STUDY OF COOLING SYSTEM WITH WATER MIST SPRAYERS FUNDAMENTAL EXAMINATION OF PARTICLE SIZE DISTRIBUTION AND COOLING EFFECTS

Similar documents
Study of Cooling System with Water Mist Sprayers: Fundamental Examination of Particle Size Distribution and Cooling Effects

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

Analysis of wind and radiant environment in street canyons for production of urban climate maps at district scale

therefore cold air is released to the outdoor space, contributing to changes in the outdoor microclimate (Figure 1). This results in a cool spot in th

HEAT TRANSFER AND FLOW CHARACTERISTICS OF A BACKWARD-FACING STEP FLOW WITH MIST

Chapter 3. Basic Principles. Contents

Climatically Adapted Piloti Arrangement and Ratio of Residential Blocks in a Subtropical Climate City

Chapter 3- Energy Balance and Temperature

5) The amount of heat needed to raise the temperature of 1 gram of a substance by 1 C is called: Page Ref: 69

2. Climate (Outdoor) Altitude. Distance from the ocean. Conditions of the ocean. Store/release heat. angle of solar radiation Amount of solar energy

The inputs and outputs of energy within the earth-atmosphere system that determines the net energy available for surface processes is the Energy

Chapter 5 MATHEMATICAL MODELING OF THE EVACATED SOLAR COLLECTOR. 5.1 Thermal Model of Solar Collector System

AIJ COOPERATIVE PROJECT FOR PRACTICAL APPLICATIONS OF CFD TO URBAN VENTILATION

VALIDATION OF LES FOR LOCAL HEAT ENVIRONMENT IN TOKYO -COMPARISON WITH FIELD MEASUREMENT DATA-

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

( ) = 1005 J kg 1 K 1 ;

METHOD OF IN-SITU MEASUREMENT OF THERMAL INSULATION PERFORMANCE OF BUILDING ELEMENTS USING INFRARED CAMERA

LES of wind turbulence and heat environment around dense tall buildings

Final Examination. Part A Answer ONLY TWELVE QUESTIONS in Part A. (Each question is 3 points)

UNIT FOUR SOLAR COLLECTORS

Keywords: Large-eddy simulation, Turbulent coherent structure, Four quadrant analysis, Integral scale

Convection and Heat Transfer in the Atmosphere

EVALUATION OF VENTILATION PERFORMANCE IN VOID SPACE BY EXCEEDANCE PROBABILITIES BASED ON CFD SIMULATION

Global Climate Change

5. Thermal Design. Objective: Control heat flow to: Maintain comfortable indoor conditions

Radiative-Convective Models. The Hydrological Cycle Hadley Circulation. Manabe and Strickler (1964) Course Notes chapter 5.1

Estimation Method of Emission Rate and Effective Diffusion Coefficient using Micro Cell

Chapter 1 INTRODUCTION AND BASIC CONCEPTS

MATTER IN OUR SURROUNDINGS

EFFECT OF PILOTI ON WIND ENVIRONMENT IN RESIDENTIAL AREA IN A HOT AND HUMID CITY --TAKING RESIDENTIAL AREA IN WUHAN AS STUDY CASE --

ARCH 348 BUILDING AND ENVIRONMENTAL SYSTEMS

Internal Flow Measurements of Turbomachinery using PIV

Department of Energy Science & Engineering, IIT Bombay, Mumbai, India. *Corresponding author: Tel: ,

Simplified Collector Performance Model

Level 7 Post Graduate Diploma in Engineering Heat and mass transfer

Energy: Warming the earth and Atmosphere. air temperature. Overview of the Earth s Atmosphere 9/10/2012. Composition. Chapter 3.

