Evaluation of Performance of Thermal and Electrical Hybrid Adsorption Chiller Cycles with Mechanical Booster Pumps

Similar documents
Evaluation of the Characteristic of Adsorption in a Double-Effect Adsorption Chiller with FAM-Z01

Long-Term Durability and Reactivation of Thermochemical Heat Storage Driven by the CaO/Ca(OH)2 Reversible Reaction

A Novel Model Considered Mass and Energy Conservation for Both Liquid and Vapor in Adsorption Refrigeration System.

The Seismic-Geological Comprehensive Prediction Method of the Low Permeability Calcareous Sandstone Reservoir

Performance investigation of a waste heat driven pressurized adsorption refrigeration cycle

Area Classification of Surrounding Parking Facility Based on Land Use Functionality

A Review On Solar Adsorption Refrigeration System

Macroscopic Equation and Its Application for Free Ways

A Review on Performance Improvement of Adsorber Bed by Effective Heating and Cooling

The Influence of Abnormal Data on Relay Protection

Title Process of Ethanol in Activated Car. Citation Physics Procedia (2015), 69:

Hubble s Constant and Flat Rotation Curves of Stars: Are Dark Matter and Energy Needed?

Investigation into NH 3 -MnCl 2 and NH 3 -CaCl 2 Reaction Rates for the Development of a Thermal Transformer

Study on the Concentration Inversion of NO & NO2 Gas from the Vehicle Exhaust Based on Weighted PLS

Study of the performance of activated carbon methanol adsorption systems concerning heat and mass transfer

Control Rod Calibration and Worth Calculation for Optimized Power Reactor 1000 (OPR-1000) Using Core Simulator OPR1000

NEGST. New generation of solar thermal systems. Advanced applications ENEA. Comparison of solar cooling technologies. Vincenzo Sabatelli

Lift Truck Load Stress in Concrete Floors

GHGT-11. A Moisture Swing Sorbent for Direct Air Capture of Carbon Dioxide: Thermodynamic and kinetic. analysis

Numerical Simulation of the Thin Film Coating Flow in Two-Dimension

Helicoidal Surfaces and Their Relationship to Bonnet Surfaces

Proposal and Verification of Simultaneous Measurement Method for Three Thermoelectric Properties with

Thermochemical Storage Technologies

Modelling the Dynamical State of the Projected Primary and Secondary Intra-Solution-Particle

Applications of Adsorption Refrigeration Cycle Review

Properties a Special Case of Weighted Distribution.

Optimisation of Effective Design Parameters for an Automotive Transmission Gearbox to Reduce Tooth Bending Stress

Development of Advanced Multi Stage Adsorption Refrigeration Cycles

8.21 The Physics of Energy Fall 2009

Complex Compounds Background of Complex Compound Technology

Effect of Transition Metal Mixing on Reactivities of Magnesium Oxide for Chemical Heat Pump

Study on Precipitation Forecast and Testing Methods of Numerical Forecast in Fuxin Area

Thermodynamic Analysis of the Effect of Generator Temperature on the Performance of a Single-Effect Absorption Refrigeration Cycle

Numerical Experiments Using MATLAB: Superconvergence of Nonconforming Finite Element Approximation for Second-Order Elliptic Problems

Energy Conservation and Gravitational Wavelength Effect of the Gravitational Propagation Delay Analysis

Pulsating heat pipe panels

(2017) Relativistic Formulae for the Biquaternionic. Model of Electro-Gravimagnetic Charges and Currents

Finite Element Analysis of Graphite/Epoxy Composite Pressure Vessel

Available online at ScienceDirect. Physics Procedia 67 (2015 ) Superfluid helium heat pipe. P.

PERFORMANCE OF THE ABSORPTION PROCESS IN A SEASONAL SORPTION HEAT STORAGE PROTOTYPE

A generic adsorption heat pump model for system simulations in TRNSYS

Lecture 35: Vapor power systems, Rankine cycle

High-Pressure Volumetric Analyzer

(Refer Slide Time: 00:00:43 min) Welcome back in the last few lectures we discussed compression refrigeration systems.

