SIM_ZONAL: A SOFTWARE TO EVALUATE THE RISK OF DISCOMFORT: COUPLING WITH AN ENERGY ENGINE, COMPARISON WITH CFD CODES AND EXPERIMENTAL MEASUREMENTS

Similar documents
Proceedings of CLIMA 2000 World Congress, Brussels, Belgium. Simplified Method for Indoor Airflow Simulation

Comparison of two equations closure turbulence models for the prediction of heat and mass transfer in a mechanically ventilated enclosure

IMPACT OF THE ATMOSPHERIC BOUNDARY LAYER PROFILE ON THE VENTILATION OF A CUBIC BUILDING WITH TWO LARGE OPPOSITE OPENINGS

ROOM AVERAGE VELOCITY EQUATION A TOOL TO IMPROVE DESIGN OF THERMAL COMFORT CONDITIONS

USING DESIGN OF EXPERIMENTS METHODS TO DEVELOP LOW ENERGY BUILDING MODEL UNDER MODELICA

Calculating equation coefficients

NUMERICAL MODELLING OF TEMPERATURE AND AIR FLOW DISTRIBUTION IN ENCLOSED ROOM

NUMERICAL SIMULATION OF THERMAL CONVECTION IN A CLOSED CAVITY IN THE PRESENCE OF A THIN HORIZONTAL HEATED PLATE

DEFINING THE PERFORMANCE OF THE DOUBLE SKIN FAÇADE WITH THE USE OF THE SIMULATION MODEL

ARE 3D HEAT TRANSFER FORMULATIONS WITH SHORT TIME STEP AND SUN PATCH EVOLUTION NECESSARY FOR BUILDING SIMULATION? Villeurbanne Cedex, France

VALIDATION OF THE ZONAL METHOD FOR THE CASE OF ISOTHERMAL AIRFLOW IN A RECTANGULAR CAVITY

A Numerical Investigation on Active Chilled Beams for Indoor Air Conditioning

Modelisation methods and data structuration induced for simulation codes

STUDY ON THE THERMAL PERFORMANCE AND AIR DISTRIBUTION OF A DISPLACEMENT VENTILATION SYSTEM FOR LARGE SPACE APPLICATION

BSE Public CPD Lecture Numerical Simulation of Thermal Comfort and Contaminant Transport in Rooms with UFAD system on 26 March 2010

THERMAL BUILDING MODELLING ADAPTED TO DISTRICT ENERGY SIMULATION

A Simulation Tool for Radiative Heat Exchangers

CFD as a Tool for Thermal Comfort Assessment

Modeling night-time ventilation in Stanford s Y2E2 building

Natural Ventilation. CFD modelling of a double-skin facade. Huw Birch. Supervisor: Abigail Hathway

Figure 1: Details of a cluster of buildings within the historical district of Cayenne, French Guyana.

MODEL REDUCTION APPLIED TO A HEATING FLOOR COUPLED WITH A BUILDING. Jean Jacques Roux Iolanda Colda Jean Brau

Study of a new concept of photovoltaic-thermal hybrid collector

NUMERICAL AND EXPERIMENTAL INVESTIGATIONS OF AIR FLOW AND TEMPERATURE PATTERNS OF A LOW VELOCITY DIFFUSER

Supply air window PAZIAUD : Comparison of two numerical models for integration in thermal building simulation

Object-oriented quasi-3d sub-zonal airflow models for energy-related building simulation

TURBULENCE MODELING OF AIR CIRCULATION IN AN ENCLOSURE WITH MULTIPLE OPENINGS AND LOCAL HEAT SOURCES

STUDY OF A PASSIVE SOLAR WINTER HEATING SYSTEM BASED ON TROMBE WALL

Study on Thermal Load Calculation for Ceiling Radiant Cooling Panel System

Institut national des sciences appliquées de Strasbourg GENIE CLIMATIQUE ET ENERGETIQUE APPENDICES

