DIRECT STROKE LIGHTNING PROTECTION DESIGN

Similar documents
66kV & 220kV Substation Protection From Lightning by Fixed Angle, Rolling Sphere and Early Streamer Method

Proposed revisions to IEEE Standard 998 (1996) Guide for Direct Lightning Stroke Shielding of Substations

Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

A Roadmap for Evaluation of Lightning Elimination Technologies

EPRI Lightning Protection Design Workstation

This case study also provides recommendations for future lightning protection design for existing (brownfield) substation.

Modeling of Transmission Line and Substation for Insulation Coordination Studies

The Lightning Study of Overhead Transmission Lines

Lightning performance of distribution lines: sensitivity to computational methods and to data

Field Sensitive Air Terminal (F-SAT) Simply the Best Lightning Rod

THE EARLY STREAMER EMISSION PRINCIPLE DOES NOT WORK UNDER NATURAL LIGHTNING!!

Lightning. Electricity and Charge. Primary types of lightning. Primary types of lightning. How do clouds gain a charge?

Application of Lightning Location System Data for Designing the External Lightning Protection System

Chapter 21. Lightning Facts. Lightning Facts 4/12/17. Lightning

Chapter Six. Corona:

LIGHTNING PHYSICS AND LIGHTNING PROTECTION: STATE OF ART 2013 Prof. Carlo Mazzetti di Pietralata

Aalborg Universitet. Published in: Cigré International colloquium on lightning and power systems, Lyon Publication date: 2014

Lightning Insulation Coordination Study

Dr. Kim D. Coder, Professor of Tree Biology & Health Care, Warnell School, UGA

Fatima Michael College of Engineering & Technology

Lightning Effect on Scaled Protected and Un-Protected Building Structures and the Air Terminal Bypasses


Analysis of Very Fast Transients in EHV Gas Insulated Substations

Lightning Phenomenon, Effects and Protection of Structures from Lightning

The leader propagation velocity in long air gaps

UNIT I - INTRODUCTION SYLLABUS

Copyright 2014 IEEE. Paper presented at 2014 IEEE conference on electrical insulation and dielectric phenomena, Des Moines, USA, October, 2014.

(part I) Dr. Kim D. Coder. Professor of Tree Biology & Health Care Warnell School, University of Georgia

, times the dielectric constant of the material, k d. . With these definitions, Eq. 1 can be written as:

Today s lecture. Charge separation in clouds Lightning and thunder

Lightning location system in Croatia

Available online at ScienceDirect. Reynaldo Zoro*

Energy Stored in Capacitors

Experimental and Analytical Studies on Lightning Surge Response of 500kV Transmission Tower

Charges that are different attract each other.

PRESENT PROBLEMS OF POWER SYSTEM CONTROL

Parameters of Rocket-Triggered Lightning

Influence of Grounding Material s Property on the Impulse Grounding Resistance of Grounding Grids

5/26/2010. Hailstone Formation and Growth Lightning Stroke Downburst Formation, Structure, and Type

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

Lightning Protection Of Wind Turbines. EWEC 2010 Warsaw Poland By Vidyadhar Peesapati

with Implications for Air Terminals

Keywords- Metal Oxide Surge Arrester, Model, Transient, Laboratory Experiment, Simulation.

Lightning Protection Of Wind Turbines

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

NOVEL LIGHTNING INCIDENCE MODEL BASED ON THE ELECTRIC FIELD GRADIENT: 2D ELECTROSTATIC ANALYSES

iclicker A metal ball of radius R has a charge q. Charge is changed q -> - 2q. How does it s capacitance changed?

Lightning Performance of Transmission Lines

Yr. 9 Electricity WorkBook

Carlos T. Mata, Jonathan D. Hill, Angel G. Mata Stinger Ghaffarian Technologies Kennedy Space Center, FL

Exponential Expression of Relating Different Positive Point Electrode for Small Air Gap Distance

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

Preliminary study on the modeling of negative leader discharges

Lightning Interception. Non conventional lightning protection systems

THE INITIATION OF LIGHTNING STRIKES. THE PROTECTION PROVIDED BY LIGHT- NING RODS EQUIPPED WITH DOWN

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

Lightning performance of EHV and UHV overhead transmission Lines in China southern power grid

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Lightning Parameters for Engineering Applications: Recent Updates and Outlook

Lightning Attachment Models and Perfect Shielding Angle of Transmission Lines

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Electric Charge. Physics 4B. Atomic Structure

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Analysis of surge arresters failures in the installation of broadcasting transmitter

