CLIENT: TA CHEN INTERNATIONAL, INC. 5855 Obispo Avenue Long Beach, CA 90805 John Elsenheimer Test Report No: RJ0329-2 Date: September 23, 2009 SAMPLE ID: The Client submitted and identified the following test material as Polytec Shutter. DATE OF RECEIPT: Samples were received on August 17, 2009. TESTING PERIOD: September 14, 2009. AUTHORIZATION: Testing authorized by John Elsenheimer. TEST REQUESTED: The submitted sample was tested in accordance with the procedures outlined in UL94-2006, "Tests for Flammability of Plastic Materials" (Vertical Burning Test, V-O, V-1 or V- 2). TEST RESULTS: See page 2. CLASSIFICATION: The submitted sample is Classified V-0. See classification requirements on page 2. Prepared By Signed for and on behalf of QAI Laboratories Inc. Brian Ortega Test Technician Greg Banasky Supervisor Fire Technology
Client: TA CHEN INTERNATIONAL, INC. Report No: RJ0329-2 Date: September 23, 2009 Page 2 of 2 TEST RESULTS: Specimen Dimensions mm *After first flame application T1 Afterflame, Seconds *After second flame application T2 Afterflame, Seconds After glow time after second application T3 Afterglow Seconds Does specimen burn up to the holding clamp? Yes or No Cotton Indicator Ignited 1 0 0 0 No No 2 0 0 0 No No 3 0 0 0 No No 4 0 0 0 No No 5 0 0 0 No No 6 0 0 0 No No 7 0 0 0 No No 8 0 0 0 No No 9 0 0 0 No No 10 0 0 0 No No CRITERIA CONDITIONS V-O V-1 V-2 Afterflame time for each individual specimen t1 or t2 10s 30s 30s Total afterflame time for any condition set (t1 plus t2 50s 250s 250s for the 5 specimens) Afterflame plus afterglow time for each individual 30s 60s 60s specimen after the second flame application (t2+t3) Afterflame or afterglow of any specimen up to the No No No holding clamp Cotton indicator ignited by flaming particles or drops No No Yes
CLIENT: TA CHEN INTERNATIONAL, INC. 5855 Obispo Avenue Long Beach, CA 90805 John Elsenheimer Test Report No: RJ0329-4 Date: September 24, 2009 SAMPLE ID: The Client submitted and identified the following test material as Polytec Shutter. DATE OF RECEIPT: Samples were received on August 17, 2009. TESTING PERIOD: September 23, 2009. AUTHORIZATION: Testing authorized by John Elsenheimer. TEST REQUESTED: The sample material was tested in accordance with the procedures outlined in NFPA 701 Fire Test 1 (small) 2004 Edition "Standard Methods of Fire Tests for Flame- Resistant Textiles and Films. TEST RESULTS: Pass. See page 2 for detailed results. See page 2 for Performance Criteria. Prepared By Signed for and on behalf of QAI Laboratories Inc. Brian Ortega Test Technician Greg Banasky Supervisor Fire Technology
Client: TA CHEN INTERNATIONAL, INC. Report No: RJ0329-4 Date: September 24, 2009 Page 2 of 2 TEST RESULTS: Specimen No. Initial Weight, g. Final Weight, g. Weight Loss, g. Percent Weight Loss Time of Flaming of pieces on floor (seconds) 1 1027 1026 1 0.1 0 2 1028 1025 3 0.3 0 3 1026 1025 1 0.1 0 4 1025 1023 2 0.2 0 5 1027 1025 2 0.2 0 6 1022 1019 3 0.3 0 7 1028 1026 2 0.2 0 8 1029 1027 2 0.2 0 9 1031 1030 1 0.1 0 10 1021 1018 3 0.3 0 0.2 Average Percent Weight Loss 0.1 Standard Deviation 0.0 Average Time of Flaming of Pieces on the Floor (seconds) PERFORMANCE CRITERIA 1) Where fragments or residues of specimens that fall to the floor of the test chamber continue to burn for more than an average of 2 seconds per specimen for the sample of 10 specimens, the material shall be recorded as failing the test. 2) Where the average weight loss of the 10 specimens in a sample is greater than 40 percent, the material shall be recorded as failing the test.
CLIENT: TA CHEN INTERNATIONAL, INC. 5855 Obispo Avenue Long Beach, CA 90805 John Elsenheimer Test Report No: RJ0329-7 Date: September 24, 2009 SAMPLE ID: The Client submitted and identified the following test material as Polytec Shutter. DATE OF RECEIPT: Samples were received on August 17, 2009. TESTING PERIOD: September 14, 2009. AUTHORIZATION: Testing authorized by John Elsenheimer. TEST REQUESTED: Flammability in accordance with the procedures outlined in California Administrative Code, Title 19, Section 1237.1 Original Condition. TEST RESULTS: Please refer to page 2 CONCLUSION: The submitted sample meets the flammability requirements. See requirements on page 2. Prepared By Signed for and on behalf of QAI Laboratories Inc. Brian Ortega Test Technician Greg Banasky Supervisor Fire Technology
Client: TA CHEN INTERNATIONAL, INC. Report No: RJ0329-7 Date: September 24, 2009 Page 2 of 2 TEST RESULTS: Specimen No. After Flame (seconds) After Glow (seconds) Char Length (inches) 1 0 0.0 0.5 2 0 0.0 0.7 3 0 0.0 0.9 1 0 0.0 0.5 2 0 0.0 0.9 3 l 0 0.0 0.8 Average 0 0.0 REQUIREMENTS: Current Proposed* After Flame Time: -Avg. No Requirement 4 sec. max. -Individual 2.0 sec. max. No Requirement Char length: -Avg. No Requirement No Requirement -Individual 6.0 inch max. 6.0 inch max. After Glow: No requirements for After Glow.