Short-circuit protection to a fault: Superconducting fault current limiters

Similar documents
Superconducting Fault Current Limiters

Superconducting Fault Current Limiters

KIT-ENERGY CENTRE. KIT The research University in the Helmholtz Association

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Fault Calculation Methods

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Fault Current Limiters

Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

Conductor Requirements for Superconducting Fault Current Limiters

Combined HTS Cable and Fault Current Limiter Project in Germany

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

2 nd Generation High-Temperature Superconducting Wires for Fault Current Limiter Applications

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Feasibility of HTS DC Cables on Board a Ship

Fault Current Limiter Based on Coated Conductor

Superconducting Fault Current Limiter in DC Systems with MLI Fed to IM

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

EPRI Technology Watch 2010 Superconducting Cables Fault Current Limiters

Symposium VV: Future Directions in HTS

Superconductivity for Electric Systems DOE 2006 Wire Development Workshop

What is a short circuit?

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid

Status and outlook on superconducting fault current limiter development in Europe

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Cryogenic and Electrical Test Results of a 30 M HTS Power Cable

Superconducting cables Development status at Ultera

TeSys circuit-breakers

Commissioning testing of a 1 MVA Superconducting transformer featuring 2G HTS Roebel cable

1SDC007004D0201. Discrimination tables

High-Performance 2G HTS Wire for an Efficient and Reliable Electricity Supply

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

T h e rm i s t o r s

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Experimental Investigation of High-Temperature Superconducting Magnet for Maglev

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

High-temperature superconducting magnet for use in Saturated core FCL

Selecting the current rating for equipment

Commissioning and Testing of AVR and PSS

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

5SJ4...-.HG Circuit Breakers to IEC and UL 489

VX25 Enclosure System. Technical documentation PE conductor connection, current carrying capacity

New Transmission Options Case Study Superconductor Cables. Transmission Policy Institute Sheraton Downtown Denver, Colorado April 20-21, 2011

The development of a Roebel cable based 1 MVA HTS transformer

Progress in Scale-up of 2G HTS Wire at SuperPower Part III

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK

GENERATOR INTERCONNECTION APPLICATION

3/31/2006 9:36:15 AM RECENT DEVELOPMENT SUPERCONDUCTIVITY: THE FUTURE OF POWER TRANSMISSION

Communique. International Superconductivity Industry Summit (ISIS)-20 Gonjiam Resort, Korea October 2011

HTS Roadmap for Electric Power Systems October 2015

Superconducting Cables

Latest Status of High Temperature Superconducting Cable Projects

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

EMTP-ATP Modeling of a Resistive Superconducting Fault Current Limiter

Harmonic Modeling of Networks

KINGS COLLEGE OF ENGINEERING Punalkulam

Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

Applications Using SuperPower 2G HTS Conductor

Development of 2 MVA Class Superconducting Fault Current Limiting Transformer (SFCLT) with YBCO Coated Conductors

Reliability of Bulk Power Systems (cont d)

I, THERMAL ANALYSIS OF BUS-BAR FOR SWITCH BOARD

Instruction. Vacuum Circuit Breaker Operator Module. Type 3AH 4.16kV to 38kV. Power Transmission & Distribution

Coil in Coil Components for the High Voltage Superconducting Resistive Current Limiter CULT 110

INSTALLATION AND COMMISSIONING OF TRIAX HTS CABLE

Failure Analysis of Medium Voltage Capacitor Banks: The Egyptian Experience

Experiences with Superconducting Cable & Fault Current Limiter in a German City Center Mark Stemmle

Electric Distribution Storm Hardening Initiatives. Paul V. Stergiou Distribution Engineering October 14 th, 2015

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

1. Wind turbines are designed to operate within specified design criteria. Often the operating environment extends beyond these limits and causes

Reliability Analysis of Moog Ultrasonic Air Bubble Detectors

HiLumi LHC FP7 High Luminosity Large Hadron Collider Design Study. Milestone Report. Cryogenic Scenarios for the Cold Powering System

