Fachgesprach 12. HVAC Pumps. For Project Managers

Similar documents
TOTAL HEAD, N.P.S.H. AND OTHER CALCULATION EXAMPLES Jacques Chaurette p. eng., June 2003

The following article was authored by Jacques Chaurette, President Fluide Design, Inc. ( All rights reserved.

Department of Energy Fundamentals Handbook. THERMODYNAMICS, HEAT TRANSFER, AND FLUID FLOW, Module 3 Fluid Flow

barmesapumps.com SELF-PRIMING CENTRIFUGAL TRASH PUMP SPECIFICATIONS Series: SH8-U Suction: 8" Discharge: 8" Spherical solids handling: 3"

Basic Math Concepts for Water and Wastewater Operators. Daniel B. Stephens & Associates, Inc.

PUMP PERFORMANCE MEASUREMENTS Jacques Chaurette p. eng. April 2003

Chapter Four Hydraulic Machines

Calio-Therm NC Type Series Booklet

Chapter Four Hydraulic Machines

Fast and Ultimate Vibration Field Solution: From Problem Detection to Field Performance Validation

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

PUMP SYSTEM ANALYSIS AND SIZING. BY JACQUES CHAURETTE p. eng.

WATER DISTRIBUTION NETWORKS

Pressure and Flow Characteristics

TPH. 60Hz. Standard mode TPH 4T 2K. Code TPH 4T 2K S F A H

Interactivity-Compatibility. TA Hydronic College Training

1. DEFINITIONS. B. BTUH Hourly Rate of change in Mass Heat BTUH = * CFM * ΔT (Air Heat Transfer) BTUH = 500 * GPM * ΔT (Water Heat Transfer)

P U M P S. The quality standard for hydraulic efficiency and suction lift. PERIPHERAL PUMPS TEP/ TSP - SERIES 50Hz

Northern Lesson 2 Gear Pump Terminology. Gear Pump 101. Lesson 2: Gear Pump Terminology. When your reputation depends on it!

Contents. Identification LHC. Horizontal split case pumps. Type key. Identification Type key

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Experimental and Numerical Investigations of the Effect of Net Positive Suction Head on Water Hammer In Pipeline Systems

NEBB Fundamental Formulas

P U M P S. The quality standard for hydraulic efficiency and suction lift. PERIPHERAL PUMPS TEP/ TSP - SERIES 50Hz

CIVE HYDRAULIC ENGINEERING PART II Pierre Julien Colorado State University

Thermal & Fluids PE Exam Technical Study Guide Errata

Pumping Stations Design For Infrastructure Master Program Engineering Faculty-IUG

Determining the G Values or Effectiveness of Chemical Diffusers and Injectors

BV SERIES. VERTICAL BLOWER COIL UNITS Nominal Sizes 2 thru 10 Ton

Chemical Engineering 374

9. Pumps (compressors & turbines) Partly based on Chapter 10 of the De Nevers textbook.

Introduction to Fluid Machines, and Compressible Flow Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

COURSE CODE : 3072 COURSE CATEGORY : B PERIODS/ WEEK : 5 PERIODS/ SEMESTER : 75 CREDIT : 5 TIME SCHEDULE

CHAPTER EIGHT P U M P I N G O F L I Q U I D S

BNA Series. PLENUM FAN with Backward Wheels

Investigations on the Performance of Centrifugal Pumps In Conjunction With Inducers

CHAPTER 12 Turbomachinery

Clausing Industrial, Inc. Variable Speed 20" Single and Multi-spindle, Belt Drive Industrial Drill Presses

HEAT CONTENT DECREASES U D R HEAT CONTENT INCREASESO. Btu/lb

IJREAS Volume 2, Issue 2 (February 2012) ISSN:

Lecture 3: Electrical Power and Energy

ISO 9906 INTERNATIONAL STANDARD. Rotodynamic pumps Hydraulic performance acceptance tests Grades 1 and 2

SOLUTION (17.3) Known: A simply supported steel shaft is connected to an electric motor with a flexible coupling.

