Available online at ScienceDirect. Evaluation of the streaming current detector (SCD) for coagulation control

Similar documents
Optimizing Coagulation with Streaming Current Plant Operations Conference Presented by the VA AWWA Plant Operations Committee

Optimizing Coagulation with the Streaming Current Meter. Chuck Veal Micrometrix Corp

OPERATIONS MANUAL. Coagulant Charge Analyzer. CCA 3100 Laboratory Model. Chemtrac Systems, Inc.

Feasible Use of Electrical Conductivity for Optimizing Polymer Dosage and Mixing Time Requirement in Sludge Conditioning

INDBOND 3000 Dry Strength Resin for Paper

L-17 Coagulation and Flocculation Part-I. Environmental Engineering-I

Evaluation of a modified chitosan biopolymer for coagulation of colloidal particles

ScienceDirect. Primary treatment of dye wastewater using aloe vera-aided aluminium and magnesium hybrid coagulants

Membrane for water reuse: effect of pre-coagulation on fouling and selectivity

REMOVAL OF REACTIVE YELLOW DYE USING NATURAL COAGULANTS IN SYNTHETIC TEXTILE WASTE WATER

Sanitary Engineering. Coagulation and Flocculation. Week 3

Delvin DeBoer, Ph.D., PE. MN/ND/SD SWTW April 29, 2014 OUTLINE

Water Treatment: Coagulation

OPERATIONS MANUAL. Models: LCA-1, LCA-2, LCA-3. Laboratory Charge Analyzer

ECOTAN SERIES. Natural Based Coagulants

ISEmax CAM40/CAS40. Technical Information

CHAPTER 5 CONVECTIVE HEAT TRANSFER COEFFICIENT

Treatment Processes. Coagulation. Coagulation. Coagulation. Coagulation. Coagulation and Flocculation

Organic Polymer Feeding

Relationship between the characteristics of cationic polyacrylamide and sewage sludge dewatering performance in a full-scale plant

Residual Chlorine Monitor

ENVIRONMENTAL ENGINEERING. Chemical Engineering department

Available online at ScienceDirect. Procedia Engineering 119 (2015 ) 13 18

BOXA-II ON-STREAM X-RAY FLUORESCENCE ANALYZER. Technical Description Version 2 BGRIMM AUTOMATION

Water Soluble Polymers For Industrial Water Treatment Applications

ISO Colloidal systems Methods for zetapotential. Part 1: Electroacoustic and electrokinetic phenomena

ScienceDirect Abstract

CEE 371 Water and Wastewater Systems

Methods for charge and size characterization colloidal systems

SurPASS. Electrokinetic Analyzer for Solid Samples. ::: Innovation in Materials Science

Poly Prep N Floc. Part No Instruction Manual. Updated 6/2/2009 Ver. 2.0

Coagulant Overview. Tom Coughlin Chemtrade 2015

Particle Charge Titration Zeta Potential Size Distribution

COAGULATION AND FLOCCULATION

Control Loop Investigations

METHOD 9040B. ph ELECTROMETRIC MEASUREMENT

CT4471 Drinking Water 1

A UNIQUE METHOD TO CONTROL SETTLING OF FIRST CARBONATION JUICE

Available online at ScienceDirect. Procedia Engineering 174 (2017 )

Immediate Free Chlorine Correction for Fluctuating Flow & Changes in Water Quality. Sadiq Khan May 25th, 2016

Mixing Process of Binary Polymer Particles in Different Type of Mixers

Factorial Experimental Design for Reactive Dye Flocculation Using Inorganic-Organic Composite Polymer

= A x (t) + B utt), by d{ _-=-=-

RESEARCH ON AIRBORNE INTELLIGENT HYDRAULIC PUMP SYSTEM

Technical Paper 3 Verifying Particle Counter Calibration: Size Verification

Novel method for on-line rheology measurement in manufacturing of non- Newtonian liquids

