University of Science and Technology, Sudan Department of Chemical Engineering.

Similar documents
Cascade Control of a Continuous Stirred Tank Reactor (CSTR)

Chemical Process Dynamics and Control. Aisha Osman Mohamed Ahmed Department of Chemical Engineering Faculty of Engineering, Red Sea University

ISSN: [Nehal* et al., 6(4): April, 2017] Impact Factor: 4.116

Index Accumulation, 53 Accuracy: numerical integration, sensor, 383, Adaptive tuning: expert system, 528 gain scheduling, 518, 529, 709,

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRONICS AND COMMUNICATION ENGINEERING

Index. INDEX_p /15/02 3:08 PM Page 765

Table of Laplacetransform

Feedback Control of Linear SISO systems. Process Dynamics and Control

MULTILOOP PI CONTROLLER FOR ACHIEVING SIMULTANEOUS TIME AND FREQUENCY DOMAIN SPECIFICATIONS

VALLIAMMAI ENGINEERING COLLEGE SRM Nagar, Kattankulathur

(b) A unity feedback system is characterized by the transfer function. Design a suitable compensator to meet the following specifications:

Advanced Control of the Waste Water Treatment Unit in White Nile Tannery

Guide to Selected Process Examples :ili3g eil;]iil

Solutions for Tutorial 10 Stability Analysis

CHAPTER 6 CLOSED LOOP STUDIES

Outline. Classical Control. Lecture 1

Root Locus Methods. The root locus procedure

Control System Design

STABILITY OF CLOSED-LOOP CONTOL SYSTEMS

Multi-Input Multi-output (MIMO) Processes CBE495 LECTURE III CONTROL OF MULTI INPUT MULTI OUTPUT PROCESSES. Professor Dae Ryook Yang

Improved Identification and Control of 2-by-2 MIMO System using Relay Feedback

6.1 Sketch the z-domain root locus and find the critical gain for the following systems K., the closed-loop characteristic equation is K + z 0.

7.4 STEP BY STEP PROCEDURE TO DRAW THE ROOT LOCUS DIAGRAM

Chapter 6 - Solved Problems

Theory of Machines and Automatic Control Winter 2018/2019

Digital Control Systems

Systems Analysis and Control

Contents. PART I METHODS AND CONCEPTS 2. Transfer Function Approach Frequency Domain Representations... 42

Design of de-coupler for an interacting tanks system

SRI VENKATESWARA COLLEGE OF ENGINEERING

Index. Index. More information. in this web service Cambridge University Press

Multi-Loop Control. Department of Chemical Engineering,

Some special cases

Process Modelling, Identification, and Control

Design and Tuning of Fractional-order PID Controllers for Time-delayed Processes

CHAPTER 10: STABILITY &TUNING

Closed-loop system 2/1/2016. Generally MIMO case. Two-degrees-of-freedom (2 DOF) control structure. (2 DOF structure) The closed loop equations become

Control Systems. University Questions

Compensation 8. f4 that separate these regions of stability and instability. The characteristic S 0 L U T I 0 N S

CHAPTER 7 : BODE PLOTS AND GAIN ADJUSTMENTS COMPENSATION

Feedback Control of Dynamic Systems

Systems Analysis and Control

Ch 14: Feedback Control systems

Robust and Optimal Control, Spring A: SISO Feedback Control A.1 Internal Stability and Youla Parameterization

Analysis of SISO Control Loops

Analysis and Synthesis of Single-Input Single-Output Control Systems

CHAPTER 5 ROBUSTNESS ANALYSIS OF THE CONTROLLER

Design of Decentralised PI Controller using Model Reference Adaptive Control for Quadruple Tank Process

Systems Engineering and Control

EC CONTROL SYSTEM UNIT I- CONTROL SYSTEM MODELING

Control System Design

3.1 Overview 3.2 Process and control-loop interactions

Possible Way of Control of Multi-variable Control Loop by Using RGA Method

Modeling and Control of Chemical Reactor Using Model Reference Adaptive Control

MAS107 Control Theory Exam Solutions 2008

IC6501 CONTROL SYSTEMS

Control of MIMO processes. 1. Introduction. Control of MIMO processes. Control of Multiple-Input, Multiple Output (MIMO) Processes

FEEDBACK and CONTROL SYSTEMS

Course Summary. The course cannot be summarized in one lecture.