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Section 9: Using a Charged Electroscope to Determine the Charge on Another Object. Examples:

TRANSIENTS POWER SYSTEM. Theory and Applications TERUO OHNO AKIH1RO AMETANI NAOTO NAGAOKA YOSHIHIRO BABA. CRC Press. Taylor & Francis Croup

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

Technical Challenge of Lightning Protection for Wind Power Generation

Assessment of the interception efficiency of CVM-based lightning protection systems

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

PhysicsAndMathsTutor.com

MODELING OF THE DIRECT LIGHTNING STRIKE ON A TOWERS CASCADE EQUIPPED WITH ITS PROTECTIONS

Modeling and Simulation of Air Insulated and Gas Insulated Substations

Code No: RR Set No. 1

Electric Charge and Electric Forces

STATIC ELECTRICITY. I. Tick ( ) the most appropriate answer. 1. When an ebonite rod is rubbed with fur, the charge acquired by the fur is:

Concurrent Upward Lightning Flashes from Two Towers

Chapter 19, Electricity Physical Science, McDougal-Littell, 2008

Dynamics of streamer propagation in air

DETERMINATION OF THE DIELECTRIC STRENGTH OF LPS COMPONENTS BY APPLICATION OF THE CONSTANT-AREA-CRITERION

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

Chapter Assignment Solutions

EXPERIMENTAL DEVELOPMENTS ON SOIL IONIZATION: NEW FINDINGS

The objective of a grounding system are: 1. To provide safety to personnel during normal and fault conditions by limiting step and touch potential.

A Comparison between Analytical Solutions for Lightning-Induced Voltage Calculation

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

VKES. Contents. Page 2 No 213, 13th Main RBI Layout JP Nagar 7th Phase, Bangalore Vidyuth Kanti Engineering Services

Alternating Current (AC): Alternating Current is electric current that reverses directions at regular intervals.

This is the submitted version of a paper published in Journal of Electrostatics. Citation for the original published paper (version of record):

EFFECTIVENESS OF WORLDWIDE EXISTING ESE LIGHTNING PROTECTION SYSTEMS MANUFACTURED IN EUROPE

Electricity. Prepared by Juan Blázquez, Alissa Gildemann. Electric charge is a property of all objects. It is responsible for electrical phenomena.

Power System Engineering Prof. Debrapriya Das Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Transcription:

International Journal of Research in Engineering and Applied Sciences(IJREAS) Available online at http://euroasiapub.org/journals.php Vol. 7 Issue 1,January7, pp. 1~12cv ISSN (O): 2249-3905, ISSN(P) : 2349-6525 Impact Factor: 6.573 Thomson Reuters ResearcherID: L-5236-2015 DIRECT STROKE LIGHTNING PROTECTION DESIGN Akshay Patil (Electrical and Electronics Engineering, Navrachana University, India) Abstract: This guide includes methods that have been utilized for decades as well as some that have been developed more recently. The general nature of lightning is discussed, and the problems associated with providing shielding from direct strokes are described. Tables, formulas, and examples are provided to calculate whether substation equipment is effectively shielded from direct lightning strokes. Keywords: Direct Strokes, Lightning, Shielding, Strokes. I. Introduction: Direct strokes from lightning can damage substation equipment and bus work. To protect equipment, substation engineers can install direct stroke lightning shielding. This guide is intended to provide engineers with information pertaining to the interception of damaging direct lightning strokes to outdoor substations. Because of the unpredictability of lightning and the costs associated with damage from direct lightning strokes, research into lightning phenomenon is ongoing. This guide includes descriptions of four non-conventional modeling methods for lightning interception, as well as a review of active lightning terminals. The four non-conventional methods are in various stages of development and are presented as a sample of the continuing research in direct lightning stroke shielding. These methods have potential to be used as design models for substation direct lightning stroke shielding in the future. An open access scholarly, Online, print, peer-reviewed, interdisciplinary, monthly, and fully refereed journal. 1

