TH 202 / TH 202-Ex. Field mounted temperature transmitter, HART programmable, Pt 100 (RTD), thermocouples, electrical isolation. ABB Instrumentation

Similar documents
S95.3U02 / S95.3U12. Head mounted temperature transmitters, HART programmable, Pt 100 (RTD), thermocouples, electrical isolation

S95.3U01 / S95.3U11. Head mounted temperature transmitters, programmable, Pt 100 (RTD), thermocouples, electrical isolation

TF 212 / TF 212-Ex. Field mounted temperature transmitter, Profibus PA, Pt 100 (RTD), thermocouples, 1 or 2 independent channels. ABB Instrumentation

TF 202 / TF 202-Ex. Field mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

TF 212 / TF 212-Ex. Field mounted temperature transmitters, PROFIBUS PA, Pt 100 (RTD), thermocouples, 1 or 2 independent channels 10/11-8.

Field mounted Temperature Transmitter TF212/TF212-Ex

SINEAX VK 626 Programmable Temperature Transmitter for RTD and TC inputs, with HART protocol

SINEAX VK 636 Programmable Temperature Transmitter with PROFIBUS-PA protocol

ED 701 General Industry Pressure Transmitter

Exchangeable measuring insets SensyTemp TSA101

PHOENIX CONTACT - 04/2016. Features

Physikalisch-Technische Bundesanstalt

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

Pressure transmitters for industrial applications MBS 32 and MBS 33

Multi-function, economical instrument with 4 functions in the same casing. Accessibility and safety: large-dimension terminals Insulated circuits

DMP 331P. Industrial Pressure Transmitter. Process Connections With Flush Welded Stainless Steel Diaphragm

SCTP20 Programmable 2-Wire Temperature Transmitter, Head Mount

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

DS 200P. Electronic Pressure Switch. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm

4.2. Ex-Ceiling light fittings AB 80 / AB 05 LED / AB 05 / AB 12 NAV 70. (Zone 1, 2, 21, 22)

DS 300. Electronic Pressure Switch. with IO-Link interface. Stainless Steel Sensor. accuracy according to IEC 60770: 0.35 % FSO.

Reflex-Radar BM 100 A

Z7A. Load cells. Special features. Data sheet. Wiring code

Installation guide 862 MIT / MIR

CALYS 120 IS. ATEX documenting multifunction calibrator with high accuracy 0.006%

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level

BMXART0814 analog input module M340-8 inputs - temperature

E X - C O N T R O L U N I T S A N D C O N T R O L S T A T I O N S

Field IT 50T Series Transmitters

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. SensyTemp TSA101 Exchangeable measuring insets

Level Sensor PanCake PR 6251 and Mounting Kit PR 6051

Safety Barriers Series 9001, 9002 Standard Applications

Capacitance Level Measurement Electronic Inserts EC 37 Z, EC 47 Z

4.3. Ex-Pendant light fittings AB 50 / SPG 1N / AB 51 / EVI 200 / EVI 500 / EV35 LED. (Zone 1, 2, 21, 22)

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Pressure Transmitter ED 701

HYGRASGARD KFF KFTF HYGRASGARD AFF AFTF HYGRASGARD AFF - LC AFTF - LC

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

THM80X Series Feature Application. Temperature & Humidity / Flow Measuring Specialist

PRODUCT CATALOGUE PREssURE switch

4.13. Ex-Floodlights of the series FMV LED / NSSFMV. (Zone 2, 22) service life and a high level of efficiency. NFMV floodlights for highpressure

I Ex d/e Switch- and Control-Equipment I

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

CALYS 80P. Field pressure calibrator with high accuracy 0.01%

Operating Instructions for Digital Manometer. Model: MAN-SD

Relative pressure transmitter type 520

DS 200 DS 200 DRUCK & TEMPERATUR LEITENBERGER GMBH. Electronic Pressure Switch. Stainless Steel Sensor. Electronic Pressure Switch

BMXART0814 analog input module M340-8 inputs - temperature

Impedance relay and protection assemblies

Ex-Floodlights of the series FMV LED / NFMV / NSSFMV. Stainless steel NSSFMV floodlights for particularly. in harsh environments

