Pressure Losses for Fluid Flow Through Abrupt Area. Contraction in Compact Heat Exchangers

Similar documents
CFD Analysis of Forced Convection Flow and Heat Transfer in Semi-Circular Cross-Sectioned Micro-Channel

Basic Fluid Mechanics

Pressure Drop Across Orifices in Microchannels

DEVELOPED LAMINAR FLOW IN PIPE USING COMPUTATIONAL FLUID DYNAMICS M.

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

Application of COMSOL Multiphysics in Transport Phenomena Educational Processes

Lecture 22. Mechanical Energy Balance

Chapter 10. Solids and Fluids

vector H. If O is the point about which moments are desired, the angular moment about O is given:

CONVECTIVE HEAT TRANSFER

The effect of Entry Region on Thermal Field

Lesson 37 Transmission Of Air In Air Conditioning Ducts

Internal Forced Convection. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

FE Exam Fluids Review October 23, Important Concepts

Fluid Flow Analysis Penn State Chemical Engineering

Study fluid dynamics. Understanding Bernoulli s Equation.

Ch. 10 Compact Heat Exchangers

Angular momentum equation

Phan-Thien-Tanner Modeling of a Viscoelastic Fluid in the Stick-Slip Scenario. Andrew Griffith

Chapter 3 NATURAL CONVECTION

Differential relations for fluid flow

Piping Systems and Flow Analysis (Chapter 3)

Fluids. Fluids in Motion or Fluid Dynamics

LECTURE 1 THE CONTENTS OF THIS LECTURE ARE AS FOLLOWS:

Convection. forced convection when the flow is caused by external means, such as by a fan, a pump, or atmospheric winds.

طراحی مبدل های حرارتی مهدي کریمی ترم بهار HEAT TRANSFER CALCULATIONS

Lesson 6 Review of fundamentals: Fluid flow

Analysis of Fully Developed Turbulent Flow in a AXI-Symmetric Pipe using ANSYS FLUENT Software

Mixing in Flow Devices:

Mixing of Liquids in Microfluidic Devices

PHYSICAL MECHANISM OF CONVECTION

Chemical and Biomolecular Engineering 150A Transport Processes Spring Semester 2017

UNIT II CONVECTION HEAT TRANSFER

Laminar flow heat transfer studies in a twisted square duct for constant wall heat flux boundary condition

NUMERICAL HEAT TRANSFER ENHANCEMENT IN SQUARE DUCT WITH INTERNAL RIB

Chapter 7 The Energy Equation

report: Computational Fluid Dynamics Modelling of the Vortex Ventilator MK4 Rev 2 Ventrite International

Fluid Dynamics Exercises and questions for the course

A Comparative Second Law Analysis of Microchannel Evaporator with R-134A & R-22 Refrigerants

CFD Analysis on Flow Through Plate Fin Heat Exchangers with Perforations

Lecture23. Flowmeter Design.

ABSTRACT I. INTRODUCTION

Outlines. simple relations of fluid dynamics Boundary layer analysis. Important for basic understanding of convection heat transfer

Experimental and CFD analysis of flow through venturimeter to determine the coefficient of discharge

Interphase Transport in Isothermal Systems

FACULTY OF CHEMICAL & ENERGY ENGINEERING FLUID MECHANICS LABORATORY TITLE OF EXPERIMENT: MINOR LOSSES IN PIPE (E4)

ENERGY PERFORMANCE IMPROVEMENT, FLOW BEHAVIOR AND HEAT TRANSFER INVESTIGATION IN A CIRCULAR TUBE WITH V-DOWNSTREAM DISCRETE BAFFLES

A numerical study of heat transfer and fluid flow over an in-line tube bank

Chapter 8: Flow in Pipes

Shell Balances in Fluid Mechanics

Analysis and Comparison of the Performance of Concurrent and Countercurrent Flow Heat Exchangers

Heat Transfer Performance in Double-Pass Flat-Plate Heat Exchangers with External Recycle

Applied Fluid Mechanics

Numerical Investigation of The Convective Heat Transfer Enhancement in Coiled Tubes

External Forced Convection. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

ME332 FLUID MECHANICS LABORATORY (PART II)

