STEADY-STATE MODELING AND ANALYSIS OF THREE PHASE SELF-EXCITED INDUCTION GENERATOR WITH SERIES COMPENSATION

Similar documents
Modeling and Analysis of Six-phase Self-excited Induction Generators for Wind Energy Conversion

CHAPTER 5 STEADY-STATE ANALYSIS OF THREE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 2 CAPACITANCE REQUIREMENTS OF SIX-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 6 STEADY-STATE ANALYSIS OF SINGLE-PHASE SELF-EXCITED INDUCTION GENERATORS

CHAPTER 3 ANALYSIS OF THREE PHASE AND SINGLE PHASE SELF-EXCITED INDUCTION GENERATORS

MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator

AN EFFICIENT APPROACH FOR ANALYSIS OF ISOLATED SELF EXCITED INDUCTION GENERATOR

TRANSIENT ANALYSIS OF SELF-EXCITED INDUCTION GENERATOR UNDER BALANCED AND UNBALANCED OPERATING CONDITIONS

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

KINGS COLLEGE OF ENGINEERING Punalkulam

A simple model based control of self excited induction generators over a wide speed range

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Introduction to Synchronous. Machines. Kevin Gaughan

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Synchronous Machines

MATLAB Based Steady State Analysis of Self Excited Induction Generator

Performance Analysis of Self-Excited Induction Generator Driven At Variable Wind Speeds

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

Determination of Magnetising Reactance and Frequency of Self-Excited Induction Generator using ANN Model

Chapter 4. Synchronous Generators. Basic Topology

Output Voltage Control of a Wind Generation Scheme using Neural Networks

Module 3 : Sequence Components and Fault Analysis

A GENERALISED OPERATIONAL EQUIVALENT CIRCUIT OF INDUCTION MACHINES FOR TRANSIENT/DYNAMIC STUDIES UNDER DIFFERENT OPERATING CONDITIONS

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

390 IEEE Transactions on Energy Conversion, Vol. 9, No. 2, June 1994

EEE3405 ELECTRICAL ENGINEERING PRINCIPLES 2 - TEST

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Review of Basic Electrical and Magnetic Circuit Concepts EE

ECEN 460 Exam 1 Fall 2018

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Fault Analysis Power System Representation

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Lesson 17: Synchronous Machines

1 Unified Power Flow Controller (UPFC)

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Generators for wind power conversion

mywbut.com Lesson 16 Solution of Current in AC Parallel and Seriesparallel

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Brief Steady of Power Factor Improvement

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

EE Branch GATE Paper 2010

LO 1: Three Phase Circuits

Sinusoidal Steady State Analysis (AC Analysis) Part II

INDUCTION MOTOR MODEL AND PARAMETERS

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

Eddy Current Heating in Large Salient Pole Generators

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

AC Circuits Homework Set

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

Direct Flux Vector Control Of Induction Motor Drives With Maximum Efficiency Per Torque

11. AC Circuit Power Analysis

Tutorial Sheet Fig. Q1

Chapter 6. Induction Motors. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

Q. 1 Q. 25 carry one mark each.

Conventional Paper-I-2011 PART-A

PERFORMANCE ANALYSIS OF DIRECT TORQUE CONTROL OF 3-PHASE INDUCTION MOTOR

QUESTION BANK SUBJECT: NETWORK ANALYSIS (10ES34)

Power System Operations and Control Prof. S.N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur. Module 3 Lecture 8

Chapter 2 Voltage-, Current-, and Z-source Converters

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

ELECTROMAGNETIC OSCILLATIONS AND ALTERNATING CURRENT

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

Work, Energy and Power

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

Analysis of the Dynamic Characteristics of an Isolated Self-Excited Induction Generator Driven by a Wind-Turbine

Power and Energy Measurement

Harmonic Modeling of Networks

We are IntechOpen, the first native scientific publisher of Open Access books. International authors and editors. Our authors are among the TOP 1%

Implementation of Twelve-Sector based Direct Torque Control for Induction motor

Lecture (5) Power Factor,threephase circuits, and Per Unit Calculations

Three Phase Circuits

Power Factor Improvement

Comparative Analysis of Speed Control of Induction Motor by DTC over Scalar Control Technique

Module 4. Single-phase AC circuits. Version 2 EE IIT, Kharagpur

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

JRE SCHOOL OF Engineering

Power density improvement of three phase flux reversal machine with distributed winding

GATE 2008 Electrical Engineering

ECEN 667 Power System Stability Lecture 18: Voltage Stability, Load Models

Sinusoidal Steady State Analysis (AC Analysis) Part I

ECE 585 Power System Stability

GENERATOR INTERCONNECTION APPLICATION

Available online at ScienceDirect. Procedia Technology 25 (2016 )

Dynamic Modeling of Surface Mounted Permanent Synchronous Motor for Servo motor application

International Journal of Advance Engineering and Research Development SIMULATION OF FIELD ORIENTED CONTROL OF PERMANENT MAGNET SYNCHRONOUS MOTOR

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

Dynamics of the synchronous machine

ELG4125: Power Transmission Lines Steady State Operation

Design of PSS and SVC Controller Using PSO Algorithm to Enhancing Power System Stability

Transformer Fundamentals

MODELING AND HIGH-PERFORMANCE CONTROL OF ELECTRIC MACHINES

Different Techniques for Calculating Apparent and Incremental Inductances using Finite Element Method

GATE 2010 Electrical Engineering

Mathematical Modeling and Dynamic Simulation of DC Motors using MATLAB/Simulink Environment

Pretest ELEA1831 Module 11 Units 1& 2 Inductance & Capacitance

Low Frequency Transients

Transcription:

STEADY-STATE MODELING AND ANALYSIS OF THREE PHASE SELF-EXITED INDUTION GENERATOR WITH SERIES OMPENSATION S. Singaravelu and S. Sasikumar Department of Electrical Engineering, Annamalai University, hidambaram, India ABSTRAT This paper presents a generalized mathematical model for the analysis of three-phase self-excited induction generators (SEIG) with series compensation. Two methods of series compensation namely short-shunt and long-shunt compensation are analyzed to improve the voltage regulation of the SEIG. The proposed mathematical model is formed directly from the equivalent circuit of SEIG based on nodal admittance method by inspection. The proposed model completely eliminates the tedious work of separating real and imaginary parts of complex admittance. Also, any equivalent circuit elements can be easily included or eliminated from the model. Genetic algorithm is used to determine the performance of SEIG. KEYWORDS: Induction Generator, Self-excitation, Voltage Variation, Genetic Algorithm & Series ompensation I. INTRODUTION If an appropriate three-phase capacitor bank is connected across an externally driven induction machine, an EMF is induced in the machine windings due to the excitation provided by the capacitor. This phenomenon is termed as capacitor self-excitation, which can be used to operate the induction machine as a generator. The induced voltages and currents would continue to rise, but for magnetic saturation in the machine which results in an equilibrium state being reached. A capacitor self-excited induction generators (SEIG) offers certain advantages over a conventional synchronous generator as a source of isolated power supply. Reduced unit cost, brushless rotor, absence of a separate D source and ease of maintenance are among the advantages [1-4]. But poor voltage regulation of SEIG even at regulated speed has been major bottleneck in its application. Steady increase in capacitor VAR with load has to be achieved to maintain good voltage regulation. Several voltage regulating schemes like switched capacitor or variable inductor or saturated core reactor based close loop schemes using relay/contractors or semiconductor switches can be incorporated to improve voltage regulation. But complex system configuration, complicated control circuit design and operational problems like harmonics and switching transients, associated with voltage regulators make ineffective the very advantages of recommending induction machine to autonomous power generation. Inclusion of additional series capacitance to provide additional VAR with load is one of the attractive options to improve voltage regulation of SEIG. han proposed long-shunt compensation to examine parameter k, which is defined as the ratio of the capacitive reactance to shunt capacitive reactance, on the performance of an induction generator under different loading conditions [5]. The results shown in [5] clearly demonstrate that the long-shunt compensation can be employed to maintain load voltage under various load currents. Sridhar, et al. [6] also presented both steady-state and transient performances of both short-shunt and simple shunt compensations of an induction generator. Li Wang, et al. [7] analyzed and compared the effects of both short-shunt connections as shown in Figure 1 and long-shunt connections as shown in Figure 2 on load voltage variation of the SEIG. 371 Vol. 3, Issue 2, pp. 371-38