II. Terminology associated with DSLP: For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary Online should be consulted for terms not defined in this clause. 2.1 Critical Stroke Amplitude The amplitude of the current of the lightning stroke that, upon terminating on the phase conductor, would raise the voltage of the conductor to a level at which flashover is likely. The critical stroke amplitude can flow from the first stroke or any of the subsequent strokes in a lightning flash. 2.2 Dart Leader The downward leader of a subsequent stroke of a multiple-stroke lightning flash. 2.3 Effective Shielding That which permits lightning strokes no greater than those of critical amplitude (less design margin) to reach phase conductors. Effective (100% reliable) shielding cannot be achieved in substations because subsequent strokes can flow in the same channel established by the first stroke in a flash, and the models of first-stroke termination of flashes rely on statistical relationships among lightning parameters. 2.4 Electrogeometric Model (EGM) A geometrical representation of a facility that, together with suitable analytical expressions correlating its dimensions to the current of the lightning stroke, is capable of predicting if the first return stroke of a lightning flash will terminate on the shielding system, the earth, or the element of the facility being protected. 2.5 Electrogeometric Model Theory The theory describing the electrogeometric model together with the related quantitative analyses including the correlation between the striking distance and the electrical parameters, such as charge and peak current, of the prospective first return stroke. 2.6 Ground Flash Density (GFD) The average number of lightning flashes per unit area per unit time at a particular location. 2

2.7 Isokeraunic Lines Lines on a map connecting points having the same keraunic level. 2.8 Keraunic Level The average annual number of thunderstorm days or hours for a given locality. A daily keraunic level is called a thunderstorm-day and is the average number of days per year in which thunder is heard during a 24-hour period. An hourly Keraunic level is called a thunderstorm-hour and is the average number of hours per year that thunder is heard during a 60-minute period. 2.9 Lightning Flash The complete lightning discharge, most often composed of leaders from a cloud followed by one or more return strokes. 2.10 Lightning Mast A column or narrow-base structure containing a vertical conductor from its tip to earth, or that is itself a suitable conductor to earth. Its purpose is to intercept lightning strokes so that they do not terminate on objects located within its zone of protection. 2.11 Negative Shielding Angle The shielding angle formed when the shield wire is located beyond the area occupied by the outermost conductors. 2.12 Positive Shielding Angle The shielding angle formed when the shield wire is located above and inside of the area occupied by the outermost conductors. 2.13 Rolling Sphere Method A simplified technique for applying the electrogeometric theory to the shielding of substations. The technique involves rolling an imaginary sphere of prescribed radius over the surface of a substation. The sphere rolls up and over (and is supported by) lightning masts, shield wires, fences, and other grounded metal objects intended for lightning shielding. A piece of equipment is protected from a direct stroke if it remains below the curved surface of the sphere by virtue of the sphere being elevated by shield wires or other devices. Equipment that touches the sphere or penetrates its surface is not protected. 3

2.14 Shielding Angle (A) (Of shield wires with respect to conductors): The angle formed by the intersection of a vertical line drawn through a shield wire and a line drawn from the shield wire to a protected conductor. The angle is chosen to provide a zone of protection for the conductor so that most lightning strokes will terminate on the shield wire rather than on the conductor. (B) (of a lightning mast): The angle formed by the intersection of a vertical line drawn through the tip of the mast and another line drawn through the tip of the mast to earth at some selected angle with the vertical. Rotation of this angle around the structure forms a coneshaped zone of protection for objects located within the cone. The angle is chosen so that lightning strokes will terminate on the mast rather than on an object contained within the protective zone so formed. 2.15 Shield Wire (Overhead Power Line or Substation) A wire suspended above the phase conductors positioned with the intention of having lightning strike it instead of the phase conductor(s). 2.16 Stepped Leader Static discharge that propagates from a cloud into the air. Current magnitudes that are associated with stepped leaders are small (on the order of 100 A) in comparison with the final stroke current. The stepped leaders progress in a random direction in discrete steps from 10 to 80 m in length. It is not until the stepped leader is within striking distance of the point to be struck that the stepped leader is positively directed toward this point. 2.17 Striking Distance The length of the final jump between the downward stepped leader and the grounded structure, as the electric field in this gap exceeds the electrical breakdown strength. The length of the final jump is a function of the leader potential, the associated charge, the rate of change of electric field, and the geometry of the gap. The first peak return stroke currents of negative downward lightning flashes are reasonably correlated with the respective impulse charge values. 2.18 Surge Impedance The ratio between voltage and current of a wave that travels on a conductor. 2.19 Thunder The sound that follows a flash of lightning and is caused by the sudden expansion of the air in the path of electrical discharge. 4