Application of Solution Mapping to Reduce Computational Time in Actively Cooled Power Electronics

AEROSPACE ENGINEERING DEPARTMENT. Second Year - Second Term ( ) Fluid Mechanics & Gas Dynamics

Chapter Four fluid flow mass, energy, Bernoulli and momentum

Studies on flow through and around a porous permeable sphere: II. Heat Transfer

Analysis of the Cooling Design in Electrical Transformer

EXPERIMENT II - FRICTION LOSS ALONG PIPE AND LOSSES AT PIPE FITTINGS

Chapter 8: Flow in Pipes

DESIGN & COMPUTATIONAL FLUID DYNAMICS ANALYSES OF AN AXISYMMETRIC NOZZLE AT TRANSONIC FREE STREAM CONDITIONS

1 st Law Analysis of Control Volume (open system) Chapter 6

Modeling a Catalytic Converter in Comsol Multiphysics

Performance. 5. More Aerodynamic Considerations

Lecture 30 Review of Fluid Flow and Heat Transfer

Numerical Investigation on The Convective Heat Transfer Enhancement in Coiled Tubes

10.52 Mechanics of Fluids Spring 2006 Problem Set 3

Principles of Convection

Impact of a Jet. Experiment 4. Purpose. Apparatus. Theory. Symmetric Jet

THE EFFECT OF POROUS BLOWING AND SUCTION ON AERODYNAMICS AND HEAT TRANSFER IN SEPARATED LAMINAR FLOW IN DUCT BEHIND OF BACKWARD-FACING STEP S.R.

Supplementary Information for Engineering and Analysis of Surface Interactions in a Microfluidic Herringbone Micromixer

MOMENTUM TRANSPORT Velocity Distributions in Turbulent Flow

Study on the improved recuperator design used in the direct helium-turbine power conversion cycle of HTR-10

PIPE FLOWS: LECTURE /04/2017. Yesterday, for the example problem Δp = f(v, ρ, μ, L, D) We came up with the non dimensional relation

Numerical Heat and Mass Transfer

Applied Thermodynamics for Marine Systems Prof. P. K. Das Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Part A: 1 pts each, 10 pts total, no partial credit.

LEAKLESS COOLING SYSTEM V.2 PRESSURE DROP CALCULATIONS AND ASSUMPTIONS

OPTIMUM GEOMETRY OF MEMS HEAT EXCHANGER FOR HEAT TRANSFER ENHANCEMENT

CFD study for cross flow heat exchanger with integral finned tube

FE Fluids Review March 23, 2012 Steve Burian (Civil & Environmental Engineering)

EXPERIMENT No.1 FLOW MEASUREMENT BY ORIFICEMETER

The effect of geometric parameters on the head loss factor in headers

Experiment No.4: Flow through Venturi meter. Background and Theory

Viscous Fluids. Amanda Meier. December 14th, 2011

Applied Fluid Mechanics

Viscous Flow in Ducts

BERNOULLI EQUATION. The motion of a fluid is usually extremely complex.

Objectives. Conservation of mass principle: Mass Equation The Bernoulli equation Conservation of energy principle: Energy equation

Chapter 4 DYNAMICS OF FLUID FLOW

ME332 FLUID MECHANICS LABORATORY (PART I)

FLUID MECHANICS PROF. DR. METİN GÜNER COMPILER

STUDY OF BOUNDARY LAYER PARAMETERS ON A FLAT PLATE USING WIND TUNNEL

DESIGN CONSIDERATIONS FOR COMPACT CERAMIC OFFSET STRIP -FIN HIGH TEMPERATURE HEAT EXCHANGERS

PIPE FLOW. General Characteristic of Pipe Flow. Some of the basic components of a typical pipe system are shown in Figure 1.