2.12. Ex-Linear light fittings for fluorescent lamps. nllk W - 58 W (Zone 2, 21, 22)

RoHS. Versatile. X g. X 2 e

Pressure Measurement Single-range transmitters for general applications

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en

VersaFlow Ultrasonic clamp-on Flowmeter Specifications

Explosion-protected recessed ceiling LED-light and fluorescent light fittings

I nllk 08018/18 I nllk I nllk 08036/36 I nllk I I nllk 08058/58 I

Analog - Digital multimeters

473-SHX Dew Point Mirror

5SJ4...-.HG Circuit Breakers to IEC and UL 489

Ultrasonic Gas Flow Meter

ST3000 Series 900 Smart Transmitter Differential Pressure Transmitters

EX-EMERGENCY LIGHT FITTINGS

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)

DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER

AIR PREPARATION. ELECTRONICALLY CONTROLLED PRESSURE REGULATING VALVE (PROPORTIONAL PRESSURE REGULATING VALVE) SERIES control

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

FKC... 5 DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER FEATURES SPECIFICATIONS. Functional specifications

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

DM70. Hand-held Dewpoint Meter. Truly Fast Response - Superior Long-term Stability

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

v = m / s Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes

TÜV NORD CERT GmbH Hanover Office Am TÜV Hanover Germany. Testing Laboratory Explosion Protected Equipment and Monitoring Devices

E8EB-N0C2B E8EB-N0B2B

Page 1 of 16 Issue No. 0 of IECEx TUN X

ANNEX to IECEx Certificate

Linear measuring technology

Industrial Resistance Thermometers according to DIN Model MWD

Temperature sensors SensyTemp TSP311, TSP321, TSP331

Single point load cells

Non-Contact Safety Systems CMS

BMXART0814 analog input module M340-8 inputs - temperature

ABB i-bus KNX Analogue Input AE/A 2.1

2.12. Ex-Linear light fittings for fluorescent lamps - max. ambient temperature + 60 C - nllk W - 58 W for Zone 2 and 22

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

ISEmax CAM40/CAS40. Technical Information

v = 00,20 m/s Thermal Flow Sensors TA with thin-film sensor element Probes Probe guides Measuring tubes

Load Cells. 3/2 Introduction. 3/3 Mounting components 3/3 Introduction

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

K04 TYPE -40 C +85 C 20000H

TABLE OF CONTENT. ATEX Certificate. Designation code. Circuit diagrams. Sensors. Sensors. Explosion-proof sensors from Pulsotronic

Thermal-Magnetic Circuit Breaker 2210-S2..

PTF30 Series. Features. Ordering information. G 6 N N F8 (0 to 5 kgf/cm 2 ) PTF30

Dimensional drawing face mount flange radial. R = bending radius min. 40 mm. Dimensional drawing face mount flange axial

Model DS1200-AMT-Ex Intrinsically Safe 4-20mA ATEX Certified Dewpoint Hygrometer Ranges available between -120 C to +20 C (-166 F to +68 F) dewpoint

Pressure. 1 Fitting PA R - N R2

Type UB1 Load Cell. Option Stainless steel cable gland

Transcription:

TH 0 / TH 0-Ex Field mounted temperature transmitter, HART programmable, Pt 00 (RTD), thermocouples, electrical isolation 0/-8.6 EN Input Resistance thermometer (,, -wire circuit) Thermocouples Resistance remote signalling unit (0...5000 Ω) Voltages, mv ( 5...00 mv) Output -wire technique...0 ma, HART signal Electrcal isolation (I/O)) Digital low-drift processing of measurement values Customer-specific linearization Continuous sensor and self-monitoring Parameter saved permanently in EEPROM Monitoring of data integrety every 0 s Substitution strategy in case of error (NE) Approvals for explosion protection intrinsically safe II G EEx [ia] ib IIC T6, mount in zone II G EEx n A II T6, mount in zone pressure-proof II G EEx d IIC T6, mount in zone Input functionality (absolute, differential, average value) EMC acc. to EN 5008- and NE Parameterization PC software application SMART VISION Hand held terminals STT 0, HC 75 CoMeter (HART-Configurator/LC-Display) 5 years warranty ABB Instrumentation