Readings for this homework assignment and upcoming lectures

Curriculum Vitae. Education Background

III E

Adsorption Asmaa Shankar

Radar Signal Intra-Pulse Feature Extraction Based on Improved Wavelet Transform Algorithm

Condensation and Evaporation Characteristics of Flows Inside Three Dimensional Vipertex Enhanced Heat Transfer Tubes

CHAPTER 8 ENTROPY. Blank

QUASI STEADY STATE MODEL FOR ADSORPTION COOLING SYSTEMS: AUTOMOTIVE APPLICATIONS

On-Site Calibration Method of Dosimeter Based on X-Ray Source

First tests on a solid sorption prototype for seasonal solar thermal storage.

Investigations on Performance of an Auto-Cascade Absorption Refrigeration System Operating with Mixed Refrigerants

Study of thermal and adsorption characteristics of composite ammonia adsorber with expanded graphite and using nano fluids.

PERFORMANCE OF ABSORPTION HEAT PUMP USING FINE PARTICLE SLURRY OF LIBR CRYSTAL

MAE 11. Homework 8: Solutions 11/30/2018

An Efficient Algorithm for the Numerical Computation of the Complex Eigenpair of a Matrix

Development of high-efficiency Stirling cryocoolers for high temperature superconducting motors


Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

Advanced heat driven hybrid refrigeration and heat pump systems. Z. Tamainot-Telto School Engineering University of Warwick Coventry CV4 7AL - UK)

Performance Investigation on Electrochemical Compressor with Ammonia

Theoretical and Experimental Study of Explosion Limits and the Inhibition of Flammable Refrigerants

Supporting information (SI)

Y.; Kobayashi, H.; Inatani, Y. Citation Physics Procedia (2015), 67: Right article under the CC BY-NC-ND

Heat Transfer Modelling of Plate Heat Exchanger in Solar Heating System

Pressure Swing Adsorption: A Gas Separation & Purification Process

NATIONAL RESEARCH COUNCIL OF ITALY

Engineering Thermodynamics. Chapter 5. The Second Law of Thermodynamics

Basic Principles of an Adsorption Heat Storage System

Adsorption Processes. Ali Ahmadpour Chemical Eng. Dept. Ferdowsi University of Mashhad

Chemical Engineering Thermodynamics Spring 2002

Design& Analysis Of Solar Vapour Absorption System Using Water And Lithium Bromide

CHAPTER 6 THE SECOND LAW OF THERMODYNAMICS

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E)

Thermodynamic Properties of Low-GWP Refrigerant for Centrifugal Chiller

2 Copyright Pearson Education, Inc., or its affiliates. All Rights Reserved.

The Qualitative and Quantitative Methods of Kovalevskys Case

Heat transfer coefficient of near boiling single phase flow with propane in horizontal circular micro channel

MATHEMATICAL MODEL OF A VAPOUR ABSORPTION REFRIGERATION UNIT

Critical Current Properties of HTS Twisted Stacked-Tape Cable in Subcooled- and Pressurized-Liquid Nitrogen

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Spring_#7. Thermodynamics. Youngsuk Nam.

Adsorption heat storage: state of the art and future perspectives

Lecture 44: Review Thermodynamics I

Gas Chromatography Separation of H 2 -D 2 -Ar Using Pd/K

Investigations Of Heat Transfer And Components Efficiencies In Two-Phase Isobutane Injector

Carbon dioxide removal processes by alkanolamines in aqueous organic solvents Hamborg, Espen Steinseth

Assembly and Maintenance manual according to regulation DIN 82079

CONTRIBUTION TO IMPROVING THE PERFORMANCE COEFFICIENT OF A SOLAR ABSORPTION REFRIGERATION SYSTEM

Computer-Aided Design and Simulation of Working Fluid Pairs for Absorption Refrigerators

