He II Heat transfer through a Corrugated Tube - Test Report

Similar documents
HE II HEAT EXCHANGER TEST UNIT FOR THE LHC INNER TRIPLET

Measurements of temperature on LHC thermal models

THERMOHYDRAULIC BEHAVIOUR OF HEII IN STRATIFIED CO-CURRENT TWO-PHASE FLOW AT HIGH VAPOR VELOCITIES

Supercritical Helium Cooling of the LHC Beam Screens

LHC HTS CURRENT LEADS

National Superconducting Cyclotron Laboratory Michigan State University, East Lansing, Michigan, 48823, USA

Available online at ScienceDirect. Physics Procedia 67 (2015 ) Superfluid helium heat pipe. P.

Kapitza resistance and thermal conductivity of Mylar at superfluid helium temperature

Thermal analysis of superconducting undulator cryomodules

EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH Laboratory for Particle Physics

Report Liquid Hydrogen Target for the COMPASS Experiment

Preliminary design of the new HL-LHC beam screen for the low-β triplets

Investigation of anomalous heat production in Ni-H systems

Vacuum. Residual pressure can thwart the best cryogenic design. Each gas molecule collision carries ~kt from the hot exterior to the cold interior.

THE CERN CRYOGENIC TEST FACILITY FOR THE ATLAS BARREL TOROID MAGNETS

Critical Current Properties of HTS Twisted Stacked-Tape Cable in Subcooled- and Pressurized-Liquid Nitrogen

CURRENT LEADS FOR THE LHC MAGNET SYSTEM

Semiconductor thermogenerator

Thermal design of the CFRP support struts for the spatial framework of the Herschel Space Observatory

Also with RWTH Aachen, Germany CEA / CENG, DRFMC SBT, 17 rue des Martyrs, F Grenoble Cedex 9, France

Very Large Hadron Collider - phase 2 Optimization of the beam screen cooling & Impact of the photon stop on the cryogenic system

13000 A HTS CURRENT LEADS FOR THE LHC ACCELERATOR: FROM CONCEPTUAL DESIGN TO PROTOTYPE VALIDATION

The LHC: the energy, cooling, and operation. Susmita Jyotishmati

Low Vibration Cryogenic Equipment

AE 3051, Lab #16. Investigation of the Ideal Gas State Equation. By: George P. Burdell. Group E3

IMPLEMENTATION OF ETHANOL HEAT PIPE AT CETIAT

Low Temperature Instrumentation: Detectors, Cooling Systems and Superconducting Magnets LOW TEMPERATURE INSTRUMENTATION - DDAYS

DEVELOPMENT AND PRODUCTION OF SUPERCONDUCTING AND CRYOGENIC EQUIPMENT AND SYSTEMS FOR ACCELERATORS BY IHEP

HIMARC Simulations Divergent Thinking, Convergent Engineering

Performance Testing of the Astro-H Flight Model 3-stage ADR

Russell B. Schweickart and Gary Mills

Cryogenic and Electrical Test Results of a 30 M HTS Power Cable

A PHOTON-STOP FOR THE VLHC-2 ENGINEERING DESIGN PART 1

Y.; Kobayashi, H.; Inatani, Y. Citation Physics Procedia (2015), 67: Right article under the CC BY-NC-ND

Grounding and Shielding

Frozen Spin Targets. In a Nutshell. Version 2.0. Chris Keith

Nonlinear Model Predictive Control for the Superfluid Helium Cryogenic Circuit of the Large Hadron Collider

Microscopy Cryostat System

Experimental Investigation of Hybrid System Pulse Tube and Active Magnetic Regenerator

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

4.1. Physics Module Form 4 Chapter 4 - Heat GCKL UNDERSTANDING THERMAL EQUILIBRIUM. What is thermal equilibrium?

Notkestraße 85, 22607, Hamburg, Germany

Chapter Four. Experimental

Impact of the forces due to CLIQ discharges on the MQXF Beam Screen. Marco Morrone, Cedric Garion TE-VSC-DLM