SUMMER 14 EXAMINATION

The FLUX F 430 with mechanical seal

EVOTRON WET ROTOR ELECTRONIC CIRCULATORS TECHNICAL DATA APPLICATIONS ADVANTAGES

Innovative Solutions from the Process Control Professionals

LES. Single-stage end-suction pumps Identification Type key

Standardized Chemical Pumps. Fields of Application. Designation. Design. Operating Data. Type Series Booklet /7-10 G2 CPK-H

Copyright by KSB Aktiengesellschaft Published by: KSB Aktiengesellschaft, Communications (V5), Frankenthal / Germany

Contents. 2 Basic Components Aerofoils Force Generation Performance Parameters xvii

Methods For Reducing Vibration (Intro to Vibration Control) Robert J. Sayer, PE President, The Vibration Institute Owner, Applied Structural Dynamics

Chapter 4. Turbomachinery. 4.1 Introduction. 4.2 Pumps

2.0 KEY EQUATIONS. Evaporator Net Refrigeration Effect. Compressor Work. Net Condenser Effect

Chapter 6. Hydraulic cylinders/rams (linear motors), and Lines/fittings. - Transforms the flow of a pressurized fluid into a push or pull of a rod.

PFI Closed circuit cooling towers

EUROVENT 8/12 SOUND TEST METHOD FOR DUCTED FAN COIL UNITS. FCP 2008 testing procedures FCP acoustical test method pag. 1

CORIOLIS MASS FLOW METERS FOR GAS AND LIQUID MEASUREMENT. Michael Keilty (Presented by Hubbard Donald) Endress + Hauser Flowtec AG

Fluid Flow Analysis Penn State Chemical Engineering

DOMESTIC HOT WATER PUMPS WITH FIXED-SPEED MOTOR, 3x400V AP-, AKP- and AEP- series, threaded G1/2 G1 ¼ LOREM IPSUM JE ZULT MAAR 60 HZ.

Fluid Properties: := 1.35 cp liquid viscosoty. m 3 density of the flowing liquid. sg:= specific gravity of the flowing liquid. Pipe System Conditions:

Applied Fluid Mechanics

MOTOR WIRING DATA From National Electrical Code 3 PHASE SQUIRREL CAGE INDUCTION MOTORS 230 Volt 460 Volt Min. # Max. Rating

Variable Speed 20" Single and Multi-spindle, Belt Drive Industrial Drill Presses

Estimation of Power Consumption by Centrifugal Pump with Reduced Impeller Size

Fluid Statics, Hydrodynamics and Hydraulic Machines

Plant Design LECTURE 8: REBOILER CIRCUIT DESIGN. Daniel R. Lewin Department of Chemical Engineering Technion, Haifa, Israel

9/20/11. Physics 101 Tuesday 9/20/11 Class 8" Chapter " Weight and Normal forces" Frictional Forces"

Centrifugal Machines Table of Contents

Pump ED 101. Confusing Units of Measure Work, Power, & Torque

Duct System Losses Are Total Pressure Losses

Introduction to Fluid Machines and Compressible Flow Prof. S.K Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Purpose of Today s Presentation

GRUNDFOS DATA BOOKLET MAGNA, UPE. Series 2000 circulator pumps

50 Hz n= 2900 rpm. Standardised EN 733 centrifugal pumps INSTALLATION AND USE. PERFORMANCE RANGE Flow rate up to 6000 l/min (360 m³/h) Head up to 98 m

High-efficiency Circulator Pump. Rio-Eco N / Rio-Eco Z N. Type Series Booklet

Cartridge Valves Technical Information. Quick reference

Developing component models for automated functional testing

Fluid Dynamics Midterm Exam #2 November 10, 2008, 7:00-8:40 pm in CE 110

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

Numerical Study of the Semi-Open Centrifugal Pump Impeller Side Clearance A. Farid Ayad *, H. M. Abdalla,A. S. Abo El-Azm Egyptian Armed Forces, Egypt

THE CERN CRYOGENIC TEST FACILITY FOR THE ATLAS BARREL TOROID MAGNETS

Pumps type MP Motor pump combination for mounting into tanks for on/off service

405 Compact Orifice Series and 1595 Conditioning Orifice Plate Flow Test Data Book and Flow Handbook

TECHNICAL INFORMATION Bulletin

Objectives. Power in Translational Systems 298 CHAPTER 6 POWER

A 954 C HD. Technical Description Hydraulic Excavator. Machine for Industrial Applications

D O T 1 ; O T 2 ; O T 3 ; O T i

ANSI - CURVE BOOK CHEMICAL PROCESS PUMPS

GRUNDFOS DATA BOOKLET MAGNA, UPE. Series 2000 circulator pumps

Piedmont Chapter Vibration Institute Training Symposium 10 May, 2012 FIELD BALANCING OF ROTATING MACHINERY.


