Numerical Analysis of Tube-Fin Heat Exchanger using Fluent

Similar documents
Numerical Investigation on Air Side Performance of Fin and Tube Heat Exchnagers with Different Types of Fins

Experimental and Numerical Investigation of a Multi Louvered Plate Fin-and-Tube Heat Exchanger using Computational Fluid Dynamics

3D NUMERICAL STUDY OF LOCAL HEAT TRANSFER COEFFICIENT OF WAVY PLATE FIN WITH CIRCULAR TUBE HEAT EXCHANGERS USING CFD

International Conference on Energy Efficient Technologies For Automobiles (EETA 15) Journal of Chemical and Pharmaceutical Sciences ISSN:

CFD study for cross flow heat exchanger with integral finned tube

Computational Fluid Dynamics Based Analysis of Angled Rib Roughened Solar Air Heater Duct

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

FLOW MALDISTRIBUTION IN A SIMPLIFIED PLATE HEAT EXCHANGER MODEL - A Numerical Study

FLUID FLOW AND HEAT TRANSFER INVESTIGATION OF PERFORATED HEAT SINK UNDER MIXED CONVECTION 1 Mr. Shardul R Kulkarni, 2 Prof.S.Y.

Numerical simulation of fluid flow in a monolithic exchanger related to high temperature and high pressure operating conditions

NUMERICALLY-BASED PARAMETRIC STUDY OF A COMPACT FIN-TUBE HEAT EXCHANGER

The Effect of Solid and Perforated Pin Fin on the Heat Transfer Performance of Finned Tube Heat Exchanger

SIMULATION OF FLOW STRUCTURE AND HEAT TRANSFER ENHANCEMENT IN A TRIANGULAR DUCT WITH RECTANGULAR WING

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN

Investigation of Jet Impingement on Flat Plate Using Triangular and Trapezoid Vortex Generators

PLATE FIN AND TUBE HEAT EXCHANGER MODELING: EFFECTS OF PERFORMANCE PARAMETERS FOR TURBULENT FLOW REGIME

EXPERIMENTAL AND NUMERICAL STUDIES OF A SPIRAL PLATE HEAT EXCHANGER

Numerical Analysis of a Multi-Row Multi-Column Compact Heat Exchanger

Enhancement of Heat Transfer Effectiveness of Plate-pin fin heat sinks With Central hole and Staggered positioning of Pin fins

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel

FLOW DISTRIBUTION ANALYSIS IN A HEAT EXCHANGER WITH DIFFERENT HEADER CONFIGURATIONS

Numerical Study of the Three-dimensional Flow in a Flat Plate Solar Collector with Baffles

PERFORMANCE SCREENING OF A LOUVERED FIN AND VORTEX GENERATOR COMBINATION

Numerical Investigation of Multijet Air Impingement on Pin Fin Heat Sink with Effusion Slots

DESIGN & COMPUTATIONAL FLUID DYNAMICS ANALYSES OF AN AXISYMMETRIC NOZZLE AT TRANSONIC FREE STREAM CONDITIONS

Keywords: Spiral plate heat exchanger, Heat transfer, Nusselt number

Chapter 3. CFD Analysis of Radiator

CFD Analysis on Flow Through Plate Fin Heat Exchangers with Perforations

COMPUTATIONAL ANALYSIS OF LAMINAR FORCED CONVECTION IN RECTANGULAR ENCLOSURES OF DIFFERENT ASPECT RATIOS

Effect of roughness shape on heat transfer and flow friction characteristics of solar air heater with roughened absorber plate

Performance of Elliptical Pin Fin Heat Exchanger with Three Elliptical Perforations

Using Computational Fluid Dynamics And Analysis Of Microchannel Heat Sink

FLOW SIMULATION AND HEAT TRANSFER ANALYSIS USING COMPUTATIONAL FLUID DYNAMICS (CFD)

Analysis of the Cooling Design in Electrical Transformer

Energy Conversion and Management

Numerical Investigation of Secondary Flow In An Axial Flow Compressor Cascade

Pressure Losses for Fluid Flow Through Abrupt Area. Contraction in Compact Heat Exchangers

