Data Bulletin. SEPAM 49RMS Application Note Protection for Motor Applications Class Number SEPAM 49RMS Protection for Motor Applications

Similar documents
Thermal overload. Operation

Stator Thermal Time Constant

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

INSTRUCTION MANUAL FOR MM10 Relay

WeatherWatcher ACP. Astronomers Control Panel (V4 or >) Ambient Virtual Weather Station (Pro or Internet editions) ASCOM platform v4.

Motor-CAD combined electromagnetic and thermal model (January 2015)

Periodic Inspection and Testing of Electrical Installations Sample Test ( ) Version 1.3 July 2018

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

ADVANCED THERMAL MOTOR PROTECTION USING DIGITAL RELAYS

TEMPERATURE EFFECTS ON MOTOR PERFORMANCE

XM1 Motor Protection Relay. Manual XM1 (Revision B)

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

An Introduction to Insulation Resistance Testing

MPR500 Motor Protection Relay User's Guide

Motor thermal protection function

Issued August DATA SHEET. 3VT5 MCCB up to 1600 A

3VT4 Molded Case Circuit Breakers up to 1000 A

Introduction to Synchronous. Machines. Kevin Gaughan

Encoders. Understanding. November design for industry: Help clean up the ocean. Horizon failure forensics

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Selecting the current rating for equipment

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

SERVOSTAR S- and CD-Series Regeneration Requirements

TeSys circuit-breakers

Fault Calculation Methods

CHV Series Vector Control Inverter Options. Operating Instructions for Tension Control Card

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy

Peltier Application Note

BioMechanics and BioMaterials Lab (BME 541) Experiment #5 Mechanical Prosperities of Biomaterials Tensile Test

SUBJECT TO CHANGE WITHOUT NOTICE

EE 6501 POWER SYSTEMS UNIT I INTRODUCTION

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

Thermal Analysis & Design Improvement of an Internal Air-Cooled Electric Machine Dr. James R. Dorris Application Specialist, CD-adapco

90 MCB range Modular circuit breakers for circuit protection

Accurate Joule Loss Estimation for Rotating Machines: An Engineering Approach

90 MCB MODULAR CIRCUIT BREAKERS FOR CIRCUIT PROTECTION

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

6 INCH W X 5-3/4 INCH D X 8-3/8 INCH H

TeraLED. Thermal and Radiometric Characterization of LEDs. Technical Specification.

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Dynamic Behavior of Three phase Inductions Motors as Loads in an Electric Power System with Distributed Generation, a Case of Study.

Intel Stratix 10 Thermal Modeling and Management

GENERATOR INTERCONNECTION APPLICATION

400 Volts, 50HZ 480 Volts, 60HZ 600 Volts, 60HZ TECHNICAL REFERENCE MANUAL

Lesson 17: Synchronous Machines

Issued August DATA SHEET. 3VT3 MCCB up to 630 A

CiA Draft Standard Proposal CANopen. Application Profile for Lift Control Systems. Part 2: Virtual device definitions

Energy saving in electromechanical equipment with power coefficient correction. Dimitris Al. Katsaprakakis Aeolian Land S.A.

Current protection I 2 t long-time protection

user's manual nx frequency converters resolver option board opt-bc

i.mx 6 Temperature Sensor Module

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

MetConsole AWOS. (Automated Weather Observation System) Make the most of your energy SM

6 Chapter 6 Testing and Evaluation

Third harmonic current injection into highly saturated multi-phase machines

Selection of precision micro drives

Loss analysis of a 1 MW class HTS synchronous motor

Selection of precision micro drives

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Parameter Prediction and Modelling Methods for Traction Motor of Hybrid Electric Vehicle

SKF actuators available for quick delivery. Selection guide

Chapter 21. Harmonic Analysis

Design Guidelines for SFT Chipsets Assembly

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

Loss of excitation protection function (40Z)

Renewables and the Smart Grid. Trip Doggett President & CEO Electric Reliability Council of Texas

EDSA IEC 909 SHORT CIRCUIT ANALYSIS

Module 3 : Sequence Components and Fault Analysis

Analyzing Accuracy of a Battery Fuel Gauge System

3- BASICS. YTransformation. for balanced load. \V ab 120 = \V bc. \V ab 240 = \V ca \I a 120 = \I b \I a 240 = \I c V ab I a

Electric Machines I Three Phase Induction Motor. Dr. Firas Obeidat

LAB REPORT: THREE-PHASE INDUCTION MACHINE

Energy. This provides a practical measure of the usefulness of a machine. The useful energy transfer in a generator can be represented by:

6) Motors and Encoders

Multiphysics Modeling

CHAPTER 3 ENERGY EFFICIENT DESIGN OF INDUCTION MOTOR USNG GA

ALPS. Advanced Line Protection System

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Cooling Water Flow Regulator

Reactive Power Solutions

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

Prince Sattam bin Abdulaziz University College of Engineering. Electrical Engineering Department EE 3360 Electrical Machines (II)

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

Single Phase Motors Technical Datasheets

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver. Last Updated 12/14/2004

DYNAMIC LOAD COMPENSATION

7. Transient stability

TeraLED. Thermal and Radiometric Characterization of LEDs. Technical Specification.

FRENIC-Ace (C2) (Supplement to RS-485 User's Manual)

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

EAS 535 Laboratory Exercise Weather Station Setup and Verification

The Ordering Code for various standard model Recorders with an AC supply and without any additional options are as follows:

Transcription:

Data Bulletin 3000DB08 09/008 LaVergne, TN, USA SEPAM 49RMS Application Note Protection for Motor Applications Class Number 3000 SEPAM 49RMS Protection for Motor Applications Introduction Thermal protection of a motor can be accomplished by using various protection elements. ANSI 49 provides over-current protection based on the magnitude of current, both past and present. The SEPAM 49RMS element uses current magnitude to model the heating effect the current has on the motor windings. If a motor is equipped with RTDs (resistance temperature detectors), this information can be used by the 49RMS element. Motor circuits have two distinct protection requirements; one for the rotor and one for the stator (see Figure ). The SEPAM 49RMS function was designed to provide maximum protection, while allowing the motor its full capacity to start and run during adverse voltage conditions. The SEPAM 49RMS function has two distinct protection elements (Thermal Rate and Thermal Rate ; see Figure ) to match both damage curves of a motor (stator and rotor; see Figure ). Certain motors run extremely critical loads and must be allowed more acceleration time if the voltage is depressed. Figure : Motor Damage Curve 49ST

SEPAM 49RMS Application Note 3000DB08 09/008 Figure : Motor Tripping Curve 49MTC 000.00 Motor Tripping Curve Notes: ) If SF=.0 then set Es_ = 00%. Es0_ can be set to any value except 00%. t_trip_hot t_trip_cold_es0 Mtr_Withstd_Cold Es_ 3% TR->TR 337% Es_ 3% Mtr_Withstd_Hot T_ 7 min T_ 9 min 00.00 Es0_ 0% Es0_ 90% Tripping Time (sec) 0.00.00 0 0.5.5.5 3 3.5 4 4.5 5 5.5 6 6.5 7 I / Ib Default Settings Figure 3 provides a sample listing of the default settings for 49RMS protection using SFT84 software. Figure 3: SFT84 49 RMS Default Settings listed with 49RMS Spreadsheet Variables Es_ Es_ T_ T_ Es0_ Es_ Es_ T_ T_ Es0_ TR -> TR 008 Schneider Electric

3000DB08 09/008 SEPAM 49RMS Application Note Thermal Replica At every time step Δt, SEPAM calculates the thermal capacity used (E) by the motor, as seen from the formula below: E I Ib Δt T () t = E( t Δt) + E( t Δt) where: Ib is the full load amperes (FLA) of the motor T is the heating time constant These two parameters are set with the SFT84 software. Δt T The thermal capacity used increases due to the copper losses, directly related to I², decreases due to the temperature difference between the motor and its environment, directly related to thermal capacity (E). Suppose thermal capacity (E) starts at 0 value and the current (I) is continuously equal to the FLA (Ib). The value of E will rise exponentially up to 63% with the time constant T. Figure 4: Heat Rise and Cooling Time Constants MT049 E 0.63 MT040 E 0.36 0 T t 0 T t Heat rise time constant Cooling time constant Suppose the motor has been operated at FLA for a long time. The thermal capacity used is equal to 00%. When the motor is stopped, I=0. The thermal capacity used decreases exponentially from 00% to 36% with time constant T_ (Cooling time constant). Setting Thermal Rate : Es_, the Alarm Set Point Set this alarm value above the maximum continuous operation level. Example If: FLA= 6, SF=.5 Max current (based on known or theoretical max load) = 7A Then: Calculate Es_ as follows: Es_ = (7/6) = 08% therefore set to 0%, NOTE: This is an alarm set point that typically does not trip off the motor but notifies an operator of the overload condition. The SFT84 can be configured to close a non-tripping dry contact (for the power monitoring system). 008 Schneider Electric 3

SEPAM 49RMS Application Note 3000DB08 09/008 Setting Thermal Rate : Es_, the Trip Set Point Time-Current Characteristic The 49RMS element will trip when the thermal capacity used reaches the Es_ set point. Es_ and Es_ are equal to the square of SF, expressed in %. For example: If SF=.5 then Es_ and Es_ =.5² = 3 If SF=.00 then Es_ and Es_ =.00² = 00 Sometimes a motor manufacturer will provide heating and cooling time constants. Typically, when this information is supplied, the damage curves are also supplied. If the provided time constant does not protect the provided damage curve, decrease Es_ to a value below the SF until the 49RMS curve protects the damage curve. The tripping time of the 49RMS protection can be shown on a time-current coordination curve as for any over-current protection. However, the 49RMS protection has a hot and a cold curve; the usual over-current protection has only one tripping curve: For a usual over-current protection, the tripping time is not related to the initial value of the current as long as it is below the set point. For the 49RMS protection, the initial value of the current, if applied during a long time, will increase the thermal capacity used, E, as processed by the relay. The hot/cold determination is based on the present magnitude of E. If E > 50, the motor is considered "hot" and will follow the hot curve. If E < 50, it follows the cold curve. During actual operation, for a given value of current, the tripping time of the 49RMS protection will be somewhere between the cold and the hot curves, depending on the thermal capacity used by the motor prior to the overcurrent. For coordination studies, if a 5 element is not used, the cold curve should have proper selectivity with the upstream relay. Cold Curve Equation t T = Ln I Ib I Ib Es Hot Curve Equation t T = Ln I Ib I Ib Es Refer to Figure 5 for a graphical representation. 4 008 Schneider Electric

3000DB08 09/008 SEPAM 49RMS Application Note Figure 5: Graphical Representation of Hot and Cold Curves 0 cold curve hot curve service factor t / T 0. 0.0 0.00 0. 0 00 I / Ib Setting Thermal Rate : T_ Time Constant T_ should be set to protect the motor damage curve supplied by the motor manufacture in the same manner as an over current relay curve is set to protect the transformer damage curve. While "T" is technically a time constant, it behaves much like a 50/5 "time dial." The following tools can be used: SKM PowerTools CAPTOR Program 49RMS Spreadsheet on www.powerlogic.com On an old motor (common in retrofit situations), the stall time may need to be estimated if no data is available. It should first be stated that no motor can be properly protected without having the thermal damage curves. If these values do not exist, motor protection is an "educated guess." Sometimes a motor manufacture will provide heating and cooling time constants. Typically when this information is supplied, the damage curves are also supplied. If the provided time constant does not protect the provided damage curve, decrease Es_ to a value below the SF until the 49RMS curve protects the damage curve. 008 Schneider Electric 5

SEPAM 49RMS Application Note 3000DB08 09/008 Specific Case when SF = SF = means that the motor cannot accept more than 00% thermal capacity used. In this case the motor horsepower should have been determined based on some level of margin (so the normal load is below rated FLA). When E=00%, a trip will occur. When the SF=, Es0 cannot be equal to 00%. Setting Thermal Rate : T_ The following methods should be used to determine T:. Motor manufacture recommendation.. Learned based on Motor RTD feedback (SFT84 software setting: see next section). 3. If no other data is available, begin with T_= 3 x T_ and monitor to validate. Automatic Setting for T_, the Cooling Time Constant If the motor has stator RTDs, the relay can measure the cooling time constant T. Accuracy is better if ambient temperature is measured also. Follow these steps to set the function:. Connect the stator RTDs to the inputs, and 3 of the MET48 module number. At least one stator RTD must be connected to input.. Go to the SEPAM hardware menu of SFT84. 3. Set MET48 module number for motor/generator use. 4. If available, connect the ambient temperature sensor to input 8 of the MET48 module number. 5. Select the accounting for ambient temperature option in the 49RMS menu of the SFT84. A new value for T_ is estimated after each heating/cooling sequence. It is displayed on the front panel of the SEPAM unit and in SFT84 software when connected. It can also be accessed through the communication interface. The T_ setting of the thermal image protection can be automatically updated each time a new value for the cooling time constant is made available. For that purpose, select the "use learned cooling time constant T" option in the 49RMS menu of SFT84 software. The evolution of the measured value of the cooling time constant is of interest for predictive maintenance. 6 008 Schneider Electric

3000DB08 09/008 SEPAM 49RMS Application Note Setting Thermal Rate : Es0_ This setting is to protect cold stator damage curve provided by the motor manufacture. Set to 0% if a cold curve is not supplied. If a cold curve is supplied, adjust as necessary (using the spreadsheed tool) to protect cold curve. The impact on the thermal model of the motor is that the thermal capacity used by the motor cannot decrease below the setting of Es0_. From a mathematical point of view, the equation of the cold curve becomes: t T I Ib = Ln I Ib Es0 Es Figure 6: t/t with varying Es0 0 t / T 0. 0.0 0.00 Es0 = 0 Es0 = 0% Es0 = 40% Es0 = 60% Es0 = 80% hot curve 0. 0 00 I / Ib 008 Schneider Electric 7

SEPAM 49RMS Application Note 3000DB08 09/008 Effect of Thermal Rate, Es0_ Setting on Starts per Hour (66) Setting Thermal Rate Negative Sequence Current Motor manufactures also provide information about how many times a motor can be started hot and cold during a specified period of time. Typically the time period is one hour. SEPAM uses the 49RMS element settings to determine if a motor is in a hot state or cold state. If the calculated E (Thermal Capacity) is 50% or greater, the motor is considered hot. If the calculated E (Thermal Capacity) is less than 50%, the motor is considered cold. The relay uses user-determined values or default 49RMS settings to perform this calculation (even when the 49RMS element is turned off). The default Es0_ is 0%. If Es0_ is set to 50% or greater, the motor is always considered hot. The starts-per-hour then are limited to the number of hot starts that are programmed into the element. Keep this in mind when setting Es0_ > 50%. Typically this value is set to 0% or a small value and does not affect the starts-per-hour (66) function. On a new installation it should be feasible to obtain the hot/cold stator and rotor damage curves (see Figure ). On motors that have been in operation for some time, this may not be possible. The following settings are the same as Thermal Rate : Es_ = Es_ T_ = T_ Es0_ should be set to protect the cold rotor damage curve (provided by the motor manufacture) using coordination software (an example is SKM PowerTools for Windows ) or the Thermal Overload Excel spreadsheet (www.powerlogic.com). If you have not been given a cold rotor damage curve, set Es0_ = 00%. Set T_ to protect the hot rotor damage curve (or at least the hot stall time or, worst case, an estimate of the hot stall time). Es_ should be set to 300%. Since no real alarming capability for the timing is necessary to protect the rotor damage curve, this value is set at the maximum allowable value of 300%. The Transition Current (TR->TR) setting should be made to optimize protection for the last supplied damage point of the stator and the first damage point of the rotor. If a curve is not available, set this to 00% for Reduced Voltage (RV) applications and 300% for Full Voltage (FV) applications. Negative sequence currents directly affect the heating of the rotor. ANSI C37.96 states in part: A small-voltage unbalance produces a large negative-sequence current flow in either a synchronous or induction motor. The per unit (pu) negative-sequence impedance of either motor is approximately equal to the reciprocal of the rated voltage pu locked-rotor current. [For example, when] a motor has a locked-rotor current [of six times the rated value], it has a negative-sequence impedance of approximately 0.67 pu on the motor-rated input [kva] base. When voltages having 0.05 pu negativesequence component are applied to the motor, negative-sequence currents of 0.30 pu flow in the windings. Thus, a 5% voltage unbalance produces a stator negative-sequence current of 30% of full-load current. The severity of this condition is indicated by the fact that with this extra current, the motor may experience a 40% to 50% increase in temperature rise. 8 008 Schneider Electric

3000DB08 09/008 SEPAM 49RMS Application Note Negative sequence heating can be taken into account by the thermal image protection by increasing the current, Ieq, processed by the thermal image: where: Iph is the largest phase current I is the negative sequence current K is a setting factor K can be set to 0,.5, 4.5, or 9. Ieq = Iph + K.I With a typical setting K= 4.5, a negative sequence of 0.3 p.u. will increase the thermal capacity used by a ratio of 4.5*0.3 = 40%. Ambient Temperature General and special-purpose motors and industrial control equipment are rated for use in a maximum ambient environment of 40 C (04 F). When this value of the ambient temperature is exceeded, the thermal capacity used of the motor is increased by a ratio fa: T max 40 C fa = T max Tambient where: Tmax is the maximum temperature of the windings, according to the insulation class. The thermal image protection can take into account the ratio fa:. Connect the ambient temperature sensor to input 8 of the MET48 module number and select the accounting for ambient temperature option in the 49RMS menu of the SFT84 software.. Set the maximum temperature of machine (Tmax) in the 49RMS menu of the SFT84 software. NOTE: The protection will never allow values above for the fa ratio. This means, the thermal capacity used, as calculated by the thermal model, can be increased due to excessive ambient environment but never reduced. Summary To summarize: No motor can be properly protected without having thermal damage curves. Use both Thermal Rate and to provide proper protection of stator and rotor damage curves. The setting procedure should be thought of as curve fitting two, independent curves, one for the stator (Thermal Rate ) and one for the rotor (Thermal Rate ) to protect each damage curve. 008 Schneider Electric 9

SEPAM 49RMS Application Note 3000DB08 Data Bulletin 09/008 Schneider Electric USA 95 Tech Park Drive, Suite 00 LaVergne, TN 37086, USA -888-SquareD (-888-778-733) www.us.squared.com Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 008 Schneider Electric. All Rights Reserved.