QNET Experiment #05: HVAC System Identification. Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual

Similar documents
Quanser NI-ELVIS Trainer (QNET) Series: QNET Experiment #02: DC Motor Position Control. DC Motor Control Trainer (DCMCT) Student Manual

QNET Experiment #04: Inverted Pendulum Control. Rotary Pendulum (ROTPEN) Inverted Pendulum Trainer. Instructor Manual

QNET DC Motor Control

Experiment P43: RC Circuit (Power Amplifier, Voltage Sensor)

Experiment # 5 5. Coupled Water Tanks

Ideal Gas Law and Absolute Zero

Double Inverted Pendulum (DBIP)

Lab 1a Wind Tunnel Testing Principles & Drag Coefficients of Golf balls

YTÜ Mechanical Engineering Department

Rotary Motion Servo Plant: SRV02. Rotary Experiment #01: Modeling. SRV02 Modeling using QuaRC. Student Manual

SRV02-Series Rotary Experiment # 1. Position Control. Student Handout

Temperature Measurement and First-Order Dynamic Response *

Hands-on Lab 3. System Identification with Experimentally Acquired Data

Circular Motion and Centripetal Force

Activity P27: Speed of Sound in Air (Sound Sensor)

Exp. P-6 Blackbody Radiation

Sudden Expansion Exercise

3 Lab 3: DC Motor Transfer Function Estimation by Explicit Measurement

Old Dominion University Physics 112N/227N/232N Lab Manual, 13 th Edition

( ) ( ) = q o. T 12 = τ ln 2. RC Circuits. 1 e t τ. q t

RC Circuit Lab - Discovery PSI Physics Capacitors and Resistors

SOTM LAB: P16 OHM S LAW I. TEACHER NOTES & GUIDELINES TITLE OF LAB: Ohm s Law DEVELOPERS OF LAB:

Exercise 1: Capacitors

MASSACHUSETTS INSTITUTE OF TECHNOLOGY /6.071 Introduction to Electronics, Signals and Measurement Spring 2006

Magnetic Fields. Experiment 1. Magnetic Field of a Straight Current-Carrying Conductor

SECTION 1.2. DYNAMIC MODELS

Name Class Date. RC Circuit Lab

Activity 1: Investigating Temperature

LAB 3: Capacitors & RC Circuits

The purpose of this lab is to investigate phases of matter, temperature, and heat energy.

Lab 4 Motion in One-Dimension Part 2: Position, Velocity and Acceleration Graphically and Statistically (pre-requisite Lab3)

Rotary Motion Servo Plant: SRV02. Rotary Experiment #11: 1-DOF Torsion. 1-DOF Torsion Position Control using QuaRC. Student Manual

Simple circuits - 3 hr

PHYS320 ilab (O) Experiment 2 Instructions Conservation of Energy: The Electrical Equivalent of Heat

THERMAL RADIATION. The electromagnetic radiation emitted by a hot tungsten filament will be studied.

Lab 5 RC Circuits. What You Need To Know: Physics 212 Lab

15. Compare the result with the value you have taken above Compare the calculated pressure value with the actual pressure value that you have

Inverted Pendulum System

PHY222 - Lab 7 RC Circuits: Charge Changing in Time Observing the way capacitors in RC circuits charge and discharge.

Experiment 3. Electrical Energy. Calculate the electrical power dissipated in a resistor.

SRV02-Series Rotary Experiment # 7. Rotary Inverted Pendulum. Student Handout

Lab 3: Quanser Hardware and Proportional Control

Lab 10: DC RC circuits

Technical Explanation for Axial Fans

Coefficient of Friction Lab

Lab 5 RC Circuits. What You Need To Know: Physics 212 Lab

first name (print) last name (print) brock id (ab17cd) (lab date)

PHYSICS 122 Lab EXPERIMENT NO. 6 AC CIRCUITS

Physics 197 Lab 11: Spectrometer

EE 4443/5329. LAB 3: Control of Industrial Systems. Simulation and Hardware Control (PID Design) The Torsion Disks. (ECP Systems-Model: 205)

Photoluminescence Spectrometer (FLS980)

Impulse and Change in Momentum

RC Circuit (Power amplifier, Voltage Sensor)

MASSACHUSETTS INSTITUTE OF TECHNOLOGY Department of Physics 8.02 Spring 2003 Experiment 17: RLC Circuit (modified 4/15/2003) OBJECTIVES

