v = m / s Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes

Similar documents
v = 00,20 m/s Thermal Flow Sensors TA with thin-film sensor element Probes Probe guides Measuring tubes

ED 701 General Industry Pressure Transmitter

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

DMP 331P. Industrial Pressure Transmitter. Process Connections With Flush Welded Stainless Steel Diaphragm

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

DMP 331Pi. Precision Pressure Transmitter. pressure ports and process connections with flush welded stainless steel diaphragm

VK2 volume flow controller Overview

SINEAX VK 636 Programmable Temperature Transmitter with PROFIBUS-PA protocol

Pressure Transmitter ED 701

Mineral-insulated thermocouples to DIN and EN

Turbine Meter TRZ 03 PRODUCT INFORMATION. Reliable Measurement of Gas

Latest generation testo air velocity & IAQ probes with cable handle. Instruction manual

DS 200P. Electronic Pressure Switch. Pressure Ports And Process Connections With Flush Welded Stainless Steel Diaphragm

Installation guide 862 MIT / MIR

Ex-Floodlight PXLED. (Ex-Zone 1, 2, 21 and 22)

DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications

Full Metal Variable Area Flow Meter and Counter

SINEAX VK 626 Programmable Temperature Transmitter for RTD and TC inputs, with HART protocol

Ex-Floodlights of the series FMV LED / NFMV / NSSFMV. Stainless steel NSSFMV floodlights for particularly. in harsh environments

ATEX/IECEx RTD temperature probe

Thermal Mass Flow Meter for Gases

Pressure transmitters for industrial applications MBS 32 and MBS 33

Field IT 50T Series Transmitters

Switches in conformity with ATEX directive

PRODUCT CATALOGUE PREssURE switch

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

EX-EMERGENCY LIGHT FITTINGS

4.2. Ex-Ceiling light fittings AB 80 / AB 05 LED / AB 05 / AB 12 NAV 70. (Zone 1, 2, 21, 22)

DS 300. Electronic Pressure Switch. with IO-Link interface. Stainless Steel Sensor. accuracy according to IEC 60770: 0.35 % FSO.

Air velocity & IAQ measuring instruments

4.3. Ex-Pendant light fittings AB 50 / SPG 1N / AB 51 / EVI 200 / EVI 500 / EV35 LED. (Zone 1, 2, 21, 22)

4.13. Ex-Floodlights of the series FMV LED / NSSFMV. (Zone 2, 22) service life and a high level of efficiency. NFMV floodlights for highpressure

THM80X Series Feature Application. Temperature & Humidity / Flow Measuring Specialist

Air velocity & IAQ measuring instruments

Fitting PS P - B - R2

Conductivity sensor for hygienic applications

DOG-1/-3. Oscillation Flowmeter. for gases. Measuring ranges: m 3 /h air : 120 C. p max. : PN 40; t max

Reflex-Radar BM 100 A

Electromagnetic Flowmeter

TF 212 / TF 212-Ex. Field mounted temperature transmitters, PROFIBUS PA, Pt 100 (RTD), thermocouples, 1 or 2 independent channels 10/11-8.

DS 200 DS 200 DRUCK & TEMPERATUR LEITENBERGER GMBH. Electronic Pressure Switch. Stainless Steel Sensor. Electronic Pressure Switch

HYGRASGARD KFF KFTF HYGRASGARD AFF AFTF HYGRASGARD AFF - LC AFTF - LC

DM70 Hand-Held Dewpoint Meter for Spot-Checking Applications

Operating Instructions for Digital Manometer. Model: MAN-SD

Relative pressure transmitter type 520

Pressure Measurement. Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level 2/27

Capacitance Level Measurement Electronic Inserts EC 37 Z, EC 47 Z

- compressed air plants (refrigerating/adsorption dryers) - granulate dryers - medical gases - non-corrosive gases, e. g. nitrogen

Oscillation Flow Meter for Gases

DM70. Hand-held Dewpoint Meter. Truly Fast Response - Superior Long-term Stability

TF 202 / TF 202-Ex. Field mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

Solenoid valves Type EVUL

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

Ultrasonic Gas Flow Meter

Surface-mounting Thermostats ATH Type Series

I nllk 08018/18 I nllk I nllk 08036/36 I nllk I I nllk 08058/58 I

Pascal ET is an handheld multifunction calibrator for the measurement and simulation of the following parameters: - pressure

Cooling Water Flow Regulator

Physikalisch-Technische Bundesanstalt

Surface-mounting thermostats Series ATH

ISEmax CAM40/CAS40. Technical Information

Intuitive air velocity and IAQ.

