SESSION 3. Short Circuit Calculations, Unsymmetrical Faults. Leonard Bohmann, Michigan State University Elham Makram, Clemson University

Similar documents
Last Comments on Short-Circuit Analysis

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Module 3 : Sequence Components and Fault Analysis

4 Fault Calculations. Introduction 4.1. Three phase fault calculations 4.2. Symmetrical component analysis 4.3 of a three-phase network

Chapter 8: Unsymmetrical Faults

EE2351 POWER SYSTEM ANALYSIS UNIT I: INTRODUCTION

KINGS COLLEGE OF ENGINEERING Punalkulam

Fault Analysis Power System Representation

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

SECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems

SHORT QUESTIONS AND ANSWERS. Year/ Semester/ Class : III/ V/ EEE Academic Year: Subject Code/ Name: EE6501/ Power System Analysis

CHAPTER 8 UNSYMMETRICAL FAULTS

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous)

Fault Calculation Methods

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

Sinusoidal Steady State Analysis (AC Analysis) Part II

Technical Concepts - Fault Analysis Methods

EE 205 Dr. A. Zidouri. Electric Circuits II. Two-Port Circuits Two-Port Parameters. Lecture #42

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

4.10 Unbalanced fault analysis using Z BUS matrix:

Chapter 9 Balanced Faults, Part II. 9.4 Systematic Fault Analysis Using Bus Impedance Matrix

The Effect of the Harmonics, the Fault Location and the Fault Resistance on the Performance of the Impedance-Type Distance Relay

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY Mamalapuram Chennai QUESTION BANK V SEMESTER. EE6501-Power system Analysis

GENERAL FAULT ADMITTANCE METHOD LINE- TO- LINE-TO-LINE UNSYMMETRICAL FAULT

Fall 2011 ME 2305 Network Analysis. Sinusoidal Steady State Analysis of RLC Circuits

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

POWER SYSTEM STABILITY

Transient Behavior of

QUESTION BANK ENGINEERS ACADEMY. Power Systems Power System Stability 1

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

Electric Circuits II Sinusoidal Steady State Analysis. Dr. Firas Obeidat

Transmission Line Fault Analysis using Bus Impedance Matrix Method

Power Flow Analysis. The voltage at a typical bus i of the system is given in polar coordinates by

Transformer. Transformer comprises two or more windings coupled by a common magnetic circuit (M.C.).

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

In the previous chapter, attention was confined

Three Phase Circuits

Module 3 : Sequence Components and Fault Analysis

Chapter 10 Sinusoidal Steady State Analysis Chapter Objectives:

Synchronous Machine Modeling

Final Exam, Second Semester: 2015/2016 Electrical Engineering Department

ECE 476. Exam #2. Tuesday, November 15, Minutes

Module 4. Single-phase AC Circuits

Schedule. ECEN 301 Discussion #20 Exam 2 Review 1. Lab Due date. Title Chapters HW Due date. Date Day Class No. 10 Nov Mon 20 Exam Review.

Power System Fault Detection Using Conductor Dynamics

ECEN 667 Power System Stability Lecture 25: FFT, Energy Methods

Module 4. Single-phase AC Circuits. Version 2 EE IIT, Kharagpur 1

Introduction to Synchronous. Machines. Kevin Gaughan

Consider a simple RC circuit. We might like to know how much power is being supplied by the source. We probably need to find the current.

IMPERIAL COLLEGE OF SCIENCE, TECHNOLOGY AND MEDICINE UNIVERSITY OF LONDON DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING EXAMINATIONS 2010

The Mathematical Model of Power System with Static Var Compensator in Long Transmission Line

Power system model. Olof Samuelsson. EIEN15 Electric Power Systems L2 1

Chapter 10: Sinusoidal Steady-State Analysis

Chapter 10: Sinusoids and Phasors

Sinusoids and Phasors

Lecture 11 - AC Power

Mathematical Model of a Synchronous Machine under Complicated Fault Conditions

CHAPTER 2 DYNAMIC STABILITY MODEL OF THE POWER SYSTEM

Sinusoidal Steady-State Analysis

Electromagnetic Torque From Event Report Data A Measure of Machine Performance

Tutorial Sheet Fig. Q1

2 Power System Network Matrices I

POWER SEMICONDUCTOR BASED ELECTRIC DRIVES

Electrical Circuits Lab Series RC Circuit Phasor Diagram

The Mathematical Model of Power System with Thyristor Controlled Series Capacitor in Long Transmission Line

