Simple Improved Equations for Arc Flash Hazard Analysis

Similar documents
DC Arc Flash Analysis

Fault Calculation Methods

16 Appendix 16 Electrical Research Association Report

SWITCHGEAR: design concepts, testing, standards and safety of persons and installations

1. Explain the various methods of methods of grounding. In power system, grounding or earthing means connecting frame of electrical equipment (non-cur

Revision checklist SP10. SP10 Electricity and Circuits. SP10a Electric circuits. SP10b Current and potential difference

STUDIES ON LIGHTNING CHARACTERISTICS

Cahier Technique N 13 Principe de réduction des courants d enclenchement des transformateurs

EE 3120 Electric Energy Systems Study Guide for Prerequisite Test Wednesday, Jan 18, pm, Room TBA

You know for EE 303 that electrical speed for a generator equals the mechanical speed times the number of poles, per eq. (1).

Request Ensure that this Instruction Manual is delivered to the end users and the maintenance manager.

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Measurement of Electrical Resistance and Ohm s Law

Development of axial flux HTS induction motors

Mathematical Model of a Synchronous Machine under Complicated Fault Conditions

1P22/1P92 Exam Review Problems 2013 Friday, January 14, :03 AM. Chapter 20

Selecting the current rating for equipment

POWER FACTOR IN THE DIGITAL AGE A N E N V I R O N M E N T A L P O T E N T I A L S W H I T E P A P E R. Power Quality For The Digital Age

Chapter 15 Power And Harmonics in Nonsinusoidal Systems

Transient analysis of the behaviour of grounding systems consisted by driven rods

Document Number: SPIRE-UCF-DOC Issue 1.0. November Matt Griffin

Fundamentals of Electrical Circuit Analysis

Reactor Characteristic Evaluation and Analysis Technologies of JFE Steel

magneticsp17 September 14, of 17

Parallel Circuits. Chapter

Different Techniques for Calculating Apparent and Incremental Inductances using Finite Element Method

Phys 2025, First Test. September 20, minutes Name:

EA Guidelines on the Calibration of Temperature Indicators and Simulators by Electrical Simulation and Measurement

VKES. Contents. Page 2 No 213, 13th Main RBI Layout JP Nagar 7th Phase, Bangalore Vidyuth Kanti Engineering Services

Two point charges, A and B, lie along a line separated by a distance L. The point x is the midpoint of their separation.

V-I Characteristic Formulas of Voltage Limiting Type SPD and Their Applications

PH2200 Practice Final Exam Summer 2003

Computation of Electromagnetic Energy Absorption in the Human Body Tissues by High Frequency Structure Simulator

FACTORS AFFECTING SOIL CHARACTERISTICS UNDER FAST TRANSIENTS

B.E. / B.Tech. Degree Examination, April / May 2010 Sixth Semester. Electrical and Electronics Engineering. EE 1352 Power System Analysis

UNIVERSITY OF TECHNOLOGY, JAMAICA Faculty of Engineering and Computing School of Engineering

Physics 102 Spring 2007: Final Exam Multiple-Choice Questions

PhysicsAndMathsTutor.com

Basic Electricity Video Exam

Physics 1212 Exam #4A (Final)

ECE 420. Review of Three Phase Circuits. Copyright by Chanan Singh, Panida Jirutitijaroen, and Hangtian Lei, For educational use only-not for sale.

Physics 1212 Exam #4B (Final)

CHAPTER 20 ELECTRIC CIRCUITS

ELECTRICAL AND THERMAL DESIGN OF UMBILICAL CABLE

EMISSION SPECTROSCOPY

Film Capacitors. EMI suppression capacitors. Date: June 2018

An Innovative Simple Test Circuit for Single-Phase Short Circuit Making Test of High-Voltage Switching Devices

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM

ELECTRIC POWER CIRCUITS BASIC CONCEPTS AND ANALYSIS

GCSE ADDITIONAL SCIENCE PHYSICS

Physics 102 Spring 2006: Final Exam Multiple-Choice Questions

PRACTICE NO. PD-AP-1309 PREFERRED PAGE 1 OF 5 RELIABILITY PRACTICES ANALYSIS OF RADIATED EMI FROM ESD EVENTS CAUSED BY SPACE CHARGING

EXP. NO. 3 Power on (resistive inductive & capacitive) load Series connection

Bridge Measurement 2.1 INTRODUCTION Advantages of Bridge Circuit

The Effect of the Harmonics, the Fault Location and the Fault Resistance on the Performance of the Impedance-Type Distance Relay

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

Electromagnetic Induction Faraday s Law Lenz s Law Self-Inductance RL Circuits Energy in a Magnetic Field Mutual Inductance

MrN Physics Private Tuition in GCSE and A level Physics AQA GCSE Combined Science: Trilogy Physics (2016 onwards)

ECE 325 Electric Energy System Components 7- Synchronous Machines. Instructor: Kai Sun Fall 2015

THE INDIAN COMMUNITY SCHOOL, KUWAIT

By choosing to view this document, you agree to all provisions of the copyright laws protecting it.

Circuit Analysis for Power Engineering Handbook

A Roadmap for Evaluation of Lightning Elimination Technologies

Chapter 28. Direct Current Circuits

Project 1: Analysis of an induction machine using a FEM based software EJ Design of Electrical Machines

THE DIMENSIONING OF ELECTRICAL CONDUCTORS FOR USE IN "PANEL BOARDS" ADDRESSED TO HAZARDOUS AREAS - PART THREE

An Optimised High Current Impulse Source

Sensibility Analysis of Inductance Involving an E-core Magnetic Circuit for Non Homogeneous Material

SECTION 7: FAULT ANALYSIS. ESE 470 Energy Distribution Systems

THE UNIVERSITY OF NEW SOUTH WALES. School of Electrical Engineering & Telecommunications FINALEXAMINATION. Session

Jacob s Ladder Controlling Lightning

Industrial Electricity


Electromagnetic Oscillations and Alternating Current. 1. Electromagnetic oscillations and LC circuit 2. Alternating Current 3.

Copyright 1996, by the author(s). All rights reserved.

Effects of Capacitor Bank Installation in a Medium Voltage (MV) Substation

MAGNETIC HYSTERESIS MODELING AND VISUALIZATION FOR SPICE BASED ENVIRONMENTS

AR/IA 241 LN 231 Lecture 4: Fundamental of Energy

1 Phasors and Alternating Currents

Physics 196 Final Test Point

On the Emissivity of Silver Coated Panels, Effect of Long Term Stability and Effect of Coating Thickness

with embedded electrode

The electrical Discharge Characteristics of the 3.5 KJ Electrothermal Plasma Gun Experiment

Influence of the simulation model on the spatial arc resistance distribution of an axially blown switching arc

RLC Circuit (3) We can then write the differential equation for charge on the capacitor. The solution of this differential equation is

Circuits. PHY2054: Chapter 18 1

Maintenance/ Discontinued

Varistors to

Electroscope Used to are transferred to the and Foil becomes and

University of Moratuwa, Sri Lanka. EE3231: Design of Electrical Installation

Experiment 9 Equivalent Circuits

Measurement method for the proficiency testing program

Plasma Simulation in STAR-CCM+ -- towards a modern software tool

Physics 1252 Exam #3A

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Physics 214 Spring

THE EFFECT OF REVