Sendai Water Pipeline Response to the 2011 Tohoku Earthquake

Similar documents
Department of Urban Environment Systems, Chiba University, Japan. Kajima Technical Research Institute, Kajima Corporation Co., Ltd., Japan.

Estimation of Damage Ratios of Wooden Houses and Water Distribution Pipelines in an Earthquake Scenario for the Tokyo Metropolitan Region

To estimate damage ratios of water and gas distribution pipes, fragility curves were empirically obtained based on damage datasets after the 1995 Kobe

DAMAGE ANALYSIS OF WATER SUPPLY PIPES DUE TO THE 2004 NIIGATA-KEN CHUETSU, JAPAN EARTHQUAKE ABSTRACT

NATIONWIDE SITE AMPLIFICATION ZONATION STUDY USING JAPAN ENGINEERING GEOMORPHOLOGIC CLASSIFICATION MAP

EVALUATION OF SITE AMPLIFICATIONS IN JAPAN USING SEISMIC MOTION RECORDS AND A GEOMORPHOLOGIC MAP

REPORT ON THE TOHOKU AREA PASIFIC OFFSHORE EARTHQUAKE

Keywords: Tohoku earthquake, Liquefaction, Hot spot, Pipeline damage, Topographic history

Semi-automated landform classification for hazard mapping of soil liquefaction by earthquake

SEISMIC VULNERABILITY OF A WATER-SUPPLY PIPELINE BASED ON THE DAMAGE ANALYSIS OF TWO EARTHQUAKES DURING THE GREAT EAST JAPAN EARTHQUAKE

PREDICTION OF AVERAGE SHEAR-WAVE VELOCITY FOR GROUND SHAKING MAPPING USING THE DIGITAL NATIONAL LAND INFORMATION OF JAPAN

Developing a 7.5-sec site-condition map for Japan based on geomorphologic classification

Study of the liquefaction phenomenon due to an earthquake: case study of Urayasu city

RELATIONSHIP BETWEEN AGE OF GROUND AND LIQUEFACTION OCCURRENCE IN THE 2011 GREAT EAST JAPAN EARTHQUAKE

ESTIMATION OF LANDFORM CLASSIFICATION BASED ON LAND USE AND ITS CHANGE - Use of Object-based Classification and Altitude Data -

Comparison of Mitigation Alternatives for Water Distribution Pipelines Installed in Liquefiable Soils. Donald Ballantyne 1 William Heubach 2

KNOWLEDGE NOTE 5-1. Risk Assessment and Hazard Mapping. CLUSTER 5: Hazard and Risk Information and Decision Making. Public Disclosure Authorized

A Study on the Risk Assessment of Emergency Supplies. Transportation Routes Considering Scenario Earthquakes

STUDIES ON SEVARAL COUNTERMEASURES AGAINST LIQUEFACTION-INDUCED FLOW AND AN APPLIVATION OF A MEASURE TO EXISTING BRIDGES IN TOKYO

Estimation of Seismic Shutoff of Intelligent Gas Meters in the Tokyo Metropolitan Area

PROBABILISTIC SEISMIC HAZARD MAPS AT GROUND SURFACE IN JAPAN BASED ON SITE EFFECTS ESTIMATED FROM OBSERVED STRONG-MOTION RECORDS

4-3-1 Earthquake and Tsunami Countermeasures of Tokyo s

UPLIFT OF SEWAGE PIPES DURING THE 2007 NIIGATAKEN- CHUETSU-OKI EARTHQUAKE

Earthquakes and Earth s Interior

An analysis on the relationship between land subsidence and floods at the Kujukuri Plain in Chiba Prefecture, Japan

REAL-TIME ASSESSMENT OF EARTHQUAKE DISASTER IN YOKOHAMA BASED ON DENSE STRONG-MOTION NETWORK

RISK OF EARTHQUAKE DAMAGE ON RESIDENTIAL FILL LAND

Hawke s Bay Liquefaction Hazard Report - Frequently Asked Questions

ANALYTICAL STUDY ON SOIL-PIPELINE INTERACTION DUE TO LARGE GROUND DEFORMATION

Soil liquefaction and slope failures during the 2011 Tohoku, Japan Earthquake

BROADBAND STRONG MOTION SIMULATION OF THE 2004 NIIGATA- KEN CHUETSU EARTHQUAKE: SOURCE AND SITE EFFECTS

SHAKING AND GROUND FAILURE-INDUCED DAMAGE TO BUILDINGS BY THE 2010 AND 2011 CHRISTCHURCH EARTHQUAKES AND ITS LESSONS

Ground motion intensity map of the Tainan earthquake (Central Weather Bureau).