Analysis of Flow over a Convertible

II. GOVERNING AND CFD EQUATION

Computational Fluid Dynamics Study Of Fluid Flow And Aerodynamic Forces On An Airfoil S.Kandwal 1, Dr. S. Singh 2

Manhar Dhanak Florida Atlantic University Graduate Student: Zaqie Reza

SIMULATION OF THERMAL CHARACTERISTICS OF RADIATORS USING A POROUS MODEL. YETSAN Auto Radiator Co. Inc Çorum, Turkey NOMENCLATURE

ENERGY PERFORMANCE IMPROVEMENT, FLOW BEHAVIOR AND HEAT TRANSFER INVESTIGATION IN A CIRCULAR TUBE WITH V-DOWNSTREAM DISCRETE BAFFLES

CFD-Based Correlation Development for Air Side Performance of Wavy Fin Tube Heat Exchangers using Small Diameter Tubes

UNIT II CONVECTION HEAT TRANSFER

Multiphysics Numerical Modeling of a Fin and Tube Heat Exchanger

Applied Thermal Engineering

A CFD Analysis Of A Solar Air Heater Having Triangular Rib Roughness On The Absorber Plate

Impact of Magnetic Field Strength on Magnetic Fluid Flow through a Channel

Fluid Flow and Heat Transfer Characteristics in Helical Tubes Cooperating with Spiral Corrugation

Numerical Analysis of Fe 3 O 4 Nanofluid Flow in a Double Pipe U-Bend Heat Exchanger

International Journal of Engineering Research and General Science Volume 3, Issue 6, November-December, 2015 ISSN

CFD Simulation and Experimental Study on Airside Performance for MCHX

A COMPARISON OF HEAT TRANSFER AROUND A SINGLE SERRATED FINNED TUBE AND A PLAIN FINNED TUBE

Numerical Prediction of Laminar Characteristics of Fluid Flow and Heat Transfer in Finned-Tube Heat Exchangers

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

EFFECTIVENESS OF HEAT TRANSFER INTENSIFIERS IN A FLUID CHANNEL

Experimental Study of Convective Heat Transfer and Thermal Performance in the Heat-Sink Channel with Various Geometrical Configurations Fins

CFD Analysis of Forced Convection Flow and Heat Transfer in Semi-Circular Cross-Sectioned Micro-Channel

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

ENGR Heat Transfer II

Numerical Investigation of Convective Heat Transfer in Pin Fin Type Heat Sink used for Led Application by using CFD

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

Project #1 Internal flow with thermal convection

This section develops numerically and analytically the geometric optimisation of

ABSTRACT I. INTRODUCTION

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE TEMPERATURE DISTRIBUTION INSIDE OIL-COOLED TRANSFORMER WINDINGS

DEVELOPMENT OF CFD MODEL FOR A SWIRL STABILIZED SPRAY COMBUSTOR

CFD Simulation in Helical Coiled Tubing

CFD based design and analysis of micro-structured. surfaces with application to drag and noise reduction

Principles of Convection

Initial and Boundary Conditions

HEAT TRANSFER ANALYSIS OF FLAT AND LOUVERED FIN-AND-TUBE HEAT EXCHANGERS USING CFD

MAE 598 Project #1 Jeremiah Dwight

Prediction of Channel Diameter to Reduce Flow Mal Distribution in Radiators using ANN

External Forced Convection. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

COMPUTATIONAL FLUID DYNAMICS ON DIFFERENT PASSAGES OVER A PLATE COIL EVAPORATOR FOR 40 LITER STORAGE TYPE WATER COOLER

Optimization of Shell & Tube Heat Exchanger by Baffle Inclination & Baffle Cut

PERIODICALLY FULLY DEVELOPED LAMINAR FLOW AND HEAT TRANSFER IN A 2-D HORIZONTAL CHANNEL WITH STAGGERED FINS

Experimental investigation of heat transfer augmentation in triangular duct with rectangular wing

Applied CFD Project 1. Christopher Light MAE 598

EVALUATION OF FOUR TURBULENCE MODELS IN THE INTERACTION OF MULTI BURNERS SWIRLING FLOWS

Boundary Conditions - Inlet

Heat Transfer Analysis of a Helical Coil Heat Exchanger by using CFD Analysis

Use of a CFD Code in the Analysis of Heat Transfer Surfaces

Effect of radius ratio on pressure drop across a 90 bend for high concentration coal ash slurries

