Controlled Environment Testing Report

Similar documents
Approval Block. Prepared by: Signature Date Evan Parnell 08 NOV Reviewed by: Signature Date. Approved by: Signature Date

Fundamentals of Particle Counting

FEDERAL STANDARD 209E. Airborne Particulate Cleanliness Classes in Cleanrooms and Clean Zones

ISO STANDARD INTERNATIONAL. Cleanrooms and associated controlled environments Part 1: Classification of air cleanliness

Cleanrooms and associated controlled environments. Part 1: Classification of air cleanliness by particle concentration

PARTICLE MEASUREMENT IN CLEAN ROOM TECHNOLOGY

Order No. G Date: September 8, 2010 REPORT NO CRT-001 TEST OF SMF/PAPI SYSTEM RENDERED TO

Determination of particle size distribution Single particle light interaction methods. Part 4:

MATERIAL TEST REPORT STATIC DECAY AND SURFACE RESISTIVITY TESTING OF SOCK AND SPUNBOND SAMPLES NEW PIG CORPORATION FEBRUARY 28, 2008

Standard Practices for Air Speed Calibration Testing

Clean Corona Ionization Technology. Peter Gefter Simco-Ion phone: (1)

Particle number concentration standards at NMIJ, including a new calibration service with an inkjet aerosol generator.

Review of Anemometer Calibration Standards

Traceability research activities in the field of airborne particle number/ mass concentration measurement Liu Junjie, Zhang Wenge, Song Xiaoping

Recent Advances and Challenges in Nanoparticle Monitoring for the Semiconductor Industry. December 12, 2013

Ball screw. Linear. Coupling cover. 1Positioning table of a structure with enhanced sealing property. 3 High corrosion resistance

CALIBRATION CERTIFICATE FAILURE EXPLANATION FOR AEROTRAK PARTICLE COUNTERS

PRETREATMENT TECHNICAL DATA SHEET A CHROME-FREE FINAL RINSE PRODUCT DESCRIPTION

PRETREATMENT TECHNICAL DATA SHEET CHROMIUM-FREE ORGANIC PASSIVATING RINSE PRODUCT DESCRIPTION

In Association With. Introduces. TPT Contractor

TEST METHOD FOR STILL- AND FORCED-AIR JUNCTION-TO- AMBIENT THERMAL RESISTANCE MEASUREMENTS OF INTEGRATED CIRCUIT PACKAGES

CERTIFICATE OF ACCREDITATION

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. ALLOMETRICS, INC Bayport Blvd. Seabrook, TX Terry Baldwin Phone: CALIBRATION

CALIBRATION CERTIFICATE # 503

Brian Sargent, Assistant Director, Designee 3/21/18. See Thread for Approval

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005. J. A. KING & COMPANY, LLC 8813 Old Craft Road Olive Branch, MS CONNIE FOSTER PHONE:

AMBIENT INLINE PURIFIER 502 PURIFICATION MEDIA SPECIFICATION

Evaluation of standards for transmission loss tests

AMBIENT INLINE PURIFIER 302 PURIFICATION MEDIA SPECIFICATION

AMBIENT INLINE PURIFIER 804 PURIFICATION MEDIA SPECIFICATION

Sample Analysis Design. Solution Mode

Air Flow through Woven Stainless Steel Mesh

Reflectec Thermal Fabric & Reflectec Fiberboard

Correlation of SODAR and Meteorological Tower Measurements. Prepared for: West Virginia Division of Energy

Height Master Page 343. Check Master Page 347. Calibration Tools Page 352

Application for Radioactive Material Use

GUIDE TO LABORATORY SURVEYS. Introduction

Technical Requirements. Version No. 1.0 Effective Date 10/1/2008

6 INCH W X 5-3/4 INCH D X 8-3/8 INCH H

Mechanical Engineering Division June 1, 2010

Eye Safety With LED Components

Morehouse. Edward Lane, Morehouse Instrument Company 1742 Sixth Ave York, PA PH: web: sales:

Quality Test Center PERiMETER: Applications

AAE 520 Experimental Aerodynamics Aero & Space Technology. Products & Services. In collaboration with. Space Tango Kentucky, USA

CLIPPER SCREEN SIZES - DECEMBER 28, 2005

SSi Super Systems Inc.

