Dynamic Pile Testing ASTM D4945

Similar documents
ASD and LRFD Methods Codes and Economics of Dynamic Testing ASTM D4945

PDA Workshop: Stresses, Integrity, Energy and Capacity

BACKGROUND AND INTRODUCTION

Additional Pile Design Considerations

Lesson 25. Static Pile Load Testing, O-cell, and Statnamic. Reference Manual Chapter 18

CAPWAP rules Important!

This document downloaded from vulcanhammer.net vulcanhammer.info Chet Aero Marine

Interpretation of Pile Integrity Test (PIT) Results

Congreso Internacional de Fundaciones Profundas de Bolivia Santa Cruz, Bolivia, 12 al 15 de Mayo de 2015 Day 1: Software Demonstrations

Drilled Shaft Foundations in Limestone. Dan Brown, P.E., Ph.D. Dan Brown and Associates

Maximum Envelope of Lateral Resistance through Dynamic Increasing Energy Test in Piles

LOAD RESISTANCE FACTOR DESIGN (LRFD) FOR DRIVEN PILES BASED ON DYNAMIC METHODS WITH ASSESSMENT OF SKIN AND TIP RESISTANCE FROM PDA SIGNALS

Understanding Dynamic Pile Testing and Driveability

vulcanhammer.info the website about Vulcan Iron Works Inc. and the pile driving equipment it manufactured Terms and Conditions of Use:

LRFD GEOTECHNICAL IMPLEMENTATION

INTRODUCTION TO STATIC ANALYSIS PDPI 2013

Implementation of Pile Setup in the LRFD Design of Driven Piles in Louisiana

CAPWAP Introduction. 2016, Pile Dynamics, Inc. CAPWAP is a registered trademark of Pile Dynamics, Inc. Load (kn) Displacement (mm) Pile Top Bottom

DRILLED DISPLACMENT PILE PERFORMANCE IN COASTAL PLAIN AND RESIDUAL SOILS

CPT Pore Water Pressure Correlations with PDA to Identify Pile Drivability Problem

Use of Ultra-High Performance Concrete in Geotechnical and Substructure Applications

vulcanhammer.info the website about Vulcan Iron Works Inc. and the pile driving equipment it manufactured Terms and Conditions of Use:

PILE SETUP LA-1 EXPERIENCE. Ching-Nien Tsai, P.E.

SHEET PILE WALLS. Mehdi Mokhberi Islamic Azad University

50 ksi Steel H-pile Capacity

LRFD Calibration of Axially-Loaded Concrete Piles Driven into Louisiana Soils

Comparison of Static and Dynamic Pile Load Tests at Thi Vai International Port in Viet Nam

EVALUATION OF LOAD TESTS FOR DRIVEN PILES FOR THE ALABAMA DEPARTMENT OF TRANSPORTATION. Jacob Wayne Hill

vulcanhammer.info the website about Vulcan Iron Works Inc. and the pile driving equipment it manufactured Terms and Conditions of Use:

Improving site specific modified driving formulae using high frequency displacement monitoring

In-class Exercise. Problem: Select load factors for the Strength I and Service I Limit States for the. Loading Diagram for Student Exercise

Neutral Plane Method for Drag Force of Deep Foundations and the AASHTO LRFD Bridge Design Specifications

S E C T I O N 1 2 P R O D U C T S E L E C T I O N G U I D E - H E L I C A L S C R E W P I L E F O U N D A T I O N S

Calibration of Resistance Factors for Drilled Shafts for the 2010 FHWA Design Method

ISC 5 SELF-BORING PRESSUREMETER TESTS AT THE NATIONAL FIELD TESTING FACILITY, BALLINA 5 9 SEPT 2016

Testing and Remediation Observational Method for the Design and Construction of Non-Redundant Pile Foundations

Type approval granted by the Finnish Ministry of the Environment

A presentation of UniPile software for calculation of Capacity, Drag Force, Downdrag, and Settlement for Piles and Piled Foundations

