Transient Analysis of Doubly Fed Wind Power Induction Generator Using Coupled Field-Circuit Model

Similar documents
Publication P4. By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

3 d Calculate the product of the motor constant and the pole flux KΦ in this operating point. 2 e Calculate the torque.

Behaviour of synchronous machine during a short-circuit (a simple example of electromagnetic transients)

An Introduction to Electrical Machines. P. Di Barba, University of Pavia, Italy

EE Branch GATE Paper 2010

Hinkkanen, Marko; Repo, Anna-Kaisa; Luomi, Jorma Influence of magnetic saturation on induction motor model selection

Dynamics of the synchronous machine

PERFORMANCE ANALYSIS OF DIRECT TORQUE CONTROL OF 3-PHASE INDUCTION MOTOR

Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Electric Machines

Simulations and Control of Direct Driven Permanent Magnet Synchronous Generator

ECE 585 Power System Stability

From now, we ignore the superbar - with variables in per unit. ψ ψ. l ad ad ad ψ. ψ ψ ψ

The synchronous machine (detailed model)

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

Introduction to Synchronous. Machines. Kevin Gaughan

Control of Wind Turbine Generators. James Cale Guest Lecturer EE 566, Fall Semester 2014 Colorado State University

International Journal of Advance Engineering and Research Development SIMULATION OF FIELD ORIENTED CONTROL OF PERMANENT MAGNET SYNCHRONOUS MOTOR

Prediction of Electromagnetic Forces and Vibrations in SRMs Operating at Steady State and Transient Speeds

Comparative Analysis of an integration of a Wind Energy Conversion System of PMSG and DFIG Models Connected to Power Grid

CHAPTER 5 SIMULATION AND TEST SETUP FOR FAULT ANALYSIS

University of Jordan Faculty of Engineering & Technology Electric Power Engineering Department

A GENERALISED OPERATIONAL EQUIVALENT CIRCUIT OF INDUCTION MACHINES FOR TRANSIENT/DYNAMIC STUDIES UNDER DIFFERENT OPERATING CONDITIONS

AC Induction Motor Stator Resistance Estimation Algorithm

Gentle synchronization of two-speed synchronous motor with asynchronous starting

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

Small-Signal Analysis of a Saturated Induction Motor

Sensorless Control for High-Speed BLDC Motors With Low Inductance and Nonideal Back EMF

INDUCTION MOTOR MODEL AND PARAMETERS

A High Performance DTC Strategy for Torque Ripple Minimization Using duty ratio control for SRM Drive

GATE 2010 Electrical Engineering

Three phase induction motor using direct torque control by Matlab Simulink

Analytical and numerical computation of the no-load magnetic field in induction motors

Equivalent Circuits with Multiple Damper Windings (e.g. Round rotor Machines)

Lesson 17: Synchronous Machines

A Direct Torque Controlled Induction Motor with Variable Hysteresis Band

Keywords: Electric Machines, Rotating Machinery, Stator faults, Fault tolerant control, Field Weakening, Anisotropy, Dual rotor, 3D modeling

DEVELOPMENT OF DIRECT TORQUE CONTROL MODELWITH USING SVI FOR THREE PHASE INDUCTION MOTOR

Aspects on Wind Turbine Protections and Induction Machine Fault Current Prediction

Generators. What its all about

Review of Basic Electrical and Magnetic Circuit Concepts EE

Sensorless DTC-SVM of Induction Motor by Applying Two Neural Controllers

Step Motor Modeling. Step Motor Modeling K. Craig 1

The effect of voltage dips on wound rotor induction motors used in slip energy recovery drives implications for converters

Lecture 9: Space-Vector Models

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

JRE SCHOOL OF Engineering

MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator

Control of an Induction Motor Drive

Doubly salient reluctance machine or, as it is also called, switched reluctance machine. [Pyrhönen et al 2008]

Synchronous Machines

Module 3 : Sequence Components and Fault Analysis

The doubly-fed induction generator in the rotortied configuration

Doubly-Fed Induction Generator Wind Turbine Model for Fault Ride-Through Investigation

ELECTRICAL ENGINEERING

PRINCIPLE OF DESIGN OF FOUR PHASE LOW POWER SWITCHED RELUCTANCE MACHINE AIMED TO THE MAXIMUM TORQUE PRODUCTION

DTC Based Induction Motor Speed Control Using 10-Sector Methodology For Torque Ripple Reduction

A simple model based control of self excited induction generators over a wide speed range