Electron Beam Processed Polyelectrolytes

next generation Welcome to the Dispersion options Smarter particle sizing Your sample, expertly processed and prepared Particle size

ECA 2100 OPERATIONS MANUAL

PARTICLE MEASUREMENT IN CLEAN ROOM TECHNOLOGY

Chemistry Instrumental Analysis Lecture 31. Chem 4631

Lecture 3: Coagulation and Flocculation

University of Bristol - Explore Bristol Research

Use of Near Infrared Spectroscopy for in- and off-line performance determination of continuous and batch powder mixers: opportunities & challenges

MRI Flocculation. MRI Flocculation Systems. Mix & Match for Maximum Pretreatment Control

Available online at ScienceDirect. Procedia Engineering 154 (2016 )

Automated Clinical Analyzer

Geotube Technology for Residuals and Biosolids Management

Application Your benefits

Electrophoretic Light Scattering Overview

CCS140 and CCS141. Technical Information. Sensors for free chlorine Amperometric, membrane-covered sensors for installation in the CCA250 assembly

Removal of copper and cadmium using industrial effluents in continuous. column studies by mixed adsorbent

ScienceDirect. Simulating Friction Power Losses In Automotive Journal Bearings. H. Allmaier a, D.E. Sander a, F.M. Reich, a, *

INJECTION ELECTRODE POLARIZATION IN RESISTIVITY AND INDUCED POLARIZATION

ADVANCED SEPARATION TECHNOLOGY APPLICATION FOR NOM REMOVAL FROM A FRESHWATER SUPPLY

Polyaluminum Chloride and Chitosan Composite Coagulant for Natural Organic Matter Removal

Optimization Studies on Textile Wastewater Decolourization by Fe 3+ /Pectin

CCS140 and CCS141. Technical Information. Sensors for free chlorine Amperometric, membrane-covered sensors for installation in the CCA250 assembly

Effective Modes of Axial Balancing of Centrifugal Pump Rotor

Available online at ScienceDirect. Physics Procedia 67 (2015 ) Calibration of a HTS based LOX 400mm level sensor

473 Dew Point Hygrometer

Available online at ScienceDirect. Nuclear power plant explosions at Fukushima-Daiichi. Takashi Tsuruda*

Available online at ScienceDirect. Procedia Engineering 90 (2014 )

ANALYSIS OF LOW DENSITY PARTICLES USING DIFFERENTIAL CENTRIFUGAL SEDIMENTATION

CHAPTER 3. CONVENTIONAL RHEOMETRY: STATE-OF-THE-ART. briefly introduces conventional rheometers. In sections 3.2 and 3.

Basic Math Concepts for Water and Wastewater Operators. Daniel B. Stephens & Associates, Inc.

Frequently asked question about our new Platinum Water Ionizer

Glossary of Common Laboratory Terms

Organic Carbon, Total (Low Level) (UV Promoted, Persulfate Oxidation) CAS # Total Organic Carbon TOC C

Automated volume measurement for weihts using acoustic volumeter

Behavior of Micro-Stickies in Papermaking Environment

Available online at ScienceDirect. The 2014 conference of the International Sports Engineering Association

o0, and since the period of vibration of the scale is related to the mass,

Determining of the Residence Time Distribution in CPC reactor type

Mercury Stack Monitor SM-4

THE RESEARCH OF ACTIVATED SLUDGE DEWATERING PROCESSES.

473-SHX Dew Point Mirror

Reprint. Project Summary. Side by Side Evaluation of ChemScan UV-4100 and Hach (Dr. Lange) Optiquant at Littleton-Englewood Colorado

Flocculation Test Unit PEF. Technical Teaching Equipment PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION. Meters. TDS and Temperature

Continental J. Engineering Sciences 6 (2): 7-15, 2011 ISSN: Wilolud Journals, ` Printed in Nigeria

Available online at ScienceDirect. Procedia Engineering 105 (2015 )

See us (live!) at Pittcon Booth 1039

Water & Wastewater Mixing: Lighting Up A Dark Art (or cramming a quart into a pint pot!)