SEISMIC HAZARD ASSESSMENT FOR JAPAN AFTER THE 2011 TOHOKU-OKI MEGA-THRUST EARTHQUAKE (Mw9.0)

Damage Estimation of the Road Bridge Structure Using the Seismic Hazard map for BCM in Hokkaido, Japan

Surviving the Big One: Understanding and Preparing for a Major Earthquake in Western Oregon

Prevention Tsunami wall 10m high (breached by the tsunami due to land level falling by 3m)

S. Toda, S. Okada, D. Ishimura, and Y. Niwa International Research Institute of Disaster Science, Tohoku University, Japan

RELATIONSHIP BETWEEN DAMAGE RATIO OF EXPRESSWAY EMBANKMENT AND SEISMIC INTENSITY IN THE 2004 MID-NIIGATA EARTHQUAKE

Important Concepts. Earthquake hazards can be categorized as:

Design of Safety Monitoring and Early Warning System for Buried Pipeline Crossing Fault

Tsukuba, Japan International Institute of Seismology and Earthquake Engineering Building Research Institute STUDY TRIP TO ITAKO CITY

Special feature: Are its lessons being adequately applied? Follow-up on the ten-year anniversary of the Hanshin-Awaji Earthquake

Physical Geography of East Asia

Seismic Activity and Crustal Deformation after the 2011 Off the Pacific Coast of Tohoku Earthquake

Tatsuo Sekiguchi* and Hiroshi Sato*

International Journal of Modern Trends in Engineering and Research e-issn No.: , Date: April, 2016

ESTIMATION OF SITE AMPLIFICATION FACTORS USING STRONG MOTION RECORDS OF HOKKAIDO

Three Fs of earthquakes: forces, faults, and friction. Slow accumulation and rapid release of elastic energy.

RESIDENTIAL DAMAGE IN IBARAKI DURING THE GREAT EASTERN JAPAN EARTHQUAKE

Earthquake Loss Estimation Techniques for Pipelines. Donald Ballantyne, P.E. 1

THE 2011 TOHOKU EARTHQUAKE IN JAPAN. VSU Lyuben Karavelov, Sofia, Bulgaria. Key words: Tohoku earthquake, strong ground motion, damage

Geology 229 Engineering Geology Lecture 27. Earthquake Engineering (Reference West, Ch. 18)

EVALUATION OF SITE AMPLIFICATION AND PHASE EFFECTS IN KUSHIMOTO TOWN, WAKAYAMA PREFECTURE, JAPAN


Forces in Earth s Crust

Wainui Beach Management Strategy (WBMS) Summary of Existing Documents. GNS Tsunami Reports

Earthquakes. Earthquake Magnitudes 10/1/2013. Environmental Geology Chapter 8 Earthquakes and Related Phenomena

Field Investigation and Dynamic Analysis of Damaged Structure on Pile Foundation during the 2011 off the Pacific Coast of Tohoku Earthquake

Earthquake Source. Kazuki Koketsu. Special Session: Great East Japan (Tohoku) Earthquake. Earthquake Research Institute, University of Tokyo

INTRODUCTION. Climate

How to communicate Cascadia Subduction Zone earthquake hazards

Japan Seismic Hazard Information Station

COMPARISON OF ACCELERATION AND LIQUEFACTION POTENTIAL ESTIMATED BY RSPM WITH OBESERVED ONES DURING THE 2011 GREAT EAST JAPAN EARTHQUAKE

Unit 7.2 W.E.D. & Topography Test

- Information before strong ground motion -

Study on the Mechanism of the Damaged Housing Lots during the 2011 Tohoku - Pacific Ocean Earthquake in Japan

Magnitude 6.3 SOUTH ISLAND OF NEW ZEALAND

Resiliency of Power Grids After Earthquakes

The 2011 Tohoku earthquake and dams

Roles of natural levees in the Ara River alluvial fan on flood management

Analysis of Liquefaction-Induced Lateral Spreading Data from the 2010 Darfield and 2011 Christchurch Earthquakes

PILE FOUNDATION RESPONSE DUE TO SOIL LATERAL SPREADING DURING HYOGO-KEN NANBU EARTHQUAKE

Department of Civil Engineering, Kyoto University, by Shunzo OKAMOTO, M. J. A., Sept.

Plate Tectonics IDEA THAT EARTH S SURFACE IS BROKEN INTO PLATES THAT MOVE AROUND. Fault = fracture in the crust where the movement has occurred

Application of a GIS for Earthquake Hazard Assessment and Risk Mitigation in Vietnam

Comparison between predicted liquefaction induced settlement and ground damage observed from the Canterbury earthquake sequence

Unit 7: Dynamic Planet: Earthquakes & Volcanoes

Debris flow: categories, characteristics, hazard assessment, mitigation measures. Hariklia D. SKILODIMOU, George D. BATHRELLOS

SEISMIC VULNERABILITY CURVES OF CAST IRON BURIED PIPELINES

Plates & Boundaries The earth's continents are constantly moving due to the motions of the tectonic plates.