Capacitor Application Issues

C60N circuit breakers0 B, C and D curves IEC 60898: 6000 A, IEC : 10 ka

Thermal Properties of Power Terminals in High Power IGBT Modules

Critical Current Properties of HTS Twisted Stacked-Tape Cable in Subcooled- and Pressurized-Liquid Nitrogen

An Optimised High Current Impulse Source

3VT4 Molded Case Circuit Breakers up to 1000 A

System Technology and Test of CURL 10, a 10 kv, 10 MVA Resistive High-Tc Superconducting Fault Current Limiter

Damping resistor design consideration

Section 1 Electric Charge and Force

MCB NB1-63H Miniature Circuit Breaker

New Electric Reluctance Motor with Bulk Superconducting Materials on the Rotor

08/072 PKZ2 Motor-Protective Circuit-Breakers Tripping Characteristics

R&D of 22.9kV/50MVA HTS Transmission Power Cable in Korea

Modeling of the Resistive Type Superconducting Fault Current Limiter for Power System Analysis and Optimization

EXPERIMENT 9 Superconductivity & Ohm s Law

Tutorial on Shunt Capacitor Banks Design, Application and Protection Considerations

EXEMPLAR NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL PRINCIPLES AND PRACTICE NQF LEVEL 3 ( ) (X-Paper) 09:00 12:00

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

EE2351 POWER SYSTEM OPERATION AND CONTROL UNIT I THE POWER SYSTEM AN OVERVIEW AND MODELLING PART A

SuperPower s path to leadership in clean, green and smart energy technology

Transient Analysis of a 150 kv Fault Current Limiting High Temperature Superconducting Cable

Faults on Electrical System. A Research

Fundamentals of Polymeric PTC 0vercurrent Circuit Protection

TRANSFORMERS. Pascal Tixador. Grenoble INP - Institut Néel / G2Elab. Introduction

Current protection I 2 t long-time protection

Techno-Economic Study of Series Current Limiting Reactor and Its Impact in the 11KV Network with Harmonic Pollution

Transcription:

Dr. Joachim Bock, Nexans Superconductors, Germany Short-circuit protection to a fault: Superconducting fault current limiters Nexans has commissioned the world s first superconducting fault current limiter to protect a power plant s internal power supply at the Boxberg lignite plant in Germany. Joachim Bock, CEO of Nexans Superconductors, explains how this technology can help to increase personnel and plant safety while simultaneously reducing investment costs. Vattenfall Europe Generation AG s Boxberg power station in Germany is An increasingly decentralized supply of power, higher power flows and the present backlog of investment in equipment are all developments that will require stronger adaptations to the power network in the coming years. In this context, high short-circuit currents play an essential role. For example, in power networks short circuits can arise because of lightning strikes or failures of system components and power lines, resulting in high fault currents. These cause extremely high dynamic and thermal loads that all system components of the power network must resist. Due to their modular construction, superconducting fault current limiters (SCFLs) can be used for various nominal voltages and currents, and can be adapted to particular limiting characteristics in case of short circuits. Electrical equipment that controls high fault currents can increase the security of the network and allow power equipment to be designed more cost effectively. The SCFL is such a device. In contrast to a high-voltage fuse it does not disconnect the line in case of a short circuit but limits the very high currents to defined values. In addition, it allows electrical interconnections of existing systems, which would not be possible without limiters. During operation, the superconductors of the limiter are cooled to a temperature of around -200 C, which is easily and cost effectively accomplished by means of liquid nitrogen. At these temperatures, the materials used have virtually no electrical resistance even at nominal power loads. However, if the so-called critical current, i.e. above the nominal current, is exceeded, the material suddenly loses its superconducting properties and behaves like a normal resistor. This relatively high resistance limits the current to a predefined value. These material properties only make superconductors ideal self-actuating current limiting elements. SCFL s active Module The active part of the SCFL consists of 48 superconducting elements per phase connected in series and immersed in liquid nitrogen in a cryogenic vessel. The element assemblies are connected to the outside of the vessel through high-voltage bushings and current leads designed to cope with the temperature gradient between the liquid nitrogen and the exterior of the vessel. The liquid nitrogen is cooled by an external cryocooler. A circuit breaker in series with the limiter is tripped when the fault current has been reduced. The SCFL is thoroughly instrumented to continually monitor its operation and the series circuit-breaker will be tripped if abnormal conditions (e.g. cryocooler failure) occur. Communication with the DNO telecontrol systems covers operational items and ancillary information such as failure of auxiliary electricity supplies. Maintenance-free operation After a short circuit, the limiter must be powered off for a short period so that it can automatically return to the operational state by means of cooling. After a few seconds or minutes, depending on the design, the limiter can again accept the nominal power and is ready for the next short circuit event. The compactly designed current limiter provides close to ideal operating conditions. In normal operation, it is virtually transparent to the network; in case of a fault, it limits the short circuit current automatically and reliably independent of its level. By using a SCFL as a protection device, networks can be coupled without causing the short circuit currents to be added. A short circuit current is limited to a defined value by the current limiter, which is within the realms of milliseconds. 24 www.peimagazine.com June 2010 - PEi