MULTILOOP CONTROL APPLIED TO INTEGRATOR MIMO. PROCESSES. A Preliminary Study

MIMO Toolbox for Matlab

Course roadmap. Step response for 2nd-order system. Step response for 2nd-order system

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

ECSE 4962 Control Systems Design. A Brief Tutorial on Control Design

Lecture plan: Control Systems II, IDSC, 2017

Systems Analysis and Control

SRM UNIVERSITY DEPARTMENT OF BIOMEDICAL ENGINEERING ODD Semester DAY floor

Nyquist Stability Criteria

Lecture 5: Frequency domain analysis: Nyquist, Bode Diagrams, second order systems, system types

Process Modelling, Identification, and Control

Controls Problems for Qualifying Exam - Spring 2014

Additional Closed-Loop Frequency Response Material (Second edition, Chapter 14)

Richiami di Controlli Automatici

Control Systems I. Lecture 7: Feedback and the Root Locus method. Readings: Jacopo Tani. Institute for Dynamic Systems and Control D-MAVT ETH Zürich

ECE317 : Feedback and Control

Lecture 10: Proportional, Integral and Derivative Actions

Design and Comparative Analysis of Controller for Non Linear Tank System


Learn2Control Laboratory

Automatic Control Systems

Control Systems. EC / EE / IN. For

CHAPTER 7 FRACTIONAL ORDER SYSTEMS WITH FRACTIONAL ORDER CONTROLLERS

Digital Control: Summary # 7

Principles and Practice of Automatic Process Control

ECE317 : Feedback and Control

Computation of Stabilizing PI and PID parameters for multivariable system with time delays

FATIMA MICHAEL COLLEGE OF ENGINEERING & TECHNOLOGY

Control Systems I Lecture 10: System Specifications

CONTROL SYSTEMS LECTURE NOTES B.TECH (II YEAR II SEM) ( ) Prepared by: Mrs.P.ANITHA, Associate Professor Mr.V.KIRAN KUMAR, Assistant Professor

R a) Compare open loop and closed loop control systems. b) Clearly bring out, from basics, Force-current and Force-Voltage analogies.

CYBER EXPLORATION LABORATORY EXPERIMENTS

Robust Control 3 The Closed Loop

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Dr Ian R. Manchester Dr Ian R. Manchester AMME 3500 : Review

VALLIAMMAI ENGINEERING COLLEGE

Introduction to. Process Control. Ahmet Palazoglu. Second Edition. Jose A. Romagnoli. CRC Press. Taylor & Francis Group. Taylor & Francis Group,

ECE 486 Control Systems

ECE382/ME482 Spring 2005 Homework 7 Solution April 17, K(s + 0.2) s 2 (s + 2)(s + 5) G(s) =

Automatic Control (MSc in Mechanical Engineering) Lecturer: Andrea Zanchettin Date: Student ID number... Signature...

EEE 184 Project: Option 1

Transcription:

ISO 91:28 Certified Volume 3, Issue 6, November 214 Design and Decoupling of Control System for a Continuous Stirred Tank Reactor (CSTR) Georgeous, N.B *1 and Gasmalseed, G.A, Abdalla, B.K (1-2) University of Science and Technology, Sudan Department of Chemical Engineering. Abstract: To apply the methods of stability analysis and tuning, it is necessary first to develop a control strategy for possible noninteracting and interacting loops. Then the transfer functions were identified by mathematical modeling and the overall gains were cited from the literature. Pairing of the loops were undertaken and the interact in loops were coupled according to the RGA (Relative Gain Array), thus the loops with minimal interaction were selected and put in block diagrams. The characteristic equations were obtained for both closed and open loops. An exothermic reaction in a continuous stirred tank reactor (CSTR) was selected as a case study. The loops were subjected to tuning, stability and offset investigation. Summary of the adjustable parameters, offsets and response behavior were tabulated for comparison between the methods. It is clear that all the methods are in agreement, but the Bode criteria showed a superior consistency over other methods. It is recommended that the method of Bode has to be preferentially selected for tuning and stability analysis. Index Terms: Methods of tuning, Stability, Transfer function identification, Offset investigation. I. INTRODUCTION A control system is composed of interacting loops and that the number of feasible alternative configurations needed to be configured are very large. It must be recognized that for a process with n controlled variables and n manipulated variables there are n different ways to form control the loops [1]. The question is which one to selected? The answer is to consider the interaction between the loops for all n loops and then the RGA is applied to select a loop when the interaction is minimal. The RGA provides such a methodology by pairing the input and output that give minimum interaction when together coupled, RGA was first proposed by Bristol and today it is a very popular tool for selection of control loops giving minimal interaction [1].The methods of pairings and the RGA were applied to an exothermic reaction in a jacketed CSTR, the process is a 2 2 controlled and manipulated variables. The method of stability and tuning were applied using Routh-Hurwitz, direct substitution, root-locus, and Bode and Nyquist criteria. II. OBJECTIVES 1- To select the loops with minimal interaction in CSTR. 2- To study the dynamics of a CSTR. 3- To investigate the methods of tuning and stability analysis. 4- To compare the accuracy of these methods with respect to stability, adjustable parameters and offset. III. LITERATURE REVIEW Multiple input, multiple output (MIMO) systems describe processes with more than one input and more than one output which require multiple control loops. Examples of MIMO systems include heat exchangers, chemical reactors, and distillation columns. These systems can be complicated through loop interactions that result in variables with unexpected effects. Decoupling the variables of that system will improve the control of that process [2]. An example of a MIMO system is a jacketed CSTR in which the formation of the product is dependent upon the reactor temperature and feed flow rate. The process is controlled by two loops, a composition control loop and a temperature control loop. Changes to the feed rate are used to control the product composition and changes to the reactor temperature are made by increasing or decreasing the temperature of the jacket. However, changes made to the feed would change the reaction mass, and hence the temperature, and changes made to temperature would change the reaction rate, and hence influence the composition. This is an example of loop interactions. Loop interactions need to be avoided because changes in one loop might cause destabilizing changes in another loop [2]. To avoid loop interactions, MIMO systems can be decoupled into separate loops known as single 9