Estimation of Deep Shear-Wave Velocity Profiles in Lima, Peru, Using Seismometers Arrays

Xiang Wen, & Takahashi Toru Chiba University, Chiba City, Japan. Katada Masaki Kyoto University, Kyoto, Japan

Applying Hazard Maps to Urban Planning

NGIAs' roles in successful disaster response

Analysis of Ignitions Following 2011 Tohoku Earthquake Using Kawasumi Model DRAFT

PROBABILISTIC LIQUEFACTION HAZARD ANALYSIS IN JAPAN

PRELIMINARY STUDY OF GROUND MOTION CHARACTERISTICS IN FURUKAWA DISTRICT, JAPAN, BASED ON VERY DENSE SEISMIC-ARRAY-OBSERVATION

Natural hazards in Glenorchy Summary Report May 2010

SEISMIC ZONING FOR GROUND MOTION IN TOKYO BASED ON NATION-WIDE ELECTRIC GEOTECHNICAL DATABASE SYSTEM

A physical feature of the Earth s surface

Preliminary report of the 2011 off the Pacific coast of Tohoku Earthquake *

Y. Shioi 1, Y. Hashizume 2 and H. Fukada 3

ASIAN JOURNAL OF CIVIL ENGINEERING (BUILDING AND HOUSING) VOL. 10, NO. 5 (2009) PAGES **-**

Residual Deformation Analyses to Demonstrate the Effect of Thin Steel Sheet Piles on Liquefaction-Induced Penetration Settlement of Wooden Houses

AVERAGE AND VARIATION OF FOCAL MECHANISM AROUND TOHOKU SUBDUCTION ZONE

EXTRACTION OF FLOODED AREAS DUE THE 2015 KANTO-TOHOKU HEAVY RAINFALL IN JAPAN USING PALSAR-2 IMAGES

Damage of Sewage Plant by Tsunami

LIQUEFACTION HISTORY, , IN JAPAN

Damage and Restoration of Drinking Water Systems Caused by 0206 Tainan Earthquake and Future Mitigation Measures

Transcription:

Journal of Civil Engineering and Architecture 10 (2016) 461-470 doi: 10.17265/1934-7359/2016.04.009 D DAVID PUBLISHING Sendai Water Pipeline Response to the 2011 Tohoku Earthquake Kazue Wakamatsu 1, Shigeru Nagata 2, Yoshihisa Maruyama 3 and Kyoko Ozawa 4 1. Department of Civil Engineering, Kanto Gakuin University, Yokohama 236-8501, Japan 2. Disaster Prevention and Wind Engineering Group, Kajima Technical Research Institute, Kajima Corporation, Tokyo 182-0036, Japan 3. School of Engineering, Chiba University, Chiba 263-8522, Japan 4. Department of Integrated Research on Disaster Prevention, National Research Institute for Earth Science and Disaster Prevention, Tsukuba 305-0006, Japan Abstract: Damage caused by the 2011 Tohoku Earthquake (M w 9.0) to transmission and distribution pipelines in Sendai City is summarized. The locations of the pipeline repairs are discussed relative to earthquake intensity, geomorphologic conditions and landform change in the developed areas of hilly land. Repair rate (repairs/km) is summarized according to pipe material and presence or absence of artificial landform change. The following findings were obtained: (1) More than 80% of the repairs took place in pipelines installed in higher lands such as hill and terrace areas consisting of hard soils; (2) Nearly all the pipe repair locations in hill areas are where landform change was made through land development for residential purposes over the past several decades; (3) The aforementioned repair rate was more than 3.6 times than that of other lowland areas where no landform change occurred. The heaviest concentrations of pipe repairs of vinyl chloride pipes and ductile iron pipes were observed within the boundary area between cutting and filling, having a thickness between 2.5 m and 2.5 m. Approximately 78% of the all pipe repairs occurred outside of areas where severe ground failures took place. A mechanism of pipe damage in the areas free of severe ground failure was discussed. Key words: Water pipeline damage, the 2011 Tohoku Japan Earthquake, developed land, landform change, landslide. 1. Introduction Sendai City is the most densely inhabited city in the Tohoku Region, the northern part of Japan s main island Honshu, which was severely affected by the M w 9.0 Tohoku Earthquake of March 11, 2011 (officially named the 2011 off the Pacific Coast of Tohoku Earthquake by the Japanese Meteorological Agency). A 4,458-km water supply network in the city suffered extensive damage, with 1,064 locations seriously affected, resulting in cutoffs of water supply to approximately 230,000 households just after the earthquake. The damage to the water supply network included 437 transmission and distribution pipes, 522 water supply pipes and 105 pieces of auxiliary Corresponding author: Kazue Wakamatsu, professor, research field: geotechnical earthquake engineering. equipment, i.e., air valves, hydrants, pressure reducing valves, etc. Buried pipelines including water pipeline networks have been severely damaged during past major earthquakes in urban areas. Main cause of damage was liquefaction-induced ground deformation in artificial fills and/or flood plains of rivers, except in some cases caused by earthquake ground shaking and surface faulting [1-12]. However, water pipelines in Sendai during the 2011 Tohoku Earthquake, most of the damaged pipelines were found to be located above low-lying land consisting of soft soil, in hilly residential land. There is no precedent for so many pipelines being damaged in hilly land in Japan, and possibly any other country in the world either, with only exception in the same