Induction generator Series capacitance sh sh Load Shunt capacitance sh Figure 1. Block diagram of short-shunt SEIG system Induction generator Series capacitance lo lo Load lo Shunt capacitance Figure 2. Block diagram of long-shunt SEIG system Most of the methods available in literature [5-13] on steady-state performance evaluation of SEIG need separation of real and imaginary component of complex impedance. Moreover the model becomes complicated if the core loss of the machine is also accounted for. It is also observed that the mathematical model is different for each type of loads and also capacitor connections configuration at the machine terminals. Subsequently, the coefficients of mathematical model are also bound to change with change in load, capacitance configuration at the machine terminals. The author made an attempt for the first time to overcome the complication of three-phase and single-phase SEIG models [14-15] by introducing the concept of graph theory which avoids the lengthy and tedious mathematical derivations of nonlinear equations. In the present paper, the author has developed a further simplified mathematical model of three-phase SEIG in matrix form using nodal admittance method based on inspection. In the proposed model, the nodal admittance matrix can be formed directly from the equivalent circuit of three-phase SEIG by inspection rather than deriving it from the concept of graph theory [14-15]. The proposed model completely eliminates the long and tedious manual work involved in segregating the real and imaginary parts of complex impedance or admittance. Moreover, this model is also flexible such that any equivalent circuit elements can be easily included or eliminated. Genetic algorithm (GA) is proposed to determine the steady-state performance of three-phase SEIG. II. PROPOSED METHOD In the analysis presented in this section, the following assumptions are made: Only the magnetizing reactance is assumed to be affected by magnetic saturation, and all other parameters of the equivalent circuit are assumed to be constant. Self-excitation results in the saturation of the main flux. As the value of the magnetizing reactance X M reflects the magnitude of the main flux, it is essential to incorporate in the analysis the variation of X M with the saturation level of the main flux. Passage of the leakage fluxes occurs primarily in the air and thus these fluxes are not affected to any large extent by the saturation of the main flux. Leakage reactance of stator and rotor, in per unit, are taken to be equal. This assumption is normally valid in induction-machine analysis. MMF space harmonics and time harmonics in the induced voltage and current waveforms are ignored. This assumption is valid in well-designed machines. Further, the experimental waveforms of generated voltages exhibited negligible time harmonics. ore loss in the machine is neglected. 372 Vol. 3, Issue 2, pp. 371-38

- j X c s h - j X c l o R S j X F 2 F 2 F l s j X l r 2 1 V F L R L F j X L I L - j X 2 F V t F I S j X M V g F I r R r (F - ψ) Figure 3. Equivalent circuit of the induction generator with short-shunt and long-shunt configuration Figure 3 shows the steady-state equivalent circuit of the self excited induction generator. The equivalent circuit is valid for any per unit speed υ. The parameters of equivalent circuit are as follows: Y L = 1 / {R L /F + ix L - j X csh /F 2 } Y = 1 / {- j X /F 2 } Y S = 1 / {R s /F + j X ls - j X clo /F 2 } Y M = 1 / {j X M } Y R = 1 / {R r / (F-υ) + j X lr } The matrix equation based on nodal admittance method for the equivalent circuit can be expressed as [Y] [V] = [I S ] (1) Where [Y] is the nodal admittance matrix, [V] is the node voltage matrix, and [I S ] is the source current matrix. The [Y] matrix can be formulated directly from the equivalent circuit (Figure 3) using nodal admittance method based on inspection [16] as where Y S + Y M + Y R - Y S [Y] = (2) - Y S Y S + Y + Y L Y ii = Admittance of the branches connected to i th node Y ij = - Admittance of the branches connected between i th node and j th node Since, the equivalent circuit does not contain any current sources, [I S ] = [] and hence Eq. (1) is reduced as [Y] [V] = (3) For successful voltage build up, [V] and therefore from Eq. (3), [Y] should be a singular matrix i.e., det [Y] =. It implies that both the real and the imaginary components of det [Y] should be independently zero. Therefore to obtain required parameter which results det [Y] =, genetic algorithm based approach is implemented. III. GENETI ALGORITHM Application of genetic algorithm [17] to obtain det[y] =, which provides solution for unknown quantities, is illustrated in Figure 4. The objective function whose value is to be minimized is given by Eq. (4). g (F,X M or X ) = abs{real(det[y ])} + abs{imag(det[y ])} (4) 373 Vol. 3, Issue 2, pp. 371-38