ISO 91:28 Certified Volume 3, Issue 6, November 214 input, single output (SISO) systems. Decoupling may be done using several different techniques, including restructuring the pairing of variables, minimizing interactions by detuning conflicting control loops, opening loops and putting them in manual control, and using linear combinations of manipulated and/or controlled variables. If the system can t be decoupled, then other methods such as neural networks or model predictive control should be used to characterize the system [2,3,4]. There are two ways to see if a system can be decoupled. One way is with mathematical models and the other way is a more intuitive educated guessing method. Mathematical methods for simplifying MIMO control schemes include the relative gain array (RGA) [2]. The RGA provides a quantitative approach to the analysis of the interactions between the controls and the output, and thus provides a method of pairing manipulated and controlled variables to generate a control scheme. The RGA is a normalized form of the gain matrix that describes the impact of each control variable on the output, relative to each control variable's impact on other variables. The process interaction of open-loop and closed-loop control systems are measured for all possible input-output variable pairings [5]. A ratio of this open-loop gain to this closed-loop gain is determined and the results are displayed in a matrix. The array will be a matrix with one column for each input variable and one row for each output variable in the MIMO system [5]. The best pairing is discovered by taking the maximum value of RGA Matrix for each row. A digital computer can be used to control simultaneously several outputs, the control program is composed of several subprograms, each one used to control a different loop. Furthermore, the control program should be able to coordinate the execution of the various subprograms so that each loop and all together function properly [6]. Although a controller may be stable when implemented as an analog controller, it could be unstable when implemented as a digital controller due to a large sampling interval. During sampling the aliasing modifies the cutoff parameters. Thus the sample rate characterizes the transient response and stability of the compensated system, and must update the values at the controller input often enough so as to not cause instability. When substituting the frequency into the z operator, regular stability criteria still apply to discrete control systems. Nyquist criteria apply to z-domain transfer functions as well as being general for complex valued functions. Bode stability criteria apply similarly. Jury criterion determines the discrete system stability about its characteristic polynomial [6]. The system stability can be tested by considering its response to a finite input signal. This means the analysis of system dynamics in the actual time domain which is usually cumbersome and time consuming. Several methods have been developed to deduce the system stability from its characteristic equation. They are short-cut methods for providing information without finding out the actual response of the system. They give information from the s-domain without going back to the actual time-domain. All these methods are based on the criterion that a sufficient condition for stability of a control loop is to have a characteristic equation with only negative real roots and or complex roots with negative real parts. The short-cut methods for assessment of the stability of a system include the direct method, the Routh Hurwitz stability criterion and graphical methods of investigating the behavior of the roots of the characteristic equation, i.e. Root Locus method and Nyquist stability criterion. Bode plots are common graphical method. It depends only upon the open loop transfer function (OLTF). The OLTF relates the feedback or measured variable to the set point, when the feedback loop is disconnected from the comparator when the loop is broken or opened. IV. RESULTS AND DISCUSSION Interaction, coupling and control of CSTR Consider a process with two controlled outputs and two manipulated inputs (Figure 1.). The transfer functions are: 1.G C1(s) = K C1,.(1) 2.G C2(s) = K C2,.(2) 3.G f1(s) =,.(3) 1