462 Sendai Water Pipeline Response to the 2011 Tohoku Earthquake area, Sendai, during the 1978 Miyagiken-oki Earthquake [2]. In order to help preparation for future earthquakes, it is important to analyze the conditions at the damaged sites in the hilly land, especially the effects of artificial landform changes and their relation to occurrences of ground failures, because there are many of these types of residential land areas in Tokyo and its suburbs, as well as other metropolitan areas in Japan such as Nagoya and Osaka. In this study, damage caused by the 2011 Tohoku Earthquake (M w 9.0) to transmission and distribution pipelines in Sendai City is summarized. The effects of landform on pipeline damage are analyzed to find out the cause of damage in hilly land, focusing artificial landform changes by development. 2. Water Pipeline Response to the 2011 Tohoku Earthquake The City of Sendai, with a population over one million people and with an area of approximately 788 km 2, is the biggest city in the Tohoku Region of Japan. About 66% of the total area of the city is land covered with forests and farmland, and only 16% of the area is used as residential land [13]. On March 11, 2011, at 2:46 p.m. local time, a M w 9.0 earthquake struck along the subduction zone interface plate boundary between the Pacific and North American Plates. The earthquake was immediately followed by a large tsunami that inflicted widespread damage on eastern Japan s modern urban infrastructure, extending from northern Tohoku to the southern Kanto Region, an area that includes Sendai. Recorded horizontal ground motion accelerations ranged from 254 to 1,869 cm/s 2 and velocities ranged from 31 to 145 cm/s with JMA (Japan Meteorological Agency) intensities reaching 5 minor to 6 minor over large populated areas in Sendai [14, 15]. Water supply to approximately 230,000 households was suspended (affecting a population of 500,000 with a water outage rate of 50%) in Sendai; Eighteen days were required to restore water to all habitable service areas with the exception of tsunami affected and severe ground failure affected areas. This is a relatively short recovery period for an earthquake affected area [16]. The Sendai water system consists of eight water treatment plants and 14 water distribution plants, two pumping stations, and a 4458-km water distribution network. Although there was considerable damage to drainage facilities and civil engineering facilities, such as retaining walls and slopes in the yards, there was little functional damage at two water distribution plants [16]. In contrast, there was significant damage to water distribution pipelines. The 4458-km water pipeline network in the city suffered extensive damage, with 1,064 locations seriously affected; The damage to the pipeline network includes 437 transmission and distribution pipes (Fig. 1), 522 water supply pipes, and 105 pieces of auxiliary equipment. Table 1 presents a summary of damage to transmission and distribution pipes, water supply pipes and auxiliary equipment, showing that approximately 90% of the water transmission and distribution pipe repairs were in pipelines made of VP and DIP, and having diameters less than 150 mm. Furthermore, approximately Fig. 1 Repair of water distribution pipe with a diameter of 800 mm [16].

Sendai Water Pipeline Response to the 2011 Tohoku Earthquake 463 Table 1 Summary of water pipeline repairs and repair rate for the March 11, 2011 earthquake [16]. Water transmission and water distribution pipes Water supply pipes Auxiliary equipment Diameter (mm) Pipe material and number of repairs CIP DIP SP/SU VP LP PP GP Total Length (km) Repairs/km 75 0 0 3 147 2 3 6 161 695.6 0.23 75 0 17 1 77 - - - 95 439.1 0.22 100~150 0 74 6 73 - - - 153 2,236.4 0.07 200~450 0 23 1 - - - - 24 861.6 0.03 500 0 3 1 - - - - 4 225.5 0.02 Subtotal 0 117 12 297 2 3 6 437 4,458.0 0.09 75 0 0 11 113 249 97 45 515 164.57 3.13 75 0 1 0 5 0 0 0 6 6.70 0.90 100~150 0 0 0 1 0 0 1 4.54 0.22 Subtotal 0 1 0 119 249 97 45 522 175.81 2.97 Fire hydrant 0 4 0 3 0 0 0 7 Air valve 0 38 16 2 0 0 0 56 Sluice valve 0 6 2 11 0 0 0 19 Diversion valve 0 12 0 10 0 0 0 22 Water shutoff valve 0 0 0 1 0 0 0 1 Subtotal 0 60 18 27 0 0 0 105 CIP (cast iron pipe); DIP (ductile cast iron pipe); SP (steel pipe); SU (stainless steel pipe); VP (vinyl chloride pipe); LP (lead pipe); PP (Polyethylene pipe); GP(galvanized iron plating pipe). Sendai St. Tsunami inundated area Fig. 2 Map of water transmission and distribution network (black lines) and repair locations in Sendai City during the March 11, 2011 earthquake superimposed on areas of tsunami inundation [17] and the estimated PGV distribution [18]. 99% of the water supply pipe repairs were in pipelines made of VP, LP, PP, and GP, having diameters less than 75 mm. Fig. 2 shows a map of the water transmission and distribution system including repair locations in Sendai City during the 2011 earthquake superimposed

