The Distortion Influence Simulation and Experimental Study of Human Body to High Voltage Power Frequency Electric Field

Similar documents
Numerical Calculation and Analysis on the Surface Electric Field Characteristics of Hot-Line Robot

Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings

Distortion of uniform electric field by human body of technical personal in substations with super high voltages kv

Influence of Grounding Material s Property on the Impulse Grounding Resistance of Grounding Grids

Computation of Electric Field and Human Body Induced Current under Overhead Transmission Lines

Mutual Resistance in Spicelink

General review: - a) Dot Product

ELECTRO MAGNETIC FIELDS

Model of the Electrostatic Discharge (ESD) Event

Mathematical Model of Tissue Characteristics in Human-Body Communication

EFFECT OF DIELECTRIC BARRIERS TO THE ELECTRIC FIELD OF ROD-PLANE AIR GAP

Electrical Impedance Tomography Based on Vibration Excitation in Magnetic Resonance System

Antennas and Propagation. Chapter 2: Basic Electromagnetic Analysis

Modeling Electric Field and Potential Distribution of an Model of Insulator in Two Dimensions by the Finite Element Method

3D modeling of Electrical Field and Electrical Potential in different contamination condition in Polymeric Insulator

Electric Field and Potential Distributions along Dry and Clean Non-Ceramic Insulators. Integrated Engineering Software - Website Links

Maxwell s Equations:

HIGH VOLTAGE TECHNIQUES Basic Electrode Systems

Flashover Performance of Station Post Insulators under Icing Conditions based on Electric Field Distribution

xˆ z ˆ. A second vector is given by B 2xˆ yˆ 2z ˆ.

NUMERICAL ANALYSES OF ELECTROMAGNETIC FIELDS IN HIGH VOLTAGE BUSHING AND IN ELECTROMAGNETIC FLOW METER

Simulation of the Electric Field on Composite Insulators Using the Finite Elements Method

Computation of Electromagnetic Energy Absorption in the Human Body Tissues by High Frequency Structure Simulator

AP Physics C. Electricity - Term 3

Mansfield Independent School District AP Physics C: Electricity and Magnetism Year at a Glance

Physics 126 Fall 2004 Practice Exam 1. Answer will be posted about Oct. 5.

CHAPTER 7 ELECTRODYNAMICS

Electric Filed Simulation and Structure Optimization for 40.5kV GIS Based on Finite Element Method

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

Finite Element Modeling of Electromagnetic Systems

HIGH VOLTAGE TECHNIQUES REVİEW: Electrostatics & Magnetostatics

Physics (

Electric Field Mapping

TRANSIENT NUMERICAL ANALYSIS OF INDUCTION HEATING OF GRAPHITE CRUCIBLE AT DIFFERENT FREQUENCY

PHYSICS 1 (LIFE SCIENCES) ELECTRICITY

TECHNO INDIA BATANAGAR

UNIT-I INTRODUCTION TO COORDINATE SYSTEMS AND VECTOR ALGEBRA

AQA Physics A-level Section 7: Fields and Their Consequences

AP Physics C. Magnetism - Term 4

Measurement of electric potential fields

COPYRIGHTED MATERIAL. Basic Field Vectors. 1.1 The Electric and Magnetic Field Vectors

STUDIES ON LIGHTNING CHARACTERISTICS

Electric Field Mapping

AP Physics C Electricity & Magnetism Mid Term Review

THE EFFECT OF UNBALANCED LOADS IN DISTRIBUTION TRANSFORMERS AND GROUND NETWORK ON ELECTROMAGNETIC FIELDS

= [1] Coulomb s Law. 1. Objective

FREQUENCY DEPENDENT CHARACTERISTICS OF GROUNDING SYSTEM BURIED IN MULTILAYERED EARTH MODEL BASED ON QUASI-STATIC ELECTRO- MAGNETIC FIELD THEORY

Electricity & Magnetism Study Questions for the Spring 2018 Department Exam December 4, 2017