2.20 Thunderstorm Day A day on which thunder can be heard, and hence when lightning occurs. 2.12 Thunderstorm Hour An hour during which thunder can be heard, and hence when lightning occurs. III. Types of strokes: There are a number of different types of lightning strokes. These include strokes within clouds, strokes between separate clouds, strokes to tall structures, and strokes that terminate on the ground. The positive and negative strokes terminating on the ground are the types of most interest in designing shielding systems and the following discussion will be confined to those types. (A) Stepped leaders The actual stroke development occurs in a two-step process. The first step is ionization of the air surrounding the charge center and the development of stepped leaders, which propagate charge from the cloud into the air. Current magnitudes associated with stepped leaders are small (in the order of 100 A) in comparison with the final stroke current (Wagner [B142]). The stepped leaders progress in a random direction in discrete steps from 10 to 80 m in length. Their most frequent velocity of propagation is about 0.05% the speed of light, or approximately 150 000 m/s (Anderson [B7]). This produces electric fields near ground with rise times on the order of 100 to 500 microseconds. Electric fields of 250 microseconds from switching surge overvoltages tend to produce the minimum electrical strength of large air gaps compared to 1.2/50 microsecond lightning overvoltages. It is not until the stepped leader is within striking distance of the point to be struck that the leader is positively diverted toward this point. Striking distance is the length of the last step of leader under the influence of attraction toward the point of opposite polarity to be struck. (B) Return stroke The second step in the development of a lightning stroke is the return stroke. The return stroke is the extremely bright streamer that propagates upward from the earth to the cloud following the same path as the main channel of the downward stepped leader. This return stroke is the actual flow of stroke current that has a median value of about 24 000 Ampere and is actually the flow of charge from earth (flat ground) to cloud to neutralize the charge center (Mousa and Srivastava [B109]). The velocity of the return stroke propagation is lower than the speed of light and varies with atmospheric conditions; an approximate value can be 10% of the speed of light (Rakov and Uman [B126]). The amount of charge (usually negative) descending to the earth from the cloud is equal to the charge (usually positive) that flows upward from the earth. Since the propagation velocity of the 5

return stroke is so much greater than the propagation velocity of the stepped leader, the return stroke exhibits a much larger current flow (rate of charge movement). The various stages of a stroke development are shown in Figure 2. Approximately 55% of all lightning flashes consist of multiple strokes that traverse the same path formed by the initial stroke. IV. Calculation: The calculation is carried out in various method like Fixed Angle Empirical Curves Whitehead s Electro-Geometric-Model Mousa s Electro-Geometric-Model Eriksson s Electro-Geometric-Model Razevig Method Out of which fixed angle is conventionally popular. Circular Sphere (Mousa s EGM) and Razevig are most commonly used methods these days. Let s see both of these methods. 4.1 Circular Sphere/ Rolling Sphere Method: Nomenclature used in the calculations when using mast protection: Symbol S H A W&C T Y Z L X D E J Description Sphere radius Mast height Bus height Horizontal distance from origin of sphere (OOS) to bus Maximum separation from mast to bus for protection Minimum phase to steel clearance Horizontal distance between OOS and line drawn between two masts Half the separation between two masts Maximum separation between two masts Elevation difference between mast and bus Elevation difference between mast and OOS Horizontal distance between OOS and mast 6

K P Q Diagonal distance between masts when four masts support the sphere Distance between masts when four masts support the sphere Distance between masts when three masts support the sphere GIVEN DATA Sr. no. Description Notations Unit Value 1 Nominal System Voltage Vs kv 220 2 System Frequency Fs Hz 50 3 Rated Lightning Impulse Withstand Voltage Vc kv 1050 4 Limiting Corona Gradient Eo kv/m 1500 5 Strikes on shield wire k --- 1 6 Types of conductor Single Moose ACSR 7 Diameter of conductor d m 0.03177 8 No. of conductor --- No. 1 9 Sub-Conductor Spacing 1 m 0 10 Heights of Installation above FGL A m 9 11 Heights of shield wire H m 18.2 CALCULATION OF DSLP BY CIRCULAR SPHERE PROTECTION FOR TRANFORMER I. FIND CORONA RADIUS :- R c ln ( 2 h ) V c = 0 R c E o Where, RC is the corona radius in meters ~ 0.164473265 H is the average height of the conductor in meters VC E0 is the allowable insulator voltage for a negative polarity surge having a 6 μs front in kilovolts (VC = the BIL for post insulators) is the limiting corona gradient; this is taken equal to 1500 kv/m Above Equation can be solved by trial and error using a programmable calculator. (An approximate solution can be obtained) 7