JRE SCHOOL OF Engineering

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

Sinusoidal Steady State Analysis

BASIC NETWORK ANALYSIS

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

EE2351 POWER SYSTEM ANALYSIS

Power Systems - Basic Concepts and Applications - Part I

Sinusoidal Steady State Analysis (AC Analysis) Part I

GATE 2008 Electrical Engineering

SYMMETRICAL FAULTS Revised: 10/8/13 1:49 PM

Fault Locating PRESENTED BY ERIK SCHELLENBERG IDAHO POWER

Lesson 17: Synchronous Machines

Prof. Shayla Sawyer CP08 solution

LO 1: Three Phase Circuits

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

ELECTRICAL ENGINEERING

Name (print): Lab (circle): W8 Th8 Th11 Th2 F8. θ (radians) θ (degrees) cos θ sin θ π/ /2 1/2 π/4 45 2/2 2/2 π/3 60 1/2 3/2 π/

Australian Journal of Basic and Applied Sciences. General Fault Admittance Method Solution of a Balanced Line-to-Line-to-Line Fault

Single Phase Parallel AC Circuits

(Refer Slide Time: 00:55) Friends, today we shall continue to study about the modelling of synchronous machine. (Refer Slide Time: 01:09)

EKT103 ELECTRICAL ENGINEERING

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

Selecting the current rating for equipment

The per unit system is based on the formula shown in Equation (1).

Part 4: Electromagnetism. 4.1: Induction. A. Faraday's Law. The magnetic flux through a loop of wire is

Chapter 9: Transient Stability

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

Possible

Dynamic simulation of a five-bus system

Lectures 16 & 17 Sinusoidal Signals, Complex Numbers, Phasors, Impedance & AC Circuits. Nov. 7 & 9, 2011

BEE701 POWER SYSTEM ANALYSIS

Generation, transmission and distribution, as well as power supplied to industrial and commercial customers uses a 3 phase system.

Transcription:

SESSON Short Circuit Calculations, Unsymmetrical Faults Leonard Bohmann, Michigan State University Elham Makram, Clemson University

Short Circuit Calculations Leonard Bohmann Michigan State University

Line to Ground Short EEE T & D CONFERENCE

Short Circuit Fault Currents Amps (ka) 7 6 5 4 - - - dc offset t.5..5. high frequency transient decaying sinusoid EEE T & D CONFERENCE 4

Short Circuit Fault Currents (continued) X(t) R v(t) 5 4 -.5..5. v(t) (t) θ then m i(t) [cos( ωt + α θ) (t) cos( ωt m if cos( ωt + α) R + jx(t) + α θ)e Rωt X(t) ] - - EEE T & D CONFERENCE 5

dc offset 5 4 -.5..5. - - i(t) m cos( ωt + α θ) cos( ωt EEE T & D CONFERENCE + α θ) e Rωt X 6

ariable magnitude 6 4 -....4.5.6.7.8.9. -4-6 i(t) m cos( ωt + α θ) (t) t EEE T & D CONFERENCE 7

Reactance of Synchronous Machine reactance (pu).9.8.7.6.5.4... X d X' d X" d..4.6.8..4 t EEE T & D CONFERENCE 8

Use sub-transient reactance to calculate fault currents worst case for when CB is opening Do not calculate dc offset directly use X/R to approximate offset (asymmetry ratio) at opening time X/R is the time constant of the decay in cycles EEE T & D CONFERENCE 9

G L 5 T T5 T5 L5 T T4 f 4 How do you calculate the fault current ( f ) at bus? G4 EEE T & D CONFERENCE

Use Thevenin equivalent Th Th f Th : open circuit voltage also called the prefault voltage, f oftenuse EEE T & D CONFERENCE

Use for: symmetrical faults single phase networks three phase faults in three phase networks (per phase equivalent) concept for solving all faults EEE T & D CONFERENCE