EDDY CURRENT TESTING

HIGH VOLTAGE TECHNIQUES Basic Electrode Systems (3)

1 of 11 4/27/2013 8:48 PM

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad Electronics and Communicaton Engineering

Conventional Paper-I-2011 PART-A

Electric Field Mapping Lab 2. Precautions

ECE357H1S ELECTROMAGNETIC FIELDS TERM TEST March 2016, 18:00 19:00. Examiner: Prof. Sean V. Hum

Measurement and simulation of the electric field of high voltage suspension insulators

On Designing of a High Voltage Standard Capacitor Using a Semi-Analytical Field Computation Method

Modeling of Transmission Line and Substation for Insulation Coordination Studies

PH2200 Practice Final Exam Summer 2003

Inductance and Current Distribution Analysis of a Prototype HTS Cable

Measurement and simulation of the voltage distribution and the electric field on a glass insulator string

Phys222 W16 Exam 2: Chapters Key. Name:

Physics 3211: Electromagnetic Theory (Tutorial)

1. In Young s double slit experiment, when the illumination is white light, the higherorder fringes are in color.

we can said that matter can be regarded as composed of three kinds of elementary particles; proton, neutron (no charge), and electron.

1. Voltage is how much work is being done for a charge. 2. Lightning is the electric breakdown of air by weak electric fields and is a flow of energy.

The Simulation Analysis of Electromagnetic Repulsion Mechanism for. High-voltage Current-Limiting Fuse

Arrangement of conductors in 220 kv double circuit line to reduce E-fields in view of public exposure

NR/RR. Set No. 2 CODE NO: NR/RR210204

Demonstration 1: Faraday Ice Pail and Charge Production

Coulomb s law with Cobra3

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

Measurement of the electric field at the near field radiating by electrostatic discharges

Calculation of Magnetic Field Produced by OHTL under Normal and Abnormal Conditions

Research Article Simulation Analysis of Transient Earth Voltages Aroused by Partial Discharge in Switchgear

Phys 132: Supplementary Exercises

Analyses of characteristics of spatial lightning electromagnetic field at different horizontal distances and observation point heights

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

Geophysical Applications GPR Ground Penetrating Radar

Analysis of DC Power Transmission Using High T c Superconducting Cables

DHANALAKSHMI SRINIVASAN INSTITUTE OF RESEARCH AND TECHNOLOGY

DHANALAKSHMI SRINIVASAN COLLEGE OF ENGINEERING AND TECHNOLOGY

Modeling Electric Fields in High Voltage Submersible Changeover Switch

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRONICS AND COMMUNICATION ENGINEERING QUESTION BANK

Calculation of equivalent magnetic permeability of ferromagnetic materials for modeling of three-dimensional eddy current fields

Part IB Electromagnetism

MIDSUMMER EXAMINATIONS 2001

Consider a point P on the line joining the two charges, as shown in the given figure.

Numerical Analyze of Corona Discharge on HVDC Transmission Lines

PHYSICS - CLUTCH CH 24: CAPACITORS & DIELECTRICS.

with embedded electrode

Electrical Characterization of 3D Through-Silicon-Vias

INSTITUTE OF AERONAUTICAL ENGINERING DUNDIGAL ELECTRICAL AND ELECTRONICS ENGINEERING

o Two-wire transmission line (end view is shown, the radius of the conductors = a, the distance between the centers of the two conductors = d)

Lesson 3. Electric Potential. Capacitors Current Electricity

TRANSMISSION LINES. All aluminum alloy conductor (AAAC) Aluminum conductor alloy reinforced (ACAR)

Boundary and Excitation Training February 2003

A) I B) II C) III D) IV E) V

Research on Dynamic Calibration of Piezo-two-dimensional Force Sensor

CALCULATION OF POWER FREQUENCY FIELDS FROM HIGH VOLTAGE OVERHEAD LINES IN RESIDENTIAL AREAS

Transcription:

, pp.13-20 http://dx.doi.org/10.14257/ijca.2013.6.6.02 The Distortion Influence Simulation and Experimental Study of Human Body to High Voltage Power Frequency Electric Field Wang Jingang, Mao Kai and Gao Can State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400044, China jingang_023@163.com, 173661219@qq.com, 343292467@qq.com Abstract In order to eliminate the distortion influence error caused by human body on the measurement of hand-held high voltage power frequency electric field measurement device, field intensity distortion caused by induced current of human body has been analyzed, and the enhancement factor of the electric field intensity is introduced to reduce the distortion degree of electric field measurement value by electric field measuring instrument. A simple model of the human body is built, the Ansoft Maxwell is used to simulate and calculate the electric field distribution around the high voltage power frequency transmission lines when human body presented, and distortion influence of field intensity distribution caused by human body has been analyzed. In addition, the enhancement factor value of electric field is determined and the electric field distortion is corrected by experiment and comparing the measurement data with the electromagnetic field analyzer EFA300. With the actual measured values of instrument restored the value of the field intensity when the human body away from the measuring equipment, the distortion influence measurement error can be reduced and measurement precision can be improved. Keywords: Induced current, Ansoft Maxwell simulate, Enhancement factor, Electric field distortion, Electric field restoration 1. Introduction In the power industry, electric field measurement is regarded as effective and practicality means of experimental research [1]. The distribution of electric field around the transmission lines and inside the electric equipment has become an interesting research topic with the continuous improvement of the transmission voltage level. Because of the complexity of human body, dielectric constant is much larger permittivity than that of air. In case of human body being present, the field intensity around the high voltage electric field would be ten times more than that of without human body, and the induced current in the body would be out of the human safety limit [2]. Besides, the surrounding electric field distortion caused by the human body, make the electric field measuring instrument, especially the hand-held instruments can't accurately measure electric field intensity. Therefore, the influences on electric field intensity caused by human body should be considered. Firstly, according to the theory of electromagnetic fields, effects on measurement of power frequency electric field of high voltage caused by human body under alternating electric field is analyzed. And then, simulation software is used to analyze the distribution of electric field with the human body model which is supposed to be on the ground and directly below the transmission line. Furthermore, field experiment about the actual measurement is carried out, and through the data comparison, correction of field intensity value is done via introduction ISSN: 2005-4297 IJCA Copyright c 2013 SERSC

of an enhancement factor. Therefore, effectively reduce the error resulted by the handheld measurement equipment on the electric field with the presence of the human body; eliminate the main factors that cause measurement errors of the handheld measurement device; improve the high voltage transmission line non-contact measurement precision, thus more accurately analyze of power system operation condition. 2. Theoretical Analysis 2.1. Theoretical Condition: Assumption the electric field intensity is uniform around the body. For the calculation of human induction current, the induced currents generated by three coordinate components of the space field that act on the human body respectively must be considered and be superimposed to get the total induced current. For each coordinate component of field intensity, it is assumed to be uniform around the human body is uniform [3], and parallel or perpendicular to the axis of the human body [4]. Field intensity around the human body satisfies the quasi static field conditions. Quasi static field refers to alternating electric fields with frequency of 100kHz and smaller. Dielectric constant of human body is much greater than the air because of its complexity, the human body can be treated as a conductor, the surface electric field intensity vector is perpendicular to the surface of the human body. Consequently, research methods and calculation formulas in electrostatic field can be used here. In addition, charges in the electric field induced by the human body do not affect the charge distribution of transmission lines. 2.2. Calculation of Current Induced by Human Body In power frequency electromagnetic field, the human body can be regarded as a complete conductive body. Generally the body's electrical parameters are: 12 Permittivity: ε 80ε ( ε 0 0 8.85 10 F/m ); resistivity: ρ 1Ω m ; permeability: 7 μ μ 0 ( μ 0 12.56 10 H/m ); the relative dielectric constant of the body living tissue is about 1 10 5 ~2 10 6. Like any conductive object, the whole body is in equipotential state, its surface electric field intensity vector is mutually perpendicular with the human body surface[5], and can be calculated according to electromagnetic field theory [6]. In alternating electric field, the induced charge changes with the electric field, corresponding to the displacement current produced in the human body. In the case of induction electric field intensity given, internal current density can be obtained according to Ohm's law: J σe (1) i σ The conductivity of the medium(s/m) E Induction electric field intensity(v/m) i Human body total induced current I : I S JdS (2) S S Human skin surface area(m 2 ) 14 Copyright c 2013 SERSC

