STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

Similar documents
An Introduction to Insulation Resistance Testing

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual

Fitting PS P - B - R2

Installation guide 862 MIT / MIR

E8EB-N0C2B E8EB-N0B2B

473 Dew Point Hygrometer

Operating Instructions for Digital Manometer. Model: MAN-SD

473 Dew Point Hygrometer

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

ED 701 General Industry Pressure Transmitter

Pressure. 1 Fitting PA R - N R2

Field IT 50T Series Transmitters

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Today s Weather 24 Hour Forecaster

- compressed air plants (refrigerating/adsorption dryers) - granulate dryers - medical gases - non-corrosive gases, e. g. nitrogen

Cold and freeze protection of blueberries in Florida. Dr. Dorota Z. Haman Agricultural and Biological Dept. University of Florida

ph electrode Instruction Manual For use with the RAH-210 & RPH-250

Digital Stored Grain Quality Management. BinMaster Level Controls Lincoln, Nebraska, USA

BASE. Rotary limit switch. OptiOnS. FEAtuRES. CERtiFiCAtiOnS

WS-7047TWC Wireless 433 MHz Weather Station With Rainfall and Temperature. Instruction Manual

473-SHX Dew Point Mirror

PTA-427 BAROMETRIC PRESSURE TRANSDUCER OPERATOR S MANUAL

CONTENTS. La Crosse Technology, Ltd. Page 1

Proximity Sensor Ideal for High Temperatures and Cleaning Processes. Applicable to 120 C

WCAP-AS5H Aluminum Electrolytic Capacitors

SF6 Gas Standard Capacitors

Differential ph Probe Type 18

Data Sheet / Instructions. Dewpoint MeterO

ph Probe ReallyEasyData com

Pressure transmitters for industrial applications MBS 32 and MBS 33

DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications

A Case for Periodic Calibration or Verification of RTDs

Recommended Land Pattern: [mm]

Medium Pressure Sensor Analog Output

FLT5A FLT5A. abc. abc. Thermometer User Guide. Thermometer User Guide. Internet:

SkyScan EWS-PRO - Manual -

M2 SERIES THERMOSTATS 0 F to 240 F, Narrow Differential, Hermetically Sealed ½

ORP Probe ORP. Reads. +/-2000mV. Range. 95% in 1s. Response time 100 PSI. Max pressure. 60m (197 ft) Max depth 1 80 C. Temperature range C.

Dewpoint Meter Data Sheet / Instructions

ph Probe Spear Tip Silver / silver chloride Reads Range / Resolution 95% in 1s Response time 100 PSI Max pressure 60m (197 ft) Max depth

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level

SSi Super Systems Inc.

BTE5000 / PTE5000 / PTU5000 Series Precision differential pressure transmitters

THM80X Series Feature Application. Temperature & Humidity / Flow Measuring Specialist

AM 500A 500 WATT AM 1A 1 KILOWATT AM BROADCAST TRANSMITTERS. October, 1999 IM No

DM70. Hand-held Dewpoint Meter. Truly Fast Response - Superior Long-term Stability

MANUAL TT-220 TT-220

Field Pro Operation and Installation Manual

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( )

PRODUCT DATA SHEET. Eagle Eye Outdoor LED Module 5700K. RoHS Compliant. CUSTOMER :. DATE : REV : Rev. 2.0.

ph Probe Silver / silver chloride Reads Range / Resolution 95% in 1s Response time 100 PSI Max pressure 60m (197 ft) Max depth 1 99 C

PRODUCT DATA SHEET. Eagle Eye Outdoor LED Module 3000K. RoHS Compliant. CUSTOMER :. DATE : REV : Rev. 1.0.