SOPHISTICATED DESIGN, INTUITIVE OPERATION, RESEARCH-GRADE RESULTS

Energy Procedia 00 (2011) SHC J. Jänchen a, H. Stach b, a*

CONTINUOUS ADSORPTION REFRIGERATION PERFORMANCE OF ACTIVATED CARBON R134A PAIR FOR ICE-MAKING APPLICATION USING TRANSIENT CFD SIMULATION

Lecture 38: Vapor-compression refrigeration systems

Thermal conductivity measurement of two microencapsulated phase change slurries

COMPUTATIONAL ANALYSIS OF ENCAPSULATED THERMAL ENERGY PHASE CHANGE STORAGE SYSTEM: CYLINDRICAL AND SPHERICAL GEOMETRY

Article Experimental Investigations of Composite Adsorbent 13X/CaCl2 on an Adsorption Cooling System

Transcription:

Journal of Materials Science and Chemical Engineering, 217, 5, 22-32 http://www.scirp.org/journal/msce ISSN Online: 2327-653 ISSN Print: 2327-645 Evaluation of Performance of Thermal and Electrical Hybrid Adsorption Chiller Cycles with Mechanical Booster Pumps Tao Zeng 1, Takehiro Esaki 1*, Jun Li 1, Noriyuki Kobayashi 1, Hongyu Huang 2 1 Department of Chemical Engineering, Nagoya University, Nagoya, Japan 2 Integrated Technology Center, Guangzhou Institute of Energy Conversion, Chinese Academy of Sciences, Guangzhou, China How to cite this paper: Zeng, T., Esaki, T., Li, J., Kobayashi, N. and Huang, H.Y. (217) Evaluation of Performance of Thermal and Electrical Hybrid Adsorption Chiller Cycles with Mechanical Booster Pumps. Journal of Materials Science and Chemical Engineering, 5, 22-32. https://doi.org/1.4236/msce.217.553 Received: February 21, 217 Accepted: May 24, 217 Published: May 27, 217 Copyright 217 by authors and Scientific Research Publishing Inc. This work is licensed under the Creative Commons Attribution International License (CC BY 4.). http://creativecommons.org/licenses/by/4./ Open Access Abstract Large amounts of waste heat below 1 C from the industrial sector are released into the atmosphere. It has been suggested that energy system efficiency can be increased with adsorption chillers. However, the cooling power and coefficient of performance (COP) of conventional adsorption chillers significantly decrease with the desorption temperature. In this paper, we proposed a mechanical booster pump (MBP)-assisted adsorption chiller cycle, and evaluated its performances. In the cycle, a MBP was incorporated into a zeolite-water-type adsorption chiller for facilitating water vapor transportation between an adsorber and an evaporator/condenser. We have experimentally studied the effect of the input electrical power of MBP on the performances of adsorption chiller cycle. It has been demonstrated that the heat input achieved by using MBP at the desorption temperature of 5 C was 1.6 times higher than that of without MBP at the desorption temperature of 6 C. And the increase of pump power was found to be effective in increasing the heat input. Therefore, it was confirmed that the operation range of desorption temperature, which can be generated by using the waste heat, was extended and the cooling power was increased directly by using MBP. Keywords Adsorption, Chiller Cycle, Zeolite/Water Pair, Mechanical Booster Pump 1. Introduction Since the Industrial Revolution, energy consumption has increased. This has led to an increase in the amount of industrial waste heat as well. Cogeneration systems have attracted increasing attention over the past two decades due to the DOI: 1.4236/msce.217.553 May 27, 217