piloting the new SCFL based high temperature superconductor technology developed by Nexans Superconductor potential uses for SFCLs Typical uses of SCFLs are: Busbar coupling while retaining the switching equipment Transformer in-line protection Protection of local networks in industrial areas or chemical parks Protection of the house load in power plants Coupling of networks for the reduction of harmonics Additional advantages of SCFLs include: Due to the passive limiting characteristics of the superconductor, the current is reliably limited within the first half cycle in the presence of a short circuit. The SCFL is inherently safe and is free from wear and maintenance; onsite activation is not required. Thus, no additional operating costs arise from a short circuit. Considerable cost savings can be attained within the initial installation or revision of switching equipment because the equipment can be scaled down to lower short circuit power. The peak limited current and the symmetrically limited current can be defined independently of each other. In case of a short circuit, the power flow is not interrupted completely, so that existing protection designs can be retained. During a short circuit, system components are subject to less mechanical and thermal stresses. This can significantly increase their lifetime. In addition to the design, production and installation of current limiters, Nexans can also provide for their maintenance and service. Thus, the continuous security and reliability of the equipment is guaranteed. The SCFL is perceived to be a low-risk fail-safe device, utilizing a nonlinear high temperature superconducting ceramic rather than electronic, electromechanical, mechanical or pyrotechnic components. When the superconducting material is operated at below its critical temperature it loses all electrical resistance, thereby allowing normal load current to flow with negligible losses. Either the increased current density caused by the passage of fault current or the loss of the liquid nitrogen cooling medium cause the temperature of the superconducting material to rise with the result that the material reverts to a normal resistive state. This added resistance has the effect of reducing the fault current to a lower, more acceptable level. This process is referred to as clamping because it effectively sets a limit above which the fault current will not rise. The SCFL operates in a few milliseconds, after which its resistance remains high until the fault current is cleared by a circuit breaker. The SCFL s operation is sufficiently fast to ensure that the first peak of the fault current is limited; this is vitally important when considering the closing of a circuit breaker onto a section of faulty network. The degree to which the subsequent current is limited can be set at the design stage to suit a specific application. It will, in many cases, be convenient to choose this level such that existing protection arrangements do not need to be adjusted. strategic deplayment onto networks Trials will result in the development of commercially available devices, that are capable of clamping fault levels to within network design limits.this can bring a number of benefits. SCFLs could be strategically deployed onto the network in areas either with existing high fault level issues, or experiencing PEi - June 2010 www.peimagazine.com 25

