ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE

Similar documents
Increasing Transmission Capacities with Dynamic Monitoring Systems

Dynamic Line Rating for overhead lines V6

APPLICATION OF A LINE AMPACITY MODEL AND ITS USE IN TRANSMISSION LINES OPERATIONS

First South East European Regional CIGRÉ Conference, Portoroz 2016 P23. Application of an Ice-Alarm in the OTLM System

Temperature calculations and LiDAR positions

A technique for simultaneous parameter identification and measurement calibration for overhead transmission lines

Guide for Application of Direct Real-Time Monitoring Systems

Paper No Advanced prevention against icing on high voltage power lines

elgian energ imports are managed using forecasting software to increase overall network e 칁 cienc.

Alexander Abboud, Jake Gentle, Tim McJunkin, Porter Hill, Kurt Myers Idaho National Laboratory, ID USA

Incorporating Dynamic Line Ratings to Alleviate Transmission Congestion, Increase Wind Resource Utilization, and Improve Power Market Efficiency

Area-wide dynamic line ratings based on weather measurements

Composite Conductor Field Trial Summary Report: Western Area Power Administration Phoenix

A Model for Calculating ACCC Resistance Based on Fit Method

Tennessee Valley Authority. Thermal Assessment of Existing 161kv & 500kv Transmission Lines

Comparison of ice accumulation on simplex and duplex conductors in parallel overhead transmission lines in Iceland.

High Temperature Overhead Conductor Rating Considerations

Faculty of Health, Engineering & Sciences. Dynamic Conductor Ratings: Annealing Properties of Homogenous

Thermal Analysis by Conduction Convection and Radiation in a Power Cable

Experimental study of dynamic thermal behaviour of an 11 kv distribution transformer

Analysis on Ampacity of Overhead Transmission Lines Being Operated

Reducing Contingency-based Windfarm Curtailments through use of Transmission Capacity Forecasting

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

Chapter 16 Temperature and Heat

The Study of Overhead Line Fault Probability Model Based on Fuzzy Theory

Overhead lines. 110 kv wood tower with guy wires

A Novel Approach for Increasing the Reliability of Power Transmission Lines in Galloping Conditions

Figure 1. Daily variation of air temperature

Probabilistic Weather Forecasting for Dynamic Line Rating Studies

Power transfer capacity improvements of existing overhead line systems

Dynamic Simulation on a Broken Test of Conductors

188 Equating the moments of above two forces about point O, we get, T y = w x x or y = w x T The maximum dip (sag) is represented by the value of y at

Short description CTC V.6.2. Current and temperature calculations of overhead conductors.

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

What Is the Actual Conductor Temperature on Power Lines

THERMAL ANALYSIS OF UMBILICAL CABLES

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

P1 Quick Revision Questions. P1 for AQA GCSE examination 2018 onwards

Building predictive models for dynamic line rating using data science techniques

Calculation of Magnetic Field Produced by OHTL under Normal and Abnormal Conditions

Modern techniques of ice-load assessment and icing maps creation for the design of overhead transmission lines used in the Russian Federation

Feasibility of HTS DC Cables on Board a Ship

URD Cable Fault Prediction Model

SURVEYING 1 CE 215 CHAPTER -2- EXAMPLES and PROBLEMS

THERMAL BEHAVIOR OF DISTRIBUTION TRANSFORMERS IN SUMMERTIME AND SEVERE LOADING CONDITIONS

Experimental analyses for the determination of lifetime expectancy of transmission line conductors

Real-time Monitoring of Leakage Current on Insulating Cross-arms in Relation to Local Weather Conditions

The influence of solar radiation on the distribution of temperatures in historic masonry

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

Modern SLMs are very stable and shouldn t drift this much

ANALYSIS OF THERMAL STRESSES OF SOLAR PARABOLIC TROUGH COLLECTOR FOR SOLAR POWER PLANT BY FEM

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Composite Conductor Field Trial Summary Report: Western Area Power Administration FARGO

Studnice Test Station (EGÚ Brno)

Ampacity simulation of a high voltage cable to connecting off shore wind farms

The WOLF system: forecasting wet-snow loads on power lines in Italy

A TEST OF THE PRECIPITATION AMOUNT AND INTENSITY MEASUREMENTS WITH THE OTT PLUVIO

THE EFFECT OF UNBALANCED LOADS IN DISTRIBUTION TRANSFORMERS AND GROUND NETWORK ON ELECTROMAGNETIC FIELDS

Meteorological Instruments for Solar Energy

Chapter 2 Experimental Studies on Hygrothermal Behaviour of ETICS

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Energy flows and modelling approaches

DYNAMIC RATING OF TRANSMISSION LINES FOR IMPROVED WIND ENERGY INTEGRATION IN COMPLEX TERRAIN

Determination of current load of ACSR conductor based on average climatic conditions

SUBJECT AREA(S): science, math, solar power, visible light, ultraviolet (UV), infrared (IR), energy, Watt, atmospheric conditions

Calibration of Paroscientific Model 205 Pressure Sensor for use at Heard Island.