Standard Test Method for High-Strain Dynamic Testing of Deep Foundations 1

INDOT/Purdue Pile Driving Method for Estimation of Axial Capacity

INCREASE IN PILE CAPACITY WITH TIME IN MISSOURI RIVER ALLUVIUM

Numerical Modelling of Dynamic Earth Force Transmission to Underground Structures

DESIGNING FOR DOWNDRAG ON UNCOATED AND BITUMEN COATED PILES

Experimental Investigation of Interface Stresses between Soil and Laterally Loaded Shaft

Seismic Pushover Analysis Using AASHTO Guide Specifications for LRFD Seismic Bridge Design

CPT Guide 5 th Edition. CPT Applications - Deep Foundations. Gregg Drilling & Testing, Inc. Dr. Peter K. Robertson Webinar # /2/2013

INTERFACE STRESSES BETWEEN SOIL AND LARGE DIAMETER DRILLED SHAFT UNDER LATERAL LOADING

INTI COLLEGE MALAYSIA

Verification of Signal Matching Analysis of Pile Driving Using a Finite Difference Based Continuum Numerical Method

Toe Protection for H-piles on Sloping Bedrock at Rainy River

Civil Engineering, Surveying and Environmental Consulting WASP0059.ltr.JLS.Mich Ave Bridge Geotech.docx

Axially Loaded Piles

Presented by: Civil Engineering Academy

Chapter 12 Subsurface Exploration

Calibration of Resistance Factors for Driven Piles using Static and Dynamic Tests

Cone Penetration Testing in Geotechnical Practice

Comparisons of rapid load test, dynamic load test and static load test on driven piles

NEW DOWN-HOLE PENETROMETER (DHP-CIGMAT) FOR CONSTRUCTION APPLICATIONS

Chapter 7 Permeability and Seepage

Why are We Here? AASHTO LRFD Bridge Design Specifications Metal Pipe Section 12.7 Concrete Pipe Section Plastic Pipe Section 12.12

LRFD Application in Driven Piles (Recent Development in Pavement & Geotech at LTRC)

EQUIVALENT FRACTURE ENERGY CONCEPT FOR DYNAMIC RESPONSE ANALYSIS OF PROTOTYPE RC GIRDERS

NON-DESTRUCTIVE EVALUATION METHODS FOR COMPOSITE PILES

EVALUATION OF STRENGTH OF SOILS AGAINST LIQUEFACTION USING PIEZO DRIVE CONE

Discussion: behaviour of jacked and driven piles in sandy soil

R.M.HARW & ASSOCIATES LTD. GEOTECHNICAL INVESTIGATION PROPOSED BRIDGE SITE. HELAVA CREEKl MILE MACKENZIE HIGHWAY E-2510 OCTOBER 16, 1973

THE STRUCTURAL DESIGN OF PILE FOUNDATIONS BASED ON LRFD FOR JAPANESE HIGHWAYS

Literature review Quasi-static and Dynamic pile load tests

IN SITU TESTING TECHNOLOGY FOR FOUNDATION & EARTHQUAKE ENGINEERING. Wesley Spang, Ph.D., P.E. AGRA Earth & Environmental, Inc.

Liquefaction Induced Negative Skin Friction from Blast-induced Liquefaction Tests with Auger-cast Piles

Measurement of effective stress shear strength of rock

Liquefaction and Foundations

MECHANICAL BEHAVIOUR OF DAMAGED HDPE GEOMEMBRANES

Seismic Design of a Hydraulic Fill Dam by Nonlinear Time History Method

Design of RC Retaining Walls

Bored Sockets in weathered Basalt

Role of the Geotechnical Consultant in Design Build Projects a General Contractors Geotechnical Engineer s Perspective

Mechanics of Materials

Clayey sand (SC)

FHWA Bridge Design Guidance No. 1 Revision Date: July 21, Load Rating Evaluation of Gusset Plates in Truss Bridges

NON-LINEAR ANALYSIS OF SOIL-PILE-STRUCTURE INTERACTION UNDER SEISMIC LOADS

M E M O R A N D U M. Mr. Jonathan K. Thrasher, P.E., Mr. Ian Kinnear, P.E. (FL) PSI