2.3. Electric Field Intensity Enhancement Factor Considering the influence of the human body, usually using the ratio of human body surface electric field intensity E s to exogenous uniform field intensity E 0 to describe the relationship between distortion field and undistorted field, known as the electric field intensity increases factor : E s (3) E 0 E s The human body surface electric field intensity E 0 Outside things uniform electric field intensity Theoretical and experimental studies show that the body surface electric field intensity is enhanced in most parts and the strongest locates at the human head. If the body insulates form the earth, the enhancement factor of human body surface differs. The enhancement factor is about 1 at the foot and lower portion, and about 20 at the head; furthermore, about 50 at the tip of the stretched arm. The results are also shows:the tip of a conductive object would significantly promote the electric field intensity [7]. When the body directly connect to ground, electric field distortion weakens with the same height of the human body surface [8]; but from the human body bottom to the top, enhancement factor increases more than that of insulation form the earth :wherein the enhancement factor about 0.2 at the human foot, and about 17 at the head, we can see the enhancement factor increased 85 times. 3. Simulation and Analysis on Distorted Electric Field Around the Human Body In order to have a better understanding of the influence to the electric field and its distortion with the body under the transmission line, using Ansoft Maxwell software simulates the distribution of the electric field below the transmission line with human body directly connecting to the earth. 3.1. Assumption of Parameters Related to Human Body: Because the ground electric field can actually be considered uniform below transmission lines, and perpendicular to the ground [9]; and to ignore human induction current bring electromagnetic interference, etc. [10]. Therefore, a pair of parallel electrode plate applied with voltage can be regarded as the equivalent electric field of transmission line. Suppose the distance between the two plates is 2m, and the plate voltage of high voltage is 8kV, low voltage plate and the earth potential is set to 0V, ignore the edge effect, the electric field between the two plates can be considered to be uniform, which is 4 kv/m. For convenience, treat the human body as a conductor model and divide the human body model into four parts, the head, neck, waist and legs [11].Wherein the head is equivalent to a radius of 9cm sphere, the neck, waist and legs are equivalent to a cylinder, the specific parameters are as follows: neck radius is 6cm, and the waist radius is 20cm, leg radius is 15cm;neck height is 8cm, and waist height is 60cm, the leg height is 90cm. The total height of the human body model is 176cm.Suppose the conductivity of the human body is 0.1S/m, the relative Copyright c 2013 SERSC 15

dielectric constant is about 10 5, human body and the earth are equal potential [12]. Simplified human model structure is shown in Figure 1. 3.2. Simulation Analysis Figure 1. Structure of simplified human model The equivalent electric field considering the presence of human body below the transmission line can be obtained via simulation using Ansoft Maxwell. Analysis shows: the existence of human body disturbs the electric field in a certain range. The overall trend of electric field distortion is that the distortion effect and the enhancement factor increase with the height of human body. From the soles of the feet to the top of the head, the electric field intensity ranges from 7.91V/m to 79.1kV/m. Wherein the maximum field intensity at the top of the head is about 79kV/m, enhancement factor is 19.75 with respect to undistorted maximum field intensity that is 4kV/m: waist middle position field intensity is about 11kV/m, the enhancement factor is about 2.75;the field intensity of ground position place is 7.91 V/m, close to 0,but the field intensity remain has been increased relative to undistorted situation. As can be seen from the simulation analysis, the head of human body has the largest electric field intensity. This is because the human body can be approximated as a grounded conductor for a very large, the top of the head are closest to the positive plate, and gathers a large number of induced charge, so there is a maximum field intensity. With the height reducing, the further the body from the positive plate, the less induced charge, so, the field intensity decreases. Furthermore, due to the effect of electrostatic induction, charges distributed in the outermost surface of the human body. So the human body such as the inner concave place of the neck, the electric field is very small, and such as the outer convex place of shoulder, the electric field is large. Although simplified human body model is difficult to fully simulate many concave and convex parts of human body, the overall distribution of the electric field trend will not be affected by these parts. Therefore, enhancement factor generally decreases with the decreasing height of human body. 4. Field Testing 4.1. Electric Field Intensity Test Equipment Use the EFA300 low frequency electromagnetic field analyzer in the testing made in German Narda Company. EFA300 equipped with three-dimensional isotropic measurement probe (non-directional),electric field measuring range is 0.1 V/m - 200kV/m [13]. Electric field measurement value is more accurate in the low frequency high voltage [14]. 16 Copyright c 2013 SERSC