Small, Gauge Pressure Sensor

Assembly Instructions for the 1-Wire Weather Station V2.0/V3.0

Recommended Hole Pattern: [mm]

Pressure Transmitter ED 701

MLCC APPLICATION GUIDE

Small Gage Pressure Sensor

Capacitive Sensors. Contents

Cooling Water Flow Regulator

Recommended Land Pattern: [mm]

Recommended Land Pattern: [mm]

Low Pressure Sensor Amplified Analog Output SM6295-BCM-S

Low-Voltage Analog Temperature Sensors in SC70 and SOT23 Packages

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications

PTF30 Series. Features. Ordering information. G 6 N N F8 (0 to 5 kgf/cm 2 ) PTF30

Decade Capacitance System

Drive electronics pq12

ABB SpA COMEM Operating Unit Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Technical Note Series

LED light engines LED compact. Module SLE G7 ADV Modules SLE ADVANCED

15 E OWNER S MANUAL PIRATE SPYGLASS BRING EM NEAR PIRATE SPYGLASS TELESCOPE 5 W 30 W 60 W 45 W

Recommended Land Pattern: [mm]

MLCC APPLICATION GUIDE

WCAP-CSSA Ceramic Capacitors

State Unitary Enterprise Production Amalgamation Novosibirsk Instrument-Making Plant PN-6K. Servise Manual

Richter Optica. Instructions for Model: S850 Stereo Zoom Microscope

METALLIZED POLYPROPYLENE AC FILTERING CAPACITORS

Conductivity sensor for hygienic applications

Must Read Before Installation TadPoleTM Safety and Warnings

RT-6 Riflescopes. User Guide

Presco AG. Standard Air Capacitor 10 nf / 2 kv. Type CL-0N10-K201. User's manual

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Melton Series. Owners Manual. Lab Centrifuge. Model # s A C, A C, B C, B C, C C, C C, D C, D C

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

WCAP-FTXX Film Capacitors

ISEmax CAM40/CAS40. Technical Information

Rapid RH Portable ph Meter. User's Manual

25, 35, 50, 63 Vdc. RoHS Compliant. Size Code ± 0.5 ± 0.3. F to

Flexbar 6.3:1 MANUAL ZOOM STEREO MICROSCOPE. 250 Gibbs Road, Islandia, NY (P) (F)

Reference Only Spec. No. JEFL243B 0003F-01 P 1/ 6

DHS1900 DHS3000 High Temperature Hand Held Infrareds User Manual

Product Data Sheet PD-0053-A

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

Surface Mount Multilayer Ceramic Chip Capacitors Prohibit Surface Arc-Over in High-Voltage Applications

Applications. Capacitance Tolerance G = ±2% J = ±5%

Series Shrink Boot Adapters. Series Shrink Boot, EMI/RFI, Strain Relief. Series Shrink Boot, EMI/RFI, Shield Sock

Transcription:

APPLICATIONS Moisture monitoring of air or gas (SF6) Suitable for indoor or outdoor Industrial, medical or aerospace fields HIGHLIGHTS High voltage circuit breakers commonly used for distribution and transmission are reliable if they are able to operate in steady and controlled conditions. The use of SF6 as quenching gas is extremely important to guarantee a safe operation during the life of equipment. But if moisture inside the gas exceed critical limits the properties of insulation of SF6 are no more valid and severe damages can happen to switchgear. Moisture limits are defined by IEC60480 standard which defines the guidelines for checking and treatment of sulfur hexafluoride (SF6) taken from electrical equipment and specification for its re-use. The inlet of moisture inside tank can bring, during power switching and arc quenching, to chemical decomposition of SF6 into fluorides. Fluorides indeed do not reduce good insulating properties of SF6 unless the content of humidity is beyond critical limit: at this stage the byproducts also include the high corrosive HF hydrogen fluoride acid. In addition to above the content of moisture must be kept under control to guarantee that in very cold climates the water vapor can t condensate creating tracking lines or leakage currents. Wide range measurement of dewpoint High accuracy +/- 3 C (+/- 5.4 F) Patented polymer die chemically resistant Excellent long term stability Quick response time Factory calibration by laser trimming Low drift temperature compensated 14 bit ASIC core Multiple transmission data output Moisture calculation is based on measurement of two physical data: relative humidity HR% and temperature. Our sensor has an integrated sensing element able to read contemporary both HR and T which are converted by the ASIC into equivalent dew point temperature. Page 1/13