This method calculates the current going into the fault Often want the current elsewhere in the network (through a circuit breaker, in bus bars, in other lines, etc.) EEE T & D CONFERENCE

A current source, with the magnitude of the fault current, placed at the fault, has the same effect on the rest of the circuit as the short circuit. f Th f f Th f EEE T & D CONFERENCE 4

Adding a current source to the original circuit has the same electrical effect as adding it to the equivalent circuit G L 5 T T5 T T5 f Th T4 f f L5 4 G4 EEE T & D CONFERENCE 5

G L All the voltages and all the currents can be found using the new circuit. 5 T T5 T L5 T5 T4 4 G4 f Use superposition: Use the original sources (or assume currents are and voltages are ) Use just the current source, gives changes due to the fault EEE T & D CONFERENCE 6

Calculation details Bus Admittance Matrix: Y bus G L Y bus T T5 T vector of current injections vector of bus voltages 5 L5 T5 T4 4 f G4 EEE T & D CONFERENCE 7

G T5 5 L5 T T5 4 L Diagonals: Σ of Y connected at node Y / T +/ L +/ T Y Y Y5 T Y Y Y Y bus Y Y Y4 Y5 f Y4 Y44 T4 Y5 Y5 Y55 G4 Off diagonals: - of Y connected between nodes Y 5 -/ T5 EEE T & D CONFERENCE 8

Y bus is sparse (lots of zero) smallsize easy to build quick algorithms to manipulate EEE T & D CONFERENCE 9

Bus mpedance Matrix: bus bus G vector of bus voltages vector of current injections L T T5 T 5 T5 f bus Y bus - L5 4 T4 G4 EEE T & D CONFERENCE

bus 4 5 4 5 4 5 4 4 4 44 54 5 5 5 45 55 bus is a full matrix slowtoinvert slow to manipulate avoid using if possible Diagonal element is the Thevenin mpedance at that bus is the Thevenin mpedance at bus EEE T & D CONFERENCE

To find the change in voltages due to the fault current at bus : 4 5 4 5 4 5 4 5 4 4 4 44 54 5 5 5 45 55 - f EEE T & D CONFERENCE

To calculate current in line -: f T f T 5 f 4 EEE T & D CONFERENCE

Asymmetry ratio: S Method calculates the RMS worst case of the 6 Hz component this is needed to set protective relays For circuit breaker selection, need to know the total RMS current (6 Hz and dc offset) Circuit breakers are rated on symmetrical fault current, assuming an X/R ratio of 5 EEE T & D CONFERENCE 4

Asymmetry ratio RMS ac + dc RMS ac + ac e ω t X R RMS ac RMS S ac + e ωt X R ωt () X R t where S(t) is + e EEE T & D CONFERENCE 5

Calculating X/R G L 5 T T5 T5 L5 T f T4 4 G4 Equations presented are for a single order system For higher order systems, ignore R and find equivalent X, ignore X, and find equivalent R Actual decay is typically quicker than this approximation EEE T & D CONFERENCE 6

Algorithm Calculate Thevenin mpedance Calculate current into fault Find the needed elements of bus (not all of them) Find the needed changes in bus voltages Find the line currents of of interest Find the dc offset EEE T & D CONFERENCE 7

Example The oneline drawing of a system, along with bus are shown below. i) Calculate the fault current for a three phase solid fault at bus. j pu ii) Calculate the voltages at bus,, and during this fault. iii) Calculate the current flowing j.8pu j.5 pu j.5 pu from bus to bus. j.pu 5 j5 j. pu 4 f j.5 pu j. pu bus. 656. 58 j. 5. 4. 559 EEE T & D CONFERENCE. 58. 8. 675. 45. 6. 5. 675. 7. 487. 644. 4. 45. 487. 658. 49. 559. 6. 644 pu. 49. 799 8

Part (i): Calculate the fault current for a three phase solid fault at bus. Assume all initial bus voltages are therefore all initial currents are Use the, element of bus for the Thevenin impedance. f f j.7 j. 68 j. 7 f pu EEE T & D CONFERENCE 9

Multiply the negative of the fault current by elements in the rd column to get the change in voltages EEE T & D CONFERENCE Part (ii): Calculate the voltages at bus,, and 4 during this fault..68 -- 644 49 799 559 6 4 45 487 658 49 5 675 7 487 644 58 8 675 45 6 5 4 559 656 58 9 687 5 4 j j...........................