high energy efficiency (e.g. 8% when a gas turbine with waste heat boiler is used). The energy efficiency of cogeneration system can also be improved with the use of a heat energy conversion apparatus. Adsorption chiller, as one of the heat energy conversion apparatus, can use low-temperature heat source of 6 C - 1 C to generate the desired cooling effect for reducing air-conditioning loads. The refrigeration cycle generates the cooling effect by means of adsorption, absorption, and chemical reaction phenomena [1] [2] [3]. In particular, the adsorption chiller cycle has recently been receiving a lot of attention. The adsorption chiller cycle can be used to store waste heat and supply cold energy at low temperatures. Water-zeolite [4], Water-silica gel and Ammonia-activated carbon pairs [5] are some of the most common refrigerant-adsorbent pairs used in adsorption chillers. An adsorption chiller cycle using H 2 O or NH 3 refrigerant is considered to be an environment-friendly product. In a previous study, Kakiuchi et al. [6] introduced a new Functional Adsorbent Material-Zeolite 1 (FAM-Z1), which is an AFI-type structure Ferroaluminophoshate Zeolite (FAPO-5) with iron content of 2-8 mol% [6]. It was suggested that the adsorption capacity of FAM-Z1 was four times than that of silica gel at a desorption temperature of 6 C. However, the adsorption chiller cycle still has a few problems in practical use; by reason of the cooling power per unit volume of the adsorber and the COP are smaller than that of absorption chiller or vapor compression chiller. To solve the problems associated with the adsorption chiller cycle, we proposed a hybrid adsorption chiller which contained a mechanical booster pump (MBP) in the adsorption step or desorption step. Figure 1 shows the schematic diagram of the hybrid adsorption chiller cycle. It consists of an evaporator, a condenser, a MBP and an adsorber. All the units are connected under reduced pressure. The MBP is set either between the evaporator and the adsorber or between the adsorber and the condenser. The adsorption core which is installed in the adsorber consists of a heat exchanger filled with adsorbents. The heat associated with the adsorption or desorption phenomenon is removed or supplied by heat exchanger. The adsorption chiller cycle consists of an adsorption step and a desorption step. In the adsorption step, the refrigerant vapor moves from the evaporator to the adsorber, and then be adsorbed. In the desorption step, the desorption heat is supplied to the adsorber, and the desorbed refrigerant vapor moves to the condenser. In the hybrid cycle, MBP, which runs on electricity, pumps the refrigerant vapor from the evaporator to the adsorber to increase the adsorber pressure of vapor in adsorption cycle or pumps the refrigerant vapor from the adsorber to the condenser to decrease the adsorber pressure of vapor in desorption cycle. The change of pressure improves the adsorbent capacity. Figure 2 shows the adsorption isotherms of water on FAM-Z5. From Figure 2 1, it can be seen that FAM-Z5 can generate 15 C cold heat at the desorption temperature of 55 C. However, it cannot generate 1 C cold heat when it desorbs at 5 C or less (2). On the other hand, in the hybrid adsorption cycle, for example when the evaporator temperature is 1 C, the refrigerant vapor from 23

Figure 1. Schematic diagram of hybrid adsorption chiller cycle with MBP. Figure 2. Adsorption isotherms of water on FAM-Z5. the evaporator at the saturation pressure of 1.2 kpa can be compressed by the MBP, when the adsorber pressure rises to 1.7 kpa, the amount of adsorption is increased and has the same value as the condition that the evaporator temperature is 15 C without MBP. In the hybrid desorption cycle, desorption can take place when the vapor pressure of the adsorber is depressurized to 1 kpa at 5 C by MBP. The amount of desorption is equal to that of desorption under the condition of desorption temperature is 55 C without MBP. In this way, we can use MBP to expand the amount of adsorption or desorption by increasing or decreasing the vapor pressure of the adsorber. Therefore, the hybrid chiller cycle can be used at a large range of operation temperatures. In this study, we investigated the laboratory scale hybrid chiller cycle which consists mainly of a MBP and an adsorber with the FAM-Z5 adsorption core. 24

We evaluated the cooling output and desorption heat input of the hybrid chiller cycle, and researched the effect of the input electrical power of the MBP on the performances of hybrid cycle. 2. Experimental Procedure Figure 3 shows the schematic diagram of the experimental apparatus. Falling liquid film heat exchangers were used in the evaporator and the condenser, which had high heat transfer performance. Figure 4 shows the adsorption cores in the adsorber. Three pairs of adsorption cores were connected in series in the adsorber, and each pair was composed of two flat webbed tube and corrugated fin heat exchangers in parallel and FAM-Z5, had an average particle diameter of 5 μm, was coated around the tubes and fins of heat exchangers by epoxy binder. The coating thickness of adsorbent was 1 μm. MBP (MBS-52 type, ULVAC Inc.) was connected with stainless tubes and the rotating speed was Figure 3. Schematic diagram of the experimental apparatus. Figure 4. Photo of adsorption cores in the adsorber. 25

Table 1. Experimental conditions. Step Adsorption Step Desorption Step Evaporator 1 C, 15 C 15 C Adsorption temperature 3 C 3 C Desorption temperature 6 C 6 C, 55 C, 5 C, 45 C Condenser 3 C 3 C MBP power 2, 6, 1 W 5, 6, 1 W controlled by Lab View (National Instrument Inc.). When MBP was driven, we measured the electrical power consumption of it. The experimental conditions are summarized in Table 1. The condenser temperature was maintained at 3 C by thermostat bath. The evaporator temperature was set at 1 C and 15 C. The desorption temperature was set at 45 C, 5 C, 55 C and 6 C.The flow rate of the heat transfer fluid of all the units was set at a constant value of 4.5 L/min. The temperature of the fluid flow was measured by a Platinum resistance temperature sensor. This was followed by the calculation of cooling heat output, desorption heat input, amount of cooling heat and desorption heat and COP electricity using the following equations: W = Cp ρ F T (1) EVA fluid fluid fluid EVA,average W = Cp ρ F T (2) desorption fluid fluid fluid desorption,average Q = W dt (3) EvA or desorption t EVA or desorption COP electricity Q EVA = (4) Q electricity 3. Experimental Results and Discussion 3.1. Adsorption Step Figure 5 shows the cooling heat output change over time at evaporator temperature of 15 C and 1 C, respectively. Figure 6 shows the variation of adsorber pressure with time at 15 C. The valve 1 and 3 were opened and MBP was switched on at s. In Figure 5, the cooling heat output without MBP is also indicated. The maximum cooling heat output obtained without MBP was 25 W. On the other hand, the maximum cooling heat output with MBP at the input electrical power of 12 W was 38 W. The obtained cooling heat output increased with increasing the input electrical power of MBP. The refrigerant vapor from the evaporator was compressed by MBP, and then was absorbed by FAM-Z5. The adsorber pressure increased quickly by using MBP, resulted a faster adsorption rate and a higher cooling heat output. However, when the input electrical power of MBP was 2 W, the cooling heat output was lower than that of without MBP. In Figure 6, the adsorber pressure of 1.7 kpa is the saturation pressure at 15 C. The adsorber pressure was higher than the evaporator pressure when the MBP power was high. Time taken to reach the evaporator 26

4 (a) 4 (b) Cooling heat output [W] 3 2 1 MBP 6W MBP W Cooling heat output [W] 3 2 1 MBP 8W Figure 5. Time variation of cooling heat output for different MBP powers at 15 C (a) and 1 C (b). Adsorber pressure [kpa] 5. 4. 3. 2. 1. MBP 6W MBP W Evaporator pressure. Figure 6. Effect of MBP power on the adsorber pressure in adsorption step. pressure was 23 s at 2 W. The vapor transport between the evaporator and the adsorber was hampered by MBP, due to the rotational speed of MBP was extremely low at 2 W. It resulted in a very slow vapor transport rate, which was slower than that of without MBP and the adsorption rate. Figure 7 shows the amount of cooling heat in the adsorption step. As can be seen from the results, the amount of cooling heat obtained with MBP was more than twice as much as that of without MBP at 15 C. Furthermore, it was possible to obtain cooling heat at the evaporator temperature of 1 C, which cannot be acquired without MBP. Therefore, the hybrid cycle with MBP can improve the cooling heat at low evaporator temperature was confirmed. Figure 8 shows the effect of input electrical power of MBP on COP electricity which is the ratio of the cooling heat to the input electrical power of MBP. As can be seen from the results, the COP electricity decreased with increasing the input electrical power of MBP. When the evaporator temperature was 15 C, the COP electricity for the input electrical power of 2, 6, and 12 W was 7., 5. and 3., respectively. In addition, the COP electricity at the evaporator temperature of 1 C exhibited the same tendency as the results of 27