DYNAMIC INSULATION APPLIED TO THE RESIDENTIAL BUILDING (PART 2) Numerical Evaluation of Thermal Insulation Effect on Air Supply Window System

Double-Skin Facade in Low-Latitude: Study on the Absorptance, Reflectance, and Transmittance of Direct Solar Radiation

CFD Analysis of Gas Cooling

Laboratory Exercise #7 - Introduction to Atmospheric Science: The Seasons

NUMERICAL INVESTIGATION ON THE EFFECT OF COOLING WATER SPRAY ON HOT SUPERSONIC JET

Atmospheric Composition and Structure

Atmospheric Sciences 321. Science of Climate. Lecture 13: Surface Energy Balance Chapter 4

A SIMPLE MODEL FOR THE DYNAMIC COMPUTATION OF BUILDING HEATING AND COOLING DEMAND. Kai Sirén AALTO UNIVERSITY

Weather and Climate: Detailed Outline

MECHANISM BEHIND FREE /NATURAL CONVECTION

Warming Earth and its Atmosphere The Diurnal and Seasonal Cycles

Analysis of Flow inside Soundproofing Ventilation Unit using CFD

A Study on Evaporation Phenomenon of Trap Seal Water

Prototype Heat Island Application

Visualization of high-speed gas jets and their airblast sprays of cross-injected liquid

MODELING ON THE BREAKUP OF VISCO-ELASTIC LIQUID FOR EFFERVESCENT ATOMIZATION

Solar Flat Plate Thermal Collector

Thursday, June 5, Chapter 5: Condensation & Precipitation

A NUMERICAL MODEL-BASED METHOD FOR ESTIMATING WIND SPEED REGIME IN OUTDOOR AND SEMI-OUTDOOR SITES IN THE URBAN ENVIRONMENT

Naoshi Kakitsuba * Meijo University, JAPAN

ECE309 INTRODUCTION TO THERMODYNAMICS & HEAT TRANSFER. 13 June 2007

Paper ID ICLASS EFFECTS OF CAVITATION IN A NOZZLE ON LIQUID JET ATOMIZATION

Pillai and Yoshie. Journal of Urban and Environmental Engineering, v.7, n.1, p ISSN doi: /juee.2013.v7n1.

MHD Simulation of Solar Chromospheric Evaporation Jets in the Oblique Coronal Magnetic Field

HEAT TRANSFER THERMAL MANAGEMENT OF ELECTRONICS YOUNES SHABANY. C\ CRC Press W / Taylor Si Francis Group Boca Raton London New York

Outline. Stock Flow and temperature. Earth as a black body. Equation models for earth s temperature. Balancing earth s energy flows.

A Zone Model for Fast Verification of Release of Ultrafine Water Mist for Fire Extinction in Compartments

Lecture Ch. 6. Condensed (Liquid) Water. Cloud in a Jar Demonstration. How does saturation occur? Saturation of Moist Air. Saturation of Moist Air

Detailed Numerical Simulation of Liquid Jet in Cross Flow Atomization: Impact of Nozzle Geometry and Boundary Condition

Numerical Simulation of the Evolution Law of Tornado Wind Field Based on Radar Measured Data

HEAT, TEMPERATURE, AND ATMOSPHERIC CIRCULATION

The Atmosphere and Atmospheric Energy Chapter 3 and 4

Evaporation Velocity of Cryogenic Liquid With and Without Spreading

INFLUENCE OF SEA SURFACE TEMPERATURE ON COASTAL URBAN AREA - CASE STUDY IN OSAKA BAY, JAPAN -

TREES Training for Renovated Energy Efficient Social housing

Effect of moisture transfer on heat energy storage in simple layer walls

A Typical Meteorological Year for Energy Simulations in Hamilton, New Zealand

CFD calculations of the test 2-4 experiments. Author: G. de With

Cool Roofs Standards & the ECRC Product Rating Program

HEAT TRANSFER PROFILES OF AN IMPINGING ATOMIZING WATER-AIR MIST JET

2-D CFD analysis of passenger compartment for thermal comfort and ventilation

Numerical study of fire whirlwind taking into account radiative heat transfer

Table of Contents. Chapter: Atmosphere. Section 1: Earth's Atmosphere. Section 2: Energy Transfer in the Atmosphere. Section 3: Air Movement

Considerations of Urban Design and Microclimate in Historical Buildings Environment under Climate Change

Combined GIS, CFD and Neural Network Multi-Zone Model for Urban Planning and Building Simulation. Methods

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel

Simulation of Liquid Jet Breakup Process by Three-Dimensional Incompressible SPH Method

Greenhouse Steady State Energy Balance Model

CHAPTER 8 ENTROPY. Blank

Cutting Fluid Effects on Machine Shop Air Quality

NUMERICAL SIMULATION OF RADIATION PROPAGATION THROUGH WATER MIST. E. BLANCHARD (1,2), P. BOULET (1), S. DESANGHERE (2) and E.