TH 0 / TH 0-Ex 0/-8.6 EN Technical data Output Output signal (temperature linear)...0 ma Residual ripple (peak-to-peak) < 0. % Current consumption <.6 ma Max. output current.6 ma Parameterizable current error signal Underranging.6 ma Overranging ma Default value.6... ma Damping (programmable) t 6 = 0...0 s Input Resistance Resistance thermometer (IEC 75, JIS, SAMA) min. span Resistance min. span n Pt00/Ni00 to Pt000/Ni000; Cu (n=0.; 0.; 0.5; ;.; ;...0) 5 K/50 K 0...500 Ω=/ 0...5000 Ω 5 Ω / 50 Ω Max. line resistance (R w ) per core,, -wire 7.5 Ω, 0 Ω, 50 Ω Measuring current 00 µa Sensor short-circuit < 5 Ω (for RTD) Sensor break >.5 MΩ Input filter 50/60 Hz Thermocouples Types Voltages Min. span Sensor monitoring current Input filter B, E, J, K, L, N, R, S, T, U 5 mv...5 mv 5 mv...00 mv mv / 50 mv 70 na 50/60 Hz Internal reference junction Pt 00, via software switchable (no jumper necessary) Power supply (at transmitter terminals) (-wire-methode: power supply wires = signal wires)) Supply voltage, poling protected U s = 8.5...0 V DC for explosion protection application, max. U i = 8.5...9. V DC Influence of supply voltage < 0.05 %/0 V max. residual ripple... Power demand of indicators (Power demand of transmitter and indicator have to be added.) Digital indicator U sd = V DC CoMeter (HART Configurator/LC-Display) U sd =,9 V DC Maximale Load Maximum permissible load R 90 58 Ω 50 0 Z-060 (HC) RkΩ ( ) 8,5 ( Usmax Usmin) = ----------------------------------------------, 6 With CoMeter,, 7, Operation range V DC Power supply Us 0 Standard IEC 58- DIN 70 Input element Measuring range Min. measuring span Sensor Thermocouple Type B 50...+80 C (+8...+08 F) 5 C ( F) Thermocouple Type E 50...+000 C ( 8...+8 F) 0 C ( 5 F) Thermocouple Type J 0...+00 C ( 6...+9 F) 7 C ( 67 F) Thermocouple Type K 50...+7 C ( 8...+50 F) 5 C (98 F) Thermocouple Type R 50...+768 C ( 58...+5 F) 7 C (08 F) Thermocouple Type S 50...+768 C ( 58...+5 F) 9 C (8 F) Thermocouple Type T 00...+50 C ( 8...+6 F) 50 C ( 90 F) Thermocouple Type N 00...+50 C ( 8...+6 F) 60 C (08 F) Thermocouple Type L 00... +900 C ( 76...+ 8 F) 6 C ( 65 F) Thermocouple Type U 00... +600 C ( 8...+ F) 0 C ( 7 F) Resistance thermometer Pt 00 00... +850 C ( 8...+56 F) 5 C ( 8 F) Resistance thermometer Pt 000 00... +850 C ( 8...+56 F) 50 C ( 90 F) Resistance thermometer Ni 00 60... + 50 C ( 76...+ 8 F) 8 C ( 5 F) Resistance thermometer Ni 500 60... + 50 C ( 76...+ 8 F) 5 C ( 8 F) IEC 75; JIS; SAMA ), and -wire DIN 760 ), and -wire Resistance Ω 0...500 Ω / 0...5000 Ω 5 Ω / 50 Ω Voltage mv 5 mv...+5 mv mv 5 mv...+00 mv (optionally) 50 mv ) IEC 75 a = 0.0085; JIS a = 0,0096; SAMA a = 0,0090 ) Edison Curve No. 7 Page of 6 0.000