Electromechanical Interaction in Rotor Vibrations of Electric Machines

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Generators for wind power conversion

PARAMETER SENSITIVITY ANALYSIS OF AN INDUCTION MOTOR

Measurements of a 37 kw induction motor. Rated values Voltage 400 V Current 72 A Frequency 50 Hz Power 37 kw Connection Star

The Modeling and Analysis of Grid Connected DFIG with Low-Voltage Ride- Through Solution Using Series Compensator

EFFECTS OF LOAD AND SPEED VARIATIONS IN A MODIFIED CLOSED LOOP V/F INDUCTION MOTOR DRIVE

Use of the finite element method for parameter estimation of the circuit model of a high power synchronous generator

Dynamic Analysis of Grid Connected Wind Farms Using ATP

Chapter 5 Three phase induction machine (1) Shengnan Li

Synchronous Machines

Incorporation of Asynchronous Generators as PQ Model in Load Flow Analysis for Power Systems with Wind Generation

Loss analysis of a 1 MW class HTS synchronous motor

Performance analysis of variable speed multiphase induction motor with pole phase modulation

Project 1: Analysis of an induction machine using a FEM based software EJ Design of Electrical Machines

Mathematical Modelling of Permanent Magnet Synchronous Motor with Rotor Frame of Reference

Accurate Joule Loss Estimation for Rotating Machines: An Engineering Approach

SCHOOL OF ELECTRICAL, MECHANICAL AND MECHATRONIC SYSTEMS. Transient Stability LECTURE NOTES SPRING SEMESTER, 2008

MODELING surface-mounted permanent-magnet (PM)

Energy Converters. CAD and System Dynamics

Tutorial 1 (EMD) Rotary field winding

Analysis of Idle Power and Iron Loss Reduction in an Interior PM Automotive Alternator

Chapter 4. Synchronous Generators. Basic Topology

Finite Element Based Transformer Operational Model for Dynamic Simulations

POWER SYSTEM STABILITY

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Fault ride through study of doubly fed induction generator wind turbine in real-time simulation environment

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

Effects of the Controller Performance of DFIG on its Inertia Response

Modelling and Simulating a Three-Phase Induction Motor

Fault Calculation Methods

MODELING AND HIGH-PERFORMANCE CONTROL OF ELECTRIC MACHINES

Independent Control of Speed and Torque in a Vector Controlled Induction Motor Drive using Predictive Current Controller and SVPWM

Comparative Analysis of Speed Control of Induction Motor by DTC over Scalar Control Technique

International Journal of Advance Engineering and Research Development

Different Techniques for Calculating Apparent and Incremental Inductances using Finite Element Method

Performance Evaluation of DFIG to Changes in Network Frequency

EE 742 Chapter 3: Power System in the Steady State. Y. Baghzouz

Sunita.Ch 1, M.V.Srikanth 2 1, 2 Department of Electrical and Electronics, Shri Vishnu engineering college for women, India

Model of a DC Generator Driving a DC Motor (which propels a car)

The Enlarged d-q Model of Induction Motor with the Iron Loss and Saturation Effect of Magnetizing and Leakage Inductance

STAR-CCM+ and SPEED for electric machine cooling analysis

Induction Motors. The single-phase induction motor is the most frequently used motor in the world

Transcription:

Publication P2 Seman, S., Kanerva, S., Niiranen, J., Arkkio, A. 24. Transient Analysis of Wind Power Doubly Fed Induction Generator Using Coupled Field Circuit Model, Proceedings of ICEM 24, 5-8 September 24, Cracow, Poland, 6 p., (CD-ROM).