Estimation of Current Transformer Insulation Life with an Effect of Environmental Variables

Lecture 3: Light and Temperature

APPENDIX A DEFINITIONS, NOTATIONS, AND SI CONVERSION FACTORS

3.2 Wind direction / wind velocity

Unit 11 Wire Tables and Conductor Sizes

MICROENCAPSULATED PHASE CHANGE MATERIALS (PCM) FOR BUILDING APPLICATIONS

Chapter 16 Temperature and Heat

Current Lead Optimization for Cryogenic Operation at Intermediate Temperatures. L. Bromberg, P.C. Michael, J.V. Minervini and C.

APPLICATION OF THE FINITE ELEMENTS METHOD FOR THE DESIGN OF NEW CLAMPS FOR GTACSR CONDUCTORS

PRESENT PROBLEMS OF POWER SYSTEM CONTROL

Lecture Outlines Chapter 16. Physics, 3 rd Edition James S. Walker

The influence of thermal properties on power transmission characteristics of HVDC cables a factor analysis

Politecnico di Torino THERMAL ANALYSIS OF POWER LINES: METHODOLOGIES AND APPLICATIONS

Citation for the original published paper (version of record): N.B. When citing this work, cite the original published paper.

HTS Cable Integration into Rural Networks with Renewable Energy Resources

Seasonal & Daily Temperatures

Santhosh Kumar BVMP ABB GISL Chennai, India

PREDICTION OF TEMPERATURE VARIATIONS FOR INDUSTRIAL BUS DUCT SYSTEM UNDER FORCED CONVECTION COOLING WITH VARIOUS ASPECT RATIOS USING MATLAB

EXPERIMENTAL MEASUREMENTS ON TEMPERATURE GRADIENTS IN CONCRETE BOX-GIRDER BRIDGE UNDER ENVIRONMENTAL LOADINGS

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kv XLPE Cable

Meteorology 432. Barometry Spring 2013

Which expression gives the elastic energy stored in the stretched wire?

EXPERIMENTAL CHARACTERIZATION OF OVERHEAD ELECTRICAL LINE CONDUCTORS AFTER ANODIC OXIDATION

Strain Measurement. Prof. Yu Qiao. Department of Structural Engineering, UCSD. Strain Measurement

Ice, Ice PV! Investigation Worksheet Answers

HOTTEST SPOT AND LIFE EVALUATION OF POWER TRANSFORMER DESIGN USING FINITE ELEMENT METHOD

Aerial Power Cables Profile, Sag and Tension Calculations Jorge R. López, MSME, PE José A. López, MSCE, PE

Alectra Utilities List of Station Capacity

The linear mirror a cheap and simple solar concentrating system

Coupled Electromagnetic and Thermal Field Modeling of a Laboratory Busbar System

Coupled electromagnetic, thermal and stress analysis of large power electrical transformers

OPPA European Social Fund Prague & EU: We invest in your future.

Glossary Innovative Measurement Solutions

5. AN INTRODUCTION TO BUILDING PHYSICS

Transcription:

23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 ANALYSIS OF DIFFERENT DYNAMIC LINE RATING SYSTEM CONFIGURATIONS IN A DISTRIBUTION LINE Jon G. OLAZARRI, A. Javier MAZON, Elvira FERNANDEZ, Igor ALBIZU, Miren T. BEDIALAUNETA University of the Basque Country UPV/EHU Spain jongotzon.olazarri@ehu.eus, javier.mazon@ehu.eus, elvira.fernandezh@ehu.eus, igor.albizu@ehu.eus, miren.bedialauneta@ehu.eus ABSTRACT Different dynamic line rating systems have been developed for monitoring overhead lines. The aim of these systems is to estimate the actual rating of electric lines and use all the available capacity to achieve a more efficient use of the existing lines. Some systems have been installed in a distribution pilot line to evaluate the different uncertainty levels. Systems that measure weather parameters, conductor temperature and tension are assessed. The results show that in conductor temperature and tension based systems the uncertainty decreases as the conductor temperature increases. INTRODUCTION The static ratings of the distribution overhead lines are calculated with conservative weather condition values (low wind speed, high ambient temperature, high solar radiation). Dynamic line rating (DLR) systems provide the system operators with information about the actual rating of the lines. There are several DLR system technologies. Some systems are based on weather measurement: standard commercial sensors for ambient temperature, wind speed and solar radiation are located close to the line or existing weather stations are used. Other systems are based on direct measurements of the conductor temperature, tension and sag. Furthermore, the DLR systems are usually a combination of direct measurements and weather measurements. When a DLR system is chosen both the cost and the uncertainty are taken into account. The aim of this paper is to evaluate the uncertainty of different DLR systems, including direct tension and conductor temperature measurement based DLR systems and weather based DLR systems. For this purpose, some systems have been installed in a distribution line. DYNAMIC LINE RATING AND OVERHEAD CONDUCTOR THERMAL AND MECHANICAL BEHAVIOUR The rating of a line is limited by a maximum allowable temperature and a sag limit that ensure safe operation as well as integrity of the conductor material. If the conductor reaches a higher temperature than the thermal limit, the involved risks are the loss of the properties of the conductor and a sag increase. Nowadays, ratings are fixed by conservative static values. Depending on the country and the technical rules, the ratings are seasonal or remain equal for a year. In all those cases the rating is calculated with heat balance equations. In these equations the influential parameters are the meteorological ones, due to the cooling and/or heating effect of the weather. Overhead conductor thermal model The CIGRÉ [1] and IEEE [2] thermal models are used to calculate the actual rating (also called dynamic line rating or ampacity) of overhead conductors. In the overhead lines, the weather influences the actual rating, thus, ampacities vary steadily. The common practice is to monitor the influential parameters and to use the measured values to calculate the ampacity with the model. Then, the rating is calculated by a heat balance equation, as shown in equation (1). Where P c is the convective cooling of the conductor, P r the radiative cooling, P s the solar heating and R ac the conductor resistance at its maximum allowable temperature. When the line is carrying a current equal to its actual rating, the joule heating and the convection cooling are the most influential. On the contrary, the radiative cooling effect is low compared to convective losses. The solar heating is low as well, especially in cloudy days and does not have influence during night. Conductor mechanical model The conductor mechanical model [3] is defined by the catenary equations of the span. Thereby, there is a relationship between tension, sag and temperature of a conductor. One of the equations used in the mechanical models and in this work is equation (2). (1) (2) Where L is the conductor lenght, L is the initial lenght, T and H are the stringing temperature and tension respectively, α the coefficient of linear expansion of the conductor, E is the elastic modulus and A the crosssectional area. CIRED 215 1/5

23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 INSTALLED MONITORING SYSTEMS The DLR systems have been installed in a 3 kv distribution line and measurements have been recorded with a sampling period of one minute. As it is shown in Figure 1, the installed monitoring system consists of: 1. System for measuring the conductor surface temperature and current (SMT, Arteche). 2. Ultrasonic anemometer for measuring the speed and the direction of the wind. 3. Solar radiation and ambient temperature sensors. 4. Load cell for measuring the value of the mechanical tension of the conductor. 4 2 1 Weather parameters based system These systems are cheap and cost-effective and have been used in several pilot projects [4,5]. The parameters measured are the wind speed and direction, ambient temperature and solar radiation. The actual rating is calculated directly, solving equation (1) (see Figure 2). Figure 2: DLR calculation process in weather system. Conductor temperature system There are several commercial devices to measure the conductor temperature [6,7]. This system does not record wind measurements, instead, the effective wind of the line is calculated with the thermal model. Conductor temperature, intensity, solar radiation and ambient temperature measurements are required to calculate the actual rating in two steps (Figure 3). In a first step, the effective wind is calculated with the thermal model. In a second step, the calculated wind and measurements of ambient temperature, and solar radiation are used to solve equation (1) and obtain the rating. 3 Figure 1: DLR systems installed in the pilot overhead line. During the monitoring period, the average ambient temperature was 9.5 ºC and the line carried an average intensity of 165 A. The measured mean wind speed is 1.51 m/s and the maximums 14 m/s. In most days wind speed increased in the afternoons reaching between 2 and 5 m/s. Although it is not a windy place, conductor temperatures were low (13.4 ºC average) due to the low temperature and low load. In the registered data, the solar heating has contributed a 15 % to the heating of the conductor, whereas the other 85 % has been due to the joule and magnetic heating of the conductor. The wind cooling was of 85 % and the radiative ones of 15 %. ANALYSED SYSTEMS The evaluated systems are the weather parameter based system, conductor temperature based system and tension based system. In the next paragraphs the calculations made in each step and the measured parameters are explained. Figure 3: DLR calculation process in conductor temperature system. Tension system Tension systems are based on the conductor tension measurements of load cells [8]. As the conductor temperature is related to tension and sag, it is possible to calculate the conductor mean temperature along the span solving equation (2). In a second step, the effective wind is calculated with the thermal model, as it is done in conductor temperature system. With the calculated wind and other measurements, the DLR is calculated with equation (1). A diagram of the calculation process can be seen in Figure 4. Figure 4: DLR calculation process in conductor tension system. CIRED 215 2/5