STRUCTURAL ANALYSIS OF A WESTFALL 2800 MIXER, BETA = 0.8 GFS R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY

Chapter 7: External Forced Convection. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Performance Optimization of Air Cooled Heat Exchanger Applying Analytical Approach

Maximum Heat Transfer Density From Finned Tubes Cooled By Natural Convection

Friction Factors and Drag Coefficients

Effective Heat Transfer Enhancement in Finned Tube Heat Exchanger with Different Fin Profiles

Numerical Investigation of Heat Transfer and Fluid Flow Characteristics of Square Type Tabulator Roughness Solar Air Heater

Comparative study of Different Geometry of Ribs for roughness on absorber plate of Solar Air Heater -A Review

Enhancement of Heat Transfer in Crossed Flow Heat Exchangers with Aid of Oval Tubes and Multiple Delta Winglets

This chapter focuses on the study of the numerical approximation of threedimensional

A numerical study of heat transfer and fluid flow over an in-line tube bank

Thermo-Hydraulic performance of Internal finned tube Automobile Radiator

SHELL SIDE NUMERICAL ANALYSIS OF A SHELL AND TUBE HEAT EXCHANGER CONSIDERING THE EFFECTS OF BAFFLE INCLINATION ANGLE ON FLUID FLOW

Transcription:

Numerical Analysis of Tube-Fin Heat Exchanger using Fluent M. V. Ghori & R. K. Kirar Patel college of Science and Technology, Rajiv Gandhi Proudyogiki Vishwavidhyalaya, Ratibad, Bhopal- 462036, India E-mail : mayurmech7053@gmail.com,ravindrakirar@gmail.com Abstract - Three-dimensional CFD simulations are carried out to investigate heat transfer and fluid flow characteristics of two-row plain Tube and Fin heat exchanger using FLUENT software. Heat transfer and pressure drop characteristics of the heat exchanger are investigated for Reynolds numbers ranging from 330 to 7000. Model geometry is created and meshed by using GAMBIT software. Fluid flow and heat transfer are simulated and results compared using both laminar and turbulent flow models k-, and SST k-omega, with steady-state solvers to calculate pressure drop, flow, and temperature fields. Model validation is carried out by comparing the simulated value friction factor f and Colburn factor j to experimental results investigate by Wang. Reasonable agreement is found between the simulations and experimental data, and the fluent software has been sufficient for simulating the flow fields in tube-fin heat exchangers. Keywords - Tube- fin, heat exchanger, fluent, gambit I. INTRODUCTION Vestas Aircoil A/S produces compact tube-and-fin heat exchangers for ship motors, as well as other types of heat exchangers and cooling towers.the heat exchanger cools heated, compressed air from the motor with cooling water. Fins are used to increase heat transfer area on the air side, since the air has the largest influence on the overall heat transfer resistance. This study involves building a model of a fin-and-tube heat exchanger geometry using open-source software, creating a suitable mesh, setting up the cases (choosing solvers, numerical solution methods etc.) making the CFD calculations with fluent and comparing results to known experimental data. The following subsections describe this study in more details. First, a summary of other research in the heat-transfer field related to tubeand-fin heat exchangers is presented to put this study into perspective with the other work available in the open literature. II. PREVIOUS RESEARCH AND EXPERIMENTS The experiments carried out by Wang were conducted using a forced draft wind tunnel [1]. An air straightener was used to keep flow moving in the x- direction, an 8-thermocouple mesh was placed in the inlet and a16-thermocouple mesh in the outlet locations of which determined by ASHRAE recommendations. All equipment for data acquisition thermocouples, pressure transducer, airflow measurement station, and flow meter were checked for accuracy prior to running the experiments [2]. Water at the inlet was held at 60ºC, airflow velocities were tested in the range from 0.3 m/s to 6.2 m/s. Energy balances were monitored during the experiment for both the hot- and cold-side and reported to be within 2 [3].The uncertainties for the primary measurements (mass flow rate for air and water, pressure drop, and temperature of the water and air) were very small and therefore these measurements can be assumed to be accurate [4]. For this experimental study, the geometrical parameters for a two-row heat exchanger based on experimental research are used to build a CFD model, and results read from the graphs (friction factor and Colburn j-factor against Reynolds number) in the article are used to validate the results of the CFD simulations [6]. The parameters of interest: friction factor f and Colburn j-factor are widely used in industry to characterize pressure drop and heat transfer, respectively, and thereby determine heat exchanger performance and suitability for specific duties [7]. Determining and using these parameters for performance prediction is part of the heat exchanger design process. The two-row fin-and-tube heat exchanger studied has a staggered tube arrangement. Analyzing flow and heat transfer using CFD can make calculations to predict heat-exchanger performance [8]. However, it is not possible to perform CFD simulation on the entire heat 37