ISO 91:28 Certified Volume 3, Issue 6, November 214 4.G f2(s) =,.(4) 5.G m1(s) =,.(5) 6.G m2(s) =,.(6) 7. H 11(s) =,.(7) 8.H 12(s) =,.(8) 9.H 21(s) =,.(9) 1.H 22(s) =..(1) Loop 1 G m1(s) - G C1(s) G f1(s) H 11,sp + + + H 21 H 12 G,sp + - C2(s) G f2(s) + + H 22 Loop 2 G m2(s) Fig 1. Block diagram of CSTR with two controlled outputs and two manipulative variables. The Routh Hurwitz stability criterion is used for determination the stability of a system, the characteristic equation of closed loop is used. Also Bode plots, root-locus method and Nyquist stability criterion are used for determination the stability of a system, the OLTF is used. The amplitude ratio (AR) is used to get the ultimate gain(k U ) and Ziegler-Nichols tuning is brought to edge of stability under proportional control and it is used for tuning the adjustable parameters, which are substituted in overall gains for study the response. Loop 1 is closed and loop 2 is open, the transfer function is:.(11).(12) 11

Amplitude ISO 91:28 Certified Volume 3, Issue 6, November 214.(13) The characteristic equation of closed loop is:.15 s 4 +1.45s 3 + 3.85 s 2 +3.6 s + (1+ K C1 ) =.(14) Putting the characteristic equation in Routh Array: Table 1: Routh-Hurwitz Array S 4.15 3.85 (1+ K C1 ) S 3 1.45 3.6 S 2 3.4776 (1+ K C1 ) S 1 (3.183-.417 K C1 ) S (1+ K C1 ) For the system to be critically stable: (3.183-.417 K C1 ) =, K C1 = K U1 = 7.633, The system become stable for all values of K C1 K U1 7.633. The auxiliary equation is1.45s 3 +3.6 s =, s= iω; ω co = 1.5757 rad / sec; Pu = = = 3.99 sec. Tuning: Applying Ziegler- Nichols method ( Z-N method): Table 2: Z-N adjustable parameters for loop 1 Controller mode K C1 τ I ( sec) τ D ( sec) P 3.8165 - - PI 3.4349 3.325 - PID 4.5798 1.995.4988 Substituting the value of K C1 = 3.8165 of proportional controller (P- action) in characteristic equation,.15 s 4 +1.45s 3 + 3.85 s 2 +3.6 s + 4.8165= and in first column of Routh array. All elements of the first column were positive and there is no change of sign, therefore the system is stable. Response: Substituting the value of K C1 in the transfer function of loop1 (G (s) ) and introducing an impulse forcing function: 1 Peak amplitude:.849 At time (seconds): 1.12.5 Settling time (seconds): 16.9 -.5 5 1 15 2 25 3 Fig 2. Impulse response when loop1 is closed. 12

Amplitude Phase (deg) Magnitude (db) ISO 91:28 Certified Bode analysis and tuning: Open loop transfer function (OLTF) of loop 1is: Volume 3, Issue 6, November 214.(15) Bode Diagram -5-1 -15-2 -25-9 -18 Frequency (rad/s): 1.58 Phase (deg): -18-27 -36 1-2 1-1 1 1 1 1 2 1 3 Frequency (rad/s) Fig 3. Bode diagram when loop1 is open From Bode diagram, ω co =1.58 rad /sec and the amplitude ratio (AR)= 1, Pu = = 3.98 sec, the amplitude ratio (AR) is used to get K C1. 1=.(16) Substituting the value of ω co = 1.58 rad / sec in the equation to get K C1,K C1 = K U1 = 7.9962 Response: For K c1 = 3.9981 1.8.6 Peak amplitude:.886 At time (seconds): 1.11.4.2 Settling time (seconds): 18.9 -.2 -.4 -.6 5 1 15 2 25 3 Fig 4.Impulse response when loop1 is closed. 13