Page 2/13

Page 3/13

Page 4/13

Page 5/13

Page 6/13

STORAGE If the complex must be storage before use, please keep dry and repaired. Do not leave outdoor. Device is strongly sensitive to humidity hence avoid to store where relative humidity is more than 90% STORAGE TEMPERATURE: -30 C +70 C RELATIVE HUMIDITY: max 90% @ +40 C MAINTENANCE Maintenance of transmitter must be done compulsory in factory. We recommend every 5 years to send back transmitter for calibration check and inspection. WARRANTY Device is covered by 24 months after installation or max 36 months after delivery. In case of service the transmitter must be sent back to factory for inspection. Page 7/13

WARNINGS CAUTION Do not drop or hit the transmitter. The sensor is fragile and may break from sudden shock. When transporting the transmitter, use the original shipping box from Electronsystem. NOTE Keep the transmitter dry and clean. Do not remove the transparent transport protection caps before you are ready to install the transmitter. Uncapped transmitter will absorb environment moisture which will affect the dewpoint measurement and will potentially need weeks to be ready to give reliable signal. NOTE Connect the transmitter directly to the main SF6 gas volume, not behind a sampling line because this is the area where high humidity tends to accumulate. In any case after first installation the transmitter will have a small amount of moisture inside the connection. In still dry gas it takes a long time until a vapour pressure inside the measurement cell reaches equilibrium with the main gas tank. It is usual for the stabilization of the dewpoint reading to take several days after installation. Page 8/13

INSTALLATION 1. Remove the transparent transport caps when you are ready to install the transmitter. Check o-ring is clean without dust and properly assembled. 2. Install the transmitter to the mechanical coupling and tighten gently by hand. Then use a 30mm wrench to tighten the connection. Use a sufficient force to achieve a tight installation (recommended 10-15Nm). The system must be leak-free for accurate measurement. Page 9/13

3. Connect proper circular wiring into the output port checking the correct polarization of the connector then turn firmly the rotating crown of the cable. Use a cable with a suitable outdoor IP67 connector for your installation (straight or angled) 4. In case the weather shield is needed (optional), can be added to the transmitter by fitting the two rubber clamps on the body of transmitter and tightening to assure it can remain in place. Assure that the stainless roof completely cover the transmitter and the cable connection. Page 10/13

APPLICATION NOTES and FAQ: Q: What is the physical parameter transmitted by SGM/DEW/x? A: The sensor read relative humidity and temperature and converts into dewpoint temperature Q: What is dewpoint temperature, Tdew? A: The temperature (in degrees C or F) at which moisture (water vapour) in the gas begins to condense as liquid (droplets or dew) or solid (ice) Q: What is ppmv? A: Moisture volume concentration (parts per million by volume). One million times the ration of the volume of moisture (water vapour) present in the gas to the total volume of the gas (including water vapour). Q: What is ppmw? A: Moisture mass concentration (parts per million by mass). For SF6 gas, conversion to ppmw=ppmv / 8.1 Q: Is Tdew pressure dependant? A: Yes it is strongly dependant. It has no sense to deal with Tdew without indicating also the reference pressure of tank Q: Is ppmv or ppmw pressure dependant? A: No they do not depend on pressure of tank Q: What if measurement in ppmv is desired and only dewpoint is known or measured? A: To convert Tdew to ppmv (or ppmw) pressure of tank need to be known. There are some formulas able to calculate ppmv starting from Tdew and pressure. For general purpose indication please check tables below. Page 11/13

Simplified table for quick conversion to ppmv Page 12/13

Calculations have been simplified for an easier reading. DISCLAIMER NOTE: While we provide application assistance it is up to the customer to determine the suitability for its use. Specification may change without notice.the information we supply is believed to be accurate and reliable as of this printing. However we assume no responsibility for its use. The quality of ElectronsystemMD products is guaranteed by a Quality, Safety and Environmental management system certified by DNV according to ISO 9001, ISO 18001 and ISO 14001. Electronsystem MD works in partnership with its customers in designing customized executions in order to meet specific requirements, please contact us. Page 13/13