Solenoid valve Types CSV 2 - CSV 22 (NC) and solenoid coil

Vaisala DRYCAP Hand-Held Dewpoint Meter DM70. Fast Response - Low Maintenance

2.9. Namur Valves 2.9. page 175. Namur 1/4 also called Namur 1 in accordance to VDI / VDE Namur 1/2 also called Namur 2.

Automatic titrators, TitroMatic

Transmitters for basic requirements SITRANS P MPS (submersible sensor) Transmitter for hydrostatic level

WISE Damper. Active damper for Swegon s WISE System for demand-controlled ventilation QUICK FACTS

Ex floating switches and Ex immersion probes

Permanently installed and non-invasive ultrasonic flowmeter for the measurement of thermal energy and volumetric flow rate

473 Dew Point Hygrometer

close to performances of the turbine gas meters designed for custody transfer measurements.

Technical specification FLUXUS F502TE

Pressure Measurement Single-range transmitters for general applications

By-Pass. This voltage is proportional to the liquid level (threewire potentiometer circuit). The resistance reading can

Applicable Fluid. Accuracy. Flow Rate Range. Fluid Temperature. Fluid Viscosity. Connection Size. Flange Rating. Housing. Material. Blade.

Coriolis Mass Flowmeter. (MCM Series) 100% Customer Satisfaction MAXIFLO TM. Coriolis Mass Flowmeter Series MCM

Semi-automatic titrators PH-Burette. A great ph-meter with integrated burette. Incredible price! Infinite possibilities

Cone differential pressure flow meter. Operating manual WIDE PLUS PRECISION INSTRUMENTS CO., LTD.

Thermometers. Applications

ABB SpA COMEM Operating Unit Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY

Ring-Torsion Load Cells RTB

T20WN. Data Sheet. Torque transducers. Special features. Installation example with bellows couplings. B en

CoriolisMaster FCB130, FCB150, FCH130, FCH150 Coriolis mass flowmeter

TF 212 / TF 212-Ex. Field mounted temperature transmitter, Profibus PA, Pt 100 (RTD), thermocouples, 1 or 2 independent channels. ABB Instrumentation

Pressure. 1 Fitting PA R - N R2

VersaFlow Ultrasonic clamp-on Flowmeter Specifications

S95.3U01 / S95.3U11. Head mounted temperature transmitters, programmable, Pt 100 (RTD), thermocouples, electrical isolation

PHOENIX CONTACT - 04/2016. Features

Exchangeable measuring insets SensyTemp TSA101

D5.2 Type. Draw wire mechanics with incremental encoder. Measuring length max. 2 m. Compact and simple. Order code draw wire encoder

Direct-operated 2/2-way solenoid valves Type EV210B

1551A Ex/1552A Ex Intrinsically Safe Stik Thermometer. The new gold standard of industrial temperature calibration

AC axial compact fan

Amphenol. Amphenol-Tuchel Electronics GmbH. Series C 146 Heavy Duty Connectors Core Programme

Certificate: / 29 April 2014

DELTA FLOWMETER FOR GAS SERVICE (INSERTION TYPE) MODEL VF SERIES

Serie B2.1. Flanged ductile iron ball valve. made in. Application fields. Shut-off valves E U R O P E. 18

Gear Wheel Flowmeter for viscous liquids Model DZR. (option 3):

Globe Valve, Metal. Sectional drawing. *see information on working medium on page 2

Transcription:

Thermal Flow Sensors TA with thin-film sensor element Probes Probe Guides Measuring Tubes Examples of Application Flow measurements also in hazardous locations X zone 0 or zone 1 in clean rooms in air conditioning and ventilating systsms for the determination of compressed air consumption of activated sludge air in sewage treatment plants in outgoing air and exhaust gases in deposit gas, argon, helium, CO2, natural gas, nitrogen, SF6, methane... v = 0 0. 2 0 m / s Specifications Designs Information for the user