Development of an organometallic flow chemistry. reaction at pilot plant scale for the manufacture of

IMPACT OF PARTICLE AGGREGATED MICROBES AND PARTICLE SCATTERING ON UV DISINFECTION

Projects Involving Nanotechnology at The Oxford Centre for Sustainable Water Engineering. Dr Nick Hankins

Deuterium Gas Analysis by Residual Gas Analyzer

Activated Carbon as a Pseudo-reference Electrode for Potentiometric Sensing Inside Concrete

Theory of Flocculation Reprint with Authorization by David L. Forbes

Water Quality - Condensed Version 1999

Transcription:

Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 70 ( 2014 ) 1211 1220 12th International Conference on Computing and Control for the Water Industry, CCWI2013 Evaluation of the streaming current detector (SCD) for coagulation control S. Muzi Sibiya a * a Rand Water, Scientific Services Division, Vereeniging, South Africa, 1930 Abstract A streaming current detector (SCD) is an instrument for measuring the charge that exists on small, suspended particles in water. The SCD is the instrument that can be used to measure coagulated particle stability for the feedback control of coagulant dosage. This report discusses the application of SCD as an instrument for coagulation dosage control. The SCD with automatic control of coagulant dosage consistently produced acceptable water quality, even during periods of changing raw water turbidity and varying flow rates. It minimizes under and overdosing of coagulant. It requires regular cleaning and maintenance to ensure optimum operation. The SCD is no substitute for efficient water treatment management. 2013 The Authors. Published by by Elsevier Ltd. Ltd. Open access under CC BY-NC-ND license. Selection and peer-review under responsibility of of the the CCWI2013 Committee. Keywords: Streaming Current Detector; SCD; coagulation; potable water treatment; drinking water treatment; water treatment 1. Introduction In most waterworks the determination of the optimum coagulant dosage is established by jar test in combination with operators assessment. Edney and Edgar et al. (2005) indicated that this process is time consuming and in some instances unreliable. The need for a feedback control system for continuous coagulant dosage control has become necessary due to changing raw water quality and water production rate changes based on consumer demand patterns in a 24 hour plant operation cycle and increasing cost of chemicals. Coagulation is first and one of * Corresponding author. Tel.: +27 16 430 8400. E-mail address: msibiya@randwater.co.za 1877-7058 2013 The Authors. Published by Elsevier Ltd. Open access under CC BY-NC-ND license. Selection and peer-review under responsibility of the CCWI2013 Committee doi: 10.1016/j.proeng.2014.02.134

1212 S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 the most critical steps in water treatment processes and it needs to be well optimized. An efficient auto coagulant dose control system using Streaming Current Detector (SCD) technique also optimizes chemical usage. The SCD is generally effective in situations where changes in raw water flow rates in the plant also require proportional changes to the coagulant flow rate to maintain the current coagulant dose. The SCD is also effective in adjusting coagulant dose in response to raw water flow rates, quality and coagulant used (AWWA 1988, Christopher et al. 1996). SCDs have found widespread use in water treatment plants. The instrument is claimed to provide a number of benefits in monitoring and controlling coagulant feed rates, including Slater et al. (2003) and AWWA (1988, 1990): Maintain consistent high quality of final water Handles changes in raw water conditions Automate coagulant dosing Ensure coagulant reliability Record changes in water chemistry Reduce dosing chemical usage Optimize dosing chemical usage Prevent plant upsets due to early detection of plant malfunctions. Automatic coagulant control is ensured mainly by streaming current detectors (SCD) which measure the residual charge on colloidal color and turbidity particles in the water. As these particles have a negative charge and the coagulant ions have a positive charge, the amount of coagulant added dictates the magnitude and sign of the net electrical charge. The system controls this net charge at a set point which has been shown by jar testing to provide close to optimum coagulation under a certain range of raw water conditions. The aim of this study was to assess the feasibility, in the laboratory, of a SCD to control coagulation when polymeric coagulant is employed as primary coagulant. The instrument being evaluated was the 16mp Streaming Current Detector, supplied by Lechintech 1.1. Theoretical operating principle of the SCD The SCD essentially consists of a sensor and a signal processor. A simplified diagram of the sensor is presented in Figure 1.The sensor chamber is a closed unit with an inlet and outlet for the test water sample containing the particles that flow through the unit at a rate of about 1 3 liters per minute. Inside the chamber is a piston that moves vertically in a reciprocating motion. The piston moves inside a cylinder with a velocity that is sinusoidal in nature. It is the motion of charged particles in the space between the piston wall and the cylinder (called the annulus) that is critical to the ion charge analyzer. Figure 2 shows the annulus, which is in the shape of a thin cylindrical shell, containing the sample fluid and particles. Also shown in Figure 2 is the position of the electrodes in the SCD sensor. Generally, these are two metal rings located in the upper and lower areas of the cylinder.

S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 1213 Figure 1: SCD sensor (AWWA, 1988) Figure 2: Sensor electrode location (AWWA, 1988) The cylinder wall and the piston are manufactured from a special material (Teflon) that allows particles to stick on to the surface. As water flows in the annular space between the cylinder and piston, the cylinder walls and the piston become coated with particles. By their nature colloidal particles in natural raw water, are negatively charged and are said to have a negative charge density. The overall electrical charge in the water system must be neutral; therefore, the particle is surrounded by a positive charge density, called the counter ions, in water. Between the two layers of charge (negative charge close to the particles and positive further away from the particles) is the plane of shear. The motion of the piston in the cylinder causes fluid motion in the annulus of the SCD and consequently fluid shearing at the shear plane. There are two shear planes, one near the cylinder wall and the other near the piston wall. Essentially, two layers of charge move relative to each other. The movement of charge between the upper and lower electrode (Figure 2) constitute an electrical current. This current is dependent on the velocity of the fluid and the charge density. If the piston motion is constant, then the magnitude of the charge density is proportional to the magnitude of the ion charge and is determined by the amplitude (peak) height of the alternating current signal. The current generated in the sensor is in the order of 10-12 amps. Very careful processing and amplification of this signal is necessary to avoid interferences due to electronic noise. This signal can be output to a read-out, chart recorder or a control system for chemical feed. 1.2. Application in process monitoring and control The ion charge reading is proportional to the charge density of the particles in the water sample. The usefulness of SCD depends on the mechanism of charge neutralization, where a coagulant is added into the water to neutralize the negative charge density on the particles (coagulation). The destabilized particles adhere to adjacent particles (flocculation).

1214 S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 The addition of cationic coagulant to raw water, typically containing negatively charged colloids, neutralizes the charge on the colloidal particles. The neutralized colloidal particles, do not contribute to the ion charge and the net result is a relatively more positive ion charge response. Generally, the main criterion for optimum coagulant dose is the settled turbidity and the ion charge at that point corresponds to the target or set-point ion charge. Since an increase in colloidal concentration would impact on the net charge density in the sample, ion charge measurements are used to monitor and control coagulant dose. A typical application of the ion charge analyzer is shown in figure 3. Raw water Flash mixing Flocculation Sedimentation Filtration Coagulant SCD High / Low Alarm Dosing pump Controller Recorder Figure 3: Application of SCD to coagulant dose control (Rajagopaul, 2002; Edney,) The electronics of the ICA has been designed to give a negative digital output when the test sample contains an excess of negatively charged particles (typically raw water) and a positive reading when the sample contains an excess of positively charged particles (industrial effluent and process water). It has also been designed to give a large increase in positive ion charge readings for the addition of small increments (0.1mg/l) of cationic polymeric coagulants, in excess of the cationic demand of the water. A typical coagulant dose versus settled turbidity and the corresponding IC readings is presented in Figure 4(a). It can be seen that the optimum coagulant dose (A) corresponds to the streaming current reading (A1). Also from Figure 4(a), a coagulant overdose situation, indicated by B in the re-stabilization region, can be easily picked up by the corresponding ion charge reading. Dependence on turbidity measurements alone can be misleading in a coagulant under dose or over dose situation