Amount of cooling heat output [kj] 8 6 4 2 MBP 6W MBP W (a) Amount of cooling heat output [kj] 8 6 4 2 MBP 8W (b) Figure 7. Time variation of cooling heat for different MBP powers at 15 C (a) and 1 C (b). 8. (a) 8. (b) 7. 7. 6. 6. COP electricity [-] 5. 4. 3. COP electricity [-] 5. 4. 3. 2. 1.. MBP 6W 2. 1.. MBP 8W Figure 8. Effect of MBP power on the COP electricity at the evaporator temperature of 15 C (a) and 1 C (b). 15 C. When the input electrical power of MBP was high, the COP electricity of the hybrid cycle was less than or equal to that of mechanical chiller cycle. Due to the saturation pressure of water is lower than the conventional refrigerants, such as HFC and ammonia, which are commonly used in the mechanical chiller. Figure 9 shows the effect of the input electrical power of MBP on the maximum cooling heat output and COP electricity at the evaporator temperature of 15 C. As shown in Figure 9, the cooling heat output increased as the input electrical power of MBP increased, whereas the COP electricity displayed the opposite trend. The tradeoff between cooling heat output and COP electricity was thus confirmed. 3.2. Desorption Step We also studied the desorption step without and with MBP. The experimental apparatus was the same as that of the adsorption step. The desorption step was carried out after the adsorption step which had been conducted under the evaporator temperature of 15 C without MBP. Closed the valve 1 and 3, and then 28

increased the adsorber temperature from the adsorption temperature to the desorption temperature. When the adsorber pressure became equal to or higher than the condenser pressure, valve 3 and 4 were opened so that the refrigerant vapor can transport into the condenser spontaneously. On the other hand, when the MBP was running and the valve 2 and 4 were opened instead of valve 3 and 4, the refrigerant vapor was compressed into the condenser by MBP. The desorption temperature was set at 5 C and 6 C for the cycle without MBP, 55 C, 5 C and 45 C for the cycle with MBP. Figure 1 shows the variation of desorption heat input with time. s of the horizontal axis corresponds to the timing of valve opening and MBP running. The results show that the desorption of refrigerant could proceed without MBP at 6 C, reaching a maximum desorption heat input of approximately 6 W. However, no desorption heat input can be obtained at 5 C without MBP, due 4 8 Cooling heat output [W] 35 6 3 25 4 2 2 15 Cooling heat output COP electricity 1 2 4 6 8 1 12 Electrical power [W] COP electricity [-] Figure 9. Effect of MBP power on the cooling heat output and the COP electricity at 15 C. Figure 1. Time variation of desorption heat input for different MBP powers. 29

to the poor adsorption capacity at this desorption temperature as can be seen from Figure 2. On the other hand, high desorption heat input was obtained with MBP at the desorption temperature of 5 C and 55 C. When the input electrical power of MBP was 5 W, the maximum desorption input power of about 115 W was obtained at 5 C, which was higher than that of at 6 C without MBP. The higher the input electrical power of MBP the lower the desorprion temperature can be used. Figure 11 shows the adsorber pressure change during desorption step. In the desorption step, the vapor transport rate is proportional to the pressure difference between the absorber and condenser. As can be seen from Figure 11, when valve 3 and 4 were opened, the adsorber pressure decreased to the condenser pressure immediately at 6 C without MBP and the desorption heat input was obtained. However, due to the adsorber pressure at 5 C was lower than the condenser pressure, when valve 3 and 4 were opened, the refrigerant vapor transported from condenser to adsorber, the opposite transport direction to 6 C, resulted in the desorption of refrigerant could not proceed and no heat input was obtained. It would have been the same situation as at 5 C if MBP had not been used in the desorption step at 45 C. When MBP was operating at 1 W, the vapor from adsorber was compressed into condenser by MBP, and therefore the desorption heat input was acquired at 45 C. Figure 12 shows the amount of desorption heat. From Figure 12, it can be seen that the desorption heat could be obtained in less time by operating the MBP with an input electrical power of 1 W, at the low desorption temperature of 45 C. Thus, we confirmed that in comparison with the cycle without MBP, hybrid cycle could obtain cooling heat at lower desorption temperature. 4. Conclusion We assembled a lab-scale FAM-Z5/H 2 O type adsorption chiller cycle with and without MBP. The effect of the input electrical power of MBP on the perfor- Figure 11. Effect of MBP power on the adsorber pressure in the desorption step. 3