23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 DLR UNCERTAINTY RESULTS The ampacity uncertainty due to the instrument measurement inaccuracy has been evaluated for each system mentioned before. The DLR rating uncertainty level has been calculated as the difference between the maximum ampacity and the minimum ampacity. The accuracy of the instrumentation is summarized in Table 1. Table 1: Measurement sensor errors. Measured parameter Measurement error Wind speed 2% Wind direction 3º Ambient temperature 1ºC Solar radiation 5 % Conductor surface temperature 1ºC Intensity 2% Tension 2% Weather system uncertainty With weather parameter based system, the highest uncertainty in absolute terms is low, always under 4 A and with a mean value of 7,5 A (see Figure 5). In relative values, it does not exceed 1 % of the lowest DLR. The thermal model shows low sensitivity to instrumentation measurement errors. 14 125 1 75 5 23:6 23:21 7 DLR, maximum positive uncertainty (A) DLR, maximum negative uncertainty (A) Wind speed, positive uncertainty (m/s) 6 Wind speed, negative uncertainty (m/s) 5 Figure 6: maximum and minimum DLR and measured wind speed with uncertainty. Conductor temperature system uncertainty In conductor temperature system, the uncertainty values show a high dependence on the difference between the measured conductor surface temperature and the ambient temperature. The lower the difference between both temperatures the higher the uncertainty will be [9]. The wind is calculated with the thermal model and the error made in calculating the wind when the conductor temperature is similar to the ambient temperature can be high and this implies a high DLR uncertainty. For this reason and the fact that in the measured data the difference between conductor and ambient temperatures are low, the uncertainties obtained in the calculations are high (see Figure 7). 4 3 2 1 Wind speed (m/s) 12 1 8 14 12 1 6 4 8 6 4 2 2 5 1 15 2 25 3 35 4 Figure 5: Histogram of the DLR uncertainty in the weather system. The highest cooling type in a conductor is the convective cooling, and in this line, the computed convective losses represent the 85 % of the total refrigeration. The importance of wind in the refrigeration of an overhead conductor is evident and this can also be noticed in the uncertainty. In Figure 6, DLR with positive and negative wind measurement errors can be seen. The wind in the graphics has been calculated from the speed and direction measurements and it has been converted to an equivalent perpendicular wind speed. Although the ambient temperature and solar radiation uncertainties have been computed as well, the DLR uncertainty follows exactly the effective wind uncertainty. 1 2 3 4 5 6 Figure 7: Histogram of the DLR uncertainty with conductor temperature system. In Figure 8 DLR uncertainty can be seen. The ampacity uncertainty increases when the temperature difference between conductor and ambient temperature decreases. The available conductor temperature data ranges from -.5 to 42.4 ºC with an average value of 13.7 ºC, therefore it is not possible to assess the uncertainty at higher temperatures with actual data. However, the uncertainty out of this range can be calculated theoretically, increasing intensity and calculating the equivalent temperature with the thermal model. Then, with the new intensity and temperature, the DLR is calculated. In Figure 9, ampacity uncertainties are shown for different intensities. The curves are smoother than the DLR curves in Figure 8 because the model inputs have been averaged 15 minutes to see better the uncertainty in CIRED 215 3/5