Prima range. Alifter range. magnetical driven pumps in thermoplastic materials TMP TMA. centrifugal. self-priming

Radial piston pump type R and RG

CMA - B - C - D - CMR

Standardized Chemical Pumps to EN /ISO 2858/ISO 5199 sealless, with magnetic drive. Fields of Application. Designation. Design.

SHORTCUT CALCULATIONS AND GRAPHICAL COMPRESSOR SELECTION PROCEDURES

by Dr. Shibayan Sarkar Department of Mechanical Engineering

50/60 Hz. ecocirc XL and XLplus. high efficiency WET ROTOR circulators. ErP 2009/125/EC

Physical Principles 1.1 ENERGY CONVERSION IN CENTRIFUGAL PUMPS

Transcription:

Fachgesprach 12 HVAC Pumps For Project Managers WTF Philosophy: If you don t remember a certain formula, it's OK - you can always GoogleTheS h i t. But bad engineering CONCEPTS can hurt you. WTF Institute Mission: Teach correct engineering CONCEPTS to our PEs and PMs. 5/19/2016 1

General HVAC Pump Types 3" 2" - 4" 3" - 8" Small In-Line Pumps These pumps use in-line volutes and single suction impellers, but they are mounted with the shaft in a horizontal orientation. The flexible coupler and pump bearing assembly allow the use of standard motors. Close Coupled End Suction The single suction impeller is installed directly on the motor shaft, it has no coupling, so it s called a close coupled pump. Single Suction Pumps One of the most common types is the end-suction, base mounted, flexibly coupled pump The sizes above have no technical basis just a general observation of what we see in our local commercial buildings. 2

General HVAC Pump Types 8" Source: B&G TEH-1208A Double Suction Pumps: Single suction impellers are limited in terms of the flow rate they can handle, so double suction impellers must be used for high flow applications. These pumps are typically very large, base mounted, and flexibly coupled. Low Axial Thrust. Lower NPSHR. ECM, wet rotor, circulator uses the system fluid. The impeller is attached to the motor shaft, and the whole assembly rotates inside a stainless steel can. AHU Coil booster pumps? See next slide for example application. 3

General HVAC Pump Types 4

Pump References HVAC Pump Handbook, By James Rishel Highly recommended for HVAC Design Engineers and Project Managers Pump Handbook, By Igor Karassik The Bible of the pump community. (I don t have it.) JMP Co. Videos on Hydronics CHRIS EDMONDSON President James M. Pleasants Company, Inc. Greensboro, NC Good solid practical stuff. 5

The Pump Curve - 1 Required: 500 GPM @ 60' TDH Fluid: 60F Water Fixed Speed = 1780 RPM Impeller Dia. = 8.5625" 6

Note on the Pumped Fluid For this presentation the pumped fluid is water @ 60 F For glycol, and very high temperature water, corrections to the formulas are necessary 7

IP Units of Power ft.lb f /min and ft.lb f /sec or HP In our local HVAC trade we use IP units, for e.g.: Energy is ft.lb f or BTU Power is ft.lb f /min 1 HP = 33,000 ft.lbf/min 330 lb pulled up 100 feet in 1 minute = 33,000 ft.lb f per minute = 1 HP 33 lb pulled up 1000 feet in 1 minute = 33,000 ft.lb f per minute = 1 HP 3330 lb pulled up 10 feet in 1 minute = 33,000 ft.lb f per minute = 1 HP Head HEAD FLOW Flow Flow Rate x Head = Power 8