464 Sendai Water Pipeline Response to the 2011 Tohoku Earthquake Table 2 Summary of water pipe repairs and repair rate by material for the March 11, 2011 earthquake [16]. Material N. of repairs Pipe length(km) Repairs/km Cast iron (CIP) 0 14.4 0 Ductile cast iron (DIP)* 117 2,723.1 0.04 Steel/Stainless steel 12 137.3 0.09 Vinyl chloride (VP) 297 1,514.5 0.20 Lead (LP) 2 3.4 0.59 Polyethylene (PP) 3 52.7 0.06 Galvanized iron plating (GP) 6 4.9 1.22 Total 437 4,458.0 0.10 *No damage was observed in ductile cast iron pipe connected with earthquake proof joints. even with the longest pipe length of 2,723.1 km, corresponding to 61% of the total length of the water pipes. In addition, no damage was found in DIP with earthquake proof joints (Fig. 3). 3. Relationship between Locations of Pipe Repairs and Geomorphologic Conditions Fig. 3 150 mm-diameter DIP pipe with earthquake proof joints that survived the tsunami [16]. on areas of tsunami inundation [17] and the distribution of PGV (peak ground velocity) with a 250-m spatial resolution for the main event of the earthquake [18]. The PGV distribution was estimated by means of a spatial interpolation procedure, using the strong ground observation records [19]. It can be seen in Fig. 2 that the highest concentrations of damage were in the inland areas of the city where the PGVs are substantially lower than those of the coastal areas or outside tsunami inundated areas. Table 2 displays the number of repairs, pipe length, and repair rate (repairs/km) in the Sendai water distribution network differentiated by pipe material. The repair rate for GP was the highest among all the materials followed by LP, whereas no damage was found in CIP. The repair rate for DIP was fairly low, First, the distribution of pipe repairs was superimposed on geomorphological classification map to understand the ground conditions of damaged sites. Fig. 4 shows the locations of pipe repairs and the water distribution network superimposed on the 7.5-sec JEGM (Japan Engineering Geomorphologic Classification Map), which is a nationwide site condition map based on the geomorphologic classification for various kinds of hazard mapping [20]. The damage to pipes was spread across hills (moss green), gravelly terraces (orange) and lowlands such as deltas and coastal lowlands (sky blue), alluvial fans (yellow-green), and back marsh (green). The pie chart of Fig. 5 shows percentages of pipe repairs according to geomorphologic land classification, in which other lowlands include alluvial fans, natural levees, back marshes, and delta and coastal lowlands. Fig. 5 indicates that 69% and 12% of the pipe repairs took place in pipelines installed in hill and terrace areas, respectively. This implies that most of the damaged pipelines were located not on low-lying land consisting of soft soils, but on higher land consisting of hard soils.

Sendai Water Pipeline Response to the 2011 Tohoku Earthquake 465 Tsunami-inundated area [7] Fig. 4 Locations of pipe repairs and the water distribution network (black lines) superimposed on the 7.5-sec Japan Engineering Geomorphologic Classification Map [20]. N = 437 Hill Terrace Valley bottom lowland Other lowlands Fig. 5 Percentage of pipe repairs according to geomorphologic land classification. 4. Effects of the Landform to Pipe Damage 4.1 Methodology of Landform Interpretation In this study, we examined whether changes in landforms had occurred at 437 locations of water transmission and distribution pipe repair by comparing the present topographic maps [21] and 5-m DEM (grid digital elevation model) [22] with old maps drawn before land development had begun. The old maps include 1:25,000 and 1:3,000 scale topographic maps surveyed in 1928 and 1964. The surface elevation prior to land development was examined by reading the old topographic maps. In general, the leveling accuracy for the old topographic maps is an approximately one third contour interval, that is, roughly 3.3 m and 70 cm, respectively. That for 5-m DEM is 15 cm [22]. 4.2 Effects of the Artificial Landform Change Fig. 6(a) shows the locations of pipe repairs and pipelines superimposed on an old topographic map surveyed in 1964, before development. It should be noted that the hill area is dissected by many small valleys and streams. The land development of the hilly land in Sendai started in the early 1950s, and gradually extended toward the areas surrounding the old urban district. Fig. 6(b) shows locations of pipe repairs superimposed on the topographic map after the land was developed for residential purposes. The area was typically developed by cutting and leveling the hill and then filling the valleys with soil from the excavated areas of the hills. Therefore, there are two general types of subsurface conditions in the hilly land