a high degree of distributed generation connection activity (e.g. urban combined heat and power generation systems). In this application, SCFL could provide a method of deferring the replacement of switchboards or reconfiguration of networks, whilst ensuring fault levels are maintained within safe limits. Where fault levels are generally high, there may be operational benefits associated with minimizing the often complicated switching required to ensure that equipment operates within its fault rating during network reconfiguration and outages. This could reduce the risk of incurring customer interruptions and customer minutes lost arising from either network switching or from operating parts of the network temporarily on a single circuit. An improvement in staff safety may also be delivered. If network fault current magnitudes are restricted equipment will be subjected to reduced electrodynamic and thermal stresses these are both proportional to the square of the current, so a modest reduction in fault level results in a considerable reduction in these stresses potentially reducing the probability of follow-on faults and prolonging the asset life. SCFLs may, subject to resolution of protection issues, allow radial circuits to be interconnected, with associated improvements to customer supply continuity and power quality (i.e. flicker and harmonics). This could facilitate a radical change in the way networks are designed and operated. In addition to the above, there are specific benefits associated with the type of design being implemented here, which uses the superconducting to normal transition. Boxberg power plant is fueled by lignite and has a capacity of 1900 MW 26 www.peimagazine.com http://pei.hotims.com RS 14 June 2010 - PEi

In its normal state, the SCFL does not add significant reactance to the network and therefore does not affect the upper threshold of impedance envelope that DNOs need to stay within to ensure that they do not exceed voltage levels in the event of sudden loss of load etc. It will also not increase system losses. A significant issue for DNOs today is the increase in X/R ratio which increases the DC component and therefore the asymmetrical current at break time. This also (to a lesser effect) impacts the peak making current under fault conditions. Although a series reactor will reduce the AC component of short circuit current it may make the X/R ratio rise, and although it reduces the overall asymmetrical current, the DC component can be made greater. Circuit breakers are not tested for this increased DC component and associated longer arcing times. Due the superconducting/normal transition, the SCFL adds resistance to the fault path. This reduces the AC and DC components of current and the level of asymmetry dramatically. This provides much easier making and breaking duties for a circuit-breaker and additionally, greatly reduces the peak voltage generated (transient recovery voltage) at the point of current interruption. The level of fault contribution from connected inductive load is now calculated according to IEC909 and DNOs are finding sites where the peak making currents of circuit breakers are being exceeded. The fast clamping of the SCFL reduces these peaks to within circuit breaker ratings. This eliminates the need to reconfigure networks before closing operations. Choice of HTS material High-temperature superconductors (HTS) were first discovered in 1986 when Müller and Bednorz at IBM in Switzerland found a lanthanumbarium-copper oxide ceramic exhibiting superconductivity at 30 K. Since then, the numerous discoveries of materials displaying superconductivity at temperatures above 77 K have increased the potential for exploitation of superconductivity in a variety of applications. Prior to these discoveries it was necessary to use helium, which liquefies at 4 K, to cool the metallic superconductors sufficiently. Helium is very expensive and cooling to below 4 K is also costly in terms of equipment and the energy consumed. The discovery of HTS promised to reduce the costs of cooling and to deliver new applications including high-capacity power cables, more compact transformers, motors and fault current limiters. However, it has taken longer than expected for manufacturers to develop ways to produce HTS materials suitable for use in high-power applications. Ceramics are brittle by nature and susceptible to shattering when stressed which is undesirable in practical applications such as cables. Bismuth strontium calcium copper oxide (BSCCO) and similar materials have a layered structure and the superconductivity occurs in the layers containing mainly copper and oxygen atoms. It is very difficult to manufacture large single crystals of these materials so superconducting components made from bulk material, as well as tapes and wires where the HTS material is deposited on or in a metallic strip, incorporate the HTS in a polycrystalline form. PEi - June 2010 http://pei.hotims.com RS 15 www.peimagazine.com 27