RELATION OF SURROUNDING BUILDING CONFIGURATION AND MITIGATION EFFECTS OF SCHOOL LAWN PLANTING

Importance of clouds. climate. ocean. radiation. life. hydrological cycle. latent heat + loading. clouds & precip + aerosols.

Moisture content in concrete

EFFECT OF THE FLOW OF LARGE WATER DROPLETS

Laboratory Exercise #7 - Introduction to Atmospheric Science: The Seasons and Daily Weather

Chapter 3. Multiple Choice Questions

Lecture 4: Global Energy Balance

Lecture 4: Global Energy Balance. Global Energy Balance. Solar Flux and Flux Density. Blackbody Radiation Layer Model.

PHYSICAL GEOGRAPHY. By Brett Lucas

Thermal Analysis by Conduction Convection and Radiation in a Power Cable

In the Psy. Ch., plot point o, r, h r = 51.0 kj/kg, h o = 85 kj/kg

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

Transcription:

STUDY OF COOLING SYSTEM WITH WATER MIST SPRAYERS FUNDAMENTAL EXAMINATION OF PARTICLE SIZE DISTRIBUTION AND COOLING EFFECTS Yamada Hideki 1, Yoon Gyuyoug 1 Okumiya Masaya 1, Okuyama Hiroyasu 2 1 Graduate School of Environmental Studies, Nagoya University 2 SHIMIZU CORPORATION ABSTRACT A cooling system spraying micro water droplets could prove useful in mitigating temperature increases in urban areas by using heat from water evaporation, a process that consumes only small amounts of water and energy. If water mist is sprayed in a semi-outdoor area, for example under a canopy, it could potentially improve conditions on hot days. However, there is little reference data concerning the design or control of such systems. In order to propose a method for designing and predicting the performance of a water mist system, we discuss differences in cooling effects in the context of particle size distribution of water mist. From the results of numerical fluid analysis, it was observed there is no significant difference in temperature reduction for distribution of different particle sizes. However, the water particles remained in a lower position when the particle size distribution increased. KEYWORDS Water mist, Urban heat island, Numerical fluid analysis INTRODUCTION In recent years, warming of urban areas in summer has been considered a problem, known as the urban heat island. One means of mitigating this effect involves spraying micro water droplets. This method suppresses the temperature rise in urban areas by using the heat of evaporating water, while utilizing only small amounts of water and energy. If water mist is sprayed in a semi-outdoor area, for example under a canopy, it could potentially improve conditions on hot days. Through a field experiment (Yamada et al 2006), we have verified the effectiveness of this method and confirmed a temperature reduction under a canopy of up to about 3 C. The use of water mist systems is expected to become popular in the future. However, there is little reference data concerning the design or control of such systems. Therefore, the aim of this study is to propose a method for designing and predicting the performance of water mist systems. In this study, we conduct a numerical fluid analysis and then discuss the particle size distribution and the cooling effect of water mist. OUTLINE OF SIMULATION The semi-outdoor area, which is 50 m long, 15 m wide and 4 m high, shown in Fig. 1 was analyzed under the assumption that it was a waiting area at an event halltime. The boundary conditions in Table 1 are used. The air temperature and humidity in this area derived from outdoor temperature and humidity parameters of Tokyo summers. (Parameters used were air temperatures of 33.4 C, and humidity of 58%RH). Also, it was assumed that there is the airflow (wind velocity is 0.1 m/s) of the outdoor wind. The roof is made of PVC-coated glass-fiber and the ground is concrete. Sol-air temperature and thermal transmittance were given for the of the roof. At the ground, a temperature was given, which was estimated in consideration of heat transfer at ground. (heat convection, heat difussion to the ground and transmissive solar radiation of the roof) horizontal solar radiation: 1026W/ m2 inflow velocity: 0.1m/s outside temperature: 33.4 outside humidity : 18.9g/kg'(58%RH) Z Y spray position (spraying downward) 3.5m 15m 4m 7.5m q 1 q 2 15m atmospheric pressure X 50m q 3 Figure 1. Diagram of calculation area. - 1389 -

Table 1. Boundary conditions. Table 2 Spraying conditions Surface Roof (z=4) Ground (z=0) Air inflow (x=0) Air outflow (x=50) Side (y=0, y=15) Condition Material: PVC-coated glass-fiber plain-weave Thickness: d t =0.53mm Thermal conductivity: λ t =0.1125W/m K Solar absorptance: a t =10.8% Solar transmittance: τ t =13.7% Horizontal solar radiation: J=1026W/ m 2 Heat transfer coefficient: α o =23W/m 2 K Sol-air temperature: 38.2 C Material: concrete paved Depth: d c =5m Thermal conductivity: λ c =1.4W/m K Solar absorptance: a c =60% Heat transfer coefficient: α oc =23W/m 2 K Underground temperature (annual mean temperature in Tokyo): θ s =15.6 C Heat balance at ground : q 1 +q 2 +q 3 =0 Convective heat transfer from the ground: q 1 =α oc (θc -θo) Transmissive solar radiation of the roof: q 2 =τ t a c J Heat diffusion to the ground: q 3 =λ c /d c (θ s - θ c ) Ground temperature: θ c =29.8 C Inflow velocity: 0.1m/s Outside temperature: 33.4 C Outside absolute humidity: 18.9g/kg' Pressure: atmospheric pressure Free-slip Adiabatic boundary mass fraction(-) Mass flow rate 0.83g/s Water temperature 33.4 C Spray cone angle 50 Injection pressure 6MPa Table 3 Atomizer s analysis parameters Case1 24 Sheet constant [1] Case2 12 Case3 3 Ligament constant [2] 0.5 Atomizer dispersion angle [3] 6 0.20 0.15 0.10 0.05 case1 0.00 0 10 20 30 40 50 60 70 80 particle diameter(μm) Fluent Ver. 6.3 software package was used for this numerical fluid analysis. In the calculation area, the heat transfer between the water mist particles and air, the evaporation of mist and conservation of momentum are taken into consideration by using the Discrete Phase Model. The pressure-swirl Atomizer Model, which is based on the swirl atomizer used at the venue of Expo Aichi 2005, was adopted for this analysis. Table 2 gives the spraying conditions of the atomizer. While Table 3 indicates the atomizer s analysis parameters. The particle size distribution generated by an atomizer is determined by the spraying conditions given in Table 2 and also by the atomizer s characteristics, that is the atomizer s analysis parameters given in Table 3. For the purpose of this study, only the sheet constant was varied to generate different particle size distributions under the same spray conditions. Figure 2 shows the particle size distributions for the three cases considered in this analysis [4]. Under the conditions of the above mentioned analysis, we conducted simulations up to a steady state in each case. Figure 2. Particle size distributions. DISCUSSION AND RESULT ANALYSIS Single-Nozzle: Results and Discussion Figures 3 to 5 show the vertical cross-section temperature contours at the spray location (y=7.5 m) for the three cases. Figures 6 and 7 show the temperature distribution and the absolute humidity distribution at 1.5 m (y=7.5 m, z=1.5 m) above the ground. For each case, the air temperature decreased and the humidity increased about 1.5 C at the spray location (x 15 m). Also, about 2.5m behind the spray position, it was observed that the maximum air temperature increasing was about 0.5 C. This phenomenon probably occurred because the downward airflow from the mist spray position drew the surrounding warm air. The wind direction diagram of Fig. 8 also confirms this phenomenon. Also, there was no significant temperature reduction at the position behind spray location (from x=20 m to x=50 m). - 1390 -

The absolute humidity increased to about 20.0 g/kg' at the spray location to only about 19.2 to 19.5 g/kg' at the position behind the spray location, representing an increase of 0.3 to 0.6 g/kg. Figure 9 shows the remaining particle mass distribution at every height of the analysis area. The total mass of remaining particles was smaller for Case 1 than for the other two cases, indicating a fast evaporation rate. In Case 3, which is for comparatively large particles, there was a large mass of particles remaining in the area. When the mass of remaining particles was analyzed 37.3 36.4 33.6 31.7 as a function of height, the particles remained, even at a height of 1.4 m. On the basis of the above results, it was found that the temperature reduction does not vary greatly with differences in particle size distribution. However, as the particle size increases, it takes time longer for the particles to completely evaporate, and particles may remain even at low heights. Thus, it can say that the particle size is an important parameter in mist design when considering the spray height. 29.8 C Figure 3. Case 1, air temperature contours at the spray location (y=7.5m). Figure 4. Case 2, air temperature contours at the spray location (y=7.5m). Figure 5. Case 3, air temperature contours at the spray location (y=7.5m). temperature( ) 34.0 33.5 33.0 32.5 32.0 31.5 31.0 case1 without spray distance from inflow, x(m) Figure 6. Air temperature dstribution at the spray location of 1.5m height (y=7.5m, z=1.5m). absolute humidity(g/kg') 20.5 20.0 19.5 19.0 18.5 case1 without spray distance from inflow, x(m) Figure 7. Absolute humidity dstribution at the spray location of 1.5m height (y=7.5m, z=1.5m). Figure 8. Airflow direction at spray location (y=7.5m) - 1391 -

height (m) 3.8 ~ 3.8 4.0 3.6 ~ 3.6 3.8 3.4 ~ 3.4 3.6 3.2 ~ 3.2 3.4 3.0 ~ 3.0 3.2 2.8 ~ 2.8 3.0 2.6 ~ 2.6 2.8 2.4 ~ 2.4 2.6 2.2 ~ 2.2 2.4 2.0 ~ 2.0 2.2 1.8 ~ 1.8 2.0 1.6 ~ 1.6 1.8 1.4 ~ 1.4 1.6 1.2 ~ 1.2 1.4 1.0 ~ 1.0 1.2 case1 0.8 ~ 0.8 1.0 0.6 ~ 0.6 0.8 0.4 ~ 0.4 0.6 0.2 ~ 0.2 0.4 0.0 ~ 0.0 0.2 0.00 0.05 0.10 0.15 remaining particle mass (g) Figure9. Remaining particle mass distribution at each height 37.3 36.4 33.6 31.7 Multiple Nozzles: Results and Discussion This section discusses the effect of particle size distribution when multiple nozzles are arranged at equal intervals. The same calculation conditions were used as for the single-nozzle scenario. Three nozzles were used, and the 2nd and 3rd were installed at 2.5 m intervals from the single-nozzle spray position. The interval was set to 2.5 m intend to reduce the temperature increase behind the spray position. Only Cases 2 and 3, which had large particles, were investigated for particle size distribution. Also, Cases 2' and 3' have the same condition of particle size distributions as Cases 2 and 3 respectivly. Figures 10 and 11 show the cross-sectional (y=7.5 m) temperature contours for Cases 2' and 3'. Figures 12 and 13 show the air temperature distribution and the absolute humidity distribution at a height of 1.5 m (y=7.5 m, z=1.5 m). Similarly to the case of the single nozzle, there was no significant difference in the temperature reduction for different particle size distributions. 29.8 C Figure 10. Case 2, air temperature contours at the spray location (y=7.5m). temperature( ) Figure 11. Case 3, air temperature contours at the spray location (y=7.5m). 34.0 33.5 ' ' 33.0 without spray 32.5 32.0 31.5 31.0 distance from inflow, x(m) Figure 12. Air temperature dstribution at the spray location of 1.5m height (y=7.5m, z=1.5m). absolute humidity(g/kg') 20.5 20.0 19.5 19.0 18.5 ' without spray ' distance from inflow, x(m) Figure 13. Absolute humidity dstribution at the spray location of 1.5m height (y=7.5, z=1.5m) The air temperature right below each nozzle was the case of a signle nozzle. Compared with absolute about 31.3 C, which is approximately equal to that in humidity distributon, the humidity just below the 1st - 1392 -