466 Sendai Water Pipeline Response to the 2011 Tohoku Earthquake pipeline pipeline (a) (b) Fig. 6 Locations of pipe repairs and pipeline network in Sakuragaoka superimposed on topographic maps: (a) topographic map of 1:3,000 scale surveyed in 1964 (before development); (b) topographic map at present. relatively low area such as a valley, or by cutting and leveling a relatively high area such as a hill ridge. Therefore, the thickness of the cutting and filling at a total of 339 locations of pipe repairs was investigated in the developed area. The surface elevation before and N=437 N = 437 22% 78% Areas of landform change Areas of no landform change Fig. 7 Percentages of landform change at the locations of water transmission and distribution pipeline repairs. Areas of no landform change Areas of landform change 0.2 Repair rate (Repairs/km) of Sendai: (1) natural soils of the original or excavated surface of the hill, which are associated with the volcanic pumice flow deposit overlying Neocene sedimentary or volcanic bedrocks; (2) fills consisting mainly of the volcanic pumice flow deposited on the valleys in the hill. Areas underlain by these different profiles might behave differently during the earthquakes. The pie chart in Fig. 7 shows the percentages of landform change at the locations of the 437 pipe repairs, indicating that 78% of the pipe repairs took place in pipelines installed in the developed areas where landform change was made by cutting and filling. The bar chart in Fig. 8 shows the repair rate of water transmission and distribution pipelines of different geomorphological categories, including percentages of artificial landform change within each category. Nearly all the pipe repair locations in the hill area had undergone landform changes, and the repair rate was more than 3.6 times that of other lowland area without landform change. Two third of the pipe repair locations in the terrace area also had landform changes. 2 0.1 N=437 N = 437 300 10 0 17 36 4 69 4.3 Effects of Fill Thickness Subsurface ground conditions in the developed areas of hilly land were primarily determined by assessing whether the land was developed by filling a Fig. 8 Repair rate for water distribution network for different geomorphological units to differentiated whether landform change had done or not (number on the bar graph shows the number of pipe repairs).

Sendai Water Pipeline Response to the 2011 Tohoku Earthquake 467 after land development was evaluated in the method previously described. The locations where current elevation was higher than before land development were considered to be fill areas in the hill, whereas the locations where elevation was lower than before land development were considered to be cut areas. Thus, the thicknesses of the fillings and cuttings were estimated based on the differences between surface elevations before and after development. Fig. 9(a) shows the relationship between the thickness of the cut and fill, the number of pipe repairs of VP, and the different pipe diameters, in which negative values represent thicknesses of cutting and positive values represent those of filling. It can be seen from Fig. 9(a) that the heaviest concentration of damage was observed within the boundary area between cutting and filling, with a thickness ranging from 2.5 m to 2.5 m. Damage to pipelines, in general, was observed in many fill areas, but was less common in cut areas, regardless of pipe diameter. Fig. 9(b) depicts the relationship between the thickness of the cut and fill, the number of pipe repairs of DIP, and the different pipe diameters, showing that the heaviest concentration of damage was also found within the boundary area between cutting and filling. Larger pipes with diameters exceeding 200 mm required repairs only within the boundary area and fill areas having a thickness of 10 m or less. Figs. 9(a) and 9(b) imply that the performance of the fills placed on the natural ground of hilly areas is directly related to the pipeline damage. 4.4 Effects of Ground Failures to Pipe Damage Significant ground failures occurred in many places in the developed areas of hilly land in Sendai. Ground failures include landslides, slope failures and collapsing of retaining walls (Fig. 10). A lot of pipes damaged due to ground failures reached 5,080 [23]. However, many repairs in the entire area of Sendai, approximately 78% of the total 437 repairs, occurred outside of the area where severe ground failures took place. Figs. 11(a) and 11(b) show the relationship between the thickness of the cut and fill in the hilly land, the areas affected by ground failures [24], and the number of pipe repairs of VP and DIP, respectively. A number of repairs occurred outside of the areas where the severe ground failures occurred, although most of the ground failures were found to occur in fill areas. In contrast, no significant liquefaction induced Number of repairs 60 50 40 30 20 Cut areas Pipe diameter (mm) φ25 φ30 φ40 φ50 φ75 φ100 Boundary areas Fill areas N=238 N = 238 Number of repairs 35 30 25 20 15 10 Cut areas Pipe diameters (mm) φ75 φ100 φ150 φ200 φ250 φ300 φ800 Boundary areas Fill areas N N=88 = 10 5 0 0 Thickness of cut of cut and and fill (m) fill (m) Thickness of of cut cut and and fill fill (m) (m) (a) (b) Fig. 9 Relationship between thickness of the cut/fill and number of pipe repairs, for different pipe diameters: (a) VP; (b) DIP.