TH 0 / TH 0-Ex 0/-8.6 EN Technical data General characteristics Response time < 0.5 s Vibration resistance Vibration in operation g acc. to DIN IEC 68 part -6 Electrical isolation (I/O).5 kv AC Long-term stability Environment conditions Ambient temperature range 0...85 C Transport and storage temperature 0...00 C Relative humidity < 00 % (00 % humidity with isolated terminals only) condensation permitted Mechanical construction Dimensions cf. dimensional drawing Weight.5 kg (without accessories) Housing material Aluminium/stainless steel Type of protection IP 67 Color (Epoxy) light grey (RAL 900) Electrical connection Thread M0 x.5, / GK / NPT, / NPT Screwings M0,5 Ground screw ext./int. 6 mm M5 /.5 mm M Terminals, pluggable.5 mm, screw terminals Characteristics at rated conditions *) (acc. to IEC 770, related to 5 C) Measuring error incl. characteristic deviation Pt 00/resistance measurement < 0. % or < 0. K/< 80 mω whichever value is greater Thermocouple/mV < 0. % or < 0 µv whichever value is greater Additional influence of the internal reference junction Pt 00 DIN IEC 75 cl. A Influences Influence effect of temperature Pt 00/resistance measurement ) ME (Ω) < (0.08 % + 0.008 %) / 0K MS (Ω) Thermocouple/mV ) ME (mv) 0.0 K < (0.08 % + 0.0 % + 00 %) / 0 K MS (mv) MS (K) Percentage related to measuring span MS = ME MA MA = lower range value, ME = upper range value *) Percentage related to set measuring span ) Pt 00 (0...00 C): Effect of temperature influence < (0.08 % + 0.0 %)/0 K = 0.09 %/0 K ) Type K (0...000 C): Effect of temperature influence Explosion protection Intrinsically safe Zone II G EEx [ia] ib IIC T6 EC certificate PTB99 ATEX 9 X Temperature class T6/T5/T < 50 C/65 C/85 C Supply circuit Output [ib] Input [ia] Max. voltage U i = 9. V U o = 5.6 V Short-circuit current I i = 0 ma I o = 5 ma ) Max. power P i = 0.8 W P o = 0 mw Internal inductance L i = 0 µh L o = mh Internal capacitance C i = 5 nf C o =.55 µf ) Load current for connected primary element [ia] <.5 ma Zone II G EEx n A II T6 Conformity declaration PTB 99 ATEX... X Temperature class T6/T5/T < 50 C/65 C/85 C Pressure-proof enclosure II G EEx d IIC T6 EC certificate PTB 99 ATEX... X Temperature class T6/T5/T < 50 C/65 C/85 C Canadian Standards Association and Factory Mutual ) ) in preparation Intrinsically Safe FM/CSA Class I, Div./Div., Group A, B, C, D Class II, Div./Div., Group E, F, G Class III FM Class I, Zone, AEx [ia] ib IIC T6 CSA Class I, Zone, Ex [ia] ib IIC T6 Nonincendive FM/CSA Class I, Div., Group A, B, C, D, T6 Class II, Div./Div., Group E, F, G, T6 Class T6 Explosionsproof FM/CSA Class I, Div./Div., Group A, B, C, D, T6 Class II, Div./Div., Group E, F, G, T6 Class III T6 Flameproof FM Class I, Zone, AEx d IIC T6 CSA Class I, Zone, Ex d IIC T6 Electromagnetic compatibility (EMC) Pt 00: measuring range 0...00 C, span 00 K Class Type of test Degree Influence IEC burst to signal/ kv < 0.5 % 000-- data lines static discharge 000-- contact discharge to: contact plate terminals for supply terminals for sensors 8 kv 6 kv.75kv <.0 % <.0 % <.0 % radiated field 000-- 80 MHz... GHz 0 V/m <.0 % coupling 50 khz - 80 MHz 0 V <.0 % 000--6 Acc. to NAMUR NE recommendation 0.000 Page of 6

W GI RI OI N TH 0 / TH 0-Ex 0/-8.6 EN Displays (Option) Digital indicator LC display ½ digits (± 999), digit height 0 mm, 7 segments Standard scaling 0...00 % Linear scaling for measuring ranges and units possible Description of the physical unit (labels) CoMeter (HART-Configurator/LC-Display) function keys for request and programming (Code protection) LC display: 5 digits (± 999), digit height 7,6 mm, 7 segments Sign and floating point 0 segment bargraph (heading of measuring range) 7 digits alphanumeric characters 6 mm, segments Digital display CoMeter (HART Configurator) Request function Process variable, analog and display value, description of measuring point, serial number, error behaviour, lower/upper measuring range limit Change function Display mode (linear, average), physical unit, measuring range limits, damping, pass word, mains frequency filter Special function Zero point adjustment, simulation of output signal, adjustment of output signal, wet calibration Display Digital Configurator Response time 0,5 s, s Measuring error ± 0, % ± 0,5 % Overvoltage 50 % of input range 5 ma EMC EN 5008- Temperature -0...+70 C Humidity 0...00 %, condensation permitted Mind limits of application. Communication/parameterization Software-Tools SMART Vision Hand held terminal HHT STT 0; HC 75 Parameter Sensor type, error signalling, measuring range, general characteristics (i. e. TAG number), damping, signal simulation of output Software interface AMS, Cornerstone C U RI C H E N H T E R S TI C A V L I K E E P E N E ABB +. C E VI LO S PA S + - E X P O U V R ATMO S P H E RE S O U S T E N S E N Line resistance GND (50 Ω min.)* (optional) Processinterface or Isolators Controller Recorders or FSK Modem *if necessary HC 75, STT0 Z-06 Page of 6 0.000