Imaginary Axis Amplitude Imaginary Axis (seconds -1 ) Root Locus: ISO 91:28 Certified Volume 3, Issue 6, November 214 15 Root Locus 1 5-5 Gain: 7.52 Pole: -.429 + 1.57i Damping:.273 Overshoot (%): 99.1 Frequency (rad/s): 1.57-1 -15-2 -15-1 -5 5 1 15 Real Axis (seconds -1 ) Fig 5.Root-Locus diagram when loop1 is open From root-locus diagram, ω co = 1.57 rad / sec and the amplitude ratio (AR) = 1, K C1 = K U1 = 7.8939 Response: For K c1 = 3.9469 1.8.6 Peak amplitude:.875 At time (seconds): 1.11.4.2 Settling time (seconds): 18.8 -.2 -.4 -.6 5 1 15 2 25 3 Fig 6. Impulse response when loop1 is closed. Nyquist stability criterion:.8 Nyquist Diagram.6.4.2 Real: -.132 Imag:.326 Frequency (rad/s): -1.58 -.2 -.4 -.6 -.8-1 -.5.5 1 1.5 Real Axis Fig 7. Nyquist diagram when loop1 is open From Nyquist diagram, ω co = 1.58 rad / sec.the characteristic equation of closed loop is:.15 s 4 +1.45s 3 + 3.85 s 2 +3.6 s + (1+ K C1 ) =.(14).15 ω 4-1.45 iω 3-3.85 ω 2 +3.6 iω + (1+ K C1 ) =.(17) 14

Amplitude ISO 91:28 Certified Volume 3, Issue 6, November 214.15 ω 4-3.85 ω 2 + (1+ K C1 ) =.(18) Substituting the value of ω co = 1.58 rad / sec to get K C1, K C1 = K U1 = 7.6763 Response: For K c1 = 3.8382 1 Peak amplitude:.854 At time (seconds): 1.12.5 Settling time (seconds): 16.9 -.5 5 1 15 2 25 3 Fig 8. Impulse response when loop1 is closed Table 3: Comparison between the methods for continuous stirred tank reactor ( CSTR ) of loop1 Method K U P U (sec) K C Routh- 7.633 3.99 3.8165 -.276 Durwitz Bode 7.9962 3.98 3.9981 -.21 Root-Locus 7.8939 4. 3.9469 -.221 Nyquist 7.6763 3.98 3.8382 -.267 Table 4: Comparison between the methods for continuous stirred tank reactor ( CSTR ) of loop1 Method Overshoot Rise Settling time(sec) time(sec) Routh-Durwitz.849 1.12 16.9 Bode.886 1.11 18.9 Root-Locus.875 1.11 18.8 Nyquist.854 1.12 16.9 Loop 2 is closed and loop 1 is open, the transfer function is:.(19) The characteristic equation is:.4 S 5 + 2.4 s 4 +5.7s 3 + 7.1 s 2 +4.4 s + (1+ 2K C2 ) =.(2) The preceding procedure is applied. Table 5: Routh-Hurwitz Array S 5.4 5.7 4.4 S 4 2.4 7.1 (1+ 2K C2 ) S 3 4.5167 (4.23-.33K C2 ) S 2 (4.85+.18 K C2 ) (1+ 2K C2 ) 15

Phase (deg) Magnitude (db) Amplitude ISO 91:28 Certified Volume 3, Issue 6, November 214 S 1 ( ) S (1+2 K C2 ) K U2 = 1.629, ω co =.96 rad / sec, Pu = = 6.94 sec, K C2 =.815. Response: For K c2 =.815.5.4.3 Peak amplitude:.37 At time (seconds): 1.75.2.1 Settling time (seconds): 22.9 -.1 -.2 5 1 15 2 25 3 35 Fig 9. Impulse response when loop2 is closed Bode analysis and tuning: Open loop transfer function (OLTF) of loop 2is:.(21) 5 Bode Diagram -5-1 -15-2 -9-18 Frequency (rad/s):.96 Phase (deg): -18-27 -36-45 1-2 1-1 1 1 1 1 2 Frequency (rad/s) Fig 1. Bode diagram when loop2 is open 16