4. Heat and Thermal Energy

NORTHERN ILLINOIS UNIVERSITY PHYSICS DEPARTMENT. Physics 211 E&M and Quantum Physics Spring Lab #4: Electronic Circuits I

Experiment P05: Position, Velocity, & Acceleration (Motion Sensor)

YTÜ Mechanical Engineering Department

Human Arm. 1 Purpose. 2 Theory. 2.1 Equation of Motion for a Rotating Rigid Body

Acceleration/Velocity/Displacement VIBRATION METER

TALLINN UNIVERSITY OF TECHNOLOGY, INSTITUTE OF PHYSICS 6. THE TEMPERATURE DEPENDANCE OF RESISTANCE

Blackbody Radiation EX-9920 ScienceWorkshop Page 1 of 8. Blackbody Radiation

THERMOCOUPLE CHARACTERISTICS TRAINER

Energy. This provides a practical measure of the usefulness of a machine. The useful energy transfer in a generator can be represented by:

One Dimensional Collisions 1 Fall 2018

Experiment P14: Collision Impulse & Momentum (Force Sensor, Motion Sensor)

Investigation #2 TEMPERATURE VS. HEAT. Part I

ECE3510 Lab #5 PID Control

SOLIDWORKS Simulation Time Based Thermal Stress

California University of Pennsylvania. Department of Applied Engineering & Technology. Electrical / Computer Engineering Technology

Measuring the time constant for an RC-Circuit

Calibration Routine. Store in HDD. Switch "Program Control" Ref 1/ Ref 2 Manual Automatic

Measurements & Instrumentation. Module 3: Temperature Sensors

Lab 12 - Conservation of Momentum And Energy in Collisions

Modern Physics Laboratory MP2 Blackbody Radiation

Lab 08 Capacitors 2. Figure 2 Series RC circuit with SPDT switch to charge and discharge capacitor.

EE 422G - Signals and Systems Laboratory

TEMPERATURE MEASUREMENT. GROUP 3 Noah Beauchamp Kyle Camacho Jack Connolly Curtis Yu

4.2.1 Current, potential difference and resistance

ASEN 2002 Experimental Laboratory 1: Temperature Measurement and an Blow Dryer Test

Fundamentals of Circuits I: Current Models, Batteries & Bulbs

Physics Lab 202P-4. Understanding Electric Potential NAME: LAB PARTNERS:

Charge to Mass Ratio of The Electron

EE 474 Lab Part 2: Open-Loop and Closed-Loop Control (Velocity Servo)

RC Circuits. Equipment: Capstone with 850 interface, RLC circuit board, 2 voltage sensors (no alligator clips), 3 leads V C = 1

Water terminal control solutions

Resistivity and Temperature Coefficients (at 20 C)

Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202

Activity P08: Newton's Second Law - Constant Force (Force Sensor, Motion Sensor)

Linear Experiment #11: LQR Control. Linear Flexible Joint Cart Plus Single Inverted Pendulum (LFJC+SIP) Student Handout

2.004 Dynamics and Control II Spring 2008

MECHATRONICS II LABORATORY Experiment #4: First-Order Dynamic Response Thermal Systems

This page intentionally left blank.

Experiment P26: Rotational Inertia (Smart Pulley)

Experiment B6 Thermal Properties of Materials Procedure

Experiment P30: Centripetal Force on a Pendulum (Force Sensor, Photogate)

LABORATORY INVESTIGATION

O P E R A T I N G M A N U A L

Calendar Update Energy of Charges Intro to Circuits Ohm s Law Analog Discovery MATLAB What s next?

Transcription:

Quanser NI-ELVIS Trainer (QNET) Series: QNET Experiment #05: HVAC System Identification Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual

Table of Contents 1. Laboratory Objectives...1 2. References...1 3. HVAC Plant Presentation...1 3.1. Component Nomenclature...1 3.2. HVAC Plant Description...2 4. Pre-Lab Assignments...3 4.1. Pre-Lab Assignment #1: Open-Loop Modelling...3 4.2. Pre-Lab Assignment #2: Estimating The Heater Gain And Time Constant...4 4.3. Pre-Lab Assignment #3: Estimating The Blower Gain And Time Constant...7 5. In-Lab Session...10 5.1. System Hardware Configuration...10 5.2. Software User-Interface...10 5.3. Estimate The Heater Steady-State Gain And Time Constant...11 5.4. Estimate The Blower Steady-State Gain And Time Constant...15 5.5. Estimate The Heater And Blower Deadband Voltages...18 Document Number: 576 Revision: 01 Page: i