exchanger, due to the large number of volumes and calculations required. Therefore, a small section of a heat exchanger consisting of one channel of air between two fins, with the air flowing by two tubes is modelled for this project. Simulations of the air flow through this passage are carried out, while relevant characteristics of the air flow are sampled and averaged at the inflow, minimum free-flow area (s), and outflow. The characteristics sampled are: flow velocity (in all three directions: x, y, and z), temperature, pressure, and turbulence model parameters k, epsilon, and omega. These measurements are then used for calculating relevant performance parameters such as pressure drop, friction and Colburn factors, heat transfer rate, Reynold s number, etc. III. COMPUTATIONAL DOMAIN AND BOUNDARY CONDITIONS The GAMBIT Software is used to create and mesh the computational model. A diagram of the studied model is shown in Figure 1, and consists of the air flow area between two fins of plain fin geometry and around the surfaces of two rows of tubes, and a schematic of the model with dimensions is shown in Figure 1, with the geometrical dimensions listed in Table 1 [5]. 1. Geometric dimensions of heat exchanger model Geometric Parameter Fin thickness T 0.130 mm Fin pitch F p 2.240 mm Fin collar outside diameter D c 10.23 mm Transverse pitch P t 25.40 mm Longitudinal Pitch P l 22.00 mm Tube wall thickness Δ 0.336 mm Fig. 2 : Computational domain, including boundary conditions (BC) and extended flow volumes. The computational domain has contains boundary conditions as shown in Figure 2.with the following conditions: Tube surfaces as a wall, Dirichlet Boundary condition Air velocity u = v = w = 0, that is no-slip condition at tube surfaces. Fins as a wall, Dirichlet Boundary condition Air velocity u = v = w = 0, that is no-slip condition at tube surfaces. Inlet as a velocity inlet, Dirichlet Boundary condition Uniform velocity, ranging from 0.3 m/s to 6.2 m/s. v = w = 0 Outlet as an outflow, Neuman Boundary condition Zero gradients, u, v, w, pressure, and temperature. Side planes as a symmetry, symmetry planes ( u/ y)=0, v = 0, ( w/ y) = 0, ( T/ y) = 0 The entire computational domain was made up of approximate 70000 finite volumes, with a structured grid throughout most of the domain, while the areas around the tubes are more unstructured. The cell number was chosen based on the results of a grid independence test. Performance parameters Fig. 1 : Illustration of the main computational domain and geometric parameters of the heat exchanger model studied (z-direction not shown). This section describes how heat transfer and pressure drop are characterized. Included are dimensionless groups, equations for heat transfer and efficiency calculations, and equations for making pressure drop calculations. Following the descriptions 38

