Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance.

Similar documents
The Effects of Friction Factors on Capillary Tube Length

Pressure Distribution of Refrigerant Flow in an Adiabatic Capillary Tube

Mathematical Modelling for Refrigerant Flow in Diabatic Capillary Tube

Performance Comparison in Retrofit

Rating Charts of R-22 Alternatives Flow through Adiabatic Capillary Tubes

A dynamic model of a vertical direct expansion ground heat exchanger

Evaporation Heat Transfer Coefficients Of R-446A And R-1234ze(E)

Department of Mechanical Engineering, Kasetsart University, Si Racha Campus, Chonburi, Thailand *

GRAVITY EFFECT ON THE DISTRIBUTION OF REFRIGERANT FLOW IN A MULTI-CIRCUITED CONDENSER

Optimal operation of simple refrigeration cycles Part II: Selection of controlled variables

A Novel Model Considered Mass and Energy Conservation for Both Liquid and Vapor in Adsorption Refrigeration System.

Modelling of phase change for Two-Phase Refrigerant Flow inside Capillary Tube under Adiabatic Conditions

DETERMINATION OF R134A S CONVECTIVE HEAT TRANSFER COEFFICIENT IN HORIZONTAL EVAPORATORS HAVING SMOOTH AND CORRUGATED TUBES

Lecture 38: Vapor-compression refrigeration systems

Applied Thermodynamics for Marine Systems Prof. P. K. Das Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Heat Transfer of Condensation in Smooth Round Tube from Superheated Vapor

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

A PREDICTION MODEL FOR ADIABATIC AND DIABATIC CAPILLARY TUBES WITH ALTERNATIVE REFRIGERANTS. A Thesis YUPENG ZHANG

Boiling Heat Transfer and Pressure Drop of R1234ze(E) inside a Small-Diameter 2.5 mm Microfin Tube

A Numerical Estimate of Flexible Short-Tube Flow and Deformation with R-134a and R-410a

Experimental Study of Convective Heat Transfer and Thermal Performance in the Heat-Sink Channel with Various Geometrical Configurations Fins

Lecture 44: Review Thermodynamics I

MATHEMATICAL MODEL OF A VAPOUR ABSORPTION REFRIGERATION UNIT

FLOW CHARACTERISTICS OF HFC-134a IN AN ADIABATIC HELICAL CAPILLARY TUBE

Two-Phase Refrigerant Distribution in a Micro- Channel Manifold

Numerical Analysis Of Refrigerant Flow In Different Types Of Capillary Tubes Used R1270

ME 200 Exam 2 October 16, :30 p.m. to 7:30 p.m.

Feasibility Study of Replacing Steam Ejector with Liquid Ring Vacuum Pump (LRVP) in 210 MW Plant of Vijayawada Thermal Power Station (V.T.P.

(Refer Slide Time: 00:00:43 min) Welcome back in the last few lectures we discussed compression refrigeration systems.

Chapter 5. Mass and Energy Analysis of Control Volumes. by Asst. Prof. Dr.Woranee Paengjuntuek and Asst. Prof. Dr.Worarattana Pattaraprakorn

In Tube Evaporation Heat Transfer of Refrigerant Mixtures

Put sufficient ice cubes into water (1 M) and wait for equilibrium (both exist) (1 M)

THE ENERGY 68,SAVING TDVI. exible Combine Modular 24, 26, 28, 30, 32, 34, 36, 38, 40, 42, 44 HP 60, 62, 64, 66 HP

ME 200 Final Exam December 14, :00 a.m. to 10:00 a.m.

Onset of Flow Instability in a Rectangular Channel Under Transversely Uniform and Non-uniform Heating

Chemical Engineering 3P04 Process Control Tutorial # 1 Learning goals

InterPACKICNMM

ANSI/AHRI Standard (Formerly ARI Standard ) 2006 Standard for Performance Rating of Desuperheater/Water Heaters

ANALYSING MULTIVARIABLE CONTROL OF REFRIGERATION PLANT USING MATLAB/SIMULINK. C P Underwood

THE CHARACTERISTICS OF BRAZED PLATE HEAT EXCHANGERS WITH DIFFERENT CHEVRON ANGLES

Composition Shift of a Mixed-Gas Joule-Thomson Refrigerator Driven by an Oil-Free Compressor

Characteristics of CO2 Transcritical Expansion Process

ME332 FLUID MECHANICS LABORATORY (PART II)

Exergy Analysis of Solar Air Collector Having W Shaped Artificial Roughness

Two mark questions and answers UNIT I BASIC CONCEPT AND FIRST LAW SVCET

c Dr. Md. Zahurul Haq (BUET) Thermodynamic Processes & Efficiency ME 6101 (2017) 2 / 25 T145 = Q + W cv + i h 2 = h (V2 1 V 2 2)

R32 Heat Transfer Coefficient During Condensation In A Mini-Channel Multiport Tube

Modification In Charging Composition In Order To Arrive At Desired Circulation Composition In The Context Of Sorption Compressor Based J-T Cooler

Simulation Of Compressors With The Help Of An Engineering Equation Solver

Dynamic Response Analysis of Start-up Transient in Air Conditioning System

Numerical Simulation on Flow and Heat Transfer in Oscillating Heat Pipes

Prediction of Chiller Power Consumption: An Entropy Generation

Performance Investigation on Electrochemical Compressor with Ammonia

On-Line Models for Use in Automated Fault Detection and Diagnosis for HVAC&R Equipment

An experimental investigation on condensation of R134a refrigerant in microchannel heat exchanger

INDIAN INSTITUTE OF TECHNOLOGY ROORKEE NPTEL NPTEL ONLINE CERTIFICATION COURSE. Refrigeration and Air-conditioning. Lecture-09 P-h Charts

EMPIRICAL MODEL OF A 11 kw (NOMINAL COOLING) R134a WATER-WATER HEAT PUMP

Glide Effect on Performance

Evaporation of nanofluid droplet on heated surface

FLOW BOILING HEAT-TRANSFER IN PLATE MICRO- CHANNEL HEAT SINK

Case 5 Manual Selection of Water Cooled Condenser and Water Cooler

Experimental Analysis of Wire Sandwiched Micro Heat Pipes

2012 Thermodynamics Division C

Heat transfer and pressure drop experimentation inside single minichannels

ME 354 THERMODYNAMICS 2 MIDTERM EXAMINATION. Instructor: R. Culham. Name: Student ID Number: Instructions

1 st Law Analysis of Control Volume (open system) Chapter 6

ME 200 Final Exam December 12, :00 a.m. to 10:00 a.m.

Design of a Refrigerator. Department of Aerospace and Mechanical Engineering. Abdallah Soliman. Masih Ahmed. Ryan Seballos. EMAE 355 Project 4

Condensation and Evaporation Characteristics of Flows Inside Three Dimensional Vipertex Enhanced Heat Transfer Tubes

Performance Characterization of Two Selected Refrigerants in a Flat-Plate Micro-Tube Condenser

Lecture 35: Vapor power systems, Rankine cycle

Performance Rating of Thermal Storage Equipment Used for Cooling

A VAPOR-PRESSURE-DRIVEN HEAT PIPE FOR SIDEWARD LONG-DISTANCE HEAT TRANSPORT

Solenoid valves Type EVR 2 g 40 NC/ NO New EVR 6 with Steel cover design

Introduction to Chemical Engineering Thermodynamics. Chapter 7. KFUPM Housam Binous CHE 303

Pressure drop during condensation of refrigerants in pipe minichannels

Compressible Gas Flow

10 minutes reading time is allowed for this paper.

MAE 320 HW 7B. 1e. For an isolated system, please circle the parameter which will change with time. (a) Total energy;

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 06, 2015 ISSN (online):

II/IV B.Tech (Regular) DEGREE EXAMINATION. (1X12 = 12 Marks) Answer ONE question from each unit.

HEAT TRANSFER CAPABILITY OF A THERMOSYPHON HEAT TRANSPORT DEVICE WITH EXPERIMENTAL AND CFD STUDIES

PARAMETER ESTIMATION BASED MODELS OF WATER SOURCE HEAT PUMPS HUI JIN. Bachelor of Science Shanghai Jiaotong University Shanghai, China 1992

Improved Refrigerant Characteristics Flow Predictions in Adiabatic Capillary Tube

The First Law of Thermodynamics. By: Yidnekachew Messele

COOLING TOWER MODEL IN MNR

BME-A PREVIOUS YEAR QUESTIONS

first law of ThermodyNamics

Heat Exchangers for Condensation and Evaporation Applications Operating in a Low Pressure Atmosphere

Artificial Neural Network Modeling of Heat Transfer in a Staggered Cross-flow Tube-type Heat Exchanger.

Minhhung Doan, Thanhtrung Dang

Nucleate boiling heat transfer coefficients of halogenated refrigerants up to critical heat fluxes

Investigations on Performance of an Auto-Cascade Absorption Refrigeration System Operating with Mixed Refrigerants

Tick the box next to those resources for which the Sun is also the source of energy.

Clausius Clapeyron Equation

THERMODYNAMICS, FLUID AND PLANT PROCESSES. The tutorials are drawn from other subjects so the solutions are identified by the appropriate tutorial.

Chapter 5. Mass and Energy Analysis of Control Volumes

Condensation of refrigerant R407C in multiport minichannel section

UNIT I Basic concepts and Work & Heat Transfer

ASPT Series. Multi-Position, Internal TXV. Air Handler 1½ to 5 Tons

Transcription:

Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance. M.A. Akintunde, Ph.D. Federal University of Technology, Department of Mechanical Engineering PMB 74, Akure, Ondo State, Nigeria. * E-mail: ajyinka@yahoo.com ABSTRACT The effects of various geometries of capillary tubes has been investigated by many researchers. Their studies were based on the coil diameters and lengths alone, with no particular attention placed on the effect of coil pitch. At present no information is available about the effects of serpentine coiled capillary tubes on refrigerator performance. This study examined the effects of pitches of both helical and serpentine coiled capillary tubes on the performance of a vapor compression refrigeration system. Several capillary tubes of equal lengths (.3 m) and varying pitches, coiled diameters, and serpentine heights were used. Both inlet and outlet pressure and temperature of the test section (capillary tube) were measured and used to estimate the coefficient of performance () of the system. The results show that, in the case of helical coiled geometries the pitch has no significant effect on the system performance but the coil diameter as already predicted by many researchers. In the case of serpentine geometries both pitch and height affects the system performance. Performance increases with both increase in the pitch and the height. Correlations were proposed to describe relationships between straight and coiled capillary tube and between helical coiled and serpentine coiled capillary tubes. The coefficient of correlations are:.9841 for mass flow rates of helical and serpentine with straight tubes;.9864 for corresponding s and.9996 for mass flow rates of serpentine and helical coiled tube. (Keywords: capillary tube, geometry, helical coil, serpentine coil,, correlations, refrigeration) INTRODUCTION In small refrigeration and air conditioning systems one of the commonly used expansion devices to control the flow rate of refrigerants is the capillary tube. This is a simple tube of a few millimeters internal diameter, usually ranging between.5 to mm (Stoecker and Jones 198). Although the device lacks active function (mechanical or electrical) to actively adjust to any sudden change in the load conditions, it is still in use as a result of its simplicity, low cost, and requirement of low compressor starting torque (Kim et al. ). The required length of capillary tube depends mostly on the size of the system. The required length has reported by Wei et al. (1) for small refrigeration systems, ranges from 4 to 5 mm. If this length is to be kept straight in any application (that is installation), a lot of space would be required. As a result, the capillary tubes are normally folded in various configurations, so as to reduce the required space. There are extensive data for adiabatic capillary tubes and reliable diagrams. Some of these can be found in the works of Bittle et al. (1998), ASHRAE (1994), Akintunde (4a) and Kim et al. (). Since the capillary tube is to be folded in order to reduce the required space, there is the need to study the effect of capillary tube geometry on the performance of refrigeration systems. Wei et al. (1) studied the performance of capillary tubes for R-47C refrigerant. In their study a total of nine capillary tubes were tested. The capillary tubes consisted of straight and coiled configurations. Their result was compared with the correlations proposed by Bittle et al. (1998) and ASHRAE (1994). The Pacific Journal of Science and Technology 84

The geometry of the capillary tubes used by Wei et al. (1) are: length (1 mm), internal diameter (1. mm) and two coiled diameters of 5 and 13 mm. Comparing the flow rate of the coiled configuration with that of straight capillary tube, for the same inlet and out let pressures, tube diameter and length, the mass flow rate decreases with decrease in coiled diameter. The decrease ratio which was evaluated as m coil /m straigth is relatively insensitive to change of inlet sub-cooling and inlet pressure for both R- and R-47C considered. Akintunde (4b) reported the performance of R- 1 and R-134a in capillary tubes for refrigeration systems. In his work, fifty-eight (58) capillary tubes of different geometries (5 straights and 8 coiled) made of copper-tubes were used. The straight tubes were of ten different lengths (ranges from 1.53 to.63 m) and five different internal diameters (ranges from.7 to 1.6 mm), while the coiled were of two straight lengths (1.53 and.3 m) with four different coiled diameters (5, 1, 15 and mm) but of the same internal diameter of 1.6 mm. It was shown in his results that a capillary tube of length.3 m with tube diameter not less than 1.1 mm and coiled diameter of at least 1 mm could be used for small refrigeration systems of capacities ranging between 8 to 1 kw. His results also indicated that mass flow rate decreases with coil diameter. The decrease of mass flow rate with coil diameter is a general trend and this can be justified from the works of Motta et al. (); Domanski (1994); Kim et al. (1998); and Akintunde (3, 4a). These works were focused on the length and coiled diameters of the capillary tubes only but none of them talk about the pitch of the coils. Also all the available data are for helical coiled geometries; there is none for serpentine geometries. Therefore, the objectives of the present work is to: investigate the effect of pitch of both helical and serpentine coiled capillary tubes on the performance of vapor compression refrigeration systems; and compare the effects of helical coiled with those of serpentine coiled, using R-134a as the working refrigerant as suggested by Akintunde et al. (6). MATERIALS AND METHODS A schematic diagram of the experimental apparatus is show in Figure 1. The apparatus consists of a vapor compression refrigeration cycle adapted to accommodate instruments and controls that allow for the study of expansion devices. Manual service valves allowed the isolation of the expansion device to be tested so that minimal refrigerate will not be lost when the test section is changed. It also allowed the control of mass flow rate so that critical flow condition would be maintained in the evaporator. Pressure and temperature were measured both upstream and downstream of the test section. Type T thermocouples calibrated within the range of o C to 1 o C were attached to the external surface of the tube (before and after the test section). Pressure transducers model R5a from Yellow Jacket, capable of measuring pressure between and kpa with mean uncertainty of ±1 Pa, were also installed down and upstreams of the test section. A refrigerant flow meter, model R7a, manufactured by Yellow Jacket, calibrated to a mean uncertainty of ±.% was used to measure the flow rate. These instruments were tested using a straight capillary tube of length.3 m, as predicted by Jung et al. (1999), Akintunde (4b) and Akintunde et al. (6) for a vapor compression refrigeration system of 1 kw capacity, operating under the conditions of 4 o C condensing temperature, 1.6 mm capillary inside diameter and evaporator temperature of 5 o C. The average flow rate was found to be.15 kg/s, which is about 5% above the predicted value of.1 kg/s. Table 1 shows the geometry of the test section used with all dimensions in (mm); d = coil diameter; p = pitch. Figure provides the illustrations. All measurements were carried out at steadystate conditions. According to Lee et al. (), Motta et al. (), and Akintunde (4b) from system start-up, 1 minutes were typically required for the capacity used in this investigation to establish steady-state condition and approximately 9 minutes elapsed between each measured point (operating condition). The purpose of installing a heater (adjustable) is to ensure critical flow in the test section so as to maintain a constant pressure in the evaporator. This will serve as control for the experimental procedure. The Pacific Journal of Science and Technology 85

Figure 1: Schematic Diagram of Experimental Set-up. Table 1: Geometries of Test Sections. d1 = 8 d = 1 d3 = 1 d4 = 16 d5 = Helical coiled P1 P P3 P1 P P3 P1 P P3 P1 P P3 P1 P P3 4 6 1 6 8 1 6 8 1 6 8 1 6 8 1 H1 = 8 h = 1 H3 = 1 h4 = 16 h5 = Serpentine coiled The Pacific Journal of Science and Technology 86

p d (a) Helical Coiled Capillary Tube. P h (b) Serpentine Coiled Capillary Tube. Figure : Illustrations of the Test Sections. It has been reported that the degree of subcooling enhances the Akintunde et al. (6); hence the degree of sub-cooling was kept constant at 5 o C throughout the investigation. RESULTS AND DISCUSSION The measured flow rate (using straight capillary tube) in this investigation falls within the results of Jung et al. (1999), Kim et al. (), and Akintunde (4a), this is a justification of the experimental procedure. The measured parameters pressure (P) and temperature (T) were used to estimate the coefficient of performance () which is the reflection of the capillary tube configurations. Figure 3 shows the variation of mass flow rate with pitch at different helical coil diameters; while Figure 4 shows corresponding variations of. Figures 5 and 6 are the corresponding figures for mass flow rate and for serpentine coiled capillary tubes. Variation of average s, for both helical and serpentine coiled, with d and h respectively are shown in Figure 7. As can be seen in Figures 3 and 4, there is no significant increase in both mass flow rate (m) and with increase in pitch. As the coiled diameter (d) increases there is a significant increase in both m and. These show that, for helical coiled capillary tubes, the effect of pitch on system performance is not pronounced. The Pacific Journal of Science and Technology 87

mass flow rate (g/s) 1 1 8 6 4 m P1 P P3 P1 P P3 P1 P P3 P1 P P3 P1 P P3 Coil pitch Figure 3: Variation of Mass Flow Rate with Coil Pitch. 5 4.5 4 3.5 3.5 1.5 1.5 P1 P P3 P1 P P3 P1 P P3 P1 P P3 P1 P P3 helical Coil pitch Figure 4: Variation of with Coil Pitch. mass flow rate (g/s) 1 1 8 6 4 m P1 P P3 P1 P P3 P1 P P3 P1 P P3 P1 P P3 pitch Figure 5: Variation of Mass Flow Rate with Serpentine Pitch. The Pacific Journal of Science and Technology 88

5 4.5 4 3.5 3.5 1.5 1.5 P1 P P3 P1 P P3 P1 P P3 P1 P P3 P1 P P3 Serpentine Coil Pitch Figure 6: Variation of with Serpentine Pitch..3.5. hc sc.15.1.5 8 1 1 16 d or h (mm) Figure V7: Variation i i f of average of f the h Coils with i hd and dh. h In Figures 5 and 6 both mass flow rate (m) and increases with both h and d. These show that the serpentine pitch has effects on the performance of the system. Since the performance is not significantly affected by pitch in the case of helical coiled, less space will be required for its installation, while in the case of serpentine coiled more space would be required. It can be said here that helical coiled can be used for small systems why serpentine coiled that required lot of space may not be suitable for large units. A correlation of mass flow rates of both helical and serpentine coiled with straight capillary tube under the same conditions is shown in Figure 8. A model was then developed between the mass ratio and both h and d. The model equation is given in Equations (1) and () for both helical and serpentine coiled capillary tubes respectively. (.9d + 4.7d + 48) 1 M cr = x (1) The Pacific Journal of Science and Technology 89

( 5.7h + 19.6h + 5.) 1 M sr = x () The corresponding model for ratios, with a coefficient of correlation of.9864 is shown in Equation (4) and Fig. 1. As shown in Fig. 8 correlations are.9973 and.9841 respectively for both helical and serpentine coiled tubes. Two corresponding model for mass ratios of serpentine to helical coil with either h or d is shown in Equation (3). The correlation coefficient is.9996, this is justified by Figure 9. M or M r r = = ( h 17h + 19) x1 5 5 ( d 17h + 19) x1 (3) =.4l or r r =.66d.66h (.4l ) (4) Furthermore, Figures 8 through 1 show that helical coiled is more reliable that serpentine coiled in small systems. mass ratios.1 msp/ms mhc/ms Poly. (mhc/ms) Poly. (msp/ms).1 Mcr =.9d² -.47d +.489.8 R² =.9973.6.4. Msr =.57h² -.196d +.5 R² =.9841 8 1 1 16 h or d (mm) Figure 8: Variation of Mass Ratios with h/d. The Pacific Journal of Science and Technology 9

.1.9.8 msp/mhc Poly. (msp/mhc) ratio of mass flow rates.7.6.5.4.3..1 Mr = -E-5h -.17h +.19 R =.9996 8 1 1 16 h or d (mm) Figure 9: Variation of Mass Flow Rate Ratios. ratios.4.3..1..19.18.17.16.15 r =.4e -.66d R =.9864 8 1 1 16 h or d (mm) Figure 1: Variation of Ratios. sp/hc Expon. (sp/hc) The Pacific Journal of Science and Technology 91

CONCLUSION This study investigated the performance of capillary tube geometries having R-134a as the working fluid. Two specific geometries were examined, these are helical and serpentine. The test results of the helical coiled agreed well with the results of Wei et al. (1) and Akintunde et al. (6). The obtained results show that, pitch variation has no significant effect on the system performance but the coiled diameter in the case of helical coiled. While, in the case of serpentine coiled both the height (h) and the pitch affects the performance. As both height and the pitch increases the performance increases. This indicated that more space will be required for the installation and hence this configuration will not be suitable for small systems. Correlations were proposed to evaluate the correlations between straight and coiled capillary tubes and between helical coiled and serpentine coiled capillary tubes. NOMENCLATURE d = helical coiled diameter (mm) h = serpentine height (mm) p = pitch (mm) = coefficient of performance m = mass flow rate (g/s) msp = mass flow rate for serpentine coiled (g/s) mhc = mass flow rate for helical coiled (g/s) ms = mass flow rate for straight tube (g/s) R = correlation coefficient Mcr = Msp = r = mhc ms msp ms serpentine helical ACKNOWLEDGEMENT The author hereby acknowledge the Federal University of Technology, Akure for providing the grant for this research. The grant reference number is URGC/MINOR/7/183. Thank you. REFERENCES 1. Akintunde, M.A. 3. Development of a Vapour Compression Refrigeration Systems Model Based on Balanced Points Between the Operational Units. Ph.D. Thesis in the Department of Mechanical Engineering, Federal University of Technology, Akure, Nigeria.. Akintunde, M.A. 4a. Theoretical Design Model for Vapour Compression Refrigeration Systems. ASME J. 73(5):1-14. 3. Akintunde, M.A. 4b. Experimental Investigation of the Performance of R-1 and R- 134a in Capillary Tubes for Refrigeration Systems. Nigerian J. Tech. Devel. 4:1-1. 4. Akintunde, M.A., Adegoke, C.O., and Papetu, O.P. 6. Experimental Investigation of the Performance of a Design Model for Vapour Compression Refrigeration Systems. West Indian Journal of Engineering. 8():8 87. 5. ASHRAE. 1994. ASHRAE Handbook Refrigeration. Chapter 44. American. Society for Heating, Refrigeration, and Air-Conditioning Engineering: Atlanta., GA. 6. Bittle, R.R., Wolf, D.A., and Pate, M.B. 1998. A Generalized Performance Prediction Method for Adiabatic Capillary Tubes. HVAC & R Res. l4:7-43. 7. Domanski, P.A., Didion, D.A., and Doyle, J.P. 1994. Evaluation of Suction Line - Liquid Line Heat Exchanger in the Refrigeration Cycle. Int. J. Refrig. 17:487-93. 8. Jung, D., Park, C., and Park, B. 1999. Capillary Tube Selection for HCFC Alternatives. Int. J. Refrig. :64-14. 9. Kim, Y.H., Kim, C.N., and Park, Y.M. 1998. Investigation on the Selection of Capillary Tube for the Alternative Refrigerant R-47C. J. Air- Cond. Refrig. Engin. 1:56-65. 1. Kim, S.G., Kim, M.S., and Ro, S.T.. Experimental Investigation of the Performance of R-, R-47c and R-41a in Several Capillary Tubes for Air-Conditioners. Int. J. Refrig. 5: 51-31. 11. Lee, J.H., Bae, S.W., Bang, K.H., and Kim, M.H.. Experimental and Numerical Research on Condenser Performance for R- and R-47C Refrigerants. Int. J. Refrig. 5:37-8. 1. Motta, S.F.Y., Parise, J.A.R., and Braga, S.L.. A Visual Study of R-44a/Oil Flow Through Adiabatic Capillary Tubs. Int. J. Refrig. 5:586-97. The Pacific Journal of Science and Technology 9

13. Stoecker, W.F. and Jones, J.W. 198. Refrigeration and Air Conditioning. nd ed. McGraw-Hill: Bogota. Colombia. 14. Wei, C.Z., Lin, Y.T., Wang, C.C., and Lev, J.S. 1. An Experimental Study of the Performance of Capillary Tubes for R-47c Refrigerant. ASHRAE Trans. 7:634-8. ABOUT THE AUTHOR Dr. M.A. Akintunde, graduated from Obafemi Awolowo University, Ile-Ife in 199 with first class honors in the Department of Mechanical Engineering. He studied Building Services Engineering at The Federal University of Technology, Akure (Nigeria). He completed his Master's degree in 1997 and Ph.D. in 4. He is a Senior Lecturer in Mechanical Engineering at the Federal University of Technology, Akure Nigeria. His research interest includes refrigeration and air-conditioning, energy systems, thermodynamics, and mechanics. SUGGESTED CITATION Akintunde, M.A. 8. Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance. Pacific Journal of Science and Technology. 9():84-93. Pacific Journal of Science and Technology The Pacific Journal of Science and Technology 93