Transient Analysis of Doubly Fed Wind Power Induction Generator Using Coupled Field-Circuit Model S. Seman*, S. Kanerva*, J. Niiranen**, A. Arkkio* * Laboratory of Electromechanics, Helsinki University of Technology P.O.Box 3, 25 HUT, Finland e-mail slavomir.seman@hut.fi, sami.kanerva@hut.fi, antero.arkkio@hut.fi ** ABB Oy, P.O. Box 86, FIN-38, Helsinki, Finland, e-mail jouko.niiranen@fi.abb.com Abstract The paper presents the transient analysis of a.7 MVA wind-power doubly fed induction generator (DFIG) connected to the network and controlled by modified direct torque control during power system disturbances. The finite element model of DFIG is coupled with circuit models of frequency converter, transformer, network and control part in Matlab-Simulink. The transient currents and electromagnetic torque obtained from DFIG finite element model are compared with the simulation results obtained by means of an equivalent circuit-based analytical model with constant lumped parameters. I. INTRODUCTION The wind-power doubly fed induction generators are nowadays more widely used especially in large wind farms. The main reason for the increase of number of wind turbines with DFIG connected to the national networks is mainly their ability to supply power at constant voltage and frequency while the rotor speed varies. DFIG wind turbine utilizes a wound rotor induction machine while the rotor winding is supplied from rotor-side frequency converter providing speed control together with terminal voltage and power factor control for the overall system. Due to the increase in the number of wind turbines connected to the network, the new network codes were issued prescribing how the wind generator has to support the network during the power disturbances in the network []. Therefore it is necessary to carry out accurate transient simulations in order to understand the impact of the power system disturbances on a wind turbine operation. The most common approach in dynamic modeling of DFIG wind turbines is using an analytical equivalent circuit based model of the doubly fed induction machine [2]-[6]. However, simple analytical models of DFIG usually don t represent magnetic saturation of the leakage and magnetizing inductance accurately or not at all. The saturation needs to be taken into account when simulating the transients in rotor and stator currents in order to get more accurate results. This paper presents the transient simulation analysis of a.7 MVA DFIG wind turbine under symmetrical network 3-phase short circuit The doubly fed induction generator is simulated by means of finite element method (FEM) whereas frequency converter, transformer, network and control part are modeled in Matlab-Simulink. The rotorside frequency converter is controlled by a modified direct torque control (DTC) control strategy. The rotor overcurrent protection, so called passive crowbar [7], which protects the rotor of DFIG and rotor-side frequency converter during network disturbances when the generator supports the network, is also included in circuit simulator. The transient stator current, rotor current and electromagnetic torque calculated by means of DFIG finite element method model are compared with simulation results obtained by means of an equivalent circuit based analytical model with constant lumped parameters. II. FINITE ELEMENT MODEL OF DFIG The FEM computation is based on two-dimensional vector potential formulation coupled with the voltage equations of the windings [9]. The magnetic vector potential A satisfies ( ν A) = J () where ν is the nonlinear reluctivity. The current density J is determined by Ni J = (2) S in a phase winding with cross section area S and N filaments carrying the current i, and A J = σ (3) t in solid conductors with conductivity σ. Since there are no damping bars in the rotor, (3) only contains the effect of eddy currents in the steel shaft. In the laminated iron core, conductivity is set to zero for simplicity. The voltage equations for the windings are in the form dψ di u = + Ri + Le (4) dt dt where R is the total resistance of the coil and L e is the additional end-winding inductance. The flux linkage ψ is determined by adding together the contributions of all coil sides in the winding nc ψ = β A l (5) k = ave k k k where n c is the total number of coil sides in the winding, β k is either positive or negative multiplier according to the orientation of the coil side k, A ave k is the average vector potential on the coil side and l k is the length of the coil side k. The sources of the field analysis are the voltages applied in the phase windings in stator and rotor. The magnetic vector potential and phase currents are obtained from the simultaneous solution of the above equations.