The principle of measurement is based on heat transport from an electrically heated body in ambient medium dependent on the relative velocity between both. Höntzsch thermal flow sensors TA designed as TA10 probes and measuring tubes TA Di... use a thin-film sensor element. Thin-film sensor elements consist of an electrically heated Ni-resistor and a Ni-resistor temperature probe. The medium temperature and the temperature difference t between the heated Ni-resistor and the medium are the dimensions for the flow. Thermal flow sensors TA with a thinfilm sensor element from Höntzsch are able to measure not only the lowest but also high velocities and meet all requirements for industrial application: chemical corrosion resistance wide measuring range small dimensions of the probes TA10 The T 95 time constant of the thin-film sensor element at standard air velocities of around 5 m/s is approx. 1 s. velocity v in m/s Temperature difference t dependent on the standard flow velocity Nv and the temperature t The diagram shows that the correspondence between temperature difference t and the standard flow velocity is also temperature-dependent. Höntzsch flow evaluation units compensate this dependency over the entire temperature application range provided for one sensor respectively. temperature t in C normalized TA10 temp. difference 1,0 1,2 1,4 1,6 1,8 2,0 2,2 A characteristic feature to be emphasized when measuring with thermal flow sensors is that the measurement accuracy increases in decreasing flow velocities. In contrast to this, the measurement accuracy increases in increasing flow velocities in the case of vane wheel and vortex flow sensors. 2 of 6 Measurable variable is the standard flow velocity Nv. The standard volume flow and mass flow can be determined with Nv independent of pressure and temperature. Standard flow velocity and actual flow velocity The standard velocity Nv is the velocity at which a gas moves when gas temperature and gas pressure are identical with the standard conditions. The actual flow velocity Bv is the velocity at which a microscopically small particle floats in a flowing medium. Thermal anemometers measure the standard velocity Nv, that is a velocity which is referred to so-called standard conditions. Measuring the standard velocity with a thermal flow sensor is independent of pressure and temperature. The standard conditions for Höntzsch are +21 C (+70 F) and 1014 hpa (14.7 psia). The decision whether to apply the standard or actual velocities depends entirely on the measurement requirements. The standard velocity can be converted to an actual velocity and vice versa using the universal gas equation. Measuring uncertainty The measuring uncertainty for probes TA10 is specified at standard velocity measurements of up to 40 m/s with ±2 % of the measured value plus ±0.02 m/s and at standard velocity measurements between 40 m/s and 120 m/s with ±2.5 % of the measured value. See data sheet Flow Velocity Calibration TA (U194_EN)...PM6_SALE\DATA_ENG\U232_ta2

Designs of probes TA10 Drawing Zeichnung 1b 1b Drawing 2b Drawing 3b X Ø 9.5 Ø 9.5 Ø 9.5 25 13 13 25 13 25 Ø 10 Ø 10 285 265 265 Ø 10 35 35 60 30 50 Probe TA10... ZG1b optional available for connection to the pocket anemometer HTA-X for zone 1 or transducer U15-Ex for zone 0 in explosion protection EEx ia IIC T4 ATEX 80 60 80...PM6_SALE\DATA_ENG\U232_ta3 Probes TA10... ZG1b with connection cable are suitable for connection to the pocket anemometers HTA or HTA-X or the separate transducers U10a or U15-Ex. The connection cable of the probe TA10... ZG1b has a direct outlet, a standard length of 3 m and a continuous working temperature of max. +140 C. Connection plug: 423-5 respectively 423-8 if in Ex-execution. The SILICONE-coated cable is protected by an overall shielding for reasons of electromagnetic interference. Probes TA10... ZG2b with integrated transducer U10a. Transducers U10a provided with: Standard: Output 4-20 ma, pulse output for quantity measurement, RS232-Interface: only for transducer configuration using a PC. Option with LCD display and resettable quantity counter in the lid of the U10a housing AS80. Probes TA10... ZG3b X zone 1 with integrated transducer U12-Ex. They are meant for use in locations in which it can be expected that occasionally a hazardous atmosphere arises with explosibility. Explosion protection: EEx e q [ia] IIC T5 ATEX. Transducers U12-Ex provided with: Output 4-20 ma, pulse output for quantity measurement, RS232-Interface: only for transducer configuration using a PC. Connection cable: standard length 2 m. Please note Do not shorten or lengthen the TA10... ZG1b connection cable! LCD display with quantity counter 3 of 6