START read all required parameters for matrix Y read population size (PS) and ranges for F and X M or X generation (GEN) = 1 generate the initial population population count (POP) = 1 evaluate objective function g(f, X M ) or g(f, X ) is g(f, X M ) or g(f, X ) reaches desired tolerance NO POP = POP + 1 YES compute performance and print results STOP YES is POP < PS NO GEN = GEN + 1 generate new set of chromosomes using Genetic Algorithm process Figure 4. Flow chart for minimization of the objective function using genetic algorithm (GA). In many optimization problems to obtain initial estimates suitably, certain trials may be required. However, in the present problem of the SPSEIG, it is easy to give the range for the unknown variables F and X M or X because in well-designed self-excited induction generators, it is known that the slip {(F υ)/f} is small and operation of the machine is only in the saturated region of the magnetization characteristics. So, the ranges for F can be given as.8 to.999 times the value of υ and for X M as 25% to 1% of critical magnetizing reactance X MO. Similarly for X, the same range 25% to 1% of MAX can be used, where MAX is the maximum capacitance required under any conditions. Thus, starting from such initial estimates, the final value of F and X M or X is obtained through GA. The air gap voltage V g can be determined from the magnetization characteristics corresponding to X M, as described in Section 4. Once the air gap voltage V g is calculated, the equivalent circuit can be completely solved to determine the steady-state performance of SEIG. 374 Vol. 3, Issue 2, pp. 371-38

IV. EXPERIMENTAL SET UP AND MAHINE PARAMETERS The parameters of the equivalent circuit (Figure 3) are obtained from experimental measurements on a laboratory model, 3.7 KW, 23 V (line voltage), 12.5 A (line current), 5 Hz, 4 poles, delta connected induction generator. The base values are: V b (base voltage) = 23 V, I b (base current) = 12.5 / 3 = 7.22 A, Z b (base impendence) = 31.86 Ω, N b (base rotor speed) F b (base frequency) = 15 rpm, and = 5 Hz. The per-unit parameters of this machine are: R S =.678, R r =.769, X ls = X lr =.124. The magnetizing reactance X M (p.u) versus air gap voltage V g /F (p.u) expressed by a set of piecewise linear approximations as follows: 1.7315 -.2492 X M, X M 3. 26 1.9854 -.3262 X M, 3.26 < X M 3.74 4.2633 -.9328 X M, 3.74 < X M 4.1, 4.1 < X M V. RESULTS AND DISUSSION 5.1. Steady-State Performance Analysis of Short-shunt SEIG The selected unknown variables are magnetizing reactance X M and frequency F for obtaining performance characteristics of the machine. To find the steady-state performance of short-shunt SEIG, the long-shunt component X clo in the term Y S can be assigned as zero in Eq. (2). For obtaining steady-state performance characteristics of short-shunt connections, solve the determinant of the matrix shown in Eq. (2) and find the unknown variables X M and F using genetic algorithm (Figure 4). Vt, VL, IS and IL (p.u) 1.4 1.2 1.8.6.4.2.5 1 1.5 2 2.5 3 Output power (p.u) Vt VL IS IL VAr =31.5µF, sh=15µf, υ = 1p.u, pf=1 15 12 9 6 3 Volt Ampere Reactive (VAr) Figure 5. Typical characteristics of the short-shunt SEIG (UPF) The haracteristics of the short-shunt SEIG feeding pure resistive load are shown in Figure 5. apacitance is selected to be 31.5µF as it results in a no-load terminal voltage of 1.pu (base voltage is 23V). It is observed from Figure 5 that the variation of the load voltage with output power is marginal. Further the inclusion of series capacitance ( sh =15µF) results in higher overload capability of the system. 375 Vol. 3, Issue 2, pp. 371-38