Magnetic Property Measurement System

High-Pressure Volumetric Analyzer

Ideal Gas Law. Name, Date, Partner Lab Section. Date, Partner and Lab Section

Beam heat load due to geometrical and resistive wall impedance in COLDDIAG

Vacuum Pumps. Two general classes exist: Gas transfer physical removal of matter. Mechanical, diffusion, turbomolecular

CERN, 1211 Geneva 23, Switzerland *Laboratoire des Signaux et Systèmes, UMR 8506 CNRS-Supélec, Gif-sur-Yvette, France

CRYOGENIC CONDUCTION COOLING TEST OF REMOVABLE PANEL MOCK-UP FOR ITER CRYOSTAT THERMAL SHIELD

Fermi National Accelerator Laboratory. Characterization of Two Phase Flow in a Fermilab Tevatron Satellite Refrigerator

HiLumi LHC FP7 High Luminosity Large Hadron Collider Design Study. Milestone Report. Cryogenic Scenarios for the Cold Powering System

EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH Laboratory for Particle Physics

EXPERIMENTAL ANALYSIS OF R-134a FLOW CONDENSATION IN A SMOOTH TUBE

CHEM 254 EXPERIMENT 7. Phase Diagrams - Liquid Vapour Equilibrium for two component solutions

Development of high-efficiency Stirling cryocoolers for high temperature superconducting motors

4.1. Physics Module Form 4 Chapter 4 - Heat GCKL UNDERSTANDING THERMAL EQUILIBRIUM. What is thermal equilibrium?

Schroeder, C., Walter, F., Marzouki, F., Stafiniac, A., Floch, E., Schnizer, P., Moritz, G., Xiang, Y., Kauschke, M., Meier, J., Hess, G.

Contribution to the study of neon-nitrogen mixtures at low temperatures

EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH CERN - ACCELERATORS AND TECHNOLOGY SECTOR

1074 IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, VOL. 21, NO. 3, JUNE 2011

Countercurrent heat exchanger

39th International Physics Olympiad - Hanoi - Vietnam Experimental Problem

(Refer Slide Time: 01:16)

Earlier Lecture. In the earlier lecture, we have seen non metallic sensors like Silicon diode, Cernox and Ruthenium Oxide.

Cryogenic Instrumentation I Thermometry OUTLINE Thermometry Pt (pure metal) Temperature Ranges of Thermometer Application Typical Resistive Thermal

1. Mark the correct statement(s)

GENERAL PHYSICS (3) LABORATORY PHYS 203 LAB STUDENT MANUAL

THE CHARGE-TO-MASS RATIO OF THE ELECTRON (e/m)

Introduction to Blackbody Sources

DETERMINATION OF R134A S CONVECTIVE HEAT TRANSFER COEFFICIENT IN HORIZONTAL EVAPORATORS HAVING SMOOTH AND CORRUGATED TUBES

Helium two-phase flow in a thermosiphon open loop

The Vacuum Case for KATRIN

High-temperature superconducting magnet for use in Saturated core FCL

Development of cryogenic silicon detectors for the TOTEM Roman pots

Gas Thermometer and Absolute Zero

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

Fall 2014 Nobby Kobayashi

Beam-induced heat loads on the beam screens of the inner triplets for the HL-LHC

Yeon Suk Choi \ Steven W. Van Sciver \ and Ho-Myung Chang u

On the Emissivity of Silver Coated Panels, Effect of Long Term Stability and Effect of Coating Thickness

Precise Thermometry for Next Generation LHC Superconducting Magnet Prototypes

UNIVERSITY OF CAMBRIDGE INTERNATIONAL EXAMINATIONS International General Certificate of Secondary Education

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

Available online at ScienceDirect. Physics Procedia 67 (2015 ) Calibration of a HTS based LOX 400mm level sensor

Investigation of Heat Transfer on Smooth and Enhanced Tube in Heat Exchanger

A 3 Vapor pressure of volatile liquids

To be published in the Proceedings of ICEC-22, Seoul Korea, July 2008 MICE Note 232 1

Sensitivity Estimation of Permanent Magnet Flowmeter

Beam-induced heating in the TOTEM Roman Pot detectors at the LHC

Experiment Ma8: Superconductivity

PLATE TYPE HEAT EXCHANGER. To determine the overall heat transfer coefficient in a plate type heat exchanger at different hot fluid flow rate

Application of the Multi-current Transient Hot-Wire Technique for Absolute Measurements of the Thermal Conductivity of Glycols

Hydraulic validation of the LHC cold mass heat exchanger tube.