The energy performance of an airflow window

Cooling of Electronics Lecture 2

Transient Analysis of the Buoyancy Driven Flow in a Passive Solar System for Indoor Heating

International Journal of Scientific & Engineering Research, Volume 6, Issue 5, May ISSN

Prediction of Thermal Comfort and Ventilation Efficiency for Small and Large Enclosures by Combined Simulations

Atrium assisted natural ventilation of multi storey buildings

Numerical simulation of fluid flow in a monolithic exchanger related to high temperature and high pressure operating conditions

Increasing Energy Efficiency of HVAC Systems in Buildings Using Phase Change Material

USING AN INVERSE METHOD TO EVALUATE ENVELOPE THERMAL PROPERTIES

BES with FEM: Building Energy Simulation using Finite Element Methods

3D FULL PREDICTIVE THERMAL CHAIN FOR GAS TURBINE COMBUSTOR METAL TEMPERATURE

Building heat system sizing

Study of air curtains used to restrict infiltration into refrigerated rooms

EFFECT OF INTERNAL LONG WAVE RADIATION AND CONVECTION ON FENESTRATION SIMULATION

3D Modeling of urban environment taking into account the energy exchanges between the buildings and the atmosphere

EVALUATION OF THERMAL ENVIRONMENT AROUND THE BLIND ON NON-UNIFOM RADIANT FIELDS A CFD SIMULATION OF HEAT TRANSFER DISTRIBUTION NEAR THE BLINDS

Numerical Study of the Three-dimensional Flow in a Flat Plate Solar Collector with Baffles

Effect of moisture transfer on heat energy storage in simple layer walls

A RSM MODEL FOR THE PREDICTION OF HEAT AND MASS TRANSFER IN A VENTILATED ROOM

Air Diffusion Designing for Comfort

Ceiling Radiant Cooling Panels Employing Heat-Conducting Rails: Deriving the Governing Heat Transfer Equations

CHAPTER 7 NUMERICAL MODELLING OF A SPIRAL HEAT EXCHANGER USING CFD TECHNIQUE

NATURAL VENTILATION DESIGN FOR LOW-RISE BUILDINGS: COMPARISON BETWEEN A NODAL MODEL AND WIND TUNNEL TESTS

Coupled CFD-FE-Analysis for the Exhaust Manifold of a Diesel Engine

Principles and Applications of Building Science Dr. E Rajasekar Department of Civil Engineering Indian Institute of Technology, Roorkee

Numerical studies on natural ventilation flow in an enclosure with both buoyancy and wind effects

A Numerical Analysis of Indoor Thermal Environment and Human Thermophysiological Responses under Natural Ventilation S. Iizuka 1,*, T. Sakoi 2, T. Sai

USE OF CFD TOOL ANSYS FLUENT FOR FIRE SAFETY IMPROVEMENT OF AN INDOOR SPORTS ARENA

THERMAL TRANSMITTANCE OF MULTI-LAYER GLAZING WITH ULTRATHIN INTERNAL PARTITIONS. Agnieszka A. Lechowska 1, Jacek A. Schnotale 1

Numerical Analysis of Comfort and Energy Performance of Radiant Heat Emission Systems

CFD ANALYSIS OF TRIANGULAR ABSORBER TUBE OF A SOLAR FLAT PLATE COLLECTOR

PRESSURE BOUNDARY CONDITIONS IN MULTI-ZONE AND CFD PROGRAM COUPLING

INVESTIGATION OF THE PERFORMANCE OF COOLING PANELS: CEILING AND FLOOR PANElS.

CFD AND CONJUGATE HEAT TRANSFER ANALYSIS OF HEAT SINKS WITH DIFFERENT FIN GEOMETRIES SUBJECTED TO FORCED CONVECTION USED IN ELECTRONICS COOLING

NUMERICAL SIMULATION OF THE AIR FLOW AROUND THE ARRAYS OF SOLAR COLLECTORS

Modelling conjugate flow and heat transfer in a ventilated room for indoor

Chapter 3. CFD Analysis of Radiator

Analysis of the Cooling Design in Electrical Transformer

FLUID FLOW AND HEAT TRANSFER INVESTIGATION OF PERFORATED HEAT SINK UNDER MIXED CONVECTION 1 Mr. Shardul R Kulkarni, 2 Prof.S.Y.

Air Flow Modeling in a Mechanically Ventilated Room

2-D CFD analysis of passenger compartment for thermal comfort and ventilation

THE EFFECT OF A THIN FOIL ON THE HEAT LOSSES BEHIND A RADIATOR

Study on Stack Effect of Stairwell by Numerical Model of Leakage Flow through Gap of Door

MAE 598 Project #1 Jeremiah Dwight

THERMAL PERFORMANCE EVALUATION OF AN INNOVATIVE DOUBLE GLAZING WINDOW

The thermal conductance of collection tubes in geothermal energy systems

OPERATIVE TEMPERATURE SIMULATION OF ENCLOSED SPACE WITH INFRARED RADIATION SOURCE AS A SECONDARY HEATER

INFLUENCE OF THE POSITION OF EXHAUST AIR OPENINGS TO THE ROOM AIR FLOW STRUCTURE

Project #1 Internal flow with thermal convection

EXPERIMENT AND SIMULATION OF RADIANT/CONVECTIVE SPLIT FROM PASSENGER IN AIRCRAFT CABINS

Aalborg Universitet. CFD in Ventilation Design Nielsen, Peter Vilhelm. Publication date: 2009

Experimental Performance and Numerical Simulation of Double Glass Wall Thana Ananacha

ISO INTERNATIONAL STANDARD

Principles of Food and Bioprocess Engineering (FS 231) Problems on Heat Transfer

TOWARDS A MORE RELIABLE MODELLING OF NIGHT-TIME VENTILATION WITH BUILDING ENERGY SIMULATION MODELS

Numerical analysis of fluid flow and heat transfer in 2D sinusoidal wavy channel

Validation of IDA Indoor Climate and Energy

A NEW MODEL FOR ESTIMATING NEUTRAL PLANE IN FIRE SITUATION

CFD MODELLING OF CONVECTIVE HEAT TRANSFER FROM A WINDOW WITH ADJACENT VENETIAN BLINDS

Thermal environment in indoor spaces with under-floor air distribution systems: 2. Determination of design parameters (1522-

Model of Mass and Energy Transfer in a Clinker Rotary Kiln

Krantz. Radial slot outlet with square blade array RL-Q2... circular blade array RL-R2... Air distribution systems DS 4186 E 09.

EVALUATION OF FOUR TURBULENCE MODELS IN THE INTERACTION OF MULTI BURNERS SWIRLING FLOWS

International Journal of Advanced Engineering Technology E-ISSN

Aalborg Universitet. Empirical Test Case Specification Larsen, Olena Kalyanova; Heiselberg, Per Kvols. Publication date: 2006

Natural Convection Heat Loss from A Partly Open Cubic Enclosure Timothy N Anderson 1,a * and Stuart E Norris 2,b

Thermal Analysis & Design Improvement of an Internal Air-Cooled Electric Machine Dr. James R. Dorris Application Specialist, CD-adapco

THE BEHAVIOUR OF THE EXHAUST GASES EVICTED FROM THE SHIP FUNNEL

Theory & Applications of Computational Fluid Dynamics CFD

A Zone Model for Fast Verification of Release of Ultrafine Water Mist for Fire Extinction in Compartments

Transcription:

Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 SIM_ZONAL: A SOFTWARE TO EVALUATE THE RISK OF DISCOMFORT: COUPLING WITH AN ENERGY ENGINE, COMPARISON WITH CFD CODES AND EXPERIMENTAL MEASUREMENTS Etienne Wurtz 1, Francis Deque 2, Laurent Mora 1, Emmanuel Bozonnet 1 and Samuel Trompezinsky 2 1 LEPTAB, Université de la Rochelle, F-17042 La Rochelle cedex. 2 EDF Recherches et Développements, Département ADE B Les Renardières, Route de Sens, F-77818 Moret sur Loing. ABSTRACT The software Sim_Zonal is a tool for evaluating indoor temperature and air flow distributions for residential and office buildings. The aim of this EDF (Electricity of France) software developed in collaboration with LEPTAB (University of La Rochelle) is to evaluate comfort problems and specifically risks of discomfort (risk of draught, indoor gradient temperature, etc..) with taking into account the coupling with the building envelope. The objective is to obtain a simple software for rapid appraisals, which is complementary to the CFD codes. This version makes it possible for the users to achieve dynamical and parametric simulations with variable configurations of rooms, different emitters (electric heaters, heated or cooled floors, heated or cooled ceilings) and variable boundary conditions (meteorological conditions) with a one hour time step. The final aim is to calculate comfort criteria as PMV or UCRES (comfort criteria developed by CSTB). INTRODUCTION Sim_zonal is based on a rough partitioning of the room which is divided into a small number of "cells": they are rectangular parallelepipeds. (The number of cells is usually on the order of 10 to 100, compared to 100 000 or more for typical CFD calculations). The cells are coupled to the wall equations. Mass balance and heat balance equations are applied to the cells and the exchanges are calculated between them. It is an intermediate approach described in Inard et al. (1996), Musy (1999), Wurtz et al. (1999) and Wurtz et al. (2001) between one-node models (that consider a homogeneous temperature in each room, and, for that reason, do not permit to predict the thermal comfort in a room) and CFD models (that require great amount of simulation time). Sim_zonal can take into account plumes or jets with empirical laws. In low velocity domains, flow rates are calculated in respect to the pressure distribution. This airflow model is coupled with a building envelope model including the calculation of conduction through the walls, convection between inside wall surfaces and cells, and long-wave and short wave radiant interchange among the inside wall surfaces in Walton (1980). The zonal model is coupled with an energy engine in order to control the power of the emitters. These features allow assessing the risk of discomfort into a room. First, we present a graphical interface which is a very easy way to describe a simulation. This presentation shows the necessity to propose a low level of complexity is the tool has to be used by non specialists. The second part describes a comparison of Sim_zonal results with CFD codes predictions. As CFD tool, we use AIRPAK which is a dedicated version of FLUENT to the building field and which integers a zero-equation model for indoor airflow. To do this we study the cases of a heated floor and we propose some amelioration to get a better description of temperature field and air circulation. In the last part, we propose a comparison with experimental measurements in case of a room solicited by a fan cooler. First we describe how the fan cooler model has been built with experimental data and in a second time we present the first results obtained in a room and show what kind of results can be obtained with this intermediate approach. SIMULATION A graphical interface is used to describe the simulation. To explain possibilities of our software we propose to show the different steps that have to be done to describe a simulation. We first the grid density on each direction and the grid dimensions as indicated on Figure 1. The principle is to ask very few information because this software has to be used by non-specialists and the input concern the geometrical conditions but no physical variables are required. - 1415 1423 -

