Fabric STREAMER pro. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/04

Similar documents
Fabric Sport. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/02

Fabric Zetacoustic. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/07

Fabric ALEX. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/09

Curtain fabric type Ace Manufacturer Kvadrat A/S

Fabric VELOS STRATO. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/10

Fabric Corsica. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M111250/16

Fabric Medley Manufacturer Gabriel A/S

Fabric REFLECTACOUSTIC

Fabric TWIST MELANGE Manufacturer Gabriel A/S

Fabric Umbria III R. Measurement of sound absorption in a reverberation room according to EN ISO 354. Test Report No. M102794/13

Fabric Dazzle 6086 Manufacturer Carnegie Fabrics

Fabric UDINE. Measurement of sound absorption according to EN ISO 354. Test Report No. M102794/32

Renolit stretch ceilings

Roller blind fabric PRIMACOUSTIC R

Fabric XPRESS + PU-foam Manufacturer Gabriel A/S

stylegreen Iceland Moss / Reindeer Moss of the company FlowerArt

Fabric Medley Manufacturer Gabriel A/S

Fabric HUSH Manufacturer Gabriel A/S

Fabric RUNNER Manufacturer Gabriel A/S

Fabric EVENT SCREEN Manufacturer Gabriel A/S

Fabric XPRESS Manufacturer Gabriel A/S

Sound insulation of planted noise barriers

MEASUREMENTS OF SOUND ABSORPTION TIMBERCRETE

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 7MM TESTED WITH A 20MM AIR GAP IN A REVERBERATION ROOM.

Test Report. RI Acoustic Lab. Measurement of Sound Absorption Coefficient for RockDelta NoiStop Noise Barrier. 20 Feb. 07

TFI Report Sound Absorption Impact Sound Insulation

TFI Report Sound Absorption Impact Sound Insulation

REPORT ON THE DETERMINATION OF SOUND ABSORPTION COEFFICIENTS OF WOVEN IMAGE ECHO PANEL 24MM TESTED WITH NO AIR GAP MEASURED IN A REVERBERATION ROOM.

DELTA Test Report. Measurement of sound absorption coefficient for 15 mm Fraster felt Plus acoustic panels with mounting depth 45 mm

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION COEFFICIENTS OF OSCAR EVO-PANELS

DELTA Test Report. DANAK TEST Reg. no Measurement of Sound Absorption Coefficient for Kvadrat Soft Cells Wall Panel Type Time

Testing Procedure: AS ISO

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of curtains, manufacturer Vescom BV

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6986/ARL-SA6987 Revision 0 ARL

DELTA Test Report. Measurement of Sound Absorption for AqFlex ON, one Sample as a discrete Object. Performed for Flex Acoustics

Measurement of sound absorption coefficient for Fraster felt SpaceCover

LABORATORY MEASUREMENTS OF THE SOUND ABSORPTION OF CLASSICTONE 700 ASTM C Type E Mounting. Test Number 2

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6712/ARL-SA6713 Revision 0 ARL

ROLLEASE ACMEDA ACOUSTICAL PERFORMANCE TEST REPORT

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6266/ARL-SA6274 Revision 0 ARL

Measurement of Acoustic Properties of light weight concrete SL-Deck

Report. P.O. Box 70 NL 5700 AB Deurne The Netherlands Report number: A E-RA Date: 12 februari 2014 TS/TS/JW/A E-RA

Laboratory for Acoustics. Determination of the sound absorption (reverberation room method) of Airpanel, manufacturer Texdecor

TFI Report Sound Absorption Impact Sound Insulation

ETS-LINDGREN ACOUSTIC RESEARCH LABORATORY OFFICIAL LABORATORY REPORT ARL-SA6956 Revision 1 ARL

TFI Report Sound Absorption Impact Sound Insulation

REPORT N CR

Laboratory for Acoustics

Calcul des coefficients d'absorption alpha sabine

LABORATORY MEASUREMENT OF SOUND ABSORPTION OF SONOGLASS SPRAY-ON TREATMENT IN THREE CONFIGURATIONS

Report. Laboratory for Acoustics

Consultancy Report Ref: 9383-R01

Page 1 of 10 pages Appendix, 5 pages Report no.: P Glostrup, October 12th 2012 Project: Claimant:

A L I O N Technical Center. Test Report. Port Coquitlam, British Columbia, Canada

Technical Report. Project. The Laboratory Determination of The Random Incidence sound Absorption Coefficient of VertiQ Panels.