The Concept of Fluid Head HEAD is ENERGY. The units of HEAD are ft.lb f /lb f. Energy per pound of fluid. The lb f cancels out and so we use only ft. It helps if you remember the full units when thinking about pumps and flow. 500 gpm = 500 x 8.34 = 4,170 lb f /min Pump Selection 500 gpm @ 60 ft. Pump Power (Water HP) = 4,170 x 60 = 250,200 ft.lb f /min = 250,200 33,000 = 7.58 WHP 500 gpm = 500 x 8.34 = 4,170 lb f /min Throttled Valve 20 ft. HEAD Loss WASTED Power (Water HP) = 4,170 x 20 = 83,400 ft.lb f /min = 83,400 33,000 = 2.53 WHP 9

Head ft.lb lb (Disch PSI Suc Psi) x 2.31 NOT Discharge Pressure! The Pump Curve What is it? DP 26 10 36 26 psi x 2.31 = 60' What is the PUMP CURVE telling us? Very simply the Pump Curve tells us that: for any given flow (pounds/min) going through the pump, how many foot-pounds of energy will be added to every pound. 68.5 ft.lb/lb x 834 lb/min = 57,129 ft.lb/min 60 ft.lb/lb x 4170 lb/min = 250,200 ft.lb/min 59 ft.lb/lb x 4503 lb/min = 265,677 ft.lb/min For e.g. @ 500 gpm (4170 lb/min), 60 ft.lb of energy is being added to every pound, for a total of 60 x 4170 = 250,200 ft.lb/min The Best Efficiency Point (B.E.P) is where this product is a maximum on the curve 34 ft.lb/lb x 6672 lb/min = 226,848 ft.lb/min 100 x 8.34 = 834 lb/min 500 x 8.34 = 4170 lb/min 800 x 8.34 = 6672 lb/min Note as the flow rate increases the TDH decreases or a lower TDH shows a higher flow rate The pump can ONLY operate on its curve. If your field data plots a point elsewhere then you have a problem. (Happens all the time!) 10

The Pump Curve Nomenclature Shut-Off Head Shut-Off DP for Control Valves Operating Point Fixed Speed = 1780 RPM Impeller Dia. = 8.5625" 68.5 Best Efficiency Point B.E.P Accurate DP gage for troubleshooting Pump systems Run-Out 540 11

System Head Loss Calc. PD calcs documentation is now Code. Always run actual pump head calcs. Shouldn t take more than 30 minutes. Note the "fixed" DP control. Acts as a constant "static" head on the pump. Variable Primary System. Bypass not shown. Index Loop Rough approximation of Power: (500 gal/min x 8.34 lb/gal x 60 ft) / 33,000 ft.lb/min = 7.58 WHP @ 75% Pump Eff. = 7.6/0.75 = 10 BHP 12

The System Resistance Curve No Static Component ΔHead new ΔHead known = GPM new GPM known 2 2 GPM new ΔHead new = GPMknown x ΔHead known 2 GPM new ΔHead new = 500 x 60 ΔHead new 2 400 = 500 x 60 = 38.4' Note: Some experts recommend a slightly lower exponent than 2 above. But based on the accuracy of the underlying pipe and fitting pressure drop data, the added complexity is just not justified. 13

The System Resistance Curve With DP Control (Static Head) DP Control 18 ft The curve can still be plotted using the square relationship in the previous slide, modified by the constant offset of the static head. 14

Operating Point The Operating Point Best Efficiency Point B.E.P NOTES: The Pump Curve and the System Curve are two totally separate entities and yet when put together, the pump can ONLY operate where the system curve and the pump curve intersect. Energy IN = Energy OUT Pump impeller may have to trimmed to get the desired operating point. Energy OUT System Curve Pump Curve 8.0" Energy IN 9.0" 8.5" Impeller Dia. Note for next slide (Or the Pump speed may have to be adjusted to get the desired operating point.) Operating point is seldom fixed because the System Curve moves up and down as the control valves (or manual valves) change position. Most of this presentation will use a pump selected at: 500 gpm @ 60' Head (26 psi) 15