Figure 1: geometrical description The second table concerns types of building elements used (wall constitution, glazing) and their location in the simulation domain as described in Figure 2. A material file contains all description variables about a wall that means for example radiative and modal coefficient (conduction in a wall is described with Moore method). For this reason the user has only to choose the type of each wall, window or door and specify their location in the room. Figure 3: Integration of systems The last information required consists of precising external conditions which can be external temperature (given by a weather file) or another room with imposed temperature. As presented in Figure 4 temperatures have to be given both on walls and apertures and we have the possibility to put initial values to obtain rapidly stationary conditions. In each case all data are written in data files so an expert user has always the possibility to add more precise information directly in these ascii input files. That is also an easy way to make few modifications on a problem description without using the graphical interface. Figure 2: building elements Next step consists of describing solicitations inside a room. As indicated in Figure 3 the different possibilities of systems are an electric heater, heated or cooled floors or ceiling and fan coolers. There is also a possibility to integrate a heat source to take into account a computer or human presence for example. A specific model has been built for each component with again the principle to limit complexity of data and propose default values for non specialists. In the next chapter describing applications we present an example of specific model in case of a fan cooler and we describe how this model has been built with experimental data help. Figure 4: External conditions At this stage one can run the simulation. For that, as shows Figure 5, we use a file which contain weather data (solar radiation and air temperature), and heat or cool power calculated with another software based on a one node model (energy engine). Then we give simulation s period and with this approach, we need only a few minutes to describe one year simulation what is very interesting to characterize risk of discomfort in a room. - 1416 1424 -

Figure 6: Temperature field obtained with Airpack Figure 5: Weather data s choice and simulation s period After this global description which permits to understand the principle of this software we propose to present different results obtained by comparison with experimental and CFD results. APPLICATION Two kinds of results will be shown which concern at first a comparison with CFD results in case of a heated floor and after an experimental study about fan cooler influence. Comparison with CFD results Our objective consists to establish a validity domain of our models. For this reason we compare results given by a CFD code with our intermediate approach based on Sim_zonal. For the CFD approach we use Airpack, an element of FLUENT toolbox which objective is comfort characterization. Figure 6 presents what kinds of outputs are given by this software, here in case of temperature field. The description is finely detailed with more than 100 000 nodes but we have to be very careful with this kind of software. At first about the accuracy of results in a whole room because if results can be considered as valid in case of high velocity it s more difficult to trust results given by a CFD code when the airflow engine corresponds at natural ventilation effects. Another limitation of this approach is due to the fact that it s not realistic to give a PMV field in a local with more then 100 000 different values of PMV. This criterion has not been developed for that: The PMV is a unique variable calculated for a whole room in permanent conditions. For these reasons our simplified approach seems more reasonable even if we are not able to describe complex phenomena inside a room. In our case dimensions of the room are 4 m x 7.5 m x 2.5 m. The room contains 2 windows (2.5 m 2 ) and inlet and outlet have same dimensions (0.2 m x 1 m). Walls with windows and ceiling are solicited by external temperatures while others walls are in contact with heated locals. Boundary conditions are shown table 1. Table 1: Room solicitations Emitter power 1000W Outside temperature 5 C Inside temperature 20 C Mass airflow rate 0,5vol/h Inlet dimension 0,2x1,0m The first validation which has to be done is a comparison of global average temperature in the room for different heated floor powers. Table 2 shows that these differences are very small (The difference is always less then 0.2 degrees) that means the confirmation that energy balances are verified for both cases. Table 2: Average temperature in the room Average room temperature (SimZonal) Average room temperature (Airpak) P=500W 18,38 18,22 P=1000W 21,87 21,93 P=2000W 29,12 29,19 In a second time we have compared temperature of each zonal cell with average of temperatures given by AirPack. We can see Figure 7 that these differences are small excepted for the particular zones near inlets or windows. To understand the reasons of these differences we can compare mass airflow in the two cases (AirPack and Sim_zonal). Figure 8 shows the complexity of air circulation specially in the right part of the room. This kind of phenomena can t be described with our intermediate approach because the little cells number avoid to obtain air velocity values in specific places. - 1417 1425 -