of the performance parameters, the values as read from the graphs in the research done by Wang [1], for friction factor f and Colburn j-factor vs. Reynolds number are tabulated and graphed. Meshing of Geometry The geometry and computational domain were created using the geometry creation and meshing software GAMBIT. The Fluent 5/6 version 6.3.26 used for this project did not have sophisticated geometry and meshing capabilities, and therefore another meshing program was required. For this purpose, GAMBIT was chosen. The Mesh Volumes operation (volume mesh and volume modify commands) creates a mesh for one or more volumes in the model. When you mesh a volume, GAMBIT creates mesh nodes throughout the volume according to the currently specified meshing parameters. Specifying the Volume GAMBIT allows you to specify any volume for a meshing operation; however, the shape and topological characteristics of the volume, as well as the vertex types associated with its faces are decide to determine the types of mesh schemes that can be applied to the volume. Specifying Scheme Elements GAMBIT allows you to specify any of the following volume meshing Elements option. 2. Meshing scheme elements Option Hex Hex/Wedge Tet/Hybrid Description Specifying Scheme Type Specifies that the mesh includes only hexahedral elements. Specifies that the mesh is composed primarily of hexahedral elements but includes wedge elements where appropriate. Specifies that the mesh is composed primarily of tetrahedral elements but may include hexahedral, pyramidal, and wedge elements where appropriate. GAMBIT provides the following volume meshing Type options. Hexahedral elements Meshes with cooper meshing scheme In this project the geometry is meshed by hexahedral elements mesh was used. The details about this type of mesh are given below. The GAMBIT 2.4.6 version was used for creating the hexahedral meshes with cooper meshing scheme for this tube-fin heat exchanger computation domain. It could make the more structured orthogonal mesh desired. Hexagonal mesh cell numbers approximately 70000 cells. This section presents some preliminary results and observations from the simulations carried out in this project. The simulations included ten different Reynolds numbers based on ten inlet airflow velocities ranging from 0.3 m/s to 6.2 m/s, all simulated in three flow models laminar, k-epsilon turbulence model, and SST k-omega turbulence model. They are describing as a Characteristics of Flow and Characteristics of Heat Transfer. IV. RESULTS AND DISCUSSIONS A. Characteristics of Flow A characteristic of flow describes the initial observations found using Contour Display after running the CFD simulations in Fluent. The characteristics of low-reynolds flow and high Reynolds flow are compared with contour plots of velocity and contour plot of turbulent kinetic energy k. This gives behaviour of air flow velocity inside the computational domain. B. Velocity Observations The flow patterns of the two cases at low and high- Reynolds numbers (inlet air velocity 0.3 m/s vs. 6.2 m/s) are similar. The air enters at the inlet on the left and flows in the direction of the arrows, and exits at the outlet on the right-hand side as shown in figure 3 and figures 4the boundary layer growth in the tube as air flow with 0.3m/s. Fig. 3 : Vector plot for U velocity field, SST k-omega flow model, inlet air flow 0.3 m/s. Fig. 4 : Vector plot for U velocity field, laminar flow model, inlet air flow 0.3 m/s with boundary layer on tube. 39

Below three flow models laminar, k-epsilon turbulence and k-omega turbulence models contour are presented with low Reynolds number and high Reynolds number in the figure 5 to figure 10 now we can easily understand the flow characteristics of air in heat exchanger between two fins. Fig. 9 : Contours plot for U velocity field, k-epsilon flow model, inlet air flow 6.2 m/s. Fig. 5 : Contours plot for U velocity field, Laminar flow model, inlet air flow 0.3 m/s. Fig. 6.: Contours plot for U velocity field, k-epsilon flow model, inlet air flow 0.3 m/s. Fig. 7 : Contours plot for U velocity field, SST k-omega flow model, inlet air flow 0.3 m/s. Fig. 8 : Contours plot for U velocity field, Laminar flow model, inlet air flow 6.2 m/s. Fig. 10 : Contours plot for U velocity field, SST k-omega flow model, inlet air flow 6.2 m/s. In above cases, as the air flows around the first tube, it begins to speed up and then the air velocity increases again as it goes around the second tube. This is because the free-flow area of air decreases, which showed that the velocity going around the second tube is faster than that going around the first tube. The minimum free-flow area is the area of the heat exchanger between two transverse tubes, so the area just above tube one or just below the second tube are the minimum free-flow areas. The flow is forced to speed up, as the tubes act as a type of pipe contraction in the air flow channel. As the velocity increases along the flow the Pressure of air flow is decreases accordingly. It is observed that the size of the tubes impact the Reynolds number of the air flowing around them, since with larger tubes (at the same distance from each other), there would be an even smaller minimum free-flow area if the transverse pitch remained the same. In this study, the characteristic length for the Reynolds number is the tube collar diameter, and it can be seen here, that increases in this parameter (while keeping transverse pitch the same) can induce higher velocities and with it a higher turbulence and Reynolds number. In the case of higher air flow velocity, the recirculation zones behind each tube contain small backflow areas. The second recirculation zone appears larger. In the case with 0.3 m/s inlet velocity, however, a recirculation zone was not noticeable as it was for the case with inlet velocity of 6.2 m/s. 40

