1 16PESGM2316 Characterizing Transmission System Harmonic Impedances with R-X Loci Plots David Mueller
2 Transmission System Harmonics Studies In the US, the closure of older coal fired plants is a driver to new investments in static var compensators (SVC) Some SVC equipment still utilize harmonic filters Harmonic filters need to be analyzed for their interaction with the grid
3 US Power Grid Transmission grid models can be very large!
4 IEEE Standard 1031 (2011) IEEE Guide for the Functional Specification of Transmission Static Var Compensators the harmonic impedances should be plotted on an R/X diagram to provide the harmonic impedance sector for each harmonic.
5 Equivalent Study System Evaluating the SVC filter component ratings (from IEEE 1031, Annex B)
6 Frequency Scan Analysis Also referred to as driving point impedance 1 amp injection and evaluate the response 24 Mva 7% 24 Mva 7% 161 kv 24 Mva 7% 13.8 kv Bus1 13.8 kv 13.8 kv 9 Mva 3.0 Mvar 5.94% 1 A 60-3000 Hz 1.8 Mvar 4.16 kv
Impedance (ohm) 7 Example Frequency Scan Result High values ( peaks ) indicate parallel resonance conditions Low values ( valleys ) indicate series resonance Example - Impedance Scan at Bus 1 conditions 200 150 100 50 0 0 5 10 15 20 25 30 35 40 45 50 Frequency (h)
8 Representation of Loads There are many nuances to get correct results. [FromNode] Rt Lt One important aspect is the representation of loads. Rp Lp Rs Ls Parallel Component Series Component [ToNode]
Typical Transmission System Harmonic Model 9 This is generally done as a data import and conversion because a typical system may have: 340 two-winding transformers, 114 three-winding transformers, and 483 lines. Line charging capacitance values. 27 transmission system capacitor banks. 183 loads (for a total of 7433 MW and 1619 Mvar).
V o l t a g e ( V ) 10 Equivalent Source Damping At some point, even the large model is reduced with equivalent sources, which must be modified. 800 600 400 200 L a n d s to w n _ B a s e C a s e > 7 9 4.A ( 7 9 4 S C A ) L a n d s to w n _ E q S o u r c e _ D a m p i n g > 7 9 4.A ( 7 9 4 S C A ) Base Case With Source Equivalent Damping 0 0 10 20 30 40 50 F r e q u e n c y (H p u ) E le c tr o te k C o n c e p ts T O P, T h e O u tp u t P ro c e s s o r
11 Simulation Cases Generally a few hundred cases (489 in one study) are run that represent: Operating conditions. No outages are assumed, and the system resonances are affected mostly by the number of capacitor banks in service. Contingency conditions. A line, a transformer or a generator is out of service. Some cases include double contingency. For various cases, different load levels are studied.
12 System Contingencies are Also Evaluated Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Transformer 1 Transformer 2 Transformer 3
Case List Combinations 13
V o l t a g e ( V ) 14 Inductive Case Results Simple case to start with! 600 400 200 0 0 10 20 30 40 50 F r e q u e n c y ( H p u ) E le c tr o te k C o n c e p ts T O P, T h e O u tp u t P ro c e s s o r
V o l t a g e ( V ) 15 Adding Transmission Line Charging Capacitance Transmission line charging is a very important influence 600 400 200 0 0 10 20 30 40 50 F r e q u e n c y ( H p u ) E le c tr o te k C o n c e p ts T O P, T h e O u tp u t P ro c e s s o r
V o l t a g e ( V ) 16 Different Load Levels L a n d s to w n _ C a s e 2 > 7 9 4.A ( 7 9 4 S C A ) L a n d s to w n _ C a s e 3 > 7 9 4.A ( 7 9 4 S C A ) Many cases are run at light (10%) load levels 600 L a n d s to w n _ C a s e 4 > 7 9 4.A ( 7 9 4 S C A ) L a n d s to w n _ C a s e 5 > 7 9 4.A ( 7 9 4 S C A ) 500 400 300 200 100 0 0 10 20 30 40 50 F r e q u e n c y (H p u ) E le c tr o te k C o n c e p ts T O P, T h e O u tp u t P ro c e s s o r
17 R-X Plotting The resulting impedance from the scan cases are plotted together
2 nd Harmonic Results 18
3 rd Harmonic Results 19
4 th Harmonic Results 20
5 th Harmonic Results 21
7 th Harmonic Results 22
23 From IEEE 1031 Annex B IEEE 1031 Annex B Describing Search Areas
24 Psychology and Engineering Psychology has its Rorschach ink blot test, power engineering has R-X plots?
25 Conclusions Transmission system harmonic studies necessarily involve large, complicated models. Resonance involves conditions where X c =X r, so evaluation at boundary conditions is not sufficient. Correct line charging, equivalent source damping, and load representation are important.