Review of heat transfer mechanisms in superconducting magnets

Experiment 3. Electrical Energy. Calculate the electrical power dissipated in a resistor.

5CM, NO IRON SSC DIPOLE 12M MODEL CRYOSTAT THERMAL PERFORMANCE* R. J. Powers, J. D. Gonczy, J. Otavka, R. C. Niemann, A. Szymulanski, and J. L.

Condensation and Evaporation Characteristics of Flows Inside Three Dimensional Vipertex Enhanced Heat Transfer Tubes

Water Circuit Lab. The pressure drop along a straight pipe segment can be calculated using the following set of equations:

Transcription:

He II Heat transfer through a Corrugated Tube - Test Report Authors: Ch. Darve, Y. Huang, T. Nicol, T. Peterson Keywords: LHC inner triplet, heat exchanger, He II heat transfer, Kapitza resistance. Abstract The LHC inner triplet is cooled with pressurized He II at a temperature of around 1.9 K. The total heat load (beam induced heat load plus static heat load for the inner triplet) at nominal luminosity is around 180 W. The beam induced heat load distributed within the magnet coil is carried away by the static pressurized He II filling inside of the cold mass. A heat exchanger is needed to absorb the heat load within the pressurized He II to maintain the low temperature. The heat exchanger is located outside and parallel to the magnet cold mass. The saturated, two-phase He II flows inside the corrugated pipe and the static, pressurized He II surrounds the corrugated pipe. A full-sized Heat Exchanger Test Unit has been designed to simulate the LHC inner triplet cooling scheme. The test will be carried out at CERN in 2000. A small scale corrugated pipe He II heat exchanger was designed, built and tested at Fermilab. The goal of the test was to measure the thermal performance of the same corrugated pipe used for the full-sized He II Heat Exchanger Test Unit. The test sample is a closed test sample and consists of a corrugated pipe, a thick-wall stainless blank flange, detachable stainless steel flange and a matching flange. The corrugated pipe length in contact with the liquid helium is 100 mm. From the experimental data, including heat load to the test sample and temperatures inside and outside, the total heat transfer coefficient of the corrugated pipe can be determined. The test results show that the Kapitza thermal conductance is in good agreement with the results from other experiments. One more test will be carried out in the near future using the same test sample with some treatment of the corrugated pipe surface. 1 Introduction The LHC inner triplet operates in a pressurized He II bath at 1.9 K and 0.1 MPa. The heat load absorbed by the coils must be carried away by saturated He II via a heat exchanger to maintain the temperature of the pressurized He II at 1.9 K. The temperature drop across the heat exchanger may be estimated by using the Kapitza thermal resistance between the He II and copper surface. The Kapitza thermal resistance is strongly dependent on the surface material and surface treatment. Some measurements were needed to more accurately predict the total heat transfer coefficient of the proposed heat exchanger pipe. A first heat transfer model was developed in order to give dimensions to the Heat Exchanger Test Unit [1]. The initial value for overall conductance through the corrugated pipe in the heat transfer model considered up to now was scaled from very early CERN measurements of a corrugated pipe [2]. In order to measure the thermal performance of the corrugated pipe, a piece of corrugated pipe was cut from extra material purchased for the full-sized He II Heat Exchanger Test Unit and tested. The pressurized He II was contained inside the test sample and saturated He II was outside the test sample. The temperature differences between the pressurized He II (inside the test sample) and the saturated He II baths were measured at different heat loads. 1