The electromagnetic torque T e is determined from the field solution using the virtual work principle d H Te = d dω dθ B H (6) Ω where θ is the position angle of the rotor and Ω is the cross section of the air gap. The magnetic flux density B and the magnetic field strength H are determined from the field solution in terms of A and ν. The angular speed and position of the rotor are solved from ω m = ( Te TL ) dt (7) J θ = ω m dt (8) where J is the moment of inertia and T L is the load torque. The movement of the rotor is modeled by modifying the air-gap mesh. The FEM computation is implemented as a functional block in Simulink using dynamically linked program code (S-function). Voltage of the phase windings in stator and rotor are given as input variables and the phase currents, electromagnetic torque, rotor position and flux linkage in stator and rotor are obtained as output variables. This is illustrated in Figure. Before the simulation, the initial magnetic field in the electrical machine is calculated by time-harmonic steadystate analysis when sinusoidal voltages and currents are assumed [9]. The information about the magnetic field and finite element mesh is stored in a text file or Matlab's MAT-file, which is read by the S-function in the beginning of the simulation. After the time-stepping simulation, the magnetic field is stored in a new file that can be used as the initial condition for a new simulation. In time-stepping simulation, the FEM computation is coupled with Simulink by weak coupling procedure. This means that the time-stepping FEM computation runs at major time steps, which are usually longer than the minor steps elsewhere in the system model in Simulink. Accordingly, output variables from FEM computation are kept constant during a period of several simulation steps in the total system model, and changes in the variables take effect with one-step delay. The procedure of the FEM calculation in major steps is characterized by Figure 2. In spite of the weak coupling, the accuracy of the coupled solution can be maintained by choosing the time steps appropriately according to the physical time constants. By using short steps in the converter model and longer steps in the FEM model, the time-stepping simulation is also more efficient, because the timeconsuming FEM solution is not determined too frequently. The finite element mesh of the DFIG covers one quarter of the cross section, comprising 949 nodes and 848 linear triangular elements. With quadratic elements, the number of nodes increases to 3745 and the computation time also increases remarkably. Nevertheless, the differences in the current and voltage waveforms are not very significant in comparison between linear and quadratic elements. The geometry of the model is presented in Figure 3, and the ratings of the DFIG are presented in Table I. phase voltage load torque : FEM computation (S-function) : : phase current electromagn. torque angular speed angular position flux linkage Figure.. Functional block of the FEM computation. t, u s, T L (from Simulink) Major or minor step? t k+ = t k + t FEM major step Field & circuit equations A, i s, i r (), (4) Stator flux & air-gap torque Ψ, T e (5), (6) Angular speed & position ω m, θ (7), (8) minor step i s, Ψ, T e, ω m, θ (previous step) i s, Ψ, T e, ω m, θ (new values) Figure 2. FEM calculation in time stepping analysis. Figure 3. Geometry of the DFIG model. TABLE I PARAMETERS OF THE DFIG P N rated power.7 MW U N,s rated stator voltage 69 V (delta) U max,r maximum rotor voltage 2472 (star) f N rated stator frequency 5 Hz n N nominal speed 5 rpm In normal use rotor voltage is proportional to slip

III. FREQUENCY CONVERTER AND CONTROL The Frequency converter that supplies the rotor of DFIG consists of two back-to-back connected voltage source inverters as it is depicted in Figure 4. Figure 4. Doubly fed wind-power induction generator with the crowbar. The network-side converter is represented in simulation by discrete transfer function H ( z ) = (9) + τ z s whereτ s denotes the time constant of the first order discrete filter. The aim of the control of the network side inverter is to maintain the level of DC-link voltage U dc on a pre-set value. U dc is controled by PI controler based algorithm. The control of the rotor side frequency converter is realized by a modified DTC strategy [8] as it is depicted in Figure 5. The magnitude of the rotor flux estimate ψ ˆ r is calculated by means of Torque and Flux estimator from the measured rotor currents i ra, i rb, as ψˆ = ( ψˆ ) + ( ψˆ ) () 2 2 r r _ x r _ y ˆ r _ x ψˆ r y where symbols ψ and _ denote the estimated rotor fluxes in the two axis reference frame fixed to the rotor. The rotor flux estimates are ψ = L i + L i () where i rx, ry ˆ r _ x r rx m sx _ r ˆ r _ y L r i ry L m i sy _ r ψ = + (2) i denote the rotor current components in the two-axis rotational reference frame and i sx _ r, isy _ r denote the stator currents in the rotational frame. The magnitude of the grid flux estimate ψˆ grid that is used in control for synchronization of DFIG with network is also calculated in Torque and Flux estimator from the measured stator currents i sa, i sb and stator voltages v sa, v sb. The estimate of electromagnetic torque that is an input of the three-level hysteresis comparator is given by 3 Tˆ ( ˆ ˆ e = p i y _ sψ x _ s ix _ sψ y _ s ) 2 (3) Where symbols i x _ s, iy _ s and ψ ˆ x _ s, ψ ˆ y _ s denote the stator currents and estimated stator fluxes respectively in two-axis stator frame. The reference value of the rotational speed ωr is considered to be constant. The reference value of rotor flux magnitude is obtained from the reference flux calculator as function of the power factor PF_ ref and electromagnetic torque reference value T e_ref. The torque and flux hysteresis comparators provide logical output that is used together with estimated rotor fluxes for switching pattern establishment defined by an optimal switching table. When the switching pattern is established, a voltage phasor is applied to the rotor and this voltage will change the rotor flux. The tangential component of the voltage vector controls the torque whereas the radial component increases or decreases the flux magnitude. Figure 5. The Block structure of the rotor side frequency converter controlled by modified DTC.