23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 each case. 2 15 1 DLR, maximum negative uncertainty (A) DLR, maximum postive uncertainty (A) Difference between conductor and ambiente temperature ( C) 5 2.5 Temperature ( C ) In Figure 11 the tension-temperature curves for each coefficient and the measured values are shown. The new coefficient estimates better the conductor temperature at high temperatures. Between and 5ºC the calibration curve is more sensitive to measurement errors as can be seen in Figure 12. In that Figure, measured tension and maximum and minimum DLR are shown for the same period of time of Figures 6 and 8. In Figure 13, the histogram of the uncertainties is shown. 5 23:6 23:21 Figure 8: Maximum and minimum DLR and difference between conductor and ambient temperature. 9 8 7 6 5 4 3 2 1 3 x Measured intensity 2 x Measured intensity 1,4 x Measured intensity Measured intensity Conductor tension (kg) 46 44 42 4 38 36 34 Measurements Conductor tension, modified Conductor tension, theoretical 32 1 2 3 4 Conductor temperature ( C) Figure 11: Tension-temperature curves with theoretical and modified linear expansion coefficients. 23:6 23:21 Figure 9: Uncertainty levels for different intensities. In Figure 1 the histogram of uncertainty for 2 % of the measured intensity is shown. With this current increase the average conductor temperature is 39 ºC and the uncertainty has decreased notoriously, if it is compared to the measured histogram of Figure 7, in which the uncertainties are calculated with the measurements. 1 75 5 23:6 23:21 Tension (kg) DLR, maximum positive unceertainty (A) DLR, maximum negative unceertainty (A) 45 4 Tension (\kg ) 14 12 Figure 12: maximum and minimum DLR and tension measurements. 1 8 6 4 2 1 2 3 4 5 6 7 8 9 Figure 1: Histogram of the DLR uncertainty for a 2 % of measured intensity. Tension system uncertainty The theoretical relationship between the tension and temperature of a conductor is given in equation (2). However, the theoretical expansion coefficient does not show a good agreement between the recorded values and the calculated ones. Instead, it has been calculated another coefficient [1]. Figure 13: Histogram of the DLR uncertainty of the tension system. CONCLUSIONS A distribution pilot line with different DLR systems has been installed to evaluate their uncertainty level. Three different DLR systems have been evaluated. The first system measures weather magnitudes, the second CIRED 215 4/5

23 rd International Conference on Electricity Distribution Lyon, 15-18 June 215 Paper 176 measures conductor temperature and the third system measures conductor tension. The systems that measure conductor temperature and tension calculate the wind speed using the thermal model of the conductor and the measurements of other weather magnitudes and current intensity. The influence of the measurement instrumentation uncertainties on the ampacity uncertainty has been analysed. The influence depends on the load level of the line. The results show that in conductor temperature and tension based systems the ampacity uncertainty decreases as the conductor temperature increases with high load values. In these systems the ampacity uncertainty is related to the uncertainty of the calculated wind speed. The reason for the high ampacity uncertainty is the high sensitivity of the thermal model in the wind calculation when the differences between the conductor surface temperature and the ambient temperature are low. Acknowledgments This work is financially supported by the Ministerio de Economía y Competitividad under the project DPI213-4452-R and by the University of the Basque Country UPV/EHU under the Zabalduz programme. The authors would like to thank Iberdrola utility and Arteche for the help with the achievement of this project. REFERENCES [1] CIGRÉ Brochure 27, 22, Thermal behaviour of overhead conductors [2] IEEE Std. 738, 26, IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors [3] CIGRE Brochure 324, 27, Sag-tension calculation methods for overhead lines [4] M. Muhr, S. Pack, S. Jaufer, W. Haimbl, A. Messner, 28, Experiences with the Weather Parameter Method for the use in Overhead Line Monitoring Systems, 27, CIGRÉ Session, Paper B2-15 [5] F. Soto, D. Alvira, L. Martin, J. Latorre, J. Lumbreras, M. Wagensberg, 1998, Increasing the capacity of overhead lines in the 4 kv Spanish transmission network, CIGRÉ Session, 22-211 [6] J. S. Engelhardt, S. P. Basu, 1996, Design, installation, and field experience with an overhead transmission dynamic line rating system, IEEE Proceedings of Transmission and Distribution Conference, pp. 366-7 [7] Arteche: Temperature and current measurement sensor for high voltage lines, SMT, 29 [8] I. Albizu, E. Fernandez, P. Eguia, E. Torres, A. J. Mazon, 213, Tension and Ampacity Monitoring System for Overhead Lines, IEEE Transactions on Power Delivery, vol. 28, no. 1, pp. 3-1 [9] I. Albizu, E. Fernandez, A.J. Mazon, J. Bengoechea, 211, Influence of the conductor temperature error on the overhead line ampacity monitoring systems, IET Generation, Transmission& Distribution, vol. 5, no. 4, 44-447 [1] M.T. Bedialauneta, E. Fernandez, I. Albizu, A. J. Mazon, 212, Comparison of the theoretical and the actual behavior of an overhead conductor in operation, IEEE PES PowerAfrica 212, Johannesburg-South Africa CIRED 215 5/5