TH 0 / TH 0-Ex 0/-8.6 EN Ordering information Catalog No DM LZ/deliv. TH 0 / TH 0-Ex V5- W TH 0 (without expolsion protection) 78,00 * With explosion protection: Type of protection: intrinsically safe TH 0-Ex PTB / ATEX II G EEx [ia] ib IIC T6 (Zone ) 5 798,00 * TH 0-Ex FM / CSA Class I, Div. / Div., Group A,B,C,D 7 798,00 * Class II, Div. / Div., Group E,F,G Class III Class I, Zone, AEx [ia] ib IIC T6 Class I, Zone, Ex [ia] ib IIC T6 TH 0-Ex N PTB / ATEX II G EEx n A II T6 (Zone ) N 798,00 * FM / CSA Class I, Div., Group A,B,C,D, T6 nonincendive Class II, Div., Group E,F,G, T6 Class III T6 Type of protection: pressure-proof enclosure / explosion-proof TH 0-Ex d PTB / ATEX II G EEx d IIC T6 D 798,00 * TH 0-Ex d FM / CSA Class I, Div. / Div., Group A,B,C,D, T6 E 798,00 * Class II, Div. / Div., Group E,F,G, T6 Class III T6 Type of protection: flameproof TH 0-Ex d FM Class, Zone, AEx d IIC T6 F 798,00 * CSA Class, Zone, Ex d IIC T6 Display / construction AGLF housing without display N AGLFH housing (raised cover - transmitters) H 5,00 * AGLFD housing with digital indicator D 99,00 * AGLFD housing with Cometer C a.a. / o. r. * Material Aluminium A Stainless steel E a.a. / o. r. * Connections with cable-screw-connection M 0 x.5 M 0,00 * pressure-proof D 7,50 * Thread (without screw connection) M 0 x.5 /" NPT /" NPT /" GK Mounting field housing without Wall mounting (STT 7) 0,00 * Wall mounting (stainlees steel) 55,00 * Pipe mounting (STT 7) 60,00 * Pipe mounting (stainless steel) 5 95,00 * Programming Factory standard parameter: S Pt 00, -wire circuit, damping off, direct action characteristic overranging at sensor or device error ( ma) Customer-specified parameter definition K 0,00 * Certificates Two-point calibration certificate 0,00 * 9-point calibration certificate 00,00 * customer-specified certificate a.a./o.r. * metal-screw-connection EEx e bzw. EEx d (cable-diameter.5 8.7mm) Accessories Catalog No DM H&B FSKMmdem [EEx ib] IIC (parameter setting in the installation) 0705 0,00 * SMART-Vision 5 Software on CD-ROM (German/English) 7957777 0,00 * on /" diskettes (German/English) 7957778 0,00 * SMART-VISION manual German 7957779 0,00 * English 7957780 0,00 * TH 0 / -0 / -0 driver for AMS software.. (Rosemount) 795777 0,00 * 5 see Data Sheet 6-.0 Minimum hardware reuqirements: Intel 8086; 66 MHz, 8MB RAM; free hard-disk capacity; Windows.x (95, 98, NT) Notice: for local programming can be used the TS 0 programming set (without Parasoft) Data Sheet -8.7 0.000 Page 5 of 6

IVE I TH 0 / TH 0-Ex 0/-8.6 EN Connection diagram Us = 8,5...0 V DC + - Output...0 ma Microprocessor Reference junction Input a) Resistance thermometer, -wire circuit b) Resistance thermometer, -wire circuit c) Resistance thermometer, -wire circuit d) Double resistance thermometer, -wire circuit e) Potentiometer input (-wire circuit) - + + f) Thermocouple g) Double thermocouple h) Voltage measurement i) Double voltage measurement K K K K VDC a) b) c) d) e) f) g) h) i) K K VDC Z-065 Dimensional diagram (dimensions in mm) 90 0 WHEN T IGHT CIRCU IT S COVER A L I V E NE ABB +. C PA S OUV R IR SOUS T E NSION EN 97 M8 0 7 KEEP EXP ATMOSPHERE LOS 8 Electrical connections ~0 8 7 5 90 CIRCU IT S A L I V E NE PA S OUV R IR SOUS Lockscrew WHEN T E NSION 97 T IGHT EN COVER KEEP EXP ATMOSPHERE IVE LOS Thread Thread 8 Electrical connections Potential equalisation screw 5 Z-06 ABB Automation Products GmbH Subject to technical changes. Printed in the Fed. Rep. of Germany Data Sheet 0/-8.6 EN 0.000