2 Heat transfer model 2.1 Scheme of the thermal transfer The LHC inner triplet cooling scheme is based on heat exchange between the static pressurized He II and the saturated He II. Figure 1 illustrates heat transfer from the pressurized He II (T1: inside test sample) and saturated (T3: outside the test sample). The total thermal resistance is equal to the sum of the two Kapitza resistances at the interface, plus the resistance of the copper wall. Considering that both surfaces of the tube are wetted over their full length, the applied electrical load, Qelec, to the pressurized He II will generate a difference of temperature, T1-T3, across the copper wall. 2.2 Method of calculation Figure 1. Scheme of the heat transfer When the heat exchanger tube is wetted, the temperature difference between the pressurized helium and the saturated liquid, T1-T3, is minimal. This temperature difference depends only on the heat load, Qelec, and the total transverse thermal resistance, Rthtotal, which can be expressed as shown: T ( T1 T3) Rthtotal lim or Rthtotal T 0 Q Qelec If we consider the total resistance as a function of the Kapitza resistance, Rkap1 and Rkap2, and the copper conductance, Rcu, we can write: Rthtotal Rkap1 Rcu Rkap2 Within the tested low temperature range, we can consider that the bulk thermal resistance of the copper is constant. According to acoustic mistmatch theory, the Kapitza resistance should vary as T -3 [3]. We can make the hypothesis that both Kapitza resistances at each interface of the copper pipe and the He II pressurized and saturated, are equal to Rkapitza. In the current report we introduce the Kapitza coefficient Ckapitza which has units [WK -4 m -2 ]. The total thermal resistance can be expressed with the following formulas: Rthtotal If we consider that: α β 2. Rkapitza Rcu or Rthtotal α 2 Ckapitza. S e S. Ccu. 1 β T3 3 2

Then, it yields the equation (eq 1 ): Rthtotal 2. 1 e Ckapitza. S T3 3 S. Ccu where e is the wall thickness, S the interface surface, Ccu the copper thermal conductance and Ckapitza the Kapitza coefficient characterizing the interface. Thus, if we plot Rthtotal versus T -3, we obtain a straight line. Consequently, from the temperature difference, T1-T3, measured for a given T3 and various electrical load, Qelec, we can interpret the Kapitza coefficient, Ckapitza, and the thermal conductance of the copper, Ccu. Previous tests performed at CERN were also dedicated to the measurement of the Kapitza resistance and used this standard approach [4] [5]. eq 1 3 Small scale heat exchanger design The test sample, as shown in Figure 2, is composed of the same corrugated tube used in the Heat Exchanger Test Unit. The corrugated tube is made of industrial copper. The effective length of the corrugated tube is 100 mm and its outer diameter is 96 mm. The wall thickness is 0.7 mm. The corrugated tube surface area is 415.6 cm 2 (one side). The corrugated tube was soldered into the grooves of the thick-wall stainless steel flanges at both ends. Due to the lower thermal conductivity of soft solder in the grooves and thick-wall stainless steel flanges, the heat leak through the end flanges was estimated to be less than 3% of the total heat load applied to the heater. The Kapitza thermal resistance depends strongly on the surface material and conditions. The corrugated tube tested in our experiment has no chemical treatment, the same as that in the Heat Exchanger Test Unit. 4 Description of the test setup Figure 2. Corrugated tube testing device sample assembly The test setup is composed of a test dewar, pumping unit, vacuum pump, helium gas supply, and liquid helium supply. Figure 3 illustrates the schematic of the test system. The test sample is filled with pressurized He II and mounted with a resistive heater, level indicator, thermometer and pressure transducer. The saturated He II bath surrounding the test sample is used to maintain the bath temperature while absorbing any heat load from the test sample. There is also a thermometer on the saturated He II side to measure the bath temperature. The thermal transfer process is the same as in the real LHC heat exchanger. The dewar is 500 mm long and 500 mm ID. Pipe connections have been designed in order to fill the inner sample assembly with pressurized He II. The system minimizes parasitic leaks due to radiation, solid conduction, and conduction into superfluid helium. An electrical rack contains power supplies for the instrumentation and control as well as switches from the electronics. The data acquisition and control system was written in QuickBASIC. 3