C. Kinetic Energy k distribution The kinetic energy contour plots can be seen to verify previous observations made regarding flow. It is seen in Figure 11, which illustrates the kinetic energy k distribution for the low Reynolds number case. There is no kinetic energy increase in the areas behind the tubes for this case. The kinetic energy increases (slightly) in a different area corresponding to the increase in velocity as the air flows around the second tube. The other area of figure 12 the plot of lower Reynolds number, which is exhibiting higher kinetic energy is in the area of higher temperatures, which can be seen from the contour. However, this illustrates that even at very low flow rates some turbulent kinetic energy could still be present. Fig. 11 : Contours of turbulent kinetic energy k distribution, SST k- omega model, inlet air velocity 0.3 m/s. For kinetic energy in the higher-reynolds number case Figure 12 and 13 an increase in kinetic energy is found clearly after the first tube, in the same area as the close to recirculation zones observed in the higher Reynolds values. According to this plot, the second recirculation zone is not as turbulent as the first recirculation zone. This makes sense because the direction of flow has changed as the air moves between the two tubes, and is directed more downward at an angle. Turbulence kinetic energy k at behind the third tube is high in the recirculation zone which shows the higher Reynolds number. Turbulence kinetic energy k is most use full to determines the Reynolds stresses. Fig. 13: Contours of turbulent kinetic energy k distribution, k-epsilon model, inlet air velocity 6.2 m/s. Flow and kinetic energy plots have been compared and illustrated the effect flow has on kinetic energy. The next section describes the heat flow characteristics, as visualised in contours for the same cases as for flow and kinetic energy. It is found that the temperature changes, flow, and kinetic energy can be shown to be connected. D. Characteristics of Heat Transfer The first most noticeable difference between the two Reynolds number heat transfer characteristics is that once steady-state is reached, the slower-moving air (0.3 m/s) is heated up much more in the first two rows than in the case of higher Reynolds number flows. This must be due to the fact that the air flows so slowly, that there is much more time to absorb the heat (longer residence time ). It is seen that the temperature streamlines run practically perpendicular to the velocity streamlines in the beginning of the airflow channel, with the isothermal streamlines running vertical and the velocity of the flow horizontal. This acts as a cross-flow heat exchange, with the flow directly bringing the heat with it. It can then be seen that after the air has flowed through the initial section of the heat exchanger, this synergy between flow and heat transfer is no longer as effective. This means that the heat transfer coefficient is changing according to the streamline the flow is in at the time. As shown in Figures 14 to 16 for low Reynolds the heat transfer coefficient is high for k-epsilon turbulence model so the air is heated at a temperature as a tube and fin temperature after flowing around on the first tube. For laminar and SST k-omega flow model almost same heat transfer take place. Fig. 12 : Contours of turbulent kinetic energy k distribution, SST k- omega model, inlet air velocity 6.2 m/s. Fig. 14 : Contours of temperature field, laminar flow model, 0.3 m/s inlet air velocity. 41

Fig. 15 : Contours of temperature field, k-epsilon flow model, 0.3 m/s inlet air velocity. Fig. 16 : Contours of temperature field, SST k-omega flow model, 0.3 m/s inlet air velocity. For high Reynolds number as in case of air flow with 6.2m/s shown in Figure 17 to 19 the air has not sufficient time to absorb the heat from the tube and fin. So the air temperature at the outlet is lower than as in low Reynolds number flow. Laminar flow attends the more velocity for air flow so it has absorbed less heat from the heat exchanger. Fig. 19 : Contours of temperature field, SST k-omega flow model, 6.2 m/s inlet air velocity. The largest temperature changes for the cases are occurring in the recirculation and slow velocity zones just after each of the tubes. As in the slow-moving flow in the case with 0.3 m/s velocity, the slow-moving areas of the heat exchanger are also better able to absorb heat. The staggered tube arrangement is designed to have these slower-moving and recirculation areas to keep the heat flowing to the air, but at the same time, not allowing recirculation zones to stagnate as can occur in inline arrangements where these zones do not keep flowing. Fluent software gives the value of pressure drop, maximum velocity, air outlet temperature and density of air at outlet. After getting these values friction factor f is determined for all models i.e. laminar and two turbulence model (standard k-epsilon and SST k-omega model). Values of friction factor are compared below in table 4 to 6. Fig. 17: Contours of temperature field, laminar flow model, 6.2 m/s inlet air velocity. Fig. 18 : Contours of temperature field, k-epsilon flow model, 6.2 m/s inlet air velocity. Fig. 20 : Comparing the graph of Friction factor f against Reynolds number Re Friction factor f against Reynolds number Re for different inlet airflow velocities and flow models (laminar, and turbulence models k-epsilon and k-omega) with the same geometrical parameter are plotted in figure 20.It can be seen from figure 21, that in all models the friction factor was decreasing with increasing Reynolds number. All of the models are estimated the friction factor. At the lower laminar flows of Reynolds number from 330 to 1300, all the models 42