What Does a Pump Do? - A Thought Experiment " T h o u g h t " e x p e r i m e n t b e c a u s e o f f r i c t i o n l e s s a n d t h e f a c t t h a t t h e p u m p w o u l d q u i c k l y d e s t r o y i t s e l f i n t h e r e a l w o r l d! ( W e w i l l d i s c u s s w h y i n a l a t e r s l i d e. ) A l s o w e a r e i g n o r i n g p u m p i n t e r n a l p r e s s u r e d r o p a n d s y s t e m w a t e r e x p a n s i o n. PLAN View All Piping At The Same Elevation Frictionless Piping 0 ft Pressure Drop Frictionless Piping 0 ft Pressure Drop Flow Meter = 0 Flow Meter = 1,000?? Pump OFF FM Pump ON FM Suction DP 0.0 Discharge 0.0 0.0 All gages in PSI Suction DP 0.0 Discharge 0.0 0.0 500 gpm @ 60' Head (26 psi) 500 gpm @ 60' Head (26 psi) 16

What Does a Pump Do? - Thought Experiment -2 Elevation View Top Piping 100' Above Pump Frictionless Piping 0 ft Pressure Drop Frictionless Piping 0 ft Pressure Drop Flow Meter = 0 Flow Meter = 1,000?? Pump OFF FM 100 ft Pump ON FM DP DP Suction 0.0 Discharge Suction 0.0 Discharge 43 43 43 43 500 gpm @ 60' Head (26 psi) 500 gpm @ 60' Head (26 psi) 17

What Does a Pump Do? - Thought Experiment -3 Real System 60 feet (26 psi) PD @ 500 gpm flow Flat Horiz. Piping - No Vertical Elev. Flow Meter = 500 Flow Meter = 500 Pump ON FM 100 ft Pump ON FM DP Suction 26 Discharge 0.0 26 Suction DP 26 Discharge 43 69 500 gpm @ 60' Head (26 psi) 500 gpm @ 60' Head (26 psi) 18

What Does a Pump Do? - OVER-SIZED Pump Flow = 590 54 Pump ON FM Suction DP 23 Discharge 590 0.0 23 54 ft 2.3 ft/psi 23 psi Red Dashes Pump Selection Red Solid - Actual Selection 500 gpm @ 60' Head (26 psi) 19

What Does A Pump Do? - Takeaway CONCEPTS The Pump does not control the Differential Pressure reading across its flanges. The System Resistance does. For a healthy pump, a lower DP will always be caused by MORE flow NOT LESS flow. ( See why you cannot troubleshoot with bad concepts? ) The Pump does not "see" the static pressure of the system. (Of course, within working pressure limits of damage.) The Pump cannot pressurize its tail. The suction pressure can drop (or remain the same) when the pump starts but cannot increase. 20

What Happens When A Pump is Oversized? Valve Pressure Drop = 20 feet (choked) (Remember POWER is ft.lb f /min) Required 500 gpm Specified 60' TDH Actual 40' System Loss @ 500 gpm ft.lb f lb f 20 x 4170 = lb f min 83,400 ft.lb f min 83,400 ft.lb f min 1 HP x = 2.53 WHP ft.lb 33,000 f min WASTED POWER Trim or Reduce Speed 2.53 76% Pump Eff. = 3.33 BHP NOT ACCEPTABLE! Per new energy codes, either trim the impeller or provide a VFD 4,170 lb/min 21

The System Resistance Curve Open Cooling Towers Tower Sump Level Static Head Water will stand up to this level without the pump 15' Tower Static Head Condenser Pump Remember nozzle pressure drop for counter-flow towers 10' to 15'?? 22

The Pump Efficiency Curve Best Efficiency Point B.E.P 540 23

The Pump Iso-Efficiency Lines 24

The Pump Impeller Size & Trimming Suppose that for some reason we want to operate our pump at: 400 gpm @ 60 TDH 8.xx Trimmed We could trim the impeller as shown to get a new operating point. Notice what happens to the efficiency when you trim the impeller. Note: Remember the new codes want us to either trim the impeller or use VFD to slow down the pump, whenever the pump discharge valve is significantly choked for balance. 25

The Pump Impeller Size & Efficiency 9.0" 8.5" 8.0" For a given pump impeller housing, the efficiency of the pump decreases as the impeller diameter decreases. This is obvious from all manufacturer's curve plots. The reason has to do with the clearance between the wheel and the volute increasing and causing recirculation and turbulence. 26

The Pump VFD & Efficiency (VFD Peddler's Curve) System Curve 76% Constant Eff Lines Pump Curve 60 Hz 40 Hz 20 Hz 27