Figure 3. Scheme of the cryogenic system 4.1 Instrumentation Several valves, indicators and sensors permit precise control of the measurements. The sensors include thermometers, helium level indicators, and pressure transducers, all mounted inside and outside. Two calibrated Lake-Shore Germanium thermometers (T1 and T3) are supplied with a 1µA current source. These sensors measure the temperature of the pressurized and the saturated He II. Both T1 and T3 are deduced from their respective Chebychev polynomial algorithms. Two helium level indicators LT1 and LT2 are supplied with a 75 ma current source. The pressure transducers PT1 and PT2 are used to monitor the pressure during the operation and check the bath temperature measurement. A resistive heater is mounted inside the test sample to provide heat load Qelec. Each set of data consists of ten channels. The signals are read through two digital voltmeters (DVM). Each of the ten devices is powered separately. The two DVMs communicate the read-out voltages to the computer. The data acquisition system enables the recording of five sets of data per minute. 4.2 Test Procedure The test sample assembly is leak checked and then installed in the dewar. Once the test sample is filled with liquid helium, valve V1 is closed. Then, valve V3 between the gas helium cylinder and test sample is opened to maintain the pressure at above one atmospheric pressure. The test sample is connected to a gas helium cylinder to condense gas helium into liquid and maintain its pressure slightly above atmospheric pressure during the phase transition from He I to He II. Valve V2 connected to the vacuum pump is slowly opened to reduce the pressure PT1 until the bath temperature T3 reaches the required value. As described in (2.2), the test mainly consists of measuring the temperature difference, T1-T3, for various values of T3. This temperature difference provides us with the total thermal resistance. The helium level gage, LT2, indicates that the saturated He II is always above the top flange while the measurement data points are observed. During the measurement, the helium level indicator, LT1, confirms that 100% of the sample length (100 mm) is wetted by the saturated He II. For each heat load, the temperatures are recorded after bath temperature T3 is stabilized ( T <1 mk). The first set of data were always recorded corresponding to zero electrical heat load, then additional Qelec (with an increment of 0.5 W), was applied, step by step, until the vacuum pump was unable to keep the bath pressure constant. The measurements are repeated for bath temperature T3, from 1.75 K to 2.00 K with an increment of 0.05 K. 4

5 Results and Discussion 5.1 Results The accuracy of the temperature sensors is 61 mk for the observed temperature range. An error of 63 % on the measurement is estimated according to the resolution of the various devices and the effect of the soldered thick wall stainless steel flanges at both ends. If we consider the LHC inner triplet, the worst case for the temperature and pressure drops appear at the interaction point 5 (IP5-left). The temperature at the feedbox on the pumping line was estimated to be 1.851 K [6]. This case is shown in Figure 4. This figure illustrates the equilibrium response of the system once Qelec is increased, step by step, up to 6 W. In order to check the behavior of the system, Qelec is finally reduced to 2.5 W then to zero. The operation is repeated for several values of T3. For each configuration a similar graph is obtained. 60 50 T1-T3 [mk] 40 30 20 10 0 1900 2000 2100 2200 2300 2400 2500 2600 Data Point (each unity egal 12 sec.) Figure 4. Example of measurement for T3 = 1.85 K With several T3 configurations, we can show the evolution of T1-T3 versus Qelec. Figure 5 illustrates the curves for the entire range of T3 values. We observed the limitation of our pumping unit capacity, which did not allow us to run the test at a heat load above 5 W when T3 was at 1.75 K. Furthermore, Figure 5 expresses the heat capacity of the current heat exchanger design for a given temperature difference across the He II heat exchanger wall to the saturated superfluid. An optimal difference of temperature is estimated at 30 mk. Once we plot our results in the plane (Rthtotal, T -3 ), we note a linear behavior of the total thermal resistance, Rthtotal, and T -3. Figure 6 gives a calibration for the current heat exchanger. By linear regression on data point, we obtain the equation (eq 2 ). y 53.9x. 0.1904 eq 2 Considering the parameters (slope and intercept) of this line, we can deduce, the value of the Kapitza coefficient (Ckapitza) and the copper thermal conductivity (Kcu). Ckapitza = 892.8 WK -4 m -2 Kcu = 88 WK -1 m -1 Thus, the Kapitza conductance at 1.9 K is equal to 0.612 Wcm -2 K -1. The test results show that the Kapitza thermal conductance is in good agreement with the results from other experiments [7]. 5