S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 1215 Figures 4(a) and 4(b); Variation of settled turbidity and ion charge with coagulant dose (AWWA, 1988) Figure 4(b) shows that the ion charge at optimum coagulant dose remains constant despite a two-fold increase in raw water turbidity. The ion charge follows a similar trend for fluctuations in raw water flows. The optimum coagulant dose is determined from jar tests. After switching the coagulant dosing control to manual, the (jar test) recommended dosage is applied to the plant. The dosage is adjusted, using the cascade test results and settled water overflow turbidities, until the dosage is optimized. The plant is continued to operate on manual until process stability is attained, including stable reading on the SCD. The resultant SCD reading is taken as the process set point value (SP), set on the PLC /SCADA. The forward feedback control is configured to maintain the SCD set point by adjusting the coagulant dosing pump flow rate. In a water treatment plant the SCD will be positioned downstream of the point of coagulation, after the coagulant has been completely dispersed throughout the water. An operator can adjust the coagulant dose based upon a previously determined value associated with plant performance. This point is referred to as the set point (SP).

1216 S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 2. Material and methods The Vaal Dam raw water was used to conduct jar test experiments. Polymeric coagulant (SUDFLOC 3835) was employed as primary coagulant. The experiments to control the polymer dosage as primary coagulant were conducted on bench scale. Rapid mixing was performed at 200 rpm for two minutes. A sample of coagulated water was taken and streaming current was measured on the coagulated water. The SCD reading was measured at 30 second interval for the duration of 5 minutes. The average value was then recorded. Table 1 below indicates specification of SCD employed. Table 1: Specifications of the model SCD 16mp Parameter Technical data Range -5ICu to +5ICu Accuracy Ion Charge: ± 0.1ICu Cationic demand: ± 1% Cationic Power supply 220 VAC 50 Hz at 12VA A solid earth connection is essential Probe Immersible to depth of 120 mm in sample. 6 to 10 l/min sample flow rate required at 30KPa max. SCD dimensions Height : 320 mm Width: 160 mm Depth : 100 mm Calibration Two points: zero and positive span in cationic standard solution. Measuring mode Ion charge (ICu) Communication interference 4 20mA linear output scaled -5.00 ICu to +5.00 ICu ph range for operation 3 12 Conductivity range for 0 500 ms/m operation Temperature 5 0 C 60 0 C Weight 4.5 kg http://www.lechintech.com/pdf-manuals/ldt_16mp_manual.pdf. Accessed May 2013 The streaming potential is an inverse phenomenon of electro-osmosis in a capillary system, which is closely related to zeta potential and is represented by terms as pressure difference and zeta potential by Helmholtz equation (8). SP= P D/4 Where SP is the streaming potential (unit less), P the press (potential) difference, the electrokinetic potential, D the relative permittivity of the electrolyte, the viscosity coefficient and is the specific conductivity. The SP, which can be measured using a detector, is both an absolute and relative value. The former is a theoretical value that represents the charge in the water flowing between the two electrodes; the latter is the value which is manually set after appropriate manipulation or experiments.

S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 1217 3. Results and discussion 3.1. Optimum concentration of calibration standard Figure 5: Variation of charge density with polymeric coagulant concentration The critical criterion for the selection of a suitable standard concentration is that the standard concentration should be within the region where charge density is not significantly affected by polymer concentration. Figure 5 show that a polymer concentration of 100 mg/l was within the region where there is negligible change in ion charge relative a large change in polymer concentration. At the dosage of of 20 mg/l polymeric coagulant the SCD reached the saturation point. There insignificant change on the SCD reading with increased polymeric coagulant dosage. 3.2. Basic experiments: polymer dosage and streaming current. Figure 6 illustrates the resulting SC as the concentration of cationic polymer is increased from 0 to 15 mg/ experiment. The polymer is positively charged and influences the streaming current in this direction (less negative), a peak is then observed followed by a drop in SC. The streaming current reading increased with increased polymeric coagulant dosage. The results in figure 6 indicated that using SP enable direct control of the charge of the coagulated water by maintaining the charge neutralized condition in the continuous operation. Even though the polymer inter-bridging between raw water particles is also influential, the study regarding the optimum polymeric coagulant dosage reveals that coagulation is at optimal around the near zero of the streaming current. The optimum polymeric coagulant dosage is between 5 and 5.5 mg/l, the corresponding SC reading is between - 1.5 and -0.5 ICu.