Facilities Management

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

PRETREATMENT TECHNICAL DATA SHEET CHROMIUM-FREE ORGANIC PASSIVATING RINSE PRODUCT DESCRIPTION

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Quebec) J3X 1P7 Tél. : (450) Fax : (450)

CHINA MP FILTRI P.O. Box Shanghai Phone: Fax:

Addendum to ARI Standard , Air Terminals September 2002

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

ISO INTERNATIONAL STANDARD

Loadcell Calibration - Evaluation of Uncertainties

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

TI 226H Calibration of Flow Check Devices using Positive Displacement Flow Meter

SL CONTENT Page No 1 Devices Used 3

Data Sheet / Instructions. Dewpoint MeterO

The Dynamic Particle Generation of Lubricating Greases for use in Space Mechanisms

NFRC THERMAL PERFORMANCE TEST REPORT. Rendered to: C.R. LAURENCE CO., INC.

GM Pancake Probe Victoreen Model D

New! 2010 Model. Model No

Multi-element process analyzer

Technical Data Sheet DPT & DPIT-4005 SERIES DIFFERENTIAL PRESSURE TRANSDUCERS. Features. Description

CMM Uncertainty Budget

Effect of Air Density on Cyclone Performance and System Design

GP-B Telescope Determine Metering Tube Length P0364 Rev -

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

TSI AEROTRAK REMOTE 4-20 ma SENSORS LIFE SCIENCE

Field IT 50T Series Transmitters

GEOSYNTEC CONSULTANTS

M [scale units/s] of the system

FVBSS fixed volume bottle

Civil Engineering, Surveying and Environmental Consulting WASP0059.ltr.JLS.Mich Ave Bridge Geotech.docx

MOY/SCMI/36 SPECIFICATION OF ACCURACY FOR A PRECISION CLINOMETER

Photometric Test Report

DM70. Hand-held Dewpoint Meter. Truly Fast Response - Superior Long-term Stability

Chapter 3. Experimentation and Data Acquisition

ABB MEASUREMENT & ANALYTICS DATA SHEET. PGC5000 Temperature programmed gas chromatograph

DeFelsko PosiTector Dew Point Meter with Anemometer (DPMA)

product manual H-3220A Benkelman Beam

Portable Radiation Survey Instruments

Dewpoint Meter Data Sheet / Instructions

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005 & ANSI/NCSL Z

MAC Aura XB Acoustic Test Report

User Manual. Stick-Style Water-Resistant Infrared Thermometer with 8:1 Distance-to-Sight Ratio. Model with NIST-Traceable Calibration

D501 and D501-RS. Microscanner D-Series IR Thermometers. no effect. no effect. no effect. no effect no effect

To: Ross Martin, Lisa Stapleton From: Brad Lind Subject: Joint Funding Agreement with USGS for 2012 Imagery Date: March 14, 2012.

Stick-Style Water-Resistant Infrared Thermometer for Foodservice Applications with 4:1 Distance-to-Sight Ratio Model

NORM Services Provided by Institute for Energy Technology. Tore Ramsøy & Rajdeep Sidhu

ANSI/AMCA Standard (R2012) Laboratory Methods of Testing Air Curtain Units for Aerodynamic Performance Rating

10-year industry best core warranty. 2-year warranty on balance of unit.

Siddharth Institute of Engineering & Technology

GP-B Telescope Measurement of Telescope Transmission P0450 Rev -

STANDARD PROCEDURE: NWSP R2 (15) Polyacrylate Superabsorbent Powders Determination of the Particle Size Distribution by Sieve Fractionation

OPTICAL PARTICLE SIZER MASS CALIBRATION METHOD

SMP625 Product Specifications

Transcription:

Client: Controlled Environment Testing Report Services Conducted: Product Testing Project Contact: Stefan Hocom Project Manager: Stefan E. Hocom 323 Spreckels Drive, Ste. B Aptos, CA 95003 The final approval of this document before its release to the client is the responsibility of the following personnel at In signing this cover sheet, these individuals acknowledge the accuracy of the data and activities reported herein: Stefan Hocom Project Manager Date: 09/27/16 Reviewed and Approved by: Stephanie Hocom, ASQ CQA President Date: 09/27/16

1.0 Introduction The purpose of this report is to present the data and conclusions derived by CPS Certification Services, Inc. during the testing of two (2) cleanroom tables designed and built by located at 23949 Tecate Mission Road, Tecate, Ca. This testing was conducted on the date of September 27, 2016 consisted of the following: Airborne particle concentrations This report includes the following: Test data results Testing diagrams 1 Observations Equipment calibration documents 1 Diagrams are not to scale. 1.1 References ISO 14644-1 Classification of Air Cleanliness ISO 14644-3 Test Methods IES-RP-CC006.2 Testing Cleanrooms If you have any questions as to the contents of this report please contact us at (831) 662-2760.