SHEAR STRENGTH OF SOIL

PILE LOAD TEST IN OLD ALLUVIUM

EUROCODE EN SEISMIC DESIGN OF BRIDGES

Chapter 4. Test results and discussion. 4.1 Introduction to Experimental Results

STUDY OF THE BEHAVIOR OF PILE GROUPS IN LIQUEFIED SOILS

Direct Design and Indirect Design of Concrete Pipe Part 2 Josh Beakley March 2011

Appendix J. Geological Investigation

Views on Accuracy of Tests and Analyses

Deep Foundations 2. Load Capacity of a Single Pile

What Every Engineer Should Know About Structures

vulcanhammer.info the website about Vulcan Iron Works Inc. and the pile driving equipment it manufactured Terms and Conditions of Use:

Geotechnical Engineering Report

ON THE PREDICTION OF EXPERIMENTAL RESULTS FROM TWO PILE TESTS UNDER FORCED VIBRATIONS

Geotechnical Engineering Report

Boreholes. Implementation. Boring. Boreholes may be excavated by one of these methods: 1. Auger Boring 2. Wash Boring 3.

Failure in Flexure. Introduction to Steel Design, Tensile Steel Members Modes of Failure & Effective Areas

NCHRP LRFD Design Specifications for Shallow Foundations TRB AFS30 Committee Meeting January 26, 2011

Ground vibrations induced by impact pile driving.

Transcription:

Dynamic Pile Testing ASTM D4945 Pile Driving Analyzer Garland Likins, Pile Dynamics, Inc. 2011 PDCA Professor s Institute Why test driven piles? Public assured of safe foundation (bridges, buildings, etc.) We spend lots of money - $4B. Remediation is very expensive! Reduce the risk Optimize foundation -reduce cost Driven piles are tested more often than any other foundation More safe, less risk, less cost Static Analysis Methods International Prediction Event Behaviour of Bored, CFA, and Driven Piles in Residual Soil, ISC 2 Experimental Site, 2003, by Viana da Fonseca and Santos Residual (saprolitic) granite soils: fine to medium silty sand with low plasticity 1

QA Inspection: Piles always have a blow count criteria Wave Equation Analysis But wave equation contains assumptions of hammer performance & dynamic soil behavior Dynamic Pile Testing strain gage F(t) v(t) accelerometer Measurements are better than assumptions Load is applied by impacting ram Load is measured by strain transducers Motion is measured by accelerometers 2

Dynamic testing on all driven pile types STRAIN ACCELERATION Convert STRAIN ( ε ) to F F (t) = E A ε (t) Convert ACCELERATION to V V (t) = a(t) dt GRL 40 ton APPLE Testing an 84 drilled shaft, 30 drop hydraulic release Activated 4000+ tons Convert strain to force Measure Strain and Acceleration Integrate acc to velocity 3

average strains and velocities (plot proportionally by EA/c) peak rise 2L/c Expand time scale scale 2L/c Calculate wave-up; integrate vel. to displacement Strain to Force requires knowing Modulus Elastic Modulus for concrete pile (length L) is determined from concrete wavespeed, c Given: 2L/c = 12 ms = T L = 75 ft 2L/c Calculate E c = 2L / T = (2)(75)/0.012 = 12,500 ft/s E = c 2 ρ = (12,500) 2 { (0.15)/32.17 } = 729,000 k/ftft 2 (ft 2 /s 2 ) (kips/ft 3 )/(ft/s 2 ) E = 729,000/144 = 5,060 ksi 4

Attach sensors to pile prior to lofting pile Rigid foam Sensor Protectors Concrete pile testing wireless PDA smart sensors know their calibration 5

SiteLink - Remote PDA USA Patent #6,301,551 Pile Driving Analyzer Pile Site A Office Internet connection Later same day Site B Pile Experienced Engineer controls PDA as if on-site; monitors pile in real time with greatly reduced testing costs. Results available immediately to keep project on track. Dynamic Pile Monitoring For each blow determine Capacity at time of testing Pile integrity Pile stresses Hammer performance Last three items detect or prevent problems for driven piles Energy transferred to pile is equal to work done E = F du E(t) = F(t) v(t) dt F+ V+ F+ V- Max Rebound (energy returned to hammer) 6