A L I O N Technical Center. Test Report

RIVERBANK ACOUSTICAL LABORATORIES

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

Report. Laboratory for Acoustics Determination of the sound absorption (reverberation room method) of different wired mats, manufacturer Rockwool

RIVERBANK ACOUSTICAL LABORATORIES

REPORT. Client. Test object. Date of testt. Results. Rönnåsgatan 5B Ulricehamn. (7 appendices) content of the

ISO INTERNATIONAL STANDARD

Laboratory for Acoustics

Paseo Recoletos, nº Madrid TEST REPORT

Sound Absorption Test Intertek. kraft paper softwall + softblock modular system. m o l o d e s i g n, l t d

LABORATORY MEASUREMENTS OF THE REDUCTION OF TRANSMITTED IMPACT NOISE PANETTI OVERLAID BY CONCRETE FLOORING

Summary. The basic principles of the simulation technique SERT

R & D AKUSTIKA * SIA. Test Report of laboratory Sound Insulation measurements Nr. 569 / 2011 AL 8.4. CUSTOMER: AEROC AS (Estonia)

Report. Laboratory for Acoustics

Development of a small-scale reverberation room

ISO INTERNATIONAL STANDARD. Acoustics Acoustic insulation for pipes, valves and flanges

Laboratory for Acoustics. Determination of the sound insulation of sliding door constructions, manufactured by Metaflex

Micro-perforated sound absorbers in stretched materials

Technical Note. Measurement of Sound Absorption for Flex Acoustics AqTube. Performed for Flex Acoustics. TC Project no.: T Page 1 of 7

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Certificate Sound reduction of building elements

ISO INTERNATIONAL STANDARD

Design and Acoustics Brought into Harmony

VK2 volume flow controller Overview

Modeling Measurement Uncertainty in Room Acoustics P. Dietrich

THE ACOUSTIC IMPEDANCE MEASUREMNET SYSTEM USING TWO MICROPHONES

The diagram below. to the by the. outlet into. calculation. Since TRANSMISSION VIA STRUCTURE. Vibration Via Supports Duct Breakout

Evaluation of standards for transmission loss tests

Part 2: Methods for special reverberation test rooms

EXPERIMENTAL VERIFICATION OF THE EUROPEAN METHODOLOGY FOR TESTING NOISE BARRIERS IN SITU: SOUND REFLECTION

TFI Report Impact Sound Insulation

Benefits of Reduced-size Reverberation Room Testing

inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE

Ceiling Diffuser. Type ADLR with circular face. Type ADLR-Q with square face 2/16/EN/8

INVESTIGATIONS INTO THE PERFORMANCE OF THE REVERBERATION CHAMBER OF THE INTEGRATED ACOUSTICS LABORATORY. A Thesis Presented to The Academic Faculty

TFI Report Impact Sound Insulation

A suggested method to be used to measure scattering coefficients of full scale samples.

ISO 3741 INTERNATIONAL STANDARD

CIRCO. Sound-attenuating transfer unit QUICK FACTS

Philips luminous textile with. Specifications sheet luminous textile panel

Basic Study on a Laboratory Measurement Method of the Normal-Incidence Scattering Coefficient

Users Manual. Marshall Day Acoustics. Double Panels Contact 33 Details Marshall Day 37.8 Acoustics PO Box

MAC Aura XB Acoustic Test Report

Laboratory and In Situ Sound Absorption Measurement under a Synthetized Diffuse Acoustic Field: a Case Study on Five Materials

Using an ambisonic microphone for measurement of the diffuse state in a reverberant room

Transcription:

Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de M.Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com 2014-05-12 Fabric STREAMER pro Measurement of sound absorption in a reverberation room according to EN ISO 354 Test Report No. M111250/04 Client: Consultant: Date of report: 2014-05-12 Delivery date of test objects: 2013-12-18 Date of test: 2014-01-07 Total number of pages: Certified quality management system according to ISO 9001 Accredited testing laboratory according to ISO/IEC 17025 Annette Douglas Textiles AG Klosterstrasse 42 5430 Wettingen Switzerland M.Eng. Philipp Meistring In total 13 pages; 6 pages text part, 2 pages Appendix A, 1 page Appendix B and 4 pages Appendix C. Müller-BBM GmbH HRB Munich 86143 VAT Reg. No. DE812167190 Managing directors: Dr. Carl-Christian Hantschk, Stefan Schierer, Dr. Edwin Schorer, Elmar Schröder, Norbert Suritsch

Table of contents 1 Task 3 2 Basis 3 3 Test object and test assembly 3 3.1 Test object 3 3.2 Test assembly 4 4 Execution of the measurements 5 5 Evaluation 5 6 Measurement results 5 7 Remarks 6 Appendix A: Appendix B: Appendix C: Test certificates Photos Description of test method, test facility and test equipment 2014-05-12 Page 2

1 Task On behalf of the company Annette Douglas Textiles AG, 5430 Wettingen, Switzerland, the sound absorption of the fabric STREAMER pro had to be measured according to EN ISO 354 [1] in the reverberation room. The fabric was tested in a flat and a folded arrangement with a distance of 150 mm to the reflective wall. 2 Basis This test report is based on the following documents: [1] EN ISO 354: Acoustics - Measurement of sound absorption in a reverberation room. 2003-05 [2] EN ISO 11654: Acoustics Sound absorbers for use in buildings Rating of sound absorption. 1997-04 [3] ASTM C 423-09a: Standard Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method. Revision: 09a [4] ISO 9613-1: Acoustics; Attenuation of sound during propagation outdoors; part 1: calculation of the absorption of sound by the atmosphere. June 1993 [5] EN 29053: Acoustics Materials for acoustical applications Determination of airflow resistance. March 1993 3 Test object and test assembly 3.1 Test object D The tested material is described by the manufacturer as follows: - curtain fabric STREAMER pro - material 90 % Trevira CS, 10 % FR The testing laboratory has measured as follows: - thickness: t = 0.83 mm - air flow resistance acc. to EN 29053 [5]: R s = 373 Pa s/m - area specific mass: m = 150 g/m² 2014-05-12 Page 3

3.2 Test assembly The installation of the test objects was carried out by employees of the test laboratory in the reverberation room of Müller-BBM. The test objects were installed in a flat and a folded arrangement. Both arrangements were mounted as follows: - clear distance to the reflective wall 150 mm - fixed directly underneath the ceiling on a metal rail (h = 50 mm) - measurement without enclosing frame - visible side corresponding to marking by the manufacturer faced to the reverberation room The mounting details for the tested arrangements are as follows: a) flat arrangement - mounting type G-150 acc. to EN ISO 354 [1], section 6.2.1 and Appendix B of EN ISO 354 [1] - one curtain width x height = 3500 mm x 3000 mm - total dimensions of the test surface (starting at the lower edge of the metal rail) width x height = 3500 mm x 2950 mm b) folded arrangement - mounting type following G-150 acc. to EN ISO 354 [1] - 100 % folded - two curtains with each width x height = 3500 mm x 3000 mm; one curtain with a missing corner 420 mm x 280 mm - total dimensions of the test surface (starting at the lower edge of the metal rail) width x height = 3500 mm x 2950 mm; minus surface at missing corner 210 mm x 280 mm Appendix B contains photos of the tested arrangements. 2014-05-12 Page 4

4 Execution of the measurements The measurements were executed and evaluated according to EN ISO 354 [1]. The test procedure, the test stand and the test equipment used for the measurements are described in Appendix C. 5 Evaluation The sound absorption coefficient α S was determined in one-third octave bands between 100 Hz and 5000 Hz according to EN ISO 354 [1]. In addition to the sound absorption coefficients the following characteristic values were determined according to EN ISO 11654 [2]. - practical sound absorption coefficient α p in octave bands - weighted sound absorption coefficient α w as single value: The weighted sound absorption coefficient α w is determined from the practical sound absorption coefficients α p in the octave bands of 250 Hz to 4000 Hz. According to ASTM C 423-09a [3] the following characteristic values were determined: - noise reduction coefficient NRC as single value: Arithmetical mean value of the sound absorption coefficients in the four onethird octave bands 250 Hz, 500 Hz, 1000 Hz and 2000 Hz; mean value rounded to 0.05. - sound absorption average SAA as single value: Arithmetical mean value of the sound absorption coefficients in the twelve onethird octave bands between 250 Hz and 2500 Hz; mean value rounded to 0.01. 6 Measurement results The sound absorption coefficients α S in one third-octave bands, the practical sound absorption coefficients α p in octave bands and the single values α w, NRC and SAA are indicated in the test certificates in Appendix A. 2014-05-12 Page 5

7 Remarks The determined test results only refer to the test specimens and prevailing conditions on the day of measurements. M. Eng. Philipp Meistring This test report may only be published and copied as a whole including all of its appendixes. The publishing of extracts requires the prior written consent of Müller-BBM GmbH. 2014-05-12 Page 6