Figure 12. Time variation of amount of desorption heat for different MBP powers. mances of adsorption step and desorption step were investigated separately. The following results were obtained.) 1) Adsorption step with MBP The cooling heat output and the amount of cooling heat were improved and increased with the input electrical power of MBP. Moreover, the adsorption chiller could be operated at a lower evaporator temperature lever. On the other hand, COP electricity decreased with increasing the input electrical power of MBP and was less than or equal to mechanical chiller cycle at the high input electrical power. 2) Desorption step with MBP The desorption heat input and the amount of heat input were improved and increased with the input electrical power of MBP. Desorption cycle could be effectively driven by a relatively low desorption temperature such as 45 C, in comparison with the cycle without MBP. The future work will be focused on the evaluation of cooling heat output and COP electricity when using MBP in the desorption step. A two-adsorber adsorption chiller will be constructed, which one adsorber is in adsorption cycle with MBP, the other one is in desorption cycle with MBP simultaneously. The performances of it will be investigated. References [1] Wu, W., Wang, B., Shi, W. and Li, X. (214) Absorption Heating Technologies: A Review and Perspective. Applied Energy, 13, 51-71. https://doi.org/1.116/j.apenergy.214.5.27 [2] Demir, H., Mobedi, M. and Ülku, S. (28) A Review on Adsorption Heat Pump: Problems and Solutions. Renewable and Sustainable Energy Review, 12, 2381-243. https://doi.org/1.116/j.rser.27.6.5 [3] Lahmidi, H., Mauran, S. and Goetz, V. (26) Definition, Test and Simulation of Thermochemical Storage Process Adapted to Solar Thermal Systems. Sol. Energy, 31

8, 883-893. https://doi.org/1.116/j.solener.25.1.14 [4] Palomba, V., Vasta, S., Giacoppo, G., Calabrese, L., Gulli, G., La Rosa, D. and Freni, A. (215) Design of an Innovative Graphite Exchanger for Adsorption Heat Pumps and Chillers. Energy Procedia, 81, 13-14. https://doi.org/1.116/j.egypro.215.12.112 [5] Hirota, Y., Kobayashi, N., Watanabe, F., Hasatani, M., Uda, S. and Inaoka, H. (28) Development of the Adsorber in the Ammonia and AC Combination Adsorption Heat Pump. Journal of Japan Society of Energy and Resources, 29, 35-41. http://www.jser.gr.jp/journal/journal_pdf/28/journal285_6.pdf [6] Kakiuchi, H., Shimooka, S., Iwade, M., Oshima, K., Yamazaki, M., Terada, S., Watanabe, H. and Takewaki, T. (25) Novel Water Vapor Adsorbent FAM-Z1 and Its Applicability to an Adsorption Heat Pump. Kagaku Kogaku Ronbunshu (Japan), 31, 361-364. https://doi.org/1.1252/kakoronbunshu.31.361 Submit or recommend next manuscript to SCIRP and we will provide best service for you: Accepting pre-submission inquiries through Email, Facebook, LinkedIn, Twitter, etc. A wide selection of journals (inclusive of 9 subjects, more than 2 journals) Providing 24-hour high-quality service User-friendly online submission system Fair and swift peer-review system Efficient typesetting and proofreading procedure Display of the result of downloads and visits, as well as the number of cited articles Maximum dissemination of your research work Submit your manuscript at: http://papersubmission.scirp.org/ Or contact msce@scirp.org 32