nozzle was similar to the single-nozzle case. However, the humidty just below the more behind nozzle was higher than that of ahead. The humidity of the 3rd nozzle was about 0.2 g/kg greater than that for the corresponding case of the single nozzle. Figures 14 and 15 show the horizontal distribution of air temperature at a height of 1.5 m for Cases 2 and 2. In the cases where multiple nozzles are used, the air temperature in front of the 1st nozzle was lower than with the single nozzle. The reason why the difference of temperature distribution was considered that the downward flow by water mist evaporation was greater than in the case of the single nozzle, and that the heat of mist vaporization was diffused more easily because of the downflow due to mist blocking the inflow of outdoor air. This phenomenon may have occurred because the side boundary condition was a wall without of new air inflow or outflow. Figure 16 shows the particle mass distribution at different heights. In comparing the cases of single and multiple nozzles, we see that the maximum mass of remaining particles was found at almost the same height. As for the minimum height at which particles remained, however, little remained at a height of 1.8 m or lower for both Cases 2 and 2', which had comparatively small particle size distribution. Comparing Cases 3 and 3', which had comparatively large particle size distribution, a small number of particles remained even at a height of 1.0 m for Case 3'. 33.4 32.9 32.4 31.8 31.3 Figure 14. Horizontal distribution of air temperature at a height of 1.5 m with a single nozzle (Case2). Figure 15. Horizontal distribution of air temperature at a height of 1.5 m with three nozzles (Case2 ). height (m) 3.8 ~ 3.8 4.0 3.6 ~ 3.6 3.8 3.4 ~ 3.4 3.6 3.2 ~ 3.2 3.4 3.0 ~ 3.0 3.2 2.8 ~ 2.8 3.0 2.6 ~ 2.6 2.8 2.4 ~ 2.4 2.6 2.2 ~ 2.2 2.4 2.0 ~ 2.0 2.2 1.8 ~ 1.8 2.0 1.6 ~ 1.6 1.8 1.4 ~ 1.4 1.6 1.2 ~ 1.2 1.4 1.0 ~ 1.0 1.2 0.8 ~ 0.8 1.0 0.6 ~ 0.6 0.8 ' 0.4 ~ 0.4 0.6 ' 0.2 ~ 0.2 0.4 0.0 ~ 0.0 0.2 0.00 0.10 0.20 0.30 0.40 remaining particle mass (g) Figure 16. Remaining particle mass distribution at each height. CONCLUSION In this basic study on the cooling effect of mist sprays, we discussed the cooling effect in terms of particle size distribution and the height distribution of remaining particles. A significant difference in the temperature reduction for different particle size distributions was not observed. As the particle size distribution increased, however, the minimum height of remaining particles was lower. Mist particles remained at lower heights when the number of nozzles was increased. And this effect was greater for larger particle sizes. In general, however, it is known that greater spray pressure is necessary for generating finer mists, and it results increase the pump power. The above results demonstrate that spray height and particle size need to be selected carefully if the minimum height of remaining particles is to be strictly controlled. In the future, we will study the cooling effect of mist spraying for varying outdoor conditions (air temperature and himidity) and compare the results with actual measurements. ANNOTATION [1] The swirl atomizer nozzel contains an internal swirl vane that produce rotational flow. The swirl liquid forms a thin sheet along the inside walls of the injector. Generally, aerodynamic instability causes a wave on the sheet to break up into liquid ligaments and droplets. In this process, the parameter of Sheet constant is determined by the maginitude of the wave, and Sheet constant 12 is recommended by previous - 1393 -

literature. The particle size becomes smaller when this value becomes larger. [2] If a liquid sheet wave is short, the ligament thickness is proportional to the wavelength. The ligament constant means this constant of proportion. It is given a default value of 0.5 for purposes of this study. [3] The atomizer dispersion angle is the parameter of dispersion angle as the liquid ligament breaks up into droplets. Since the spray pattern in this study is hollow-cone spray, it was assigned a value of 6. [4] The droplets size distribution of the atomizer is determined by the Rosin-Rammler Diameter Distribution Method, and the Spread parameter is 3.5. REFERENCES Yamada Hideki et al, Study on the Cooling Effects of Water Mist Sprayer, Summaries of technical papers of the annual meeting of the Architectural Institute of Japan 2006 (Japanese). Institute for Liquid Atomization and Spray Systems, Atomization Technology, Morikita Publishing Co., Ltd. 2001 (Japanese) David P. Schmidt et al, Pressure-Swirl Atomization in the Near Field, SAE Paper 01-0496, SAE, 1999 Hayashi Akinori et al, Development of Heat Island Control System with Water Mist Sprayer Pat.3 Field measurement and computational fluid dynamics calculation, Summaries of technical papers of the annual meeting of the Architectural Institute of Japan 2005 (Japanese). - 1394 -