468 Sendai Water Pipeline Response to the 2011 Tohoku Earthquake ground failures were observed in the city. Superimposing the locations of pipeline repairs on liquefaction grid cells of approximately 250 m 2 containing any site of liquefaction [18], only 7% of the 437 pipe repairs were within the liquefaction grid cells. 5. Possible Mechanism of Pipe Damage Outside of the Major Ground Failure Area Fig. 10 Large crack due to landslide in Midorigaoka, where a 100 mm-diameter DIP was broken (courtesy of Sendai City). Number of repairs Number of repairs 60 50 40 30 20 10 0 35 30 25 20 15 10 Cut areas Area little affected by ground failures Area affected by ground failures Boundary areas N N=238 = Thickness of cut and and fill fill (m) (m) (a) Cut areas Area little affected by ground failures Area affected by ground failures Boundary areas Fill areas Fill areas N N=88 = Fig. 12 shows an example of a pipe repair location where no severe ground failure was observed. The current surface elevation is around 40 m above sea level, and the thickness of the fill was estimated to be more than 10 m. A VP having a diameter of 75 mm was repaired here. The ground surface displayed a gentle slope and wavy deformation after the earthquake, as shown in the Fig. 12. The pattern of ground deformation suggests that a small amount of lateral spreading of the fill took place from the valley head to land downstream, as shown in Figs. 13(a) and 13(b). Fig. 14 illustrates a cross section of the pipe repair site shown in Fig. 12, depicting the ground surfaces both before and after land development. It can be seen that the pipe repair occurred in the fill area near the boundary between cutting and filling, where the original landform before development was the slope of a V-shaped valley. This indicates that the pipeline crossing the margin of a lateral spread/slide is subjected to a bending force caused by the moving soil mass, and results in fracture as shown in Fig. 13(b). 5 0 Thickness of cut and fill (m) (m) (b) Fig. 11 Relationship between the thickness of the cut/fill and number of pipe repairs, for areas affected or not by ground failures: (a) VP; (b) DIP. Fig. 12 Pipe repair location where no severe ground failure was reported (Nankoudai 4-chome).

Sendai Water Pipeline Response to the 2011 Tohoku Earthquake 469 Pipe repair Fills placed on valley (a) Ground movement Water pipeline 25 (b) Fig. 13 Schematics of a typical pipe damage mechanism for an area free of ground failure: (a) cross-sectional view; (b) plane view. Elevation (m) Distance (m) Fig. 14 Cross-section along the pipeline across a valley in Nankoudai 4-chome. 6. Conclusions Before development After development 2011 pipe repair This study investigated damage to water transmission and distribution pipelines in Sendai City caused by the 2011 Tohoku Earthquake, specifically with respect to landform changes in developed areas of hilly land. The principal findings include: (1) More than 80% of the 437 pipe repairs occurred in pipelines installed on hill and terrace areas consisting of hard soil; (2) Nearly all the pipe repair locations in hilly land are areas of landform change associated with land development for residential purposes over the past several decades. This repair rate was more than 3.6 times that of other lowlands having no landform change; (3) Concerning thicknesses of cuttings and fillings in developed land, the heaviest concentration of pipe repairs was observed within the boundary areas between cuttings and fillings between thicknesses of 2.5 m and 2.5 m. The second heaviest concentration occurred in fill areas, regardless of pipe material; (4) Many repairs, approximately 78% of the total 437 repairs, occurred outside of the area where severe ground failures took place; (5) A small amount of lateral spreading of the fill, assumed to move soil mass from the valley head in the downstream direction, resulted in breaking the pipeline at the margin of the lateral spread/slide, that is, the boundary between cutting and filling. Acknowledgments The authors wish to thank Mr. Masao Nishino and Seiichi Suzuki of Bureau of Waterworks of Sendai, who provided the damage database of Sendai water supply network associated with the 2011 Tohoku Earthquake. References [1] O Rourke, T. D., Beaujon, P. A., and Schowthon, C. R. 1992. Large Ground Deformations and Their Effects on Lifeline Facilities: 1906 San Francisco Earthquake. Technical report 2, NCEER-92-0002: 3.1-3.85. [2] Katayam, T., Masui, Y., Isoyama, R., and Jinnai, I. 1979. Effect of the Miyagiken-Oki Earthquake of June 12, 1978 on Water Supply Systems (Part 1). Seisan Kenkyu 31 (April): 213-9. (in Japanese) [3] O Rourke, T. D., Roth, B. L., and Hamada, M. 1992. Large Ground Deformations and Their Effects on Lifeline Facilities: 1979 San Fernando Earthquake. Technical report 2, NCEER-92-0002: 1.1-1.130. [4] O Rourke, T. D., Gowdy, T. E, Stewart, H. E., and Pease, J. W. 1995. Lifeline Performance and Ground Deformation in the Marina during 1989 Loma Prieta Earthquake. In Proceedings of the 3rd Japan-US Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures against Soil Liquefaction, 129-46. [5] Wakamatsu, K., Yoshida, N., Suzuki, N., and Tazoh, T. 1992. Liquefaction-Induced Large Ground Deformations and Their Effects on Lifelines during the 1990 Luzon,

