenestration product selection criteria, but an especially important one in cold climates. In addition to the aesthetic issue of reduced visibility or window view, condensation can cause damage to curtains, carpets and wall finishes, cause mold and wood rot, lift paint and plaster, and eventually result in damage to building materials. Water contact with insulating glass sealant may result in premature failure of the edge seals. The formation of condensation on the interior surfaces of fenestration products is dependent on a number of factors including the outdoor temperature, and the relative humidity inside NFRC 500-2010 [E0A1] page 15

the building. As the outside temperature falls, the indoor surface temperature of the fenestration product may fall below the interior dew point temperature. The interior dew point temperature is a function of the relative humidity of the interior air; such that, the higher the relative humidity the higher the dew point temperature. This means that with the same fenestration product surface temperature conditions, condensation will occur sooner in a space with a higher indoor relative humidity. Measured winter relative humidity levels in buildings vary between 20 and 70 percent. The NFRC Condensation Resistance scale is 1-100, with a higher number being better. The Condensation Resistance rating is determined based on outside conditions of -18ºC (-0.4ºF) with a 5.5 m/s (12.3 mph) wind and inside conditions of 21ºC (69.8ºF) with indoor relative humidities of 30 percent, 50 percent, and 70 percent. The Condensation Resistance rating is a value that considers the relative area of condensation at the three humidities and the degree to which the surface temperatures are below the dew point for the frame and for the glazing. The Condensation Resistance rating specified in the NFRC rating is based on the lower of the frame, edge-of-glazing or center-of-glazing values. The Condensation Resistance rating is determined for very specific conditions. When installed in a building, there are numerous uncontrolled, site specific factors that may affect the condensation formation on the fenestration product, including installation details, site geometry, wind speed and direction, air circulation and fenestration product coverings, to name a few. In this procedure, the Condensation Resistance rating is meant to apply only to interior fenestration product surfaces under cold winter conditions. The procedure does not address the issue of condensation on the exterior fenestration product surface as can occur during seasons other than winter. APPENDIX B PREDETERMINED TEMPERATURE MEASUREMENT LOCATIONS This appendix indicates the correct placement of thermocouples when testing for Condensation Resistance rating in accordance with Section 5. All thermocouples intended to measure center-of-glazing temperature shall be placed at the center-of-glazing of each unit in the fenestration product. All thermocouples intended to measure edge-ofglazing temperature shall be placed 12.7 mm (0.5 in.) from the sightline of the frame along the centerline of the fenestration product. All thermocouples intended to measure frame temperatures shall be placed along the centerline of the fenestration product at a location that will be representative of the area weighted average temperature of the frame segment represented by the thermocouple. There are many different kinds of fenestration products covered by this procedure, including many different frame materials and designs. The exact placement of frame thermocouples will require the operator to make some judgment in the position of the thermocouples. NFRC 500-2010 [E0A1] page 16

Figure 6-1 Casement and Awning Thermocouple Placement (Awning - rotate 90 degrees) NFRC 500-2010 [E0A1] page 17

Figure 6-2 Fixed Window, Sidelite, and Transom Thermocouple Placement NFRC 500-2010 [E0A1] page 18

Figure 6-3 Swinging Patio Door Thermocouple Placement NFRC 500-2010 [E0A1] page 19

Figure 6-4 Horizontal Slider, Vertical Slider, and Sliding Patio Door Thermocouple Placement (Vertical Slider rotate 90 degrees) NFRC 500-2010 [E0A1] page 20

Figure 6-5 Glazed Wall and Sloped Glazing Thermocouple Placement NFRC 500-2010 [E0A1] page 21

Figure 6-6 Divider Thermocouple Placement NFRC 500-2010 [E0A1] page 22

INDEX C C 1199... 1, 15 C 1363... 15 Condensation reference point temperature... 2 D Dew point temperature... 2 E E 1423... 1, 15 N NFRC 100... 1, 3, 11, 14, 15 Table 4-3... 3, 11, 14 NFRC 102... 1, 10, 11, 14, 15 Section 6... 11 Section 9... 15 NFRC 500-2010 [E0A1] page 23