Figure 6(a) Figure 6(b) Figure 6(c) Figure 6. Effect of series capacitance on the characteristics of the short-shunt SEIG Figure 6 shows the effect of series capacitance on the characteristics of the short-shunt SEIG under the same self excitation capacitance of = 31.5 µf and rotor speed of 1pu. Three series capacitance values, 9µF, 15µF and 12µF for short-shunt connections were employed to study the steady-state performance of the short-shunt SEIG. Figure 6(a) shows the terminal voltage versus output real power for short-shunt connections. The terminal voltage decreases under lower output real powers and increases under higher output real powers. It is also observed that, under higher output real powers, the lower the series capacitance values, the higher are the terminal voltages. Figure 6(b) shows the load voltage versus output real power for short-shunt connections. Load voltage variations are less from no load to rated load conditions. When the output real power is below 1.8p.u, the smaller the short-shunt capacitance value, the larger the load voltage is. When the output real power is greater than 1.8p.u, the smaller the short-shunt capacitance value, the lower the load voltage is. Figure 6(c) shows the characteristics of stator current versus output real power for short-shunt connections. The stator winding current are well below the rated value at rated output real power. Figure 7 shows the predicted characteristics of the short-shunt SEIG with an inductive load power factor of.9. The system observes voltage sag at light load as shown in Figure 7 nevertheless, the system displays self-regulation when loaded to higher load. Figure 8 shows the steady-state characteristics of maximum voltage variation versus short-shunt capacitance at unity and.9 lagging power factor loads at rated speed. The short-shunt connection has the voltage variation of zero percent as observed at rated output power and speed with self excitation capacitance =27µF (V NL =1pu), series capacitance sh =83.44µF at unity power factor load. For.9 lagging power factor load, the short-shunt connection has the voltage variation of zero percent as observed at rated output power and speed with self excitation capacitance =27µF (V NL =1pu), series capacitance sh =117.25µF. 376 Vol. 3, Issue 2, pp. 371-38

1.4 VAr 35 1.2 VL V t 3 Vt,VL,IS and IL (p.u) 1.8.6.4.2 I S I L =35µF, sh =75µF, υ = 1p.u, pf=.9lag 25 2 15 1 5 Volt Ampere Reactive (VAr).5 1 1.5 2 2.5 3 Output power (p.u) Figure 7. Typical characteristics of the short-shunt SEIG (.9PF lag) Max. voltage variation (%) 2 15 1 5-5 -1-15 =27 µf, V NL=1 pu, Speed=15 rpm pf=.9 lag upf -2 5 1 15 2 25 3 Short Shunt apacitance - sh (µf) Figure 8. Maximum voltage variation of short-shunt connection 5.2. Performance Analysis of Long-shunt SEIG The same matrix as shown in Eq. (2) can be used to find the unknown variables X M and F for longshunt connections. Since short-shunt connections is not considered, the X csh value in the term Y L can be assigned as zero in Eq. (2). For obtaining steady-state performance characteristics of long-shunt connection, solve the determinant of the matrix shown in Eq. (2) and find the unknown variables X M and F using genetic algorithm (Figure 4). The predicted characteristics of the long-shunt SEIG feeding pure resistive load are shown in Figure 9. Shunt capacitance and long-shunt capacitance lo are selected as 5µF and 3µF as it results in a no-load terminal voltage of 1.6pu (base voltage is 23V). It is observed from Figure 9 that the variation of the load voltage with output power is marginal. Further the inclusion of series capacitance results in higher overload capability of the system. 377 Vol. 3, Issue 2, pp. 371-38