SYSTEMS VS. CONTROL VOLUMES. Control volume CV (open system): Arbitrary geometric space, surrounded by control surfaces (CS)

Convection Heat Transfer. Introduction

Transcription:

Pressure Losses for Fluid Flow Through Abrupt Area Contraction in Compact Heat Exchangers Undergraduate Research Spring 004 By Bryan J. Johnson Under Direction of Rehnberg Professor of Ch.E. Bruce A. Finlayson Date: June 11, 004

Introduction The goal of this experiment was to predict and improve on the results of Kays and London entrance pressure-loss coefficient (K c ) for a multiple tube flat-duct heat exchanger core with an abrupt-contraction entrance. [1] Kays and London determined the pressure-loss coefficient for various contraction ratios (σ) and graphed them as a line. They labeled this line as Laminar, but did not expound upon the range of Reynolds numbers the laminar flow line was applicable to. This experiment will graph the pressure loss coefficient for six contraction ratios and a range of Reynolds numbers to improve upon Kays and London s Laminar flow graph. Materials and Methods This experiment used FEMLAB 3 version.3 to determine the pressure loss across the system and the maximum velocity in the outlet tube over a range of Reynolds numbers. The simulations were run in -D Navier-Stokes Incompressible Steady State Flow. Figure 1 shows an example of the drawing used in FEMLAB to determine this data; in this case it is a 1/3- contraction ratio. The contraction ratios analyzed in this experiment were, 0.90, 0.75, 0.67, 0.5, 0.33, and 0.. The contraction ratio was calculated from the exit height over the inlet height. Height refers to the distance from the line of symmetry (boundary ) to the respective boundary (boundary 3 for the entrance tube and boundary 5 for the exit tube). The height of the exit pipe was held constant at 0.5. The exit pipe height of 0.5 was chosen based on the hydraulic diameter for irregular shapes Eq. 1 []. 4A D H = Eq. 1 C

The height of the entrance was varied to attain the desired contraction ratios. Figure 1 also shows the boundary conditions applied to some of the boundaries. 3 Slip 4 No-slip 5 No-slip 1 Slip 6 Fig. 1 -D Abrupt Contraction Ratio 1/3 Boundary one was the inlet/outlet velocity. The x-direction velocity at boundary one was set equal to the contraction ratio; the contraction ratio was chosen so that the average velocity in the exit tube would be unity. Boundaries two and three were set as slip boundaries. This would create the desired symmetry to simulate the heat exchangers flow area contraction. Boundary six was set as the inlet/outlet pressure boundary and set equal to zero. The remaining boundaries, four and five, were set as no-slip boundaries. The length of the entrance analyzed was chosen to 3

be 1.5, to allow for fully developed flow entering the contraction area. The length of the exit tube was chosen to be 10, to allow for fully developed flow to exist at the exit boundary. In the sub-domain settings the density (ρ) was set equal to 10 s. By varying the density the Reynolds number would also be varied. Using parametric solver s was varied from 3 to 3 by 0.1 increments. This would yield data for Reynolds number from 0.001 to 1000. Figure shows the mesh applied to the drawing for the 1/3-contraction ratio. The mesh refinement for all the contraction ratios averaged 1064 elements with a standard deviation of 176 elements, and a range from 911 to 13,90 elements. The mesh refinement was concentrated in the contraction area since this is the area with the most flow disturbances occurring and thus the most critical for analysis. Fig. Mesh Refinement for -D Abrupt Contraction Ratio 1/3 (This is the abrupt contraction area. The small tube refinement repeats the same geometry from 1 to 10.) 4

Fig. 3 Graphical Representation of -D Abrupt Contraction Ratio 1/3 Figure 3 shows a graphical representation for the results of a 1/3-contraction ratio. This is for a Reynolds number of 100. The x-velocity lines are graphed and the minimum and maximum x-velocities are displayed. 5

Figure 4 a is blow up of the throat area of Fig. 3. Fig. 4 Throat Area Graphical Representation of -D Abrupt Contraction Ratio 1/3 With the problem solved in FEMLAB, the pressure loss across the system was obtained from Eq. and the FEMLAB data. p * da Δp system = da Eq. In FEMLAB this was accomplished by integrating for the pressure over boundary 1 and then dividing by the entrance height. The pressure loss due to friction in the entrance area, the area prior to contraction, was zero since there are no friction losses at the boundaries. The pressure loss in the small tube due to friction losses was calculated from Eq. 3. 6