Net measured energy transfer (steel piles) 0% 20% 40% 60% 80% 100% 60% hydraulic drop hammers 100% 40% air hammers 70% 30% diesel hammers 60% 20% cabled drop hammers 80% Efficiencies on concrete piles are lower ~ 10% Hammer Performance is important. Contractor productivity To install pile to design depth Confirms W.E. assumptions Test device, quality control PDA Pile Stress Monitoring Assure dynamic stresses during driving remain below acceptable limits Average comp. stresses at sensor location Bending stresses at sensor location Tensile stresses in concrete piles Compressive stresses at pile bottom To avoid pile damage adjust driving system if needed 7

FMX, CSX Force (Stress) Maximum at gage location FMX = av E A ; CSX = av E Strain transducer FMX: Ensure that sufficient force is applied to mobilize resistance CSX: Ensure safe pile top stress compare with stress limits CSI is highest individual strain reading PDA testing - data acquisition Average force is proportional and reasonable; 2 sensors required to compensate bending Local stress 352 MPa; >50 ksi Average stress 224 MPa; ~32 ksi Large bending present Hammer-pile alignment issue 8

Compression force at toe Any downward compression force before t=2l/c will combine with the upward travelling wave reflected at L/c and received at top at 2L/c t = 0 L/c 2L/c L Downward Wave Upward Wave Resistance/Force at Bottom, CFB Computed Force at Pile Bottom: CFB = R toe = F d,1 + F u,2 R shaft R shaft - discussed later Search over time for max value For pure end bearing pile: CFB = F d,1 + F u,2 = RTL Computed Stress at Pile Bottom CSB = CFB / A Assumes stress is uniform over section CSX@T1 593/24.3 =24.35 CSB = 1.4 x CSX@T1 Capacity RX5 = 1.4 x FT1 9

Tension force at any location Any downward compression force before t=2l/c will combine with the upward travelling tension wave reflected at L/c and received at top at 2L/c toe t = 0 L/c top 2L/c L Downward Wave Upward Wave PDA testing data interpretation Maximum Net Tension force from superposition of (a) maximum upward tension, and (b) minimum downward compression How do we calculate the maximum net tension force? -1377 kn +786 kn -591 kn Min downward compression +786 kn Max upward tension -1377 kn Codes: Allowable Driving Stresses Steel piles Timber piles Concrete piles Compression: Tension : USA (AASHTO) 90% of yield strength Fy Southern Pine Douglas Fir 3.2 ksi 3.5 ksi (85% f c) - prestress prestress + (50% of t.strength) prestress + 3 sqrt (f c) [f c in psi] 10

Pile Damage: BTA, LTD Pile damage causes a tension reflection before 2L/c Time tension reflection arrives indicates depth to damage: LTD = t damage * c / 2 Extent of damage is quantified by damage factor - BTA ( ) Reflection at an Impedance Change t = 0 L/c 2x/c 2L/c Z 1 F d,1 F u1 Early Tension reflection x A B F d2 Z 2 F A = F B F d,1 + F u,1 = F d,2 v A = v B v d,1 + v u,1 = v d,2 2 nd equation: (Z 1 v d,1 + Z 1 v u,1 ) (Z 2 /Z 1 ) = Z 2 v d,2 define = Z 2 /Z 1 : ( F d,1 - F u,1 ) = F d,2 = ( F d,1 + F u,1 ) / ( F d,1 - F u,1 ) = (F d,1-1.5rx + F u,1 )/(F d,1 0.5Rx - F u,1 ) (with shaft resistance) F d,1 = 4816 kn F u,1 = -351 kn Rx = 1237 * 2 = 2474 = 4816-3711-351 4816-1237+351 = 0.192 11