Designs of measuring tubes TA Di... Measuring tubes in different designs for direct, stationary installation in pipelines, irrespective of position. Tube connection by pipe fitting (thread in conformity with DIN 2999 = ISO 7, part 1 and 2), cutting ring fitting, etc. Maximum working pressure up to : 15 bar/1.5 MPa above atmospheric Working temperature range : -10 C... +140 C Measuring tubes TA Di... ZG1b with integrated transducer U10a Measuring tubes TA Di... ZG1b with integrated transducer U10a: Transducers U10a provided with: Standard: Output 4-20 ma, pulse output for quantity measurement, RS232-Interface: only for transducer configuration using a PC. Option with LCD display and resettable quantity counter in the lid of the U10a housing AS80. The measuring tubes TA Di... ZG2b has a connection cable with direct outlet and are suitable for connection to the pocket anemometer HTA or the separate transducer U10a. The measuring tubes TA Di... ZG2b are optional available for connection to the pocket anemometer HTA-X (for zone 1) or the transducer U15-Ex (for zone 0) in explosion protection EEx ia IIC T4 ATEX The measuring tubes TA10... ZG5b X zone 1 with integrated transducer U12-Ex. They are meant for use in locations in which it can be expected that occasionally a hazardous atmosphere arises with explosibility. Explosion protection: EEx e q [ia] IIC T5 ATEX. Transducers U12-Ex as discribed at probes TA10... ZG3b....PM6_SALE\DATA_ENG\U232_ta4 Inside diameter Ø [mm] 8 16 21.6 27.2 35.9 41.8 Rating standard volume flow [m³/h] bei 60 m/s bei 120 m/s 11 43 79 125 219 296 22 86 158 250 438 592 Pipe connection SRV = cutting ring fitting SRV for pipe 12 2 Pipe thread R ½ Pipe thread R ¾ Pipe thread R 1 Pipe thread R 1¼ Pipe thread R 1½ Installation length [mm] 80 + SRV 320 650 820 1080 1250 LCD display with quantity counter 4 of 6