4.2. 500 kv Ban Chen II Line Field Testing In order to more accurately analyze the characteristics of the distortion of electric field around the human body, we had carried out experiments on the distorted electric field around the human body in Chongqing University Town 500 kv Ban Chen II line. Measured body is insulated from the ground, measures the surface electric field of the five main parts, the human head, middle of the neck, middle of the waist, middle of the legs and foots, respectively. The whole measuring process considering undistorted electric field to be unchanged and uniform. Field measurement is shown in Figure 2. And selected one measuring point at the transmission lines roadside phase outer, the actual measurement value of undistorted electric field is 4.048 kv/m where the point is 1.5m above from the ground. 4.3. Test Analysis Figure 2. Scene of field measurement Through finishing the measurement data, the relationship curve between the human body height and the electric field enhancement factor in case of body insulating from the grounded is shown in Figure 3. It can be seen from the relationship curve, when the human body is below the transmission lines, the higher the height, the closer the head to the line, so both the electric field of the head and the enhancement factor are bigger; on the contrary, because the shorter person a little far away from the line, the enhancement factor is smaller. Similarly, other parts of the body s electric field and enhancement factor can be analyzed. Figure 3. Enhancement factor curve of ungrounded human mode Copyright c 2013 SERSC 17

In addition, the body height and the electric field enhancement factor relationship curve in Figure 3 are basically consistent with the test results in literature [2], but the enhancement factor size still have slight difference. This is because the close relationship between the height and the distortion electric field caused by human body [15]. The higher the measured human body, the smaller distance from its head to a charged object, then the greater the field intensity;at the same time, different people different body model, and dielectric constant and conductivity will also differs, so the distortion of electric field will also be different ; Furthermore, due to the distortion electric field caused by the body also associated with the body's physical fitness, body size, and other factors [16], it will bring some error in the analysis process. 4.4Calibrate Reduction Test to Electric Field Considering influence on the body's distortion influence situation, introduce corresponding increase factors to conduct calibration test to of electric field distortion. We also carried the field measurement in Chongqing University Town. Choose a measuring point carry out two groups of field intensity data measurements at the transmission line roadside phase outer, wherein a group of people tight close to the measuring instrument. At the same time it should be noted that, don't change the instrument measuring height and position in the measurement to ensure the accuracy of reading. Two groups of instrument field measurement results and simulation results contrast as shown in Figure 4. From the Figure 4, two groups of measurement results are closely similar, measurement error is mostly within 10% and meet the requirements of the engineering measurement. Figure 4. The Comparison of the vertical electric field between measurement and simulation below 500kV transmission line 5. Summary Based on the theory analysis and the actual measurement indicate that the human body surface electric field intensity is enhanced in most parts. The enhancement factor is not same in different positions, which minimum is in a human foot or low parts and maximum is in the head. If the tip of stretched out arm is over the head, the enhancement factor will increase. In general, enhancement factor reduces with the reducing height of human body. In order to make the measured value close to undistorted the real data to the utmost, through several comparison measurements, introduce the corresponding enhancement factor to calibrate electric field distortion, to make the measurement value fully reflect the undistorted field when someone presented, effectively reduces the influence of the electric field measurement result due to the human body, and improve the accuracy of the electric field measuring instrument, especially the accuracy of the electric field measurement of the hand-held electric field measuring instruments. Improve the non-contact type measurement 18 Copyright c 2013 SERSC