(%) Condition 100 Uniform 80-100 Slight damage 60-80 Significant damage <60 Broken Broken Piles: β < 60 End bearing is unreliable in long term for broken piles - Only shaft capacity above break might be useful usually minimal Capacity meaningless for broken piles BTA generally overestimates Z2 / Z1 real lower section generally less Capacity At time of testing vs depth during drive resistance distribution CAPWAP icap The Case Method Equation t = 0 L/c 2L/c x F d,1 ½R -Fd,1 L R B R -½R + ½R R B Upward traveling wave at time 2L/c: F u,2 = -F d,1 + ½R + ½R + R B or (rearranging) R = F d,1 + F u,2 12

The Case Method Equation R = ½(F 1 + Zv 1 + F 2 - Zv 2 ) F 1 and v 1 are pile top force and velocity at time 1 F 2 and v 2 are pile top force and velocity at time 2 Time 2 is 2L/c after Time 1: t 2 = t 1 + 2L/c R is the total pile resistance present at the time of the test, and mobilized by the hammer impact. Case Method Static Resistance Total Resistance = Static + Dynamic To estimate dynamic resistance, a viscous damping parameter ( J v ) is introduced for multiplication of computed toe velocity v toe R d = J v v toe V toe = ( 2 WD1 - Rt ) / Z Non-dimensionalization leads to the Case Damping Factor, J c J c = J v Z R d = J c Z v Case Method Static Resistance Static = Total Resistance Dynamic R static = R - R dynamic R s = (1-J c )[F 1 + Zv 1 ]/2 + (1+J c )[F 2 - Zv 2 ]/2 R s = (1-J c ) WD 1 + (1+J c ) WU 2 13

Case Damping Factor Values for RMX 0 0.2 0.4 0.6 0.8 1.0 Gravel 0.3 0.4 Sand 0.4 0.5 Reducing Grain Size Increasing Damping factor Silt 0.5 0.7 Clay 0.7 1.0 Case Method Capacity RS (t) = (1 - J) WD1 + (1 + J) WU2 RS (t) = (1 - J) (FT1 + Z VT1) /2 + (1 + J) (FT2 - Z VT2) /2 Easy driving Case Method Capacity RS (t) = (1 - J) WD1 + (1 + J) WU2 RS (t) = (1 - J) (FT1 + Z VT1) /2 + (1 + J) (FT2 - Z VT2) /2 Hard driving 14

RMX method does a time search RMX methods not as J sensitive RX5 RMX method RP5 ½R R Ri - Wave up Most Sites Have Set-up capacity gain with time after installation Caused by reduced effective stresses in soil due to pile driving (temporary) Pore pressure (clay - drainage log time) Arching (sand - lateral motions) Soil structure (cemented) Cookie cutters (oversize shoes ) Measure it by Dynamic Tests on Both End of Drive and Restrike (varied waits) Pre-Design Tests Early Production Piles 16 15

End of Drive Low shaft resistance Restrike (8 days) Increased shaft resistance (setup) Set-up End of Drive (EOD) Temporary stop No tension Begin of Restrike (BOR) 35 minutes Increase in lower 1/3 Reports - ASTM D4945 Stop 35 min 16

Pile Setup - Side Shear 18 PSC, O Cell at bottom Side in clay and silty clay in FL = +90% in 1 day (or 9x EOD capacity) +30% 1-28d +43% about half of EOD-1d change +30% +30% EOD Capacity plotted at ~1 min Bullock, Schmertmann, McVay, Townsend. Side Shear Setup, ASCE Geotechnical Journal March 2005.however, first one caution In rare cases, the pile can lose capacity with time Identifying Soil Relaxation from Dynamic Testing Morgano & White, GRL Engineers Ohio Turnpike (I80) Piles drive in clayey silt (N=30) to weathered siltstone/shale (N=50/1 ) Pre-Construction Wave Equation Analysis suggests: 20 blows per inch (1.3 mm set) at 9.3 ft (2.8m) stroke at 300 tons 17