1.4 1.2 Vt 14 12 Vt, VL, IS and IL (p.u) 1.8.6.4.2 VL.5 1 1.5 2 2.5 IS IL VAr =5µF, lo=3µf, υ = 1p.u, pf=1 Output pow er (p.u) 1 8 6 4 2 Volt Ampere Reactive (Var) Figure 9. Typical characteristics of the long-shunt SEIG (UPF) Terminal voltage, V t (p.u) 1.3 1.25 1.2 1.15 1.1 =5µF, υ=1p.u, pf=1 lo=26µf 1.5 lo=3µf lo=34µf 1.5 1 1.5 2 2.5 Output power (p.u) Figure 1(a) Load voltage, VL (p.u) 1.2 1.1 1.9.8.7.6 =5µF, υ=1p.u, pf=1 lo=26µf lo=3µf lo=34µf.5 1 1.5 2 2.5 Output power (p.u) Figure 1(b) Stator current, IS (p.u) 1.1.9.7.5.3 =5µF, υ = 1p.u, pf=1.5 1 1.5 2 2.5 Output power (p.u) Figure 1(c) lo=26µf lo=3µf lo=34µf Figure 1. Effect of series capacitance on the characteristics of the long-shunt SEIG (UPF) Figure 1 shows the predicted characteristics of long-shunt connections under the same shunt capacitance of 5µF and rotor speed of 1pu. Three capacitance values, 26µF, 3µF and 34µF for long-shunt connections were employed to study the steady-state performance of the long-shunt SEIG. Figure 1(a) shows the terminal voltage versus output real power for long-shunt connections. When the output real power is below 1.4p.u, the smaller the long-shunt capacitance value, the lower the 378 Vol. 3, Issue 2, pp. 371-38

terminal voltage is. When the output real power is greater than 1.4p.u, the smaller the long-shunt capacitance value, the higher is the terminal voltage. Figure 1(b) shows the load voltage versus output real power for long-shunt connections. It is observed that the voltage variations are low for different values of series capacitance at rated load conditions. Figure 1(c) shows the characteristics of stator current versus output real power for shortshunt connections. The stator winding current is well below the rated value at rated output real power. Figure 11 shows the steady-state characteristics of maximum voltage variations versus long-shunt capacitance at unity and.9 lagging power factor loads. The long-shunt connections has the voltage variation of zero per cent is observed at rated output power and speed with shunt capacitance =54µF, series capacitance lo =27 µf, no-load load voltage V NL =1pu at unity power factor load. For.9 lagging power factor load the long-shunt connections has the voltage variation of zero percent is observed at rated output power and speed with shunt capacitance =9µF, series capacitance lo =27µF, no-load load voltage V NL =1pu. Max. Voltage Variation (%) 1 8 6 4 2-2 -4-6 lo =27 µf, V NL =1 pu, Speed=15 rpm upf.9 lag 5 1 15 2 25 Shunt apacitance - (µf) VI. ONLUSIONS Genetic Algorithm is proposed to determine the steady-state performance of a self-excited induction generator with series compensation. The possibility of improving voltage regulation of the SEIG by using an additional capacitance in series with the load (short-shunt) or generator terminals (longshunt) has been investigated. Higher values of capacitances are required for long-shunt connection when compared to short-shunt connection. It is also observed that it is possible to obtain almost flat load voltage characteristics of the SEIG with short-shunt connection. Therefore, short-shunt connection can be used to improve the voltage regulation of the three-phase self-excited induction generator. AKNOWLEDGEMENTS The author gratefully acknowledges the support and facilities provided by the authorities of the Annamalai University, Annamalainagar, India to carry out this work. REFERENES Figure 11. Maximum voltage variation of long-shunt connection [1]. M. Abdulla, V.. Yung, M. Anyi, A. Kothman, K.B. Abdul Hamid & J. Tarawe, (21) Review and comparison study of hybrid diesel/solar/hydro/fuel cell energy schemes for rural IT Telecenter. Energy, Vol. 35, pp. 639-646. [2]. M. anale, L. Fagiano, M. Milanese & KiteGen, (29) A revolution in wind energy generation. Energy, Vol. 34, pp. 355-361. 379 Vol. 3, Issue 2, pp. 371-38