1. Laboratory Objectives The objective of this experiment is to run open-loop tests on a Heating, Ventilation, and Air Conditioning (HVAC) plant in order to gain insights in the effects of heat radiation. The system dynamics are studied by collecting measurements that are used to perform system identification. The obtained model is required to design closed-loop controllers in subsequent experiments. Regarding Gray Boxes: Gray boxes present in the instructor manual are not intended for the students as they provide solutions to the pre-lab assignments and contain typical experimental results from the laboratory procedure. 2. References [1] NI-ELVIS User Manual. [2] QNET-HVACT User Manual. 3. HVAC Plant Presentation 3.1. Component Nomenclature As a quick nomenclature, Table 1, below, provides a list of the principal elements composing the Heating, Ventilation, and Air Conditioning (HVAC) Trainer system. Every element is located and identified, through a unique identification (ID) number, on the HVAC plant represented in Figure 1, below. ID # Description ID # Description 1 Heater / Halogen Lamp 2 Blower / Fan 3 Temperature Sensor 4 Chamber / Duct Table 1 HVAC Component Nomenclature Document Number: 576 Revision: 01 Page: 1

Figure 1 HVAC System 3.2. HVAC Plant Description The QNET-HVAC Trainer system consists of a pexiglass duct, or chamber, equipped with a heater on one end and a blower on the other. A thermistor is placed in between at the location in the chamber where the temperature is to be controlled. The heater is made of a 12- Volt halogen lamp. The blower is a 24-Volt variable-speed fan. Document Number: 576 Revision: 01 Page: 2

4. Pre-Lab Assignments This section must be read, understood, and performed before you go to the laboratory session. 4.1. Pre-Lab Assignment #1: Open-Loop Modelling The HVAC plant consists of two inputs, namely the heater and blower voltages, for one output, the chamber temperature. The system thermal resistance and capacitance are not known. Additionally, the heater and blower heatflow rate constants are also unknown. Therefore, system identification is required to model the dynamics of the plant. The thermodynamics theory shows that the behaviour of space heating can be approximated by the following first-order transfer function, G h (s), from heater voltage to chamber temperature difference: G h ( s ) T = c ( s ) = V ( ) h s K ss_h τ h s + 1 [1] where the difference with a constant ambient temperature is defined as: T c = T c T a [2] Likewise, it can also be shown that the chamber cooling dynamics due to air blowing can be approximated by the following simple-lag Laplace transfer function, G b (s), from blower voltage to chamber temperature difference: G b ( s ) T = c ( s ) = V ( ) b s K ss_b τ b s + 1 The HVAC model parameters and variables are defined in Table 2, below. Symbol Description Unit T a Ambient Temperature (Outside the Chamber) ºC T c Chamber Air Temperature ºC T c Chamber Temperature Difference ºC V h Heater Input Voltage V [3] Document Number: 576 Revision: 01 Page: 3

Symbol Description Unit V b Blower Input Voltage V K ss_h Heater Open-Loop Steady-State Gain ºC/V τ h Heater Open-Loop Time Constant s K ss_b Blower Open-Loop Steady-State Gain ºC/V τ b Blower Open-Loop Time Constant s s Laplace Operator rad/s t Continuous Time s Table 2 HVAC Model Nomenclature 4.2. Pre-Lab Assignment #2: Estimating The Heater Gain And Time Constant As defined in Equation [1], the HVAC system steady-state gain and time constant during heating, i.e. K ss_h and τ h, can be determined experimentally by analyzing the system openloop response to a step input. A typical first-order temperature response to a heater voltage step input is illustrated in Figure 2, below. The blower voltage is held constant at zero. Figure 2 Model Parameter Estimation From A First-Order Step Response During Heating Document Number: 576 Revision: 01 Page: 4

During the laboratory session you will obtain the system responses to different amplitudes, K v_h, of step input voltage to the heater. For each experimental step response, the following parameters, as shown in Table 3 and illustrated in Figure 2, should be measured: Symbol Description Unit t 0 Step Starting Time s T c_0 Starting Chamber Temperature ºC T c_ss Steady-State Chamber Temperature ºC Table 3 First-Order Step Response Parameters The time parameters presented in Figure 2, above, are characterized below such that t 1τ is defined by: t τ = t 0 + τ h [4] t 2τ by: t 2 τ = t 0 + 2 τ h [5] and t 3τ by: t 3 τ = t 0 + 3 τ h [6] 1. Applying the theory associated with first-order systems, determine the chamber temperatures T c_1τ,t c_2τ, and T c_3τ, obtained at the times, t 1τ,t 2τ, and t 3τ, respectively. This is illustrated in Figure 2, above. The expressions obtained for T c_1τ,t c_2τ, and T c_3τ should be functions of T c_0 and T c_ss. Typically, the time response of a first-order system subject to a step input of size K v_h can be described as follows (if t t 0 ): [s1] where the steady-state value can be expressed as: [s2] Document Number: 576 Revision: 01 Page: 5

Solution (continued): Therefore according to Equation [s1], the chamber temperature T c_1τ obtained at time t = t 1τ, i.e. T c ( t 1τ ), can be determined as follows: [s3] Likewise the chamber temperature T c_2τ obtained at time t = t 2τ,i.e.T c (t 2τ ), can be expressed as: [s4] Lastly, the chamber temperature T c_3τ determined as: obtained at time t = t 3τ,i.e.T c (t 3τ ), can be [s5] 2. As illustrated in Figure 2, above, the measurement times t 1τ,t 2τ, and t 3τ can be estimated by locating T c_1τ, T c_2τ, and T c_3τ, respectively, on the experimentally-obtained step response plot and by measuring their corresponding time values. As induced by Equations [4], [5], and [6], each measurement time results in an estimate of the heater open-loop time constant τ h. Express the resulting time constant estimates, namely τ h1, τ h2, and τ h3, as functions of t 0 and the measurement times t 1τ, t 2τ, and t 3τ, respectively. Using Equation [4], the first estimate of τ h, i.e. τ h1, can be expressed as follows: [s6] Likewise using Equation [5], the second estimate of τ h, i.e. τ h2, can be calculated by the following: [s7] Lastly using Equation [6], the third estimate of τ h, i.e. τ h3, can be determined such as: [s8] 3. A valid estimation of the heater time constant τ h is assumed to be the average of the three Document Number: 576 Revision: 01 Page: 6

previously-obtained estimates τ h1, τ h2,andτ h3. Determine the expression for τ h function of τ h1, τ h2, and τ h3. as a Taking the arithmetic mean of τ h1, τ h2,andτ h3 results to the following estimate for the heater open-loop time constant: [s9] 4. Finally determine the expression for K ss_h as a function of K v_h, T c_0, and T c_ss. Using Equation [s2], the heater steady-state gain can be calculated according to: [s10] 4.3. Pre-Lab Assignment #3: Estimating The Blower Gain And Time Constant As defined in Equation [3], the HVAC system steady-state gain and time constant during blowing, i.e. K ss_b and τ b, can also be determined experimentally by analyzing the system open-loop response to a step input. A typical first-order temperature response to a blower voltage step input is illustrated in Figure 3, below. The heater voltage is held constant at zero. Document Number: 576 Revision: 01 Page: 7

Figure 3 Model Parameter Estimation From A First-Order Step Response During Blowing During the laboratory session you will obtain the system responses to different amplitudes, K v_b, of step input voltage to the blower. For each experimental step response, the same parameters as those shown in Table 3 and illustrated in Figure 3, should be measured. However in this case, the time parameters presented in Figure 3, above, are characterized below such that t 1τ is defined by: t τ = t 0 + τ b [7] t 2τ by: t 2 τ = t 0 + 2 τ b [8] and t 3τ by: t 3 τ = t 0 + 3 τ b [9] 1. Following a reasoning similar to the one previously detailed in Pre-Lab Assignment #2, derive a way to estimate the blower open-loop time constant τ b. Hint: τ b should result as the average of three different experimental estimates τ b1, τ b2,andτ b3, which will be expressed as a functions of t 0 and t 1τ, t 2τ, and t 3τ, respectively. Document Number: 576 Revision: 01 Page: 8

In agreement with Equation [3], the time response of a first-order system subject to a step input of size K v_b can be described as follows (if t t 0 ): [s11] where the steady-state temperature value can be expressed as: [s12] As described in Pre-Lab Assignment #2, calculating the chamber temperatures T c_1τ, T c_2τ, and T c_3τ, obtained at the times, t 1τ,t 2τ, and t 3τ, leads to Equations [s3], [s4], and [s5], respectively. Then reporting T c_1τ,t c_2τ, and T c_3τ on the experimentally-obtained step response plot, as illustrated in Figure 3 above, gives an estimation of the measurement times t 1τ, t 2τ, and t 3τ, respectively. Then using Equation [7], the first time constant estimate, τ b1, is given by: [s13] Likewise using Equation [8], the second time constant estimate, τ b2, can be expressed as follows: [s14] Lastly using Equation [9], the third estimate of τ b, τ b3, can be determined such as: [s15] Taking the arithmetic mean of τ b1, τ b2,andτ b3 results to the following final estimate for the blower open-loop time constant: [s16] Document Number: 576 Revision: 01 Page: 9

2. Finally derive an expression for K ss_b as a function of K v_b, T c_0, and T c_ss. Using Equation [s12], the blower steady-state gain can be calculated according to: [s17] 5. In-Lab Session 5.1. System Hardware Configuration This in-lab session is performed using the NI-ELVIS system equipped with a QNET- HVACT board and the Quanser Virtual Instrument (VI) controller file QNET_HVAC_Lab_05_Sys_ID.vi. Please refer to Reference [2] for the setup and wiring information required to carry out the present control laboratory. Reference [2] also provides the specifications and a description of the main components composing your system. Before beginning the lab session, ensure the system is configured as follows: QNET HVACT module is connected to the ELVIS. ELVIS Communication Switch is set to BYPASS. DC power supply is connected to the QNET HVAC Trainer module. The 4 LEDs +B, +15V, -15V, +5V on the QNET module should be ON. 5.2. Software User-Interface Please follow the steps described below: Step 1. Read through Section 5.1 and go through the setup guide in Reference [2]. Step 2. Open the VI controller QNET_HVAC_Lab_05_Sys_ID.vi shown in Figure 4. The default sampling rate for the implemented digital controller is 350 Hz. However, you can adjust it to your system's computing power. Please refer to Reference [1] for a complete system's description. The chamber temperature, directly sensed by the thermistor, is plotted on a chart as well as displayed in a Numeric Indicator and a Thermometer located in the Temperature (degc) front panel box. The values are in degrees Celsius. Run the LabVIEW VI (Ctrl+R) to initialize the open-loop controller. At this point both heater and blower voltages (i.e. V h and V b ) are set to zero and the Document Number: 576 Revision: 01 Page: 10

chamber temperature is read. The vertical toggle switch in the Input Signal Properties box allows you to choose between the heating or cooling process of the system. In heating mode, the blower voltage (V b ) is zero and the heater voltage (V h ) can be set by the user through the Vh Numeric Control. Likewise in cooling mode, the heater voltage is set to zero while the blower voltage is user-defined through the Vb Numeric Control. However, the green START push button should be pressed in order for both commanded voltages to be applied to the HVAC plant. With the open-loop control action active, the initially green START push button should now show as a red STOP button that you can trigger to pause the controller execution. Figure 4 Front Panel Used for the QNET-HVACT System Identification Laboratory 5.3. Estimate The Heater Steady-State Gain And Time Constant Step 3. First, select COOLING in the Input Signal Properties box by flipping as required the vertical toggle switch. Ensure that the Vb Numeric Control is set to more than 16 Volts and that the initially green START push button has been pressed. The fan Document Number: 576 Revision: 01 Page: 11

should now blow in order to initialize the system by bringing the chamber to ambient temperature. Step 4. Click on the red STOP button to stop the blowing once a steady-state temperature has been reached. Let the chamber air settle for about 20 seconds and reach ambient temperature. Step 5. Then, select HEATING in the Input Signal Properties box by flipping the toggle switch. Set the Vh Numeric Control to 1.5 Volts. Clear the chart by right clicking on it and selecting the Clear Chart context menu item. You can now start the step input test by pressing the green START push button, which will apply the desired voltages to the system. The halogen lamp should now be heating proportionally to V h and the chamber temperature should be rising. The settling time should be less than 600 seconds, so that the complete step response fits within the chart time scale. At this point, also stop the heater by pressing the red STOP button. DO NOT press EXIT and do not stop the VI. Step 6. Make a screen capture of the obtained step response plot once the response has reached steady-state and join a printout to your report. Your actual response should look similar to the theoretical temperature heating plot presented in Figure 2. Document Number: 576 Revision: 01 Page: 12

A typical open-loop temperature heating step response is shown in Figure 5, below. It has been obtained for a heater input voltage step of 3 Volts. Figure 5 Heating Step: V h = 3 V Step 7. Determine the characteristics of the obtained step response plot by using the Graph Palette located on top of the Chart top left corner. Fill up the following table (i.e. Table 4) by measuring the required data points from the actual plot and by carrying out the estimation procedure detailed in Pre-Lab Assignment #2. In Table 4, the first line presents the data from Step #1, which corresponds to a heater input voltage of 1.5 Volts (i.e. K v_h ). The second line of Table 4 is for an input step of 3.0 Volts, which is called Step #2. Determine the corresponding estimates for the heater steady-state gain, K ss_h, and time constant, τ h. Document Number: 576 Revision: 01 Page: 13

Step # K v_h [V] t 0 [s] T c_0 [ºC] T c_ss [ºC] T c_1τ [ºC] 1 1.5 125.0 15.8 38.2 29.9 2 3 5.0 20.5 65.0 48.5 Step # T c_2τ [ºC] T c_3τ [ºC] t 1τ [s] t 2τ [s] t 3τ [s] 1 35.1 37.1 325.0 438.0 480.0 2 58.8 62.8 145.0 290.0 378.0 Step # τ h1 [s] τ h2 [s] τ h3 [s] τ h [s] K ss_h [ºC/V] 1 200.0 156.5 118.3 158.3 14.9 2 140.0 142.5 124.3 135.6 14.8 Average Values: 146.9 14.9 Table 4 Heating Step Actual Response Characteristics And Parameter Estimation Step 8. Obtain a second step response (Step #2) for the heating process by repeating Steps 2 to 6, as described above, but with the Vh Numeric Control set to 3.0 Volts instead of 6 in Step #1. Step 9. From your experimental results from Step #1 and Step #2 in Table 4 above, take the average of the two estimates found for the heater steady-state gain, K ss_h, and time constant, τ h. What are your final estimated (i.e. average) values for K ss_h and τ h? Averaging the values found in Step #1 and Step #2 for K ss_h leads to the following final estimate for the heater steady-state gain:. [s18] Averaging the values found in Step #1 and Step #2 for τ h leads to the following final estimate for the heater time constant:. [s19] Step 10. Once your results are obtained, you can stop the VI by pressing the red EXIT button. Document Number: 576 Revision: 01 Page: 14

5.4. Estimate The Blower Steady-State Gain And Time Constant Step 11. Select HEATING in the Input Signal Properties box by flipping as required the vertical toggle switch. Set the Vh Numeric Control to 4.0 Volts. Start the LabVIEW VI (Ctrl+R) if it has been stopped and ensure that the initially green START push button has been pressed. The halogen lamp should now be on and heat up the inside of the chamber. This raises the chamber temperature and initializes the system before the cooling step. Step 12. Monitor the heating the chamber on the front panel. Be prepared to toggle the switch to COOLING once the chamber temperature is above 60 degrees Celsius. This will stop heating and start blowing/cooling step test. However beforehand, ensure that the Vb Numeric Control is first set to 14 Volts. Step 13. Once the temperature is above 60 C, first clear the chart by right clicking on it and selecting the Clear Chart context menu item. Then select COOLING in the Input Signal Properties box by flipping the toggle switch. The open-loop step input test is now started, by applying the desired voltages, V b and V h, to the system. The fan should now be blowing proportionally to V b and the chamber temperature should be dropping. The settling time should be less than 600 seconds, so that the complete step response fits within the chart time scale. At this point, also stop the blower by pressing the red STOP button. DO NOT press EXIT and do not stop the VI. Step 14. Make a screen capture of the obtained step response plot once the response has reached steady-state, which should be around ambient temperature, and join a printout to your report. Your actual response should look similar to the theoretical temperature cooling plot presented in Figure 3. Document Number: 576 Revision: 01 Page: 15