* umax * L * µ Δ p exittube = Eq. 3 H Where: u max is the maximum x-velocity in the small tube L is the length of the small tube µ is the viscosity of the liquid H is the height of the small tube (boundary to boundary 5) The maximum x-velocity was obtained from the FEMLAB results. The pressure loss due to contraction was then calculated from Eq. 4. Δ p = Δp Δp Δp Eq. 4 contraction system entrance exittube Recall that the pressure loss due to friction in the entrance area was zero. The difference in pressure due to contraction was converted to find the pressure-loss coefficient (K c FEMLAB ). Equation 5 [1] is from Kays and London. Δp1 ρ = V g c ( 1 σ ) + K c V g c Eq. 5 Where the variable: Δp 1 is the pressure loss due to contraction ρ is the density of the fluid V is the velocity in the small tube σ is the contraction ratio ( core free-flow to frontal-area ratio [1]) K c is the pressure-loss coefficient due to abrupt contraction Equation 5 was rearranged to solve for Δp ρv 1, this is Eq. 6. 7

K Δp1 = 1 σ + c ρv ( ) Eq. 6 Equation 6 was set equal to ( Δp contraction and then solved for Kc yielding Eq. 7. Re ) Δp 1 σ K c = * contraction Re Eq. 7 Equation 7 was used to calculate the pressure-loss coefficient based on the FEMLAB data. The pressure-loss coefficient calculated in Eq. 7 was graphed against Fig. 6 from Kays and London [1]. (The Laminar line on the graph for Kc is the line of concern for this experiment.) Fig. 6 Entrance and exit pressure-loss coefficients for a multiple-tube flat-duct heat exchanger core with abrupt-contraction entrance and abrupt-expansion exit. [1] 8

Equation 8 was used to compare the pressure loss calculated by the FEMLAB based pressure-loss coefficient and the pressure loss based on Kays and London pressure-loss coefficient for a given contraction ratio. These pressure losses were graphed vs. the Reynolds number. Δp = Re ( 1 σ ) + Kc Eq. 8 Equation 8 is a rearrangement of Eq. 7. Results and Discussion The FEMLAB based pressure-loss coefficient for a given Reynolds number was graphed for the various contraction ratios. In Fig. 7 the Reynolds numbers one and ten are graphed against the Laminar points from Fig. 1 [1]. 9

Entrance Pressure-Loss Coefficients For Multiple Tube Flat Duct Heat Exchanger with Abrupt-contraction Entrance 5 0 Re 1 y = -13.36x + 3.044x + 19.638 R = 0.996 15 Re 10 y = -1.0483x + 0.17x +.361 R = 0.9961 Kc 10 Re 1 Re 10 5 Kays and London "Laminar" 0 0 0. 0.4 0.6 0.8 1 Sigma Fig. 7 Pressure-Loss Coefficient for Multiple Tube Flat Duct Heat Exchanger with Abrupt-Contraction Entrance for Kays and London Laminar and FEMLAB Reynolds Number One and Ten The blue line in Fig. is the best-fit line that represents the pressure-loss coefficient, based on the Reynolds number of 1. The pink line in Fig. 7 and Fig. 8 is the best-fit line that represents the pressure-loss coefficient, based on the Reynolds number of 10. Both of the bestfit lines are quadratic in form. 10

Figure 8 shows the Reynolds numbers 10, 100, and 1000 as they compare to Laminar points from Fig. 6 [1]. Entrance Pressure-Loss Coefficients For Multiple Tube Flat Duct Heat Exchanger with Abrupt-contraction Entrance Kc.50.00 1.50 1.00 0.50 Re 10 y = -1.0483x + 0.17x +.361 R = 0.9961 Re 100 y = -0.099x - 0.017x + 0.9569 R = 0.999 Re 1000 y = -0.0183x - 0.0774x + 0.7581 R = 0.9996 Re 10 Re 100 0.00 0 0. 0.4 0.6 0.8 1 Sigma Re 1000 Kays and London "Laminar" Fig. 8 Pressure-Loss Coefficient for Multiple Tube Flat Duct Heat Exchanger with Abrupt-Contraction Entrance for Kays and London Laminar and FEMLAB Reynolds Number 10, 100 and 1000 The pink line in Fig. 8 is the best-fit line that represents the pressure-loss coefficient, based on the Reynolds number of 10. The yellow line in Fig. 8 is the best-fit line that represents the pressure-loss coefficient, based on the Reynolds number of 100. The light blue line in Fig. 8 is the best-fit line that represents the pressure-loss coefficient, based on the Reynolds number of 100. All three of these best-fit lines are quadratic in form. 11