470 Sendai Water Pipeline Response to the 2011 Tohoku Earthquake Philippine Earthquake. Technical report 1, NCEER-92-0001: 5.1-5.52. [6] Joint Reconnaissance Team of Architectural Institute of Japan, Japan Society of Civil Engineers, and the Japanese Geotechnical Society. 2001. Damage to Lifelines. Report on the damage investigation of the 1999 Kocaeli Earthquake in Turkey, 8.1-8.7. [7] O Rourke, T. D., Toprak, S., and Sano, Y. 1996. Los Angeles Water Pipeline System Response to the 1994 Northridge Earthquake. In Proceeding of the 6th Japan-US Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures against Soil Liquefaction, 1-16. [8] Shirozu, T., Yune, S., Isoyama, R., and Iwamoto, T. 1996. Report on Damage to Water Distribution Pipes Caused by the 1995 Hyogoken-Nanbu (Kobe) Earthquake. In Proceeding of the 6th Japan-US Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures against Soil Liquefaction Disaster Prevention for Lifeline System, 93-110. [9] Shih, B. J., Chen, W. W., Wang, P. H., Chen, Y. C., and Liu, S. Y. 2000. Water System and Natural Gas Pipeline Damages in the Ji-Ji Earthquake Calculating Repair Rates. In Proceedings of Taiwan-Japan Workshop on Lifeline Performance and Disaster Mitigation during Recent Big Earthquakes in Taiwan and Japan, 63-72. [10] Earthquake Investigation Committee of the Technical Council on Lifeline Earthquake Engineering, ASCE (American Society of Civil Engineers). 2013. Water and Wastewater System. In Chile Earthquake of 2010: Lifeline Performance, edited by Tang, A. K., and Eidinger, J. M. Virginia: ASCE. [11] Knight, S., Giovinazzi, S., and Liu, M. 2012. Impact and Recovery of the Kaiapoi Water Supply Network Following the September 4th, 2010 Darfield Earthquake, New Zealand. In Proceedings of the 15th World Conference on Earthquake Engineering, 1-10. [12] O Rourke, T. D., Jeon, S. S., Toprak, S., Cubrinovsk, M., Hughes, M., and Van Ballegooy, M., et al. 2014. Earthquake Response of Underground Pipeline Networks in Christchurch, New Zealand. Earthquake Spectra 30 (1): 183-204. [13] Sendai City. 2012. Data Sendai. Sendai City. Accessed October 19, 2012. http://www.city.sendai.jp/kikaku/seisa ku/yoran/data_sendai/index.html. (in Japanese) [14] NIED (National Research Institute for Earth Science and Disaster Prevention). 2011. Strong-Motion Seismograph Network (K-NET). NIED. Accessed January 26, 2014. http://www.kyoshin.bosai.go.jp. [15] Tohoku Institute of Technology. 2011. Strong-Motion Records Obtained by Small-Titan of Tohoku Institute of Technology during the 2011 Great East Japan Earthquake. Tohoku Institute of Technology. Accessed January 26, 2014. http://smweb.tohtech.ac.jp/smalltitan/e nglish/index.html. [16] Bureau of Waterworks of Sendai City. 2012. Restoration Record on Water Service in Sendai City Associated with the Great East Japan Earthquake. Bureau of Waterworks of Sendai City. Accessed January 23, 2013. http://www.suidou.city.sendai.jp/06_bousai/jisin7.html. (in Japanese) [17] Geospatial Information Authority of Japan. 2011. Tsunami Inundated Maps with a Scale of 1 to 25,000 during the 2011 off the Pacific Coast of Tohoku Earthquake. Geospatial Information Authority of Japan. Accessed July 28, 2011. http://www.gsi.go.jp/kikaku/kikaku40014.html. [18] Wakamatsu, K., and Senna, S. 2015. 650-km Long Zone of Liquefaction during the 2011 off the Pacific Coast of Tohoku, Japan Earthquake. In Proceedings of 6th International Conference on Earthquake Geotechnical Engineering, 1-9. [19] Matsuoka, M., Wakamatsu, K., Hashimoto, M., Senna, S., and Midorikawa, S. 2015. Evaluation of Liquefaction Potential for Large Areas Based on Geomorphologic Classification. Earthquake Spectra 31 (4): 2375-95. [20] Wakamatsu, K., and Matsuoka, M. 2013. Nationwide 7.5-Arc-Second Japan Engineering Geomorphologic Classification Map and Vs30 Zoning. Journal of Disaster Research 8 (5): 904-11. [21] Geospatial Information Authority of Japan. GSI Maps. Geospatial Information Authority of Japan. Accessed July 31, 2015. http://maps.gsi.go.jp/. [22] Geospatial Information Authority of Japan. 2011. 5-m Grid Digital Elevation Model. Geospatial Information Authority of Japan. Accessed May 18, 2012. http://fgd.gsi.go.jp/download/. [23] Sendai City. 2012. Map of Damaged Housing Lots. Sendai City. Accessed July 31, 2013. http://www.city.sen dai.jp/jutaku/takuchihisai_010.html. (in Japanese) [24] Sendai City. 2013. Current State of District Examined for Public Work Project. Sendai City. Accessed July 15, 2013. http://www.city.sendai.jp/jutaku/takuchihisai_020. html. (in Japanese)