IV. ROTOR OVER-CURRENT PROTECTION The rotor over-current protection, so called passive crowbar, is connected between the rotor of DFIG and rotor side inverter. The crowbar eliminates high rotor currents during power systems disturbances when the stator of the generator can t be disconnected from the network and generator supports the network. The high currents are induced to the rotor from the stator side when stator-voltage sag due to the short circuit in the network is introduced. The crowbar circuit that was used in simulations consists of a diode bridge that rectifies the rotor phase currents and a single thyristor in series with a resistor R crow as it is depicted in Figure 6. Figure 6. The over-current protection (crowbar) connected between the rotor of DFIG and rotor-side frequency converter. The thyristor is turned on when the DC link voltage U dc reaches its maximum value. Simultaneously, the rotor circuit is disconnected from the rotor-side frequency converter and connected to the crowbar. The rotor remains connected to the crowbar until the main circuit breaker disconnects the stator from the network. V. MODEL OF THE NETWORK, TRANSFORMER AND TRANSMISSION LINE The network is modeled with three-phase voltage source in series with a short circuit inductance and reactance. The transmission line between the network and the transformer is modeled with its resistance and inductance. The transformer is represented by simple linear model, i.e. magnetic saturation was not taken into account. The transformer model contains a short circuit resistance and inductance and stray capacitance of the winding. VI. SIMULATION RESULTS The simulation analysis was carried out in Matlab Simulink. The control part, frequency converter, network, transformer and crowbar were modeled in Simulink whereas DFIG was modeled by FEM. The system simulator was running with the time step T step =.5-7 s and Forward Euler method has been used. The FEM model of DFIG was running with the time step T stepfem =.5-4 s. The operation of the.7 MVA DFIG before and during the fault in the network was investigated by applying a constant torque T ref = -.9 p.u. at constant speed.733 p.u. that represents a normal operational condition of wind-power DFIG. The equation of the movement was not included in the model. The network disturbance has been introduced at time 5.2 s. A symmetrical network 3-phase short circuit has been represented by the stator voltage dip when voltage drops down to 35% of the nominal value. Due to the transient current in rotor of DFIG, the DC-link voltage rises up and the crowbar thyristor is triggered by DClink over-voltage protection. At the time instance 5.3 s, the generator is disconnected from the network by opening the main circuit breaker. The simulation results are presented in per-unit system with the base values corresponding to the amplitudes of the respective quantities V base = 563 V, I base = 2.3 ka, T base =.9 knm. The turn s ratio from rotor to stator is t r = 3.6. Figure 7 depicts the detailed stator, rotor and DClink voltages during the network fault..5 Stator voltage A - phase Rotor voltage A - phase DC-link voltage vas var udc [p.u.].5 -.5 - -.5 4.9 4.95 5 5.5 5. 5.5 5.2 5.25 5.3 5.35 Figure 7. Stator voltage (dash), rotor voltage (solid) and DC-link voltage (dash dot) during network disturbance.

3.5 3 Stator current - A phase - FEM Stator current - A phase - analyt 2.5 ias [p.u.] 2.5.5 -.5-4.9 4.95 5 5.5 5. 5.5 5.2 5.25 5.3 5.35 Figure 8. Comparison of the transient stator current obtained from FEM model of DFIG (dash) and from analytical model (solid). 2 iar [p.u.] - -2-3 Rotor current - A phase - FEM Rotor current - A phase-analyt -4 4.9 4.95 5 5.5 5. 5.5 5.2 5.25 5.3 5.35 Figure 9. Comparison of the transient rotor current obtained from FEM model of DFIG (dash) and from analytical model (solid)..5 -.5 Te [p.u.] - -.5-2 Electromagnetic torque - FEM Electromagnetic torque - analyt -2.5-3 4.9 4.95 5 5.5 5. 5.5 5.2 5.25 5.3 5.35 Figure. Comparison of the transient electromagnetic torque from FEM model of DFIG (dash) and from analytical model (solid). Figures 8 and 9 show comparison of the transient stator and rotor current respectively obtained from FEM model of DFIG and from analytical model. The time variation of the transient electromagnetic torque obtained by means of FEM model that is compared with the transient electromagnetic torque calculated by analytical model is depicted in Figure.