Température ( C) 24 23.5 23 22.5 22 21.5 21 20.5 20 19.5 T ( C) SZ T ( C) Airpack Qv=0,83 P 1/2 Approximation 1,2* P 4 3 2 1 Qv 0,2* P+0,75 0 P -12-10 -8-6 -4-2-1 0 2 4 6 8 10 12-2 -3 0,2* P-0,75-4 19 18.5 Figure 10: linear pressure law Figure 7: Temperature comparison between AirPack and Sim_zonal approach Because of the very small pressure difference between two cells we need only a linear model at the middle of the curve to describe mass airflow that means we have obtained by this way a linear model. Nevertheless because of the too small pressure variation between two cells (less than 0.1 Pa), it seams that the linear coefficient should be higher as 1.2. For this reason we have realized a parametric study for different discharge coefficients values with a variation from 1.2 to 5. Figure 8: Mass airflow behavior obtained with AirPack Sim_Zonal Airpack 0.1500 PLAN X=1 (eo) Figure 9 presents which kind of results can be obtained with Sim_zonal. We have seen that air temperature correspond to the values given by CFD approach except where velocity is high and we obtain the same results when we consider velocity. In this case (heated flow) there are no specific laws to describe mass air flow engine and pressure law are used to calculate mass air flow at each interface level. Figure 9: Temperature and mass airflow obtained with Sim_zonal Where velocities are low air exchanges can be described with a pressure law issued from Bernoulli law like: Q v = k P n where k corresponds to a discharge coefficient and is usually fixed to 0.83 while n represents type of airflow (1 in laminar cases and 0.5 in turbulent). This non linear model isn t really adapted to our simplification approach because convergence difficulties may happen. For this reason, we have tested a linear approach in Musy (1999) as indicated Figure 10. Débits (Kg/s) 0.1000 0.0500 0.0000-0.0500-0.1000 0 0 1 0 2 0 0 1 1 1 2 1 0 2 1 2 2 2 Figure 11: Mass airflow comparison between Sim_zonal and AirPack Figure 11 shows that if we compare mass air flow obtained with Airpack, higher values of discharge coefficients permit to obtain a better air circulation representation. This result is interesting because it confirm a physical study about discharge coefficient. That example doesn t permit to propose any definitive conclusions but it indicates that the use of a pressure law needs to be very careful and avoid obtaining a complex airflow description. We have also shown that know that this coefficient should be function of meshing density because the different discharge coefficients characterize the global pressure lost in a room. For these different reasons we can conclude that a more precise study is necessary to determine the value of this coefficient in each interface function of meshing density, position in the room... - 1418 1426 -

0.15 0.1 0.05 Débit (Kg/s) 0-0.05-0.1-0.15 0 0 1 0 2 0 0 1 PLAN X=1 (eo) 1 1 2 1 0 2 1 2 C=1,2 C=2 C=3 C=5 Airpack Figure 12: Mass airflow evolution with increasing of pressure coefficient 2 2 Table 3: Conditions in room Penates Emitter Power (W) 1200 Control temperature ( C) 20 Wall temperature where near fan cool ( C) 15 Others walls temperatures ( C) 15,3 air flow rate (ach/h) 0,7 Inlet temperature( C) 20 A graphical tool, Figure 14, has been developed to represent geometric characteristics. We can see the global room meshing, presence of two windows, inlet and outlet and fan cooler disposition. Nevertheless, to keep a simple approach there is no interest to propose a complex proposition and the first results show that even with these simplifications we get a good approximation of mass airflow behavior with low air velocities. We ll see that the situation is different when airflow engine doesn t correspond to natural ventilation. Comparison with experimental results Figure 14: Geometrical disposition of Penates room Figure 13: 3D view of Penates experimental room The second case corresponds to evaluate influence of a fan cooler in a room and compare results with experimental data. The experimental study has been done in the EDF research center of Chatou and concerns a room called Penates described Figure 13 and solicited with a fan cooler. This cell is interesting for an experimental comparison because every boundary condition is measured or controlled. Table 3 presents every boundary condition in case of a 1200 W power fan cooler. Figure 15: Fan-cooler description To describe fan cooler influence we have first to build a specific model with experimental output mesured in Penates. Figure 15 present the kind of model which has to be used to describe the fan cooler in Wurtz (2000). The model has been simplified so the only empirical variable necessary is entrainment and initial mass flow. Mass and energy fluxes are then determined by conservations equations for this specific zone and linked to the equations set of the global model. To evaluate the model validity we have compared all measured variables around the fan cooler, table 4, with simulation s results. - 1419 1427 -