Part (ii): Calculate the voltages at bus,, and 4 during this fault. (continued) The voltages during the fault are the initial voltages minus the changes in the voltages f f f i i i. 687. pu. 9. 766pu pu EEE T & D CONFERENCE

Part (iii): Calculate the current flowing from bus to bus. The current is the difference between the voltages divided by the impedance f f f T f. 766 j. 5 j. 86pu 5 -j.86 pu -j.68 pu 4 EEE T & D CONFERENCE

Problem A small power system is sketched below along with bus. j. pu j. pu j.5 pu j.8 j.5 pu 4 j. pu j.5 pu 4. 78. 44. 6. 74 44 4 54 64 4 bus j..... 6. 64 4. 658. 6. 74. 4. 6 5. 44 pu a) What is the fault current for a three-phase fault to ground at bus? b) What are the voltages at busses,, and 4? c) What is the current due to the fault from bus 4 to and from to? EEE T & D CONFERENCE

Unsymmetrical Faults Elham Makram Clemson University EEE T & D CONFERENCE

SNGLE LNE TO GROUND FAULT a b c af bf cf f n Fig.. Single line to ground fault on phase A Boundary Conditions at fault location bf f (a Or, cf + a Thus f Now a) a * + af From the current equations, + a + ( a f (a * + a) + a) af + a f + a * EEE T & D CONFERENCE

SNGLE LNE TO GROUND FAULT (CONTD.) To satisfy the voltage and current boundary conditions, the sequence networks should b connected in series as shown in Fig.. ero Sequence Network + - ero Sequence Network + - f ero Sequence Network + - Fig.. Sequence connection for A-G fault EEE T & D CONFERENCE

a b c n + af af bf cf bf f cf Fig.. Line to line fault LNE TO LNE FAULT Current boundary Conditions a af bf (a (a bf + - Thus, EEE T & D CONFERENCE cf + a + a) - + a cf - a) + a + a + This leads to + f f (a - (a oltage boundary conditions + a + a + a bf - a) + a) f ( f + a + (a + a - a) )

LNE TO LNE FAULT (CONTD.) To satisfy the voltage and current boundary conditions, the sequence networks should be connected as shown in Fig. 4. Positive Sequence Network + - Negative Sequence Network + - f Fig.4. Connection of sequence network for BC fault EEE T & D CONFERENCE 4

a b c n + af DOUBLE LNE TO GROUND FAULT bf f cf af bf cf Fig.5. Double line to ground fault EEE T & D CONFERENCE CurrentboundaryConditions at thefaultlocation, af bf and, bf a Thus, + ( Thus, Also, + cf bf oltageboundaryconditions + Thus cf + a + a Thus - ) f + a + a + a + a + a + a ( + a + ) f f 5

DOUBLE LNE TO GROUND FAULT (CONTD.) Considering the voltage and current boundary conditions, the sequence networks are connected as shown in Fig. 6. ero Sequence Network + - f Positive Sequence Network + - Negative Sequence Network + - Fig.6. Sequence network connection for double line to ground fault EEE T & D CONFERENCE 6

Consider the power system shown in Fig. 7. G T Example P T. L. T G Fig. 7. Example Ratings G and G: MA, k X X.pu X.4pu T and T : MA, 45/ k X T X T.8 pu T. L. X X.5pu X.5pu EEE T & D CONFERENCE Find the voltages at Bus and the currents from T to P due to (i) (ii) Single line to ground fault at P Line to line fault at P (iii) Double line to ground fault at P 7

Positive sequence network j. j. j.8 j.5 j. j.8 j.5 j.8 P P P f th E E (. + j.8) (j.+ j.8 + j.5) j. Negative sequence network ero sequence network j. P j.8 j.5 th j. P EEE T & D CONFERENCE th j.8 8