Sound absorption coefficient ISO 354 Measurement of sound absorption in reverberation rooms Client: Annette Douglas Textiles AG Klosterstrasse 42, 5430 Wettingen, Switzerland Test specimen: Fabric STREAMER pro Mounting type G-150, flat arrangement Curtain fabric: curtain fabric STREAMER pro material 90% Trevira CS, 10% FR area specific mass m" = 150 g/m² air flow resistance Rs = 373 Pa s/m thickness t = 0.83 mm Tested arrangement: mounting type G-150 acc. to EN ISO 354, without enclosing frame one curtain width x height = 3500 mm x 3000 mm fixed directly underneath the ceiling on a 50 mm high metal rail wall distance 150 mm test surface width x height = 3500 mm x 2950 mm (starting at the lower edge of the metal rail) Room: E Volume: 199.60 m³ Size: 10.33 m² Date of test: 2014-01-07 θ [ C] r. h. [%] B [kpa] without specimen 17.1 37.7 95.5 with specimen 17.4 37.7 95.5 Frequency [Hz] α S 1/3 octave α p octave 100 0.03 125 0.06 0.05 160 0.11 200 0.15 250 0.21 0.25 315 0.37 400 0.53 500 0.62 0.60 630 0.68 800 0.61 1000 0.48 0.55 1250 0.53 1600 0.61 2000 0.57 0.60 2500 0.58 3150 0.60 4000 0.60 0.60 5000 0.63 Sound absorption coefficient α S 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 Equivalent sound absorption area less than 1.0 m² α S Sound absorption coefficient according to ISO 354 α p Practical sound absorption coefficient according to ISO 11654 Sound absorption coefficient 125 250 500 1000 2000 4000 Frequency f / Hz Rating according to ISO 11654: Weighted sound absorption coefficient α w = 0.55 Sound absorption class: D Rating according to ASTM C423: Noise Reduction Coefficient NRC = 0.45 Sound Absorption Average SAA = 0.50 MÜLLER-BBM Planegg, 2014-05-12 No. of test report M111250/4 Appendix A Page 1 Bau4(v1,7,0,0) - R:\BAU\Pruefst\Bau4Data\111\111250\2014-01-07-2E-Douglas\111250_2014-01-07-2E-Douglas_1.mb4: 13.05.2014

Sound absorption coefficient ISO 354 Measurement of sound absorption in reverberation rooms Client: Annette Douglas Textiles AG Klosterstrasse 42, 5430 Wettingen, Switzerland Test specimen: Fabric STREAMER pro Wall distance 150 mm, folded arrangement Curtain fabric: curtain fabric STREAMER pro material 90% Trevira CS, 10% FR area specific mass m" = 150 g/m² air flow resistance Rs = 373 Pa s/m thickness t = 0.83 mm Tested arrangement: mounting type following G-150 acc. to EN ISO 354, without enclosing frame two curtains with each width x height = 3500 mm x 3000 mm (one curtain with missing corner 0.42 m x 0.28 m) fixed directly underneath the ceiling on a 50 mm high metal rail wall distance 150 mm test surface width x height = 3500 mm x 2950 mm (starting at the lower edge of the metal rail), minus missing corner Room: E Volume: 199.60 m³ Size: 10.27 m² Date of test: 2014-01-07 θ [ C] r. h. [%] B [kpa] without specimen 17.1 37.7 95.5 with specimen 17.4 38.9 95.5 Frequency [Hz] α S 1/3 octave α p octave 100 0.07 125 0.12 0.15 160 0.23 200 0.39 250 0.48 0.50 315 0.70 400 0.78 500 0.81 0.80 630 0.76 800 0.79 1000 0.82 0.80 1250 0.84 1600 0.86 2000 0.84 0.85 2500 0.84 3150 0.86 4000 0.86 0.85 5000 0.88 Sound absorption coefficient α S 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 Equivalent sound absorption area less than 1.0 m² α S Sound absorption coefficient according to ISO 354 α p Practical sound absorption coefficient according to ISO 11654 Sound absorption coefficient 125 250 500 1000 2000 4000 Frequency f / Hz Rating according to ISO 11654: Weighted sound absorption coefficient α w = 0.80 Sound absorption class: B Rating according to ASTM C423: Noise Reduction Coefficient NRC = 0.75 Sound Absorption Average SAA = 0.74 MÜLLER-BBM Planegg, 2014-05-12 No. of test report M111250/4 Appendix A Page 2 Bau4(v1,7,0,0) - R:\BAU\Pruefst\Bau4Data\111\111250\2014-01-07-2E-Douglas\111250_2014-01-07-2E-Douglas_2.mb4: 12.05.2014