Table 4: Variables measured around the fan cooler Room temperature ( C) 20 Temperature outside fan cool ( C) 23,1 Temperature for Z=900mm ( C) 22,7 Plume width for Z=900mm (cm) 16 Mass air flow outside fan cool (Kg/s) 0,14 Mass air flow for Z=900mm (Kg/s) 0,31 Entrainment (%) 56 Observing that the entrainment value doesn t change very much with variation of heat power or fan mass air flow, we have chosen to impose a fixed value of entrainment: 60 %. A first validation consists to represent the average temperature variation obtained with Sim_zonal using heat power given by experimental study. Figure 16 shows that after 10 days (initialisation time) inside air temperature is higher than 19 C and after 3 weeks we obtain an average temperature exactly equal to 20 C which is the control value used in Penates. This simple case permits to confirm the energy balance conservation and we can study what happens inside the room. Température moyenne e C 21 19 17 15 13 11 9 7 5 0 100 200 300 400 500 600 700 800 Temps en heures Figure 16: Temperature evolution in the room We can see Figure 17 that we are able to describe with good precision temperature field in the room. The main error is due to the mass airflow which is going down due to the pressure model. In fact it should keep horizontal because of the hot temperature air above the fan cooler but for that a horizontal jet model should be paced at the top of the room. CONCLUSION In this paper we have presented software based on an intermediate method between CFD and one node model. The characteristic of this tool is mostly the description simplicity. In fact airflow models are often very complex and can only be employed by fluid mechanical specialists. This simplified approach should permit to architects or inhabitants to understand thermal and mass airflow behavior and consequently choose a heating system with a good knowledge of consequences on comfort characteristics. We have also shown the different simplifications which permit to obtain a very fast simulation tool while a correct choice of specific model permit to characterize comfort conditions in a room. REFERENCES Deque F., Delille S. and Dautin S., 1997 Réduction de systèmes linéaires par la méthode Moore : Application à la thermique du bâtiment, Rev. Gén. de Thermique, n 36. Inard C., Bouia H. and Dalicieux P., 1996, Prediction of temperature distribution in buildings with a zonal model, Energy and Building, 24, pp. 125 132. Musy M., 1999, Génération automatique de modèles zonaux pour la description du comportement thermo-aéraulique des bâtiments, Thèse de Doctorat, Université de La Rochelle. Walton G., 1980, A new algorithm for radiant exchange in room loads calculations, ASHRAE Transactions, Vol. 86 (2), pp.190-208. Wurtz E., 1995, Modélisation tridimensionnelle des transferts thermiques et aérauliques dans le bâtiment en environnement orienté objet, Thèse de Doctorat, Ecole Nationale de Ponts et Chaussées. Wurtz E., Nataf J.-M. and Winkelmann, F. W., 1999, Two- and three-dimensional natural and mixed convection simulation using modular zonal models in buildings, International Journal of Heat and Mass Transfer, 42, pp. 923 940. Wurtz E., Musy M. and Allard F., 2000, Modélisation d un panache d émetteur de chaleur pour le logiciel de simulation énergétique des bâtiments SPARK, Int. J Therm. Sci n 39(3) pp 433-441. Figure 17: Temperature field in a room in case of fan cooler presence Wurtz E., Deque F., Musy M. and Mora L., 2001, A thermal and air flow analysis tool using simplified models based on the zonal method, Clima 2000, Napoly. - 1420 1428 -