...PM6_SALE\DATA_ENG\U232_ta5 Model designations Sensor element A Höntzsch thin-film flow sensor, polyimide-coated. Pobes TA10 TA10-285 G E 30m/s 140 p10 ZG1b TA10-265 G E 120m/s 140 p10 ZG2b TA10-265 G E 60m/s 140 p10/ex ZG3b Sensor, probe diameter in mm Probe length in mm Medium G = air/gases Probe material E = stainless steel... Maximum adjustable nominal value Working temperature range Working pressure above atmospheric Type of protection Design according to drawing ZG... Drawing, German: Zeichnung Measuring tubes TA Di... Sensor TA Di 8 G E 120m/s 60 p15 ZG3b TA Di 16 G E 60m/s 140 p10 ZG1b TA Di 41.8 G E 120m/s140 p10 ZG2b TA Di 27.2 G E 120m/s140 p10/ex ZG5b Meas. tube inside-ø Di in mm Medium G = air/gases Material E = stainless steel... Maximum adjustable nominal value Working temperature range Working pressure above atmospheric Type of protection Design according to drawing ZG... Drawing, German: Zeichnung Measuring range The smallest measurable value with standard flow velocity measurements of air is approx. 0.2 m/s, the maximum adjustable terminal value depending on sensor type 30 m/s, 60 m/s, 120 m/s or 150 m/s. Velocity overload: up to 150 m/s The fatigue strength for infinite time of the sensor element is independent of the flow conditions within the measuring range. Medium Thermal flow sensors TA with a thinfilm sensor element are calibrated with air according to standard. Gases other than air can have varied cooling effects and can therefore influence the measurement of a sensor calibrated with/for air. Disregarding this, thermal flow sensors are also suitable for measurements in single-phase gaseous flows. Measurements in gas mixtures with air or other gases are affected to such an extent that the heat transfer property of the gas mixture differentiates from the heat transfer property of the air. Upon request: real gas calibrations for deposit gas, argon, helium, CO2, natural gas, nitrogen, SF6, methane... The use of TA sensors with a thin-film sensor element in particle-charged flows is permissible as long as the finish of the sensor element does not change and deposits are not allowed to collect on the sensor. Mediums may even contain fibres. Deposits or abrasions on the sensor element can change the heat transmissions and so influence the measurement. The effect of condensation on the sensor is to be regarded in the same way. Clean soiled sensor heads! Drifts resulting from variable humidity of the air at normal atmospheric conditions are covered by our specifications for measuring uncertainty. Working temperature range for continuous operation 140-10 C... +140 C 60-10 C... +60 C Sensor materials materials coming into contact with the medium E stainless steel 1.4571, 1.4305 epoxy resin, polyimide, glass Maximum working pressure, pressure dependence p10 sensor is designed for pressures above atmospheric of up to 10 bar/1 MPa p15 sensor is designed for pressures above atmospheric of up to 15 bar/1.5 MPa Measurements with absolute pressure of less than approx. 0.7 bar absolute are no longer covered for by the standard data relevant to measuring uncertainty. The zero point is influenced by absolute pressures which are distinctly higher than 1014 hpa. In the case of non-compensated pressure dependence the following approximate standard flow velocity values Nv arise: at 0 m/s and 5065 hpa abs 5 bar: measured value Nv 0.25 m/s instead of 0 m/s. at 0 Nm/s, 10130 hpa abs 10bar: measured value Nv 0.50 m/s instead of 0 m/s. This influence is no longer effective at velocities higher than 1 Nm/s. The software of the flow evaluation units is equipped with the possibility to set the mean working pressure for the purpose of the best possible compensation of the described pressure dependence (compenstion for one pressure stage) Type of protection all probes and measuring tubes: completely IP65. Explosion protection X ATEX Probes and measuring tubes with integrated transducer U12-Ex: EEx e q [ia] IIC T5. Probes and measuring tubes with connection cable for connection to the pocket anemometer HTA-X (for zone 1) or the transducer U15-Ex (for zone 0): EEx ia IIC T4 5 of 6

Probe guide pieces SF are used for inserting and retracting probes TA10 in and out of pipelines and ducts. The fixing device of the probe tube is to be chosen taking the pressure operating conditions into consideration. Drawing 5 SFB SF design as in diagram 5 with clamping bush SFS SF design as in diagram 5 with cutting ring fitting SFB SF design as in diagram 6 with clamping bush, clamping device providing extra support for the probe attachment and with or without chain safety device. Coefficient / Profile Factor PF PF is used to calculate the local velocity v p to the average velocity v m in measurement cross sections: v m = v p PF 22 mm Drawing 6 L When measuring with thermal flow probes TA10 in circular measurement cross-sections with interior diameter Di 25 mm and more then in turbulent flow the following coefficients are to be taken (Di25: 0,725; Di27,2: 0,74; Di35,9: 0,79; Di40: 0,81; Di41,8: 0,82; Di50 and more: 0,84) as long as the following conditions are adhered to probe to be positioned that the sensor element is centric irrotational flow developed flow profile, i.e. measurement cross-section so chosen that 20 Di straight, unhindered input section, amounts to 10 Di straight, unhindered output section. Thermal flow probes TA10 are to be aligned in the direction of flow. See flow direction arrow. Pressure drop Pressure drop of several Höntzsch flow probes when measuring in air under normal atmospheric conditions, +20 C ZS... Vane Wheel Flow Sensors: probes with Ø 16/25/30 mm TA... Thermal Flow Sensors: probes with Ø 10/20 mm VA40 Vortex Flow Sensor Pressure drop...pm6_sale\data_eng\u232_ta6 6 of 6 Höntzsch GmbH P.O. Box 1324 D-71303 Waiblingen Robert-Bosch-Str. 8 D-71334 Waiblingen (Hegnach) Telephone 07151/1716-0 Facsimile 07151/58402 E-Mail info@hoentzsch.com Internet www.hoentzsch.com Subject to alteration U232-EN 03/2003