(i) Single line to ground fault E - j.94 (th + th + th ) (j. + j. + j.8) The following are the sequence current components from T- - > P The sequence voltage components at the fault location are : - j.4 - j.94 E - -.5 * j.4 (.5+.8) -. (-j.4)(j.8).57668 - (j.4) (j.8) -.4 - j.9 (j.8) -.54 The current phase components from T- - > P a b c a a a * a a a a EEE T & D CONFERENCE 9

a b c a (-j.4) + a(-j.4) j.9 - a(-j.4) + a (-j.4) j.9 - j.799 j.799 c c b -j.799 -j.799 -j.7 -j.7 -j5.79 The phase voltages at the fault location are : a b -j.4- j.4 - j.9 - j.7 -.97- j.866 c + + a + a + + a + a -.97 + j.866 -.54 +.57668.4 -.54 + ( 4 )(.57668) + ( )(-.4) -.54 + ( )(.57668) + ( 4 )(-.4) EEE T & D CONFERENCE

(ii) Line to line fault Currents: E j.6 ( + ) (j. + j.).5 (T- - > P) j.6 (.8 +.5 ) (T- - > P) j.6 a b c a a (-j.6) + a oltages : a a a b c E - (-j.6) + a(j.6) a a -.5.5 th. - (-j.6)(j.8).5.5 th (j.6).79.79 j.6 EEE T & D CONFERENCE

SEQUENCE PHASE SHFT THROUGH WYE/DELTA TRANSFORMER BANK Positive and negative sequence impedance is independent of connection These networks ignore phase shift When current and voltages are transformed from one side to the other phase shift must be considered. Standard ANS connection has been shown in figs. 8 (a) and 8 (b). High side Low side High side Low side a A n: n: A a n a A A A A a /n b a B B b B n B B b B b /n c b C C c C n C c C C c /n c A A a a C B c b C B c b Fig. 8 (a) Wye/Delta EEE T & D CONFERENCE Fig. 8 (b) Delta/Wye

EEE T & D CONFERENCE unit per n or n a) ( - n ) a - n( ) - n( : voltage sequence Negative unit per n or n ) a ( - n ) a - n( ) - n( : current sequence Negative unit, per in or n ) a ( - n ) a - n( : volatge sequence Positive unit, per n - n a) ( - n ) a - n( ) - n( : current sequence Positive 8(a) fig. Refer to a A a a a a b a A a A A A A A C A a a A a a a a A a A A A A A C A a

4 EEE T & D CONFERENCE voltage sequence Negative unit per n or n ) a - ( n : current sequence Negative unit, per in or, n ) - a ( n : voltage sequence Postitive unit, per in or, n ) a - ( n ) - ( n : current sequence Postitive 8 (b) fig. Refer to a A a A a a a A a A A A A a a A a a a b a A

n general,in Y - or - Y connections : (i) Positive sequence High voltage Positive sequence Low voltage + (ii) Negative sequence High voltage Negative sequence Low voltage - EEE T & D CONFERENCE 5

Example Find the currents and voltages at G of Example, due to single line to ground fault at P. (i) Currents : ag ag ag ag bg cg - j.4 - - j.4 - - j.4 + a ag ag + + ag a j.4-6 - j.4 - + ag 4 (.4 - ) + (.4-6 ) (.4 ) + (.4 6 ) j.995 j.4-6 - j.995 EEE T & D CONFERENCE 6

Example ( contd.) (ii) oltages : ag ag ag ag ag bg cg ag bg cg E.666 -.4 (from sequence Network neglecting phase shift).666 - -.4 a ag.577 4. a a ag + ag a + + a g a a g. - (-j.4)(j.) (from sequence Network neglecting phase shift) ag.666 - -.4.577 6 a ag ag.666 -.4 5. 9 a * a ag ag ag.577 6.577 4. 9 EEE T & D CONFERENCE 7

PROBLEMS PROBLEM # For the system shown below, find the currents in the transformer and generator windings in per unit and amperes for a single-line-to-ground fault at (i) P (ii) R G 5/5 k R P G: MA, 5 k X X., X.5 Transformer: MA, 5/5 k X. EEE T & D CONFERENCE 8

PROBLEMS PROBLEM # Solve examples and for a double-line-to-ground fault at P. EEE T & D CONFERENCE 9

PROBLEMS PROBLEM # Solve examples and for a line-line fault at P. EEE T & D CONFERENCE