VII. DISCUSSION OF THE RESULTS Figure 7 shows the stator, rotor and DC-link voltage when the network fault is introduced. The network fault causes that amplitude of the stator voltage to drop down to 35% of the nominal value. The high transient currents in the stator and rotor will cause an increase of the DClink voltage that reaches a maximum value and the control disconnects the rotor from the frequency converter and connects the crowbar to the rotor circuit. After disconnection from frequency converter and connection to the passive crowbar, the DC-link voltage decreases slowly, and after slow transition caused by the control, reaches the nominal value. Shape of the rotor voltage is changed from pulse-modulated waveform to rectified waveform when the crowbar starts to conduct. The stator transient currents obtained from FEM and analytical model with constant lumped parameters depicted in Figure 8 show the difference of.5 p.u. that is about ka at the beginning of the transient. The difference is smaller between 5.5-5.2 s. After the generator reaches a new steady state, the simulated stator currents obtained by FEM model and by analytical model show perfect agreement A Similar situation occurs when comparing the transient rotor currents depicted in Figure 9. During the first peak of the rotor current, the difference between FEM and analytical model is almost.6 p.u., that is around.5 ka. The difference between the simulated rotor currents obtained from two different models decreases when the DFIG reaches a new steady state. Figure compares electromagnetic torques calculated by FEM and by means of simple analytical model with constant lumped parameters. The agreement between simulation results is very good except for the beginning of the transient when the difference is around.5 p.u. between FEM and analytical model. All the comparisons of the simulation results show that especially in the beginning of the transient the amplitude of the transient current and torque calculated by FEM model is higher than in case of the simple analytical model with constant lumped parameters. This is mainly due to effect of saturation in stator and rotor leakage inductance that is taken in to account in FEM model. VIII. CONCLUSIONS The transient behavior of a doubly fed wind-power induction generator connected to the network and controlled by modified direct torque control during power system disturbances has been studied. The coupled field-circuit model has been used in simulation. The transient currents and electromagnetic torque obtained from FEM model of wind-power doubly fed induction generator were compared with the simulation results obtained by means of T equivalent circuit based analytical model with constant lumped parameters. The comparison shows that the transient stator and rotor currents as well as electromagnetic torque have higher peak values in the beginning of the transient in comparison with the analytical model. This is mainly due to effect of the stator and rotor leakage inductances saturation that is taken into account in FEM. The developed simulator is a useful tool in of windpower doubly fed induction generators and power electronics used for control of the generator as well as for transient simulation studies. Acknowledgement The National Technology Agency of Finland, ABB Oy and Fortum Oyj supported this work. Slavomir Seman thanks to Tekniikan edistämissäätiö and Fortum Foundation for financial support. REFERENCES [] E.ON Netz, Ergänzende Netzanschlussregeln fur Windenergieanlagen, Dec. 2, Germany [2] Ekanayake J. B., Holdsworth L., Wu X. G., Jenkins N., Dynamic Modeling of Doubly Fed Induction Generator Wind Turbines, IEEE Transaction on Power Systems, Vol. 8. No. 2, May 23, pp. 83 89. [3] Slootweg J. G., Polinder H., Kling W. L, Dynamic Modeling of a Wind Turbine with Doubly Fed Induction Generator Proc. of 2 IEEE Power Engineering Society Summer Meeting, Vol., pp. 644 649. [4] Holdsworth L., Wu X. G.; Ekanayake J. B., Jenkins N.: Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances IEE Proceedings - Generation, Transmission and Distribution, Volume: 5, Issue: 3, 3 May 23, pp. 343 352. [5] Tapia A., Tapia G., Ostolaza J.X.,. Saenz J. R: Modeling and control of a wind turbine driven doubly fed induction generator IEEE Transactions on Energy Conversion, Volume: 8, Issue: 2, June 23, pp. 94 24. [6] Koessler R., Pillutla S, Trinh L., Dickmander D., Integration of large wind farms into utility grids (Part - Modeling of DFIG), Proc. of 23 IEEE PES General Meeting. [7] Niiranen J., Voltage Dip Ride Through of Doubly-fed Generator Equipped with Active Crowbar, presented at Nordic Wind Power Conference 24, -2 March 24, Chalmers University of Technology, Göteborg, Sweden. [8] Seman S., Niiranen J., Kanerva S., Arkkio A., Analysis of a.7 MVA Doubly Fed Wind-Power Induction Generator During Power Systems Disturbances, presented at NORPIE 24, 4-6 June 24, Norwegian University of Science and Technology, Trondheim, Norway [9] Arkkio, A.: 'Analysis of induction motors based on the numerical solution of the magnetic field and circuit equations', Doctoral Thesis, Acta Polytech. Scand. Electr. Eng. Ser., No. 59, 987, Helsinki, Finland, 97 p. http://lib.hut.fi/diss/98x/isbn9522676x/