[3]. R. Pillai Indu & Baneerjee Ranjan, (29) Renewable energy in India: Status and potential analysis of self-excited induction generator including transformer saturation. Energy, Vol. 34, pp. 97-98. [4]. I. Dimitris, V. Spyros, S. Panos, S. Fotis, P. Simira & E. ostal, (28) The effect of the hysteresis band on power management strategies in a stand-alone power system. Energy, Vol. 33, pp.1537-155. [5]. T.F. han, (1993) Steady state analysis of self excited induction generators, Paper 93 SM 355-8 E, presented at the IEEE/PES 1993 Summer Meeting, Vancouver, anada. [6]. L. Shridhar, Bhim Singh &.S. Jha, (1994) Transient performance of the self regulated short shunt self excited induction generator, paper 94 SM 364- E, presented at the IEEE/PES 1994 Summer Meeting, San Francisco, A. [7]. Li Wang & Jian-Yi Su, (1997) Effects of Long-shunt and Short-shunt connections on voltage variations of a self-excited induction generator, IEEE Transactions on Energy onversion, Vol. 12, No. 4, pp. 368-374. [8]. Ahmed, T., Nishida, K., Soushin, K., & Nakaoka, M., (25) Static VAR compensator-based voltage control implementation of single-phase self-excited induction generator, IEE Proc Generation, Transmission and Distribution, Vol. 152, pp.145 156. [9]. Saif Mohd Ali Nasir, & Khan, B.H., (25) A simplified analysis of a constant voltage singlephase self-excited induction generator, Electric Power omponents and Systems, Vol. 33, pp.13 112. [1]. Tarek Ahmed, & Mutsuo Nakaoka, (24) Static VAr compensator based terminal voltage control for stand-alone ac and dc outputted self excited induction generator, IEE Proc. pp. 4-45. [11]. han, T.F., & Lai, L.L., (24) A novel excitation scheme for a stand-alone three-phase induction generator supplying single phase loads, IEEE Trans. on Energy onversion, Vol. 19, pp.136-142. [12]. Harish Kumar, & Neel Kamal. (211) Steady state analysis of self-excited induction generator, International Journal of Soft omputing and Engineering, Vol. 1, pp. 248-253. [13]. M.I. Mosaad, (211) ontrol of self excited induction generator using ANN based SV, International Journal of omputer Applications, Vol. 23, pp. 22-25. [14]. S. Singaravelu & S. Velusami, (27) apacitive VAr requirements for wind driven self-excited induction generators, Energy onversion and Management, Vol. 48, pp.1367-1382. [15]. S. Velusami & S. Singaravelu, (27) Steady-state modeling and fuzzy logic based analysis of wind driven single-phase induction generators, Renewable Energy, Vol. 32, pp.2386-246. [16]. M.E. Van Valkenburg, (1994) Network Analysis, Third Edition, Prentice Hall of India Pvt. Ltd., New Delhi. [17]. D.E. Goldberg, (21) Genetic algorithm in search, optimisation, and machine learning, Pearson Education, New Delhi. Authors S. Singaravelu received Bachelor of Engineering in Electrical and Electronics Engineering in 199, Master of Engineering in Power System Engineering in 1992 and Ph.D in 27 from Annamalai University, Annamalainagar, Tamilnadu, India. He is Associate Professor in the Department of Electrical Engineering at Annamalai University. His research interests are in power electronics, power systems, electrical machines, wind/solar energy applications and high voltage D transmission. S. Sasikumar received Bachelor of Engineering in Electrical and Electronics Engineering in 1999, Master of Engineering in Power System Engineering in 21 from Annamalai University, Annamalainagar, Tamilnadu, India. He is currently pursing Ph.D degree in the Department of Electrical Engineering, Annamalai University. He is Assistant Professor in the Electrical Engineering department at Annamalai University. His research interests are in electrical machines, power systems, control system and wind energy applications. 38 Vol. 3, Issue 2, pp. 371-38