The Pump VFD & Efficiency (Real World Curve) 76% System Curve Constant Eff Lines Pump Curve Fixed Static 18 feet This is the DP control set-point for the VFD 60 Hz 40 Hz 20 Hz 28

Pump - POWER WHP = GPM x Head x Sp. Gr. 3960 Motor Input = 9.97 0.9 = 11 HP kw = 11 x 0.746 = 8.2 kw E motor = 0.90 BHP = 7.58 0.76 = 9.97 BHP E pump = 0.76 Water HP = 7.58 Our Selection: 500 gpm @ 60 TDH = 7.58 WHP Motor BHP = 7.58 0.76 = 9.97 BHP Motor Power Input = 9.97 0.9 = 11 HP = 11 x 0.746 = 8.2 kw WHP in kw = 7.58 x 0.746 = 5.65kW Wire to Water Efficiency: 5.65/8.2kW = 69% On an actual pump, you would measure the kw input to the motor by a Wattmeter for calculating WWE. 29

The Pump HP Lines HP Estimate Line Parallel to above and below 15 HP 10 HP 7.5 HP 30

The (often abused) Pump Affinity Laws GPM 1 GPM 2 Head 1 Head 2 BHP 1 BHP 2 = = = RPM 1 RPM 2 RPM 1 RPM 2 RPM 1 RPM 2 2 3 1. You cannot use these relationships for systems with "static" resistance. Most HVAC systems have a constant or static component. For e.g. our chilled water system example has 18' constant DP. 2. You cannot use these relationships to compare before and after you change system curve by throttling valves. GPM 1 GPM 2 Head 1 Head 2 BHP 1 BHP 2 = = = Dia. 1 Dia. 2 Dia. 1 Dia. 2 Dia. 1 Dia. 2 2 3 So if RPM is halved, the BHP goes down to (0.5) 3 = 0.125 = 12.5% 3. See previous VFD slides. 31

The (often abused) Pump Affinity Laws -2 1770 rpm System Curve passes through origin: OK to use Affinity Laws GPM 1 GPM 2 = RPM 1 RPM 2 500 250 = 1770 885 Works OK. 885 rpm 32

The (often abused) Pump Affinity Laws -3 1770 rpm System Curve has a fixed or static part: Cannot use Affinity Laws GPM 1 GPM 2 = RPM 1 RPM 2 Obviously does not work! 1160 rpm Fixed Static 18 feet This is the DP control set-point for the VFD 33

Valve Operation and the System Curve Throttling a manual or automatic valve in the index loop of a hydronic system moves the whole system resistance curve up. C B A Suppose a 2-way valves starts to modulate close in the index circuit of a hydronic system. The system curve will then "ride" the pump curve from point "A" to point "B" and then "C" etc. You cannot use any Affinity laws to predict the flow or head at points B and C. And you cannot use the square system curve flow and relationship either. Very common rookie mistake. 34

Single Volute - Radial Thrust & Pump Selection Region -34% -15% +15% OK +5% Good Cavitation!! Adapted from ASHRAE Sys & Equip Chap. 44 "Figure 5.19 (ASHRAE Fig. 29 above) is one of the most important figures in this book for the water system designer and user of volutetype pumps." Rishel, HVAC Pump Handbook 35

NPSH-R(equired) 36

NPSH-R(equired) Vs NPSH-A(vailable) OUR PUMP IS NOT A GOOD SELECTION FOR THIS DUTY. CHOOSE A PUMP WITH LOWER NPSHR. NPSH-R = 17.3' Pump Catalog Data Add 15% SF NPSH-R = 20 ft NPSH-A = 34 + X VP Piping Loss VP @ 85 F = 1.4 ft When both tower and pump are on the roof, or on the same floor: Keep suction piping short with minimum changes in direction. Keep pump close to the tower. (Not the condenser.) When the height X in feet is less than 4 or 5 feet, pay special attention to the pump suction piping. Reduce the pump suction pipe velocity below 6 FPS. Select Condenser Pump with low NPSHR If X is less than 2 feet, reduce the suction pipe velocity to 4 FPS and relocate pump suction strainer to the discharge side. 37

The Pump Curve RECAP Required: 500 GPM @ 60' TDH Fluid: 60F Water Fixed Speed = 1780 RPM Impeller Dia. = 8.5625" 38