Colburn j-factor % error in f-factor % error in j-factor International Journal on Theoretical and Applied Research in Mechanical Engineering (IJTARME) found nearly identical results. As the flow moved into transition, it appears the laminar flow model came much closer to the experimental values. At the transition point from transition to turbulent, which appears to have a critical Reynold s value of between 1700 and 2900, once again, none of the models were better than another. After moving into turbulent flow, however, the k-omega SST had the best accuracy, and the laminar flow model able to model the friction factor compared to the k- epsilon model. We have seen that there was error in all models with experiment so plot a graph. Figure 22 which shows the all three model percentage error with the experiment values. Here the error in the model k- omega and laminar flow model is the least with respect to the experiment data but in k-epsilon large error occurred this is because both k-omega and k-epsilon are created for calculate turbulence, turbulent kinetic energy and dissipation rate, but in laminar flow do not increase the accuracy since there is no turbulence in laminar flow. The k-omega is the most accurate for friction factor because it model kinetic energy and specific dissipation rate at the wall or boundary. The k-epsilon model was the least accurate flow model because it calculated the equations to model kinetic energy and dissipation rate for free-flowing fluids, and therefore the friction factor against the wall is not capable to calculate accurately. 50 40 30 20 10 0-10 Fig. 21: Fanning friction factor f Error by flow model vs. Re. A graph is plotted between Colburn-j factor and Reynolds number in the Figure 23 and an error graph is also shown in Figure 24the flow models showed very clear differences in abilities to simulate heat transfer at the different Reynolds numbers. 0.05 0.04 0.03 0.02 0.01 0 0 5000 10000 Renolds Number(Re) k-epsilon k-omega Laminar 0 2000 4000 6000 8000 Renolds Number(Re) k-omega k-epsilon Laminar Experiment Fig. 22 : Colburn j-factor against Reynolds number Re for different inlet airflow velocities and flow models In laminar flow, the laminar flow model was the best for predicting the j-factor, as would be expected. The transition heat flow was the best characterized with the k-omega turbulence model, while turbulent heat flow was best calculated using the k-epsilon model, although at the very highest Reynolds number 7000, none of the models were accurate. 100 80 60 40 20 0 0 2000 4000 6000 8000 Renolds Number(Re) Fig. 23 : Colburn j-factor error: Error by flow model vsre. Here we seen that there is good agreement in data produced by experiment and by computer simulation. The results found that different flow models performed best according to Reynolds number and whether accurate solutions were desired for pressure drop or heat transfer. V. CONCLUSION k-omega k-epsilon Laminar The objective of this project was to make CFD simulations using fluent software, and validate the results against experimental data. The system to study was a Tube and Fin heat exchanger. The purpose of the work was to investigate the possibilities of eventually using CFD calculations for design of heat exchangers instead of expensive experimental testing and prototype production. To analyse the flow and heat transfer characteristics of the heat exchanger, a model of a tworow fin and tube heat exchanger was created using GAMBIT software to create the geometry and mesh. The resulting mesh was used for running a variety of simulations using a laminar flow model and two turbulence models for comparison of results. Ten different inlet flow velocities ranging from 0.3 m/s to 6.2 m/s and corresponding to Reynolds numbers ranging from 330 to 7000 were simulated in the three different flow models laminar, k-epsilon turbulence model, and SST k-omega turbulence model. Using the simulation results and some specific non-dimensional numbers, calculations related to heat flow and pressure loss can be carried out to determine the Fanning friction factor and Colburn j-factor for comparison with the experiment. It was found that the flow model accuracy depended on the flow regime and whether the friction factor f or j- factor was being determined. From the experimental values the laminar flow region for geometry of heat 43

exchanger transfer to transitional at Reynolds number 1300, and remain in transitional stage up to Reynolds number 2900. The Reynolds number is calculated against of the tube outside diameter. For friction factor determination, little difference is found between the flow models simulating laminar flow, while in transitional flow, the laminar flow model produced the most accurate results for friction factor and the SST k- omega turbulence model was more accurate in turbulent flow regimes. For heat transfer, the laminar flow model calculated the most accurate j-factor, while for transitional flow the SST k-omega turbulence model was more accurate and the k-epsilon turbulence model was best for heat transfer simulations of turbulent flow. Future prospective Simulations for this study was carried out following as closely as possible the same operating conditions and geometrical configurations of the two-row tube-fin heat exchanger, with tube collar diameter of 10.23 mm and fin pitch 2.23 mm, as presented in the paper by Wang [1]. The Reynolds number ranges from 330 to 7000, which correspond to the frontal air velocity at the inlet ranging from 0.3 to 6.2 m/s. The work done for this project has shown that it is possible to make practical simulations of heat flow and pressure drop for a tubeand-fin heat exchanger using fluent software, and validate the results against experimental data. Data resulting from the simulations should be as accurate as possible, and therefore some considerations can be taken in future work to attempt to further improve the simulation conditions or calculations and the accuracy of the results. In this dissertation only standard k-epsilon and SST k-omega turbulence model is used but in future realizable k-epsilon turbulence model and Reynolds stress model can be used for better result and time variant solver can also be used for a validation of simulation result to experiment data. VI. REFERENCES [1] CC. Wang An experimental study of heat transfer and friction characteristics of typical louver finand-tube heat exchangers International Journal of Heat and Mass Transfer Volume 41, Issues 4 5, February March 1998, Pages 817-822 [2] CC. Wang, Chi-Chuan; Chang, Yu-Juei; Hsieh, Yi-Chung; Lin, Yur-Tsai (1996). Sensible heat and friction characteristics of plate fin-tube heat exchangers having plane fins, International Journal of Refrigeration, Vol. 19, No. 4: pp. 223-230. [3] Chi-Chuan Wang, Kuan-Yu Chi (2000). Heat transfer and friction characteristics of plain finand-tube heat exchangers, part I: new experimental data, International Journal of Heat and Mass Transfer 43: 2681 2691 [4] Erek, Aytunc; Õzerdem, Baris; Bilir, Levent; Ilken, Zafer(2005). Effect of geometrical parameters on heat transfer and pressure drop characteristics of plate fin and tube heat exchangers, Applied Thermal Engineering, Vol. 25: pp. 2421-2431. [5] Fluent Incorporated, FLUENT User s guide version 6.1, (2003). [6] Fornasieri, E.; Mattarolo, L(1991). Air-side heat transfer and pressure loss in finned tube heat exchangers: state of art, Proceedings of the European Conference on Finned Tube Heat Exchangers, Lyon, France. [7] Gongnan Xie, Qiuwang Wang, Bengt Sunden(2009). Parametric study and multiple correlations on air-side heat transferand friction characteristics of fin-and-tube heat exchangers with large number of large-diameter tube rows Applied Thermal Engineering 29: 1 16 [8] Gray, D. L.; Webb, R.L.(1986). Heat transfer and friction correlations for plate fin-and-tube heat exchangers having plain fins, Proceedings of the Ninth International Heat Transfer Conference, San Francisco. [9] Jiong Li, Shuangfeng Wang, Wang Cai, Weijun Zhang(2010) Numerical study on air-side performance of an integrated fin and microchannel heat exchanger Applied Thermal Engineering 30: pages 2738-2745 [10] Kayansayan, N.(1994). Heat transfer characterization of plate fin-tube heat exchangers, International Journal of Refrigeration, Vol. 17, No. 1: pp. 49-57. 44