Amplitude Imaginary Axis (seconds -1 ) Amplitude ISO 91:28 Certified Volume 3, Issue 6, November 214 From Bode diagram, ω co =.96 rad / sec, Pu = = 6.9379 sec, and the amplitude ratio (AR) = 1=.(22) K C2 = K U2 = 1.654. Response : For K c2 =.827.5.4.3 Peak amplitude:.371 At time (seconds): 1.75.2.1 Settling time (seconds): 23 -.1 -.2 5 1 15 2 25 3 35 Fig 11. Impulse response when loop2 is closed Root Locus: 6 Root Locus 4 2 Gain: 1.64 Pole:.626 +.99i Damping: -.689 Overshoot (%): 12 Frequency (rad/s):.99-2 -4-6 -8-6 -4-2 2 4 Real Axis (seconds -1 ) Fig 12. Root-Locus diagram when loop2 is open From root-locus diagram, ω co =.99 rad / sec and the amplitude ratio (AR) = 1, K C2 = K U2 = 1.6141. Response: For K c2 =.871.5.4.3 Peak amplitude:.373 At time (seconds): 1.75.2.1 Settling time (seconds): 23 -.1 -.2 5 1 15 2 25 3 35 Fig 13. Impulse response when loop2 is closed 17

Amplitude Imaginary Axis ISO 91:28 Certified Nyquist stability criterion: Volume 3, Issue 6, November 214 2 Nyquist Diagram 1.5 1.5 Real: -.62 Imag:.572 Frequency (rad/s): -.96 -.5-1 -1.5-2 -1 -.5.5 1 1.5 2 2.5 Real Axis Fig 14. Nyquist diagram when loop2 is open From Nyquist diagram, ω co =.96rad / sec, The characteristic equation is:.4 S 5 + 2.4 s 4 +5.7s 3 + 7.1 s 2 +4.4 s + (1+2K C2 ) =, 2.4 ω 4-7.1 ω 2 + (1+2K C2 ) =, Substituting the value of ω co =.96 rad / sec to get K C2.K C2 = K U2 = 1.654. Response : For K c2 =.827.5.4.3 Peak amplitude:.371 At time (seconds): 1.75.2.1 Settling time (seconds): 23 -.1 -.2 5 1 15 2 25 3 35 Fig 15. Impulse response when loop2 is closed Table 4. Comparison between the methods for continuous stirred tank reactor ( CSTR ) of loop2 Method K U P U (sec) K C Routh-Durwitz 1.629 6.94.815 -.3842 Bode 1.654 6.94.827 -.3838 Root-Locus 1.6141 6.91.871 -.3825 Nyquist 1.654 6.94.827 -.3838 Table 5. Comparison between the methods for continuous stirred tank reactor ( CSTR ) of loop2 Method Overshoot Rise time(sec) Settling time(sec) Routh-Durwitz.37 1.75 22.9 Bode.371 1.75 23 Root-Locus.373 1.75 23 Nyquist.371 1.75 23 18

ISO 91:28 Certified Relative Gain Array (RGA): Volume 3, Issue 6, November 214 The ratio between the two loop gain is λ 11, λ 11 = =.(23) λ 11 =.(24) s, λ 11 = -.667, λ 12 = 1+.667= 1.667. = λ 11 = -.667<,, then m 2 cause a strong effect on y 1 and in the opposite direction from that caused by m 1. In this interaction effect is very dangerous and must be avoid pairing m 1 with y 2. Nomenclature Symbols K U Ultimate gain P U Ultimate period(sec) K C Controller gain Offset Indices C Refer to controller f Refer to valve m Refer to measuring element 1 Refer to loop1 19

2 Refer to loop2 ISO 91:28 Certified Volume 3, Issue 6, November 214 V. CONCLUSION It is clear that all the methods are in agreement, but the Bode criterion has to be preferentially selected for tuning and stability analysis. For CSTR, λ 11 = -.667, then m 2 cause a strong effect on y 1 and in the opposite direction from that caused by m 1. In this interaction effect is very dangerous. ACKNOWLEDGMENT The authors wish to thank the Collage of Higher Studies and Research of Karary University for their help and for giving us opportunity for carrying out research in partial fulfillment for Ph.D in Chemical Engineering. REFERENCES [1] Stephanopoulos, G. (25), Chemical Process Control, Prentice-Hall, India. [2] Tham, M.T. (1999). "Multivariable Control: An Introduction to Decoupling Control". Department of Chemical and Process Engineering, University of Newcastle upon Tyne. [3] McMillan, Gregory K. (1983) Tuning and Control Loop Performance. Instrument Society of America. ISBN -87664-694-1. [4] Lee, Jay H., Choi, Jin Hoon, and Lee, Kwang Soon. (1997). "3.2 Interaction and I/O Pairing". Chemical Engineering Research Information Center. [5] Berber, Ridvan. (1994).Methods of Model Based Process Control, Kluwer Academic Publishers. [6] FRANKLIN, G.F.; POWELL, J.D. (1981). Digital control of dynamical systems. USA, California: Addison-Wesley. ISBN -21-8254-4. 2