A typical open-loop temperature cooling step response is shown in Figure 6, below. It has been obtained for a blower input voltage step of 18 Volts. Figure 6 Cooling Step: V b = 18 V Step 15. Determine the characteristics of the obtained step response plot by using the Graph Palette located on top of the Chart top left corner. Fill up the following table (i.e. Table 5) by measuring the required data points from the actual plot and by carrying out the estimation procedure detailed in Pre-Lab Assignment #3. In Table 5, the first line presents the data from Step #1, which corresponds to a blower input voltage of 14 Volts (i.e. K v_b ). The second line of Table 5 is for an input step of 18 Volts, which is called Step #2. Determine the corresponding estimates for the blower steady-state gain, K ss_b, and time constant, τ b. Document Number: 576 Revision: 01 Page: 16

Step # K v_b [V] t 0 [s] T c_0 [ºC] T c_ss [ºC] T c_1τ [ºC] 1 14 5.0 61.5 25.3 38.7 2 18 0.5 62.5 20.3 35.9 Step # T c_2τ [ºC] T c_3τ [ºC] t 1τ [s] t 2τ [s] t 3τ [s] 1 30.4 27.1 30.0 80.0 162.0 2 26.2 22.4 18.0 39.0 75.0 Step # τ b1 [s] τ b2 [s] τ b3 [s] τ b [s] K ss_b [ºC/V] 1 25.0 37.5 52.3 38.3 2.6 2 17.5 19.3 24.8 20.5 2.3 Average Values: 29.4 2.5 Table 5 Blowing Step Actual Response Characteristics And Parameter Estimation Step 16. Obtain a second step response (Step #2) for the blowing process by repeating Steps 10 to 14, as described above, but with the Vb Numeric Control set to 18 Volts instead of 6 in Step #1. Step 17. From your experimental results from Step #1 and Step #2 in Table 5 above, take the average of the two estimates found for the blower steady-state gain, K ss_b, and time constant, τ b. What are your final estimated (i.e. average) values for K ss_b and τ b? Averaging the values found in Step #1 and Step #2 for K ss_b leads to the following final estimate for the blower steady-state gain:. [s20] Averaging the values found in Step #1 and Step #2 for τ b leads to the following final estimate for the blower time constant:. [s21] Step 18. Once your results are obtained, you can stop the VI by pressing the red EXIT button. Document Number: 576 Revision: 01 Page: 17

5.5. Estimate The Heater And Blower Deadband Voltages Step 19. Let us define V h_off and V b_off the heater and blower positive (i.e. upper limit) deadband voltages, respectively. Deadband, or deadzone, is chiefly due to nonlinearity in the system such as static friction, or electrical offset, and the like. Step 20. To determine V h_off experimentally, select HEATING in the Input Signal Properties box by flipping as required the vertical toggle switch and set the Vh Numeric Control to 0 Volts to start. Start the LabVIEW VI (Ctrl+R) if it has been stopped and ensure that the initially green START push button has been pressed. Both halogen lamp and fan should be off as their respective input voltages, V h and V b,are set to zero. Now slowly increase V h, by steps of 0.1 Volts, until the halogen lamp filament becomes on and turns orange. You can do so by using the increment/decrement button on the left side of the Vh Numeric Control. Wait for a few seconds between two increment steps to let the heater settle at the new input voltage. Stop incrementing as soon as the bulb starts switching on. Step 21. What is your measured heater deadband voltage? The measured heater deadband voltage, V h_off, should be close to: Step 22. To determine V b_off experimentally, set the Vb Numeric Control in the Input Signal Properties box to 0 Volts and flip the toggle switch to COOLING. Start the LabVIEW VI (Ctrl+R) if it has been stopped and ensure that the initially green START push button has been pressed. Both halogen lamp and fan should be off as their respective input voltages, V h and V b, are set to zero. Now slowly increase V b,by steps of 0.1 Volts, until the fan starts to turn. You can do so by using the increment/decrement button on the left side of the Vb Numeric Control. Wait for a few seconds between two increment steps to let the fan settle at the new input voltage. Stop incrementing as soon as the fan has started. Document Number: 576 Revision: 01 Page: 18

Step 23. What is your measured blower deadband voltage? The measured blower deadband voltage, V b_off, should be close to:. Step 24. Both V h_off and V b_off could be used in a control system scheme for deadband compensation. Step 25. Shut off the PROTOTYPING POWER BOARD switch and the SYSTEM POWER switch at the back of the ELVIS unit. Unplug the module AC cord. Finally, stop the VI by pressing the red EXIT button. Step 26. Before leaving the laboratory session, ensure that you have all the experimental results required for your lab report Document Number: 576 Revision: 01 Page: 19