The orientation of the individual crystals with respect to each other has to be controlled so that the superconducting planes are substantially parallel and much work has been done on production methods to achieve this. SCFL prototypes have been designed using Bi-2212 and YBCO in a variety of guises. A Bi-2212 sheet, bonded to a metal shunt and cut into a meander to provide a low inductance current path provided the basis for ABB s singe-phase demonstrator reported in 2002. At around the same time, thin-film YBCO on a sapphire substrate was used by Siemens for a high-voltage prototype. A Bi-2212 tube, bonded to a tubular shunt and cut into a bifilar helical meander, manufactured by Nexans Superconductors, was used for the first major live network trial, known as CURL 10, hosted by RWE at Siegen in Germany in 2004. Consideration of the costs, availability and suitability of the various candidate materials for application in fault current limiting led to bulk Bi-2212 in tubular form emerging as the most attractive material to use in a commercial SFCL. Based on the experience gained in providing the superconducting elements for the CURL 10 demonstrator, Nexans was clearly in a good position to supply the superconducting components for the UK trial.the company has developed a Bi-2212 component for use in the first UK pilot. The component is made from a tube of melt-cast Bi-2212 soldered to the interior of a copper-nickel-manganese tube, which provides a metallic shunt to prevent the formation of hot spots in the HTS. This arrangement is then cut into a helix giving an effective length of 3 metres for each component. The components are supported from the interior by a tube of fibre-reinforced plastic. Pairs of tubes are joined endto-end and 24 of these connected in series provide the current limiting function for each of the three phases. The SCFL will provide short circuit protection for Boxberg s internal medium voltage supply for its coal mills and crushers Deployment of first SFCL The site for the first pilot was selected in 2006. It is in a semi-urban location in Lancashire and was chosen for two reasons. Firstly, there is plenty of space for the installation and secondly, the site provides an example of where an SFCL might be installed in response to real need. The two 33/11 kv transformers feeding the substation were recently upgraded, with the result that the fault level increased to above the making and breaking capacities of the existing circuit breakers. It was therefore necessary to build a new substation and install a new 11 kv switchboard of primary distribution circuit breakers comprising ten feeders, two incomers and one bus-section. Thus, while the fault level problem was addressed in a conventional manner, the situation has allowed the design of the SFCL to be determined according to realistic criteria, as though it were being used to provide a solution to the fault level issue. The rating of the old switchgear was taken as the basis on which the operating characteristics of the SFCL would be determined. SCFLs could provide a method of deferring the reconfiguration of networks, while ensuring fault levels are maintained within safe limits The old switchgear was rated at 11 kv with a short circuit capability of 150 MVA. This equates to a breaking capacity of 7.87 ka and a making capacity of 19.7 ka.the fault contribution of each of the two transformers is calculated to be 11 ka peak, 4.2 ka rms. It was decided that the SFCL should limit the fault current seen by any circuit breaker to 95 per cent of the old breaker rating, i.e. 7.48 ka break and 18.72 ka. The SFCL, which is deployed in a bus-section configuration, effectively in parallel with the existing bus section circuit breaker (which of course will be left open during the trial) must limit the fault contribution from the healthy to the faulted busbar when a fault occurs on an outgoing circuit. This contribution, together with the contribution from the transformer directly feeding the faulted bar, must be no more than 95 per cent of the rating of the old switchgear. The limiting, or clamping performance of the SFCL is thus defined by the network characteristics and the rating of the available plant. FIRST POWER PLANT INSTALLATION In a pilot project for Vattenfall Europe Generation AG, the SFCL will provide short circuit protection for the internal medium voltage power supply that feeds coal mills and crushers in the Boxberg brown coal power plant in Saxony, Germany. Vattenfall s SFCL, based on Nexans HTS technology and designed for a rated current of 800 A, is undergoing live testing by daily routine operation in a feeder bar of the 12 kv power supply for rebound hammer mills (used for crushing coal). For the SFCL used in Boxberg, Nexans Superconductors designed and built the device according to the specifications from Vattenfall and the Brandenburg Technical University in Cottbus (Germany), which is providing scientific support for this project. The device can limit a 63 ka prospective short circuit current to less than 30 ka immediately and to about 7 ka after 10 milliseconds. 28 www.peimagazine.com June 2010 - PEi