T1-T3 [mk] 70 60 50 40 30 20 10 0 0 2 4 6 8 10 Electrical power added [W] T3=1.75K T3=1.80K T3=1.85K T3=1.90K T3=1.95K T3=2.00K Figure 5. Dependence of the temperature difference versus the applied electrical power Rth total * 1E -3 [KW -1 ] 11.0 10.5 10.0 9.5 9.0 8.5 8.0 7.5 7.0 6.5 y = 53.9x + 0.1904 R 2 = 0.9975 6.0 0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 T3-3 [K -3 ] Figure 6. Total transverse thermal resistance 5.2 Discussion Our initial estimate for overall conductance through the corrugated pipe of the full-sized Heat Exchanger Test Unit, was scaled from early CERN measurements of a corrugated pipe. A test performed at CERN provided an overall heat conductance of 80 to 140 WK -1 per meter of length for a 39/43 mm corrugated DHP copper [2]. The test at CERN indicated that the heat exchanger tube was wetted on about 30% of its surface. This implies an overall heat transfer coefficient through the copper wall of about 0.2 Wcm -2 K -1 of active area at 1.9 K. If we scale the 80 WK -1 per meter estimate for the 39/43 mm tube up to the present 85/96 mm corrugated tube, we get 180 WK -1, assuming 30 % is wetted. Initial sizing of the corrugated tube was based on this estimate for conductance. The results from our small heat exchanger sample provide an overall wall conductance through the active area of 0.295 Wcm -2 K -1, about 50 % higher than our initial estimates. This higher conductance for the short sample is in good agreement with the higher end of the 80 to 140 WK -1 range found in the early CERN tests referenced above. These results imply heat transfer of 265 WK -1 per meter of length for our 85/96 mm corrugated tube. If we compare our results to those obtained for a smooth tube [4], we note that a similar Kapitza coefficient is obtained in the case of a sample without surface treatment. An increase of 30 % of the Kapitza coefficient was observed for a degreased sample. Thus, we might improve the heat transfer of our heat exchanger pipe if we degrease the surface. However, any method of surface treatment should be compatible with the long heat exchanger tube in the LHC inner triplet. 6

6 Conclusion The current note reports the measurement of the temperature difference across the LHC inner triplet He II heat exchanger wall to the saturated superfluid. The measured total thermal conductance yields a Kapitza coefficient of 892.8 WK -4 m -2 63%. Therefore, a Kapitza conductance of 0.612 Wcm -2 K -1 is estimated for the operating temperature of 1.9 K. These data show that the delta-t attributable to wall resistance is cut to about 65 % of what we have used to size the Heat Exchanger Test Unit. These results enable us to predict a lower temperature difference across the copper wall, hence to permit a larger margin for the distribution of temperature for the rest of the inner triplet. Another test is planned with the same test sample but with a surface treatment. References [1] A HE II Heat Exchanger Test Unit designed for the LHC interaction region magnets; by Darve Ch.; HuangY. ; Kerby J.; Nicol T. and Peterson T. - Fermilab- Subm. to CEC-ICMC '99 in Montreal, CA; 12-16 Jul 1999. [2] CERN AT/93/21 (CR) - Note 233: The Superfluid Helium Model Cryoloop for the CERN Large Hadron Collider; by Bezaguet A.; Casas-Cubillos J.; Lebrun P.; Marquet M.; Tavian L.; Van Weelderen R.; presented at the 1993 CEC in Albuquerque, 1993. [3] Materials at low temperatures; by R. P. Reed & A. F. Clark, American society for metals, Metal park, Ohio, USA, 1983. [4] CERN-LHC-Project-Report-232. Thermal Characterization of the He II LHC Heat Exchanger Tube; by Camacho, D; Chevassus, S; Policella, C; Rieubland, J M; Vandoni, G; Van Weelderen, R, 1998. [5] CERN-AT/95-34. Thermal conductance measurements on the LHC Helium II heat exchanger pipes; by M.M Kado, 1995. [6] Heat Load and Temperature Summary for the LHC Interaction Region Final Focus Superconducting Magnets; by Peterson T, Sept. 1999. [7] Helium Cryogenics; by Van Sciver S., Plenum. 7