Pile No. Test Date Blow Count (Blows/inch) Transfer Energy (Kip-ft) Hammer Stroke (ft) Case Method Capacity (tons) Test Type 13 2/15/02 20 16 9.2 290 EOID 2/16/02 15 12 8.5 200 BOR1 2/16/02 20 18 9.6 270 EOR1 2/23/02 10 14 8.5 170-200 BOR2 2/23/02 24 19 9.6 315 EOR2 18 2/23/02 7 17 9.0 172 BOR1 2/23/02 27 18 9.7 330 EOR Notes: 1. Pile 13 drove additional 5 inches during restrike sequences 2. Pile 18 drove additional 18 inches during restrike sequences Testing detected capacity problem. Prevented potentially major problem on major project 198 tons Capacity Static test on Undisturbed sister pile Soils with relaxation potential Weathered shale Rule of thumb: more weathered bedrock = more relaxation Seeping water softens bedrock surface High normal force after driving plastically creeps away with time; reduces friction Rock fracturing from driving adjacent piles Saturated dense to v.dense sands & sandy silts Due to negative pore water pressure during driving increases effective stresses of end bearing Pore water pressure equalizes after wait causing reduced soil strength 18

.back to significantly more common SETUP and how we can benefit from it by testing North Section Intermodal Transit System Guideway Orlando International Airport Boring 8 final plan Original Design Load 100 T for 24 pipe at 120 ft depth Design/Build Proposal: save$ 18 pipe, shorter depth Ref: Wayne Waters, Ed Waters & sons, PDCA Winter Roundtable, Orlando 2004 Intermodal Transit System Orlando International Airport Proving the point. Proof test > 250 tons Bent #9 Req. Cap. = 250 tons EOD PDA = 135 tons (9 bl/ft) 5 day BOR = 256 tons (64 b/ft) 303 piles - 10% tested by restrike use set-up $1 million saved vs original design 19

St. John s River Bridge test program Aug 11 EOD 25 bpf Sept 16 150 bpf 24 x 0.5 inch c.e.pipe, ICE 120S 150 bpf @ twice the Energy ST Johns River Bridge PDA test program $650,000 extra soil borings $750,000 increased loads by 33% with substantially shorter piles (set-up considered) Total project: $130 million (estimate) $110 million (actual) $20 million savings! savings in pile costs Ref: Scales & Wolcott, FDOT, presentation at PDCA Roundtable Orlando 2004 Allowable Compression Capacities (tons) using IBC max allowable stresses (PPC Piles) 20 th Cent. loads Pile size f c (psi) (assume fpe 700 psi) Increase factor over 20 th Century loads Inch 5000 6000 7000 5000 6000 7000 75 12 105 129 153 1.40 1.72 2.04 90 14 143 176 208 1.59 1.95 2.31 115 16 187 229 271 1.63 1.99 2.36 Karl Higgins Competitive Advantages of High Capacity, Prestressed Precast Concrete Piles PDCA DICEP conference, Sept. 2007 20

Potomac Yard-Arlington Initial Design Potomac Yard drilled Shafts least costly Pile Cap Costs Included for comparison Savings: 50% Final Design driven piles least costly Karl Higgins Competitive Advantages of High Capacity, Prestressed Precast Concrete Piles PDCA DICEP conference, Sept. 2007 Innovation along the Interstate Saieb Haddad, TN DOT - Piledriver Magazine, PDCA, Quarter 3 issue, 2007 www.piledrivers.org Driven Pile solution $2,000,000 Drilled Shaft Wall solution > $15,000,000 Driven piles and dynamic testing are well suited for marine and near shore applications. 21

Dynamic testing for Offshore oil projects Wireless tests Caspian Sea 2009 Underwater sensors Caspian Sea 2009 22

SPT ASTM D4633 Testing eliminates the uncertainty of bearing capacity. Static testing testing Dynamic Testing Wave Equation Dynamic Formula no testing Static Analysis Better verification methods, and more testing, results in lower SF and therefore less cost. 8 PDCA LRFD - 2000 AASHTO standard specifications (pre 2007) Application: 2000 ton column load, 200 ton ultimate capacity piles design load piles F.S. per pile needed 3.50 200/3.50 = 57.1 t 35 dyn. formula 2.75 200/2.75 = 72.7 t 28 wave equation 2.25 200/2.25 = 88.9 t 23 dynamic test 2.00 200/2.00 = 100 t 20 Static (SLT) 1.90 200/1.90 = 105.3 t 19 SLT + dynamic lower F.S. fewer piles less cost 23