accuracy of high voltage transmission lines, thus more accurate analyze the operation status of power system. Acknowledgements This work was supported by Natural Science Foundation Project of China (Grant No. 51207175). References [1] L. Conghan, H. Wei and W. Jingang, "Design of portable power frequency electric field measurement device" High Voltage Apparatus, vol. 48, no. 3, (2012), pp. 57-61. [2] L. Yuanqing, Z. Jun and Z. Bo, "Analysis of influence of 50hz electric fields generated by the high voltage power lines on human body, High Voltage Engineering, vol. 30, no. 12, (2004), pp. 35-36, 55. [3] J. Wei, W. Guangning, H. Zhen, "Analysis of effects on human body of UHVDC transmission line based on FEM" High Voltage Engineering, vol. 9, (2008). [4] F. Yanyan and Y. Jihui, "Power frequency electric field cause by EHV lines and its effect", Journal of Chongqing University, vol. 27, no. 3, (2004), pp. 10-14. [5] A. Z. El Dein, M. A. A. Wahab and M. M. Hamada, "Computation of electric field and human body induced current under overhead transmission lines", 2010 7th International Multi-Conference on Systems, Signals and Devices, (2010), pp. 1-6. [6] C. Dingxin and Q. Xuedi, Evaluated calculation of the induced current in human body produced by power frequency electric and magnetic field under ac transmission line, Guangdong Power Transmission Technology, vol. 4, (2010). [7] A. Chiba, K. Isaka and Y. Yokoi, Application of finite element method to analysis of induced current densities inside human model exposed to 60Hz electric field, IEEE Trans on PAS, vol. 103, no. 7, (1984), pp. 1895-1902. [8] M. Abdel-Salam and H. M. Abdallah, Transmission-line electric field induction in humans using charge simulation method, IEEE Transactions on Biomedical Engineering, vol. 42, no. 11, (1995), pp. 1105-1109. [9] H. Jiusheng, Possible effects of electromagnetic fields generated by electrostatic discharge from the charged human body on computer operation, Physics, vol. 10, (2000). [10] L. Qin, Electromagnetic interference effects and restraint strategy on electronic electri c energy meters, Electrical Measurement & Instrumentation, vol. 44, no. 6, (2007), pp. 50-54. [11] Z. Songyang, Y. Degui and L. Qing, Development of wireless power frequency electric field measurement and alarm device and its application, Electrical Measurement & Instrumentation, vol. 48, no. 1, (2011), pp. 21-25. [12] Z. Tiebin and M. C. Comber, "Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towers", IEEE Transaction on Power Delivery, vol. 15, no. 1, (2000), pp. 313-318. [13] G. H. Varttaneourt, S. Carignan and C. Jean, Experience with the detection of faulty composite insulators on high-voltage power lines by the electric field measurement method, IEEE Transactions on Power Delivery, vol. 13, no. 2, (1998), pp. 661-666. [14] S. Fangyin, B. Kehan and Z. Liurong, Electric field distribution and human induced current on the 220 kv to 500 kv transmission line tower, Power System Technology, no. 1, (1992), pp. 53-59. [15] M. Misakian and P. Fulcomer, Measurement of non-uniform power frequency electric fields, IEEE Transactions on Electrical Insulation, vol. EI-18, no. 6, (1983), pp. 657-661. [16] E. Lanbert, Measurement of electric and magnetic fields from alternating current power lines, IEEE Transactions on Power Apparatus and Systems, vol. PAS-97, no. 3, (1978), pp. 1104-1114. Copyright c 2013 SERSC 19

20 Copyright c 2013 SERSC