2.0 Airborne Particle Concentration Test 2.1. Purpose Airborne particle concentration testing is conducted to verify a products airborne particle concentration within a classified cleanroom environment. 2.2. Equipment 2.2.1. Met-One laser particle counter with 0.1 micron capability 2.2.2. Shortridge microprocessor based thermal anemometer 2.2.3. Shortridge microprocessor based manometer 2.2.4. 5 x 3 x 8 ISO class 3 test chamber with perforated raised floor 2.3. Methodology Certification of the test chamber was conducted prior to product testing to verify ISO class 3 levels. Results are as follows: Average ULPA filter velocity = 98 FPM (feet per minute) Differential pressure = 0.0989 to ambient ULPA filter leaks = No leaks detected at 0.1 micron Particle concentration level = 0 particles at 0.1 micron Once the ISO class 3 chamber status was verified each table was assembled and micro-cleaned with 70/30 DI water/alcohol and cleanroom wipes. The tables were tested individually and all test data was recorded at the time of testing and transferred to this report. Refer to the section Airborne Particle Count Record for all test data. 2.3.1. Test locations (see Figure 1) 2.3.1.1. Testing was conducted at six (6) total sample locations for each table. Three samples from the top midline of table and three midline samples at floor level. The sample probe was placed at each location at an approximate height of 8 inches.

Figure 1 - Sample locations Airflow Direction Table top locations 1 2 3 Under table locations 1 2 3 2.3.2. Test Descriptions 2.3.2.1. Static Test Table is placed alone in chamber. This test reflects the total particle contribution to chamber from table. 2.4. ISO 14644-1 Classification Comparison and Recommendation Currently there is no standard that allows for a cleanroom table to acquire an ISO cleanroom classification or a comparable rating. It is recommended that when promoting a product as clean, that airborne particle concentration levels fall below the ISO 14644-1 particle concentration limits for the desired class. 2.4.1. ISO 14644-1:1999(E) Classification Table ISO Particle concentration limits in cubic meters (m 3 ) Class 0.1µ 0.2µ 0.3µ 0.5µ 1.0µ 5.0µ ISO 1 10 2 ISO 2 100 24 10 4 ISO 3 1,000 237 102 35 8 ISO 4 10,000 2,370 1,020 352 83 ISO 5 100,000 23,700 10,2000 3,520 832 29 ISO 6 1,000,000 237,000 102,000 35,200 8,320 293 ISO 7 352,000 83,200 2,930 ISO 8 3,520,000 832,000 29,300 ISO 9 35,200,000 8,320,000 293,000

2.5. Test Results 2.5.1. K Series Stainless Steel Frame and Top Table Top Test 2.5.1.1. Airborne Particle Count Record Product KSN2448 (Stainless Table) Test Location: Table Top Limit: 1 13:58:57 0 0 0 0 0 0 0 0 0 0 2 14:00:10 0 0 0 0 0 0 0 0 0 0 3 14:01:21 0 0 0 0 0 0 0 0 0 0 95% UCL (if 2 to 9 locations) 0 0 0 0 0 0 0 0 0 0 Remarks : Consistant with ISO class 1 particle concentrations Under Table Test Airborne Particle Concentration Product KSN2448 (Stainless Table) Test Location: Under Table Limit: 1 14:03:21 2 0 0 0 0 71 0 0 0 0 2 14:05:24 0 0 0 0 0 0 0 0 0 0 3 14:06:37 2 0 0 0 0 71 0 0 0 0 95% UCL (if 2 to 9 locations) 6 0 0 0 0 195 0 0 0 0 Remarks : Consistant with ISO class 3 particle concentrations

2.5.2. K Series Stainless Steel Frame with 1 Phenolic Resin Top Table Top Test 2.5.2.1. Airborne Particle Count Record Airborne Particle Concentration Product KSY2448 (Resin Table) Test Location: Table Top Limit: 1 14:10:30 0 0 0 0 0 0 0 0 0 0 2 14:11:41 0 0 0 0 0 0 0 0 0 0 3 14:12:54 0 0 0 0 0 0 0 0 0 0 95% UCL (if 2 to 9 locations) 0 0 0 0 0 0 0 0 0 0 Remarks : Consistant with ISO class 1 particle concentrations Under Table Test Airborne Particle Concentration Product KSY2448 (Resin Table) Test Location: Under Table Limit: 1 14:16:41 0 0 0 0 0 0 0 0 0 0 2 14:17:51 4 2 1 0 0 141 71 35 0 0 3 14:19:05 4 0 0 0 0 141 0 0 0 0 95% UCL (if 2 to 9 locations) 11 5 2 0 0 391 172 86 0 0 Remarks : Consistant with ISO class 3 particle concentrations 2.6. Observations The tables were sturdy and easy to assemble. They both cleaned up well with IPA/DI and cleanroom wipes. The quality of each table is inline with approved cleanroom materials and fixtures.