LRDF (Load & Resistance Factor Design) (phi) Ru > f D L D + f L L L + f i L i + LRFD - Different Loading Factors ACI, AISC 1.2D + 1.6L AASHTO 1.25D + 1.75L Eurocode 1.35D + 1.5L Australia 1.20D + 1.5L need different phi factors for same equivalent F.S. AASHTO (2010) PDCA LRFD 1.25D - 2000 + 1.75L look at D/L = 3 D = 1500: L = 500 1500 x 1.25 + 500 x 1.75 = 2750 Application: 2000 ton column load 2750 ton factored load 200 ton ult capacity piles ( nominal resistance ) factored resistance piles phi per pile needed 0.40 200*0.40 = 80 t 35 Gates formula 0.50 200*0.50 = 100 t 28 wave equation 0.65 200*0.65 = 130 t 22 2%, 2# dynamic 0.70 200*0.70 = 140 t 20 25% (?) dynamic 0.75 200*0.75 = 150 t 19 SLT or 100% dyn 0.80 200*0.80 = 160 t 18 SLT and 2%,# dyn Ohio DOT uses 0.70 for dynamic testing Ru (F.S.) PDCA Qd LRFD - 2000 PDCA 2001 also has LRFD code Application: 2000 ton column load, 200 ton ult capacity driven piles design load piles SF per pile needed 3.5 200/3.50 = 57 t 35 dyn form 2.5 200/2.50 = 80 t 25 w.e. 2.1 200/2.10 = 95 t 21 2% dyn 1.9 200/1.90 = 105 t 19 1% SLT 1.65 200/1.65 = 121 t 17 15% dyn +1 SLT 24

Number of piles required for example case AASHTO ASD AASHTO LRFD Eurocode Australia AS 2159 PDCA 2001 Dynamic formula 35 35 35 Wave equation 28 28 25 Dynamic test Max (2# or 2%) 22 Dynamic test 100% 22 20 ODOT 22 2# 19 or 20 (high or low redundancy) 19 17 10% 21 19 10% Static test 19 19 23 to 16 1# to 5# Dynamic test and Static test 18 18 2% dyn 1 static 19 or 20 (1%) (high or low redundancy) 18 to 20 (2%) (high or low redundancy) 19 1% 17 15% dyn 1 static AASHTO LRFD Example - 18 sq PSC 2,750 tons total factored load 10 piles each with 275 kips factored Resistance PHI φ R u,req 275/PHI EB (100 ksf) Fs (1 ksf) Req. L pen kips kips kips ft Static Test 100% Dyn. 0.75 367 225 142 24 Dyn. Test 2% 0.65 423 225 198 33 Wave Equation 0.50 550 225 325 54 Static Formula 0.35 786 225 561 94 $ $$$ What are the consequences of insufficient testing? - two projects - Tampa Expressway April 2004 failed structure (loss of use) more than one year delay high remediation costs (more than $120 million) 25

Dynamic Testing Benefits More information in less time (reduces delays): Confirms pile capacity design Tests integrity, stresses, hammer energy Improves quality control (test more piles; tests problem piles ) Rational means to reduce pile costs shorter piles or fewer piles (lower S.F.) Significantly less cost than static test Why test driven piles? Public assured of safe foundation (bridges, buildings, etc.) We spend lots of money - $4B. Remediation is very expensive! Reduce the risk Optimize foundation -reduce cost Dynamic testing allows driven piles to have more testing than other foundations more safety, less risk, less cost More Information PDA test program Viewer with PDA sample data (no cost for universities) available on request Student notes with sample problems (and solutions) available upon request Reference papers available www.pile.com/reference/ Brochures available on www.pile.com/brochure/ Contact: info@pile.com for requests 26

One test result is worth a thousand expert opinions Werner Von Braun Father of the Saturn V rocket Garland Likins, Pile Dynamics, Inc. 2011 PDCA Professor s Institute www.piledrivers.org 27