1218 S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 Figure 6: Streaming current variation with polymeric coagulant dosage. 3.3. Required time for complete particle destabilization The response of the SCD coagulant dosing control loop was tested by monitoring the ICu readings of the ICA linked to the coagulant dosing pump. Figure 7 shows the ion charge measurements as a function of time during two periods. The first was a period of no coagulant addition (AB) when the coagulant dosing pump was turned off, until the IC reading reached a minimum value (B). The second was a period of automatic coagulant control (BC) when the coagulant pump was switched on again and automatic dosing resumed. The SCD was used to determine minimum coagulation time required at 200 rpm. Optimum polymeric dosage of 4 mg/l was added and the change in streaming current reading was monitored over the period of the time. From figure 7 complete particle destabilization was achieve within 4 minutes.

S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220 1219 C A B Figure 7: Streaming current detector reading (ICu) at a dosage of 4 mg/l polymeric coagulant dosage It can be seen from Figure 7, that the ion charge set point value (-1.7) is reached after about 4 minutes from the onset of automatic coagulant dosing. The response time is a function of the PID configuration and the closeness of the initial IC reading to the set point. In general the results indicate that the SCD provides a good measure of coagulant dosing control. 4. Conclusions This study reports the results of the on-line control of polymeric coagulant dosage at rapid mixing step in water treatment. The results show that the SCD reading increases as the polymeric coagulant dosage increases. The supplier recommended cationic polymer concentration for an SCD calibration standard of 100 mg/l was found suitable for SCD calibration purposes The streaming current reading of the coagulated water at optimum coagulant dose was not significantly affected by raw water turbidity. Indications are that the SCD automatic control coagulant dosing has potential for operation optimization, effective and reliable. Comparison study of two different SCD to be conducted to determine if there are intrinsic differences from one SCD to another.

1220 S. Muzi Sibiya / Procedia Engineering 70 ( 2014 ) 1211 1220. Consideration should be given to other methods for sensor cleaning. The available methods are ultrasonic and chemical. The ultrasonic technique should be investigated. 5. References Adgar, C.S. Cox, C.A. Jones. (2003) Coagulation control using the streaming current detector: Problems and possible solutions. Control systems centre, University of Sutherland, UK, Northumbrian Water Ltd, UK AWWA research foundation. (1988) An evaluation of streaming current detectors American Waterwoks Association (AWWA) November 1988. AWWA Research Foundation (1988) An evaluation of streaming current detectors, Research report: Water Treatment and Operation; November 1988, AWWA. Byun, S., J. Hyun Kwon, Myung-hak Kim, Ki-young Park and Seockheon Lee. (2007) Automatic control of polymer dosage using streaming potential for waterworks sludge condition. Separation Purification Technology 57, 230 236. Edney, D., (2005) Introduction to the theory of the streaming current meter Rajagopaul, R. (2002) Evaluation of Ion Charge Analysers at Wiggins Waterworks. Umgeni Water internal report, December 2002. Slater, N., P. Bahrs and C. Cumings. (1990) Streaming Current Detectors Theoretical and operational assessment. Water Institute of South Africa conference 1990, 485 495. Walker, C.A., J. T. Kirby, and Steven K. Dentel. (1996) The Streaming Current Detector: A Quantitative Model, journal of colloid and interface science 182, 71 81, article no. 0438