The pressure-loss coefficient for Reynolds numbers less than 100 was significantly different, greater than 15 percent error, than Kays and London s Laminar pressure-loss coefficient. The percent errors for the pressure-loss coefficients for Reynolds numbers 100 to 1000 are displayed in Table 1. Table 1 Percent error between the FEMLAB based Kc and Kays and London s Kc % Error Between the FEMLAB Based Kc and Kays' and London's Kc Reynolds Femlab Based Kc for the following σ Number 0.9 0.75 0.67 0.5 0.33 0. 100 37 30 6 0 18 17 16 36 7 3 17 14 13 158 34 5 1 14 11 10 00 33 4 19 1 8 7 51 3 17 10 6 4 316 3 1 16 8 4 398 31 0 14 6 0 501 31 19 13 5 0 631 30 18 1 3 1 4 794 30 17 11 3 5 1000 9 16 10 1 4 7 Table one shows that the percent error difference for the contraction ratios 0.9 and 0.75 do not get below ten percent error within the analyzed Reynolds numbers. The remaining contraction ratios do come within ten percent error. The smaller contraction ratios 0.33 and 0. at Reynolds numbers higher than 158 come close and even match Kays and London. 1

Figure 9 shows the pressure losses due to contraction over the range of Reynolds numbers from 0.01 to 100 due to the contraction ratio of 1/3. Reynolds Number vs. Pressure Loss Due to Contraction for Contraction Ratio of 1/3 Pressure Loss Due to Contraction 100.00 10.00 1.00 0.10 0.01 0.1 1.0 10.0 100.0 Reynolds Number Kays and London Femlab Fig. 9 Pressure Loss Due to the Abrupt Contraction Ratio of 1/3 vs Reynolds Number Both of the axes on the graph are log rhythmic. The blue points are the pressure losses calculated from Eq. 8 for the Kays and London pressure-loss coefficient. The green points are the pressure losses calculated from Eq. 8 for the pressure-loss coefficient based on the FEMLAB data. Figure 9 shows that the pressure-loss coefficient is independent of the Reynolds number below a Reynolds number of 10. 13

Figure 10 shows the percent error between the pressure loss based on FEMLAB data and the Kays and London Laminar points. The percent errors were graphed over a range of Reynolds numbers. The range of Reynolds numbers in the graph were chosen to show where the percent error difference becomes small enough to be considered negligible. %Error Between Pressure Losses for FEMLAB and Kays and London vs. Reynolds Number 5.00 %Error 0.00 15.00 10.00 5.00 0.9 0.75 0.67 0.5 0.33 0. 0.00 10 100 1000 Reynolds Number Fig. 10 Percent error losses between the pressure losses due to abrupt contraction for the FEMLAB and Kays and London over a range of Reynolds numbers. The Reynolds number axis is log rhythmic scale. Note that percent error in pressure losses for the contraction ratios 0.5, 0.33 and 0. are the only ones that become small enough to be considered negligible. This occurs at Reynolds numbers greater than 00. 14

Conclusions and Recommendations Kays and London s Laminar pressure-loss coefficient were improved upon. The pressure-loss coefficients can be red for a larger range of laminar flow Reynolds numbers. This will provide more accurate pressure loss data. The mesh for the /3 contraction ration was 3000 elements larger than the average. I recommend refining the mesh so that it is closer to the average, or refining the mesh of the other contraction ratios to coincide with the /3 contraction ratio mesh. I did not analyze the pressure changes due to changes in kinetic energy. I recommend that this be done to show where the pressure changes due to kinetic energy becomes significant. I would also analyze more contractions ratios. This is easy enough using FEMLAB, just time consuming. I would analyze contraction ratios at 0.05 increments, since I was able to read off Kays and London pressure-loss coefficients at this interval. 15

Literature Cited 1. Kays, W. M., and London, A. L. Compact Heat Exchangers, 3 rd edition, p. 109, 11, McGraw-Hill, New York, (1984).. Bird, R.B., et al. Transport Phenomena, nd edition, p. 183, John Wiley & Sons, New York, (00). 16