Fabric STREAMER pro Figure B.1. Flat arrangement, test object mounted in the reverberation room. Figure B.2. Folded arrangement, test object mounted in the reverberation room. 2014-05-12 Appendix B, Page 1

Description of the test procedure for the determination of the sound absorption in a reverberation room 1 Measurand The sound absorption coefficient α of the test object was determined. For this purpose the mean value of the reverberation time in the reverberation room with and without the test object was measured. The sound absorption coefficient was calculated using the following equation: With: α S α A T S = S 1 1 A T = 55,3 V 4 V ( m2 m1 ) c2t2 c1t 1 sound absorption coefficient; A T equivalent sound absorption area of the test object in m 2 ; S area covered by the test object in m 2 ; V volume of the reverberation room in m 3 ; c 1 propagation speed of sound in air in the reverberation room without test object in m/s; c 2 propagation speed of sound in air in the reverberation room with test object in m/s; T 1 reverberation time in the reverberation room without test object in s; T 2 reverberation time in the reverberation room with test object in s; m 1 power attenuation coefficient in the reverberation room without test object in m -1 ; m 2 power attenuation coefficient in the reverberation room with test object in m -1. The area covered by the test object was used as area of the test object. The different dissipation during the sound propagation in the air was taken into account according to paragraph 8.1.2 of EN ISO 354 [1]. The dissipation was calculated according to ISO 9613-1 [4]. The climatic conditions during the measurements are indicated in the test certificates. Information on the repeatability and reproducibility of the test procedure are given in EN ISO 354 [1]. 2 Test procedure 2.1 Description of the reverberation room The reverberation room complies with the requirements according to EN ISO 354 [1]. The reverberation room has a volume of V = 199.6 m 3 and a surface of S = 216 m 2. 2014-05-12 Appendix C, Page 1

In order to improve the diffusivity, six composite sheet metal boards dimensioned 1.2 m x 2.4 m and six composite sheet metal boards dimensioned 1.2 m x 1.2 m were suspended curved and irregularly. Figure C.1 shows the drawings of the reverberation room. Figure C.1. Plan view and sections of the reverberation room. 2014-05-12 Appendix C, Page 2

2.2 Measurement of reverberation time The determination of the impulse responses were carried out according to the indirect method. In all tests, a sinusoidal sweep with pink noise spectrum was used as test signal. In the reverberation room with and without test objects each 24 independent combinations of loudspeakers and microphones were measured. The reverberation time was evaluated according to EN ISO 354 [1], using a linear regression for the calculation of the reverberation time T 20 from the level of the a backward integrated impulse response. The determined reverberation times are indicated in Table C.1. Table C.1. Reverberation times without and with test object. Reverberation time T / s Frequency f / Hz T 1 (without test object) T 2 (with test object) Appendix A page 1 Appendix A page 2 100 5.04 4.80 4.51 125 5.08 4.62 4.27 160 5.34 4.52 3.83 200 5.69 4.47 3.35 250 5.40 3.96 2.97 315 5.19 3.20 2.40 400 5.56 2.87 2.34 500 5.41 2.61 2.27 630 5.22 2.44 2.31 800 4.92 2.52 2.20 1000 5.03 2.84 2.17 1250 5.16 2.76 2.17 1600 4.93 2.53 2.11 2000 4.40 2.44 2.03 2500 3.69 2.20 1.87 3150 2.91 1.88 1.64 4000 2.19 1.55 1.39 5000 1.65 1.24 1.15 2014-05-12 Appendix C, Page 3

2.3 List of test equipment The test equipment used is listed in Table C.2. Table C.2. Test equipment. Name Manufacturer Type Serial-No. Sound card RME Multiface II 22460388 Amplifier APart Champ One 09070394 Dodecahedron Müller-BBM DOD130B 265201 Dodecahedron Müller-BBM DOD130B 265202 Dodecahedron Müller-BBM DOD130B 265203 Dodecahedron Müller-BBM DOD130B 265204 Microphone Microtech M360 1783 Microphone Microtech M360 1785 Microphone Microtech M360 1786 Microphone Microtech M360 1787 Microphone Microtech M360 1788 Microphone Microtech M360 1789 Hygro-/Thermometer Testo Saveris H1E 01554624 Barometer Lufft Opus 10 030.0910.0003.9. 4.1.30 Software for measurement and evaluation Müller-BBM Bau 4 Version 1.7 2014-05-12 Appendix C, Page 4