Hence, Rc 0.188085896 II. SURGE IMPEDANCES UNDER CORONA :- Where, H RC R Hence, is the average height of the conductor z s = 60 ln ( 2 h ) ln ( 2 h R c r ) is the corona radius (use Equation as appropriate) is the metallic radius of the conductor, or equivalent radius in the case of bundled conductors Zs = 387.8073 Ω III. PROTECTION BY MASTS :- I s = BIL 2.2 Z s Hence, Is = 5.9565671 ka Assuming, K = 1.2 S = 8 K I s 0.65 Hence, S = 30.62094984 C = S 2 (S A) 2 Hence, C = 21.68356744 Also, C = S - T Therefore, T = S - C T = 8.937382393 8

IV. MAXIMUM DISTANCE BETWEEN TWO MASTS FOR SIDE STROKE :- W = S 2 (S A) 2 W = 21.68356744 m Here, Y = 1m (Assumption) Therefore, Z = W - Y Z = 20.68356744 m Similarly, L = S 2 E 2 L = 22.57947313 m Hence, X = 2 x L X = 45.15894625 m V. MAXIMUM DISTANCE BETWEEN MASTS FOR VERTICAL STROKE SPHERE SUPPORTED BY FOUR MASTS :- D = H - A D = 9.2 m E = S - D E = 21.42094984 m J = S 2 E 2 J = 21.88116718 m 9

K = 2 x J K = 43.76233435 m P = K 2 P = 30.94464338 m Q = 37.89929328 m. However, Q shall not be Greater than X Thus, Condition is satisfied. 4.2 Razevig Method: 30 π Q = 2 cos( 180 ) J Nomenclature for DSLP protection by Razevig Method for Transformer Protection Symbol Description Unit h Height of Lightning Spikes m hx Height of Live part to be Protected m ho Midway Point Protective Height Between Two LM's m P Coefficient for the LM Height - s Allowable Distance Between Two LM's m bx Midway Point Protective Distance Between Two LM's m Given data remains the same as used in above example. CALCULATION OF DSLP BY RAZEVIG METHOD FOR TRANFORMER PROTECTION I. GIVEN DATA: Height of Lightning Spikes (h) = 18.2 m Height of Live Part to be Protected (hx) = 5.5 m 10

II. FORMULAE S USED: I. Protective Radius (rx):- If, hx <= (2/3) h and h > 30m:- r x = 1.5h (1 h x 0.8h ) P m If, hx <= (2/3) h and h <= 30m:- r x = 1.5h (1 h x 0.8h ) m We use Second Formula as that Satisfies Our Condition Therefore, rx = 16.9875 II. Co-efficient for the Lightning Mast Height :- For h > 30m P = 5.5 h m For h <= 30m P = 1 m III. Allowable Distance Between Two LMs :- S = 7 x ha x P m ha = 12.7 m ( Where ha = h - hx ) Hence, S = 88.9 m (Allowable) Actual Distance between Two LMs:- S = 24.42 IV. Midway Point Protective Height (Ho) and Midway Point Protective Distance (bx) :- h o = h ( 7 P ) ho = 14.71142857 11

If hx < (2/3) ho and ho > 30 m:- b x = 1.5 h o (1 h x 0.8 h o ) P If hx > (2/3) ho and ho < 30 m:- b x = 1.5 h o (1 h x 0.8 h o ) If hx > (2/3) ho and ho < 30 m:- b x = 0.75 h o (1 h x h o ) In our case hx = 9 > (2/3) 14.711 and 14.711 < 30 V. Conclusion: Hence, b x = 1.5 14.71142857 (1 b x = 11.75464 m 9 0.8 14.71142857 ) Direct stroke lightning protection calculation was henceforth done to prevent the system from surge and protect the equipment from damage. It s evidence that all devices are inside the protected zones. Thus, the calculated heights of the masts are satisfactory. Obviously, if the mast heights were decrease, the protective zones would be narrowed. However, since those figures, if the protective zones were narrowed, they couldn t cover whole devices. Therefore, the economical criterion is satisfied. In addition, if there are some masts with certain heights and the user wants to use those masts for lightning protection, the user can use this method to calculate the required mast heights. The heights of existing masts are then compared with the calculated mast heights. The user will know that which installed masts can be salvaged and which masts must be freshly installed. REFERENCES [1] IEEE Guide for Direct Lightning Stroke Shielding of Substations. IEEE Std 998 1996, 20 Dec 1996. [2] Le Viet Dung and K. Petcharaks, Lightning Protection Systems Design for Substations by Using Masts and Matlab World Academy of Science, Engineering and Technology International Journal of Mathematical, Computational, Physical, Electrical and Computer Engineering Vol:4, No:5, 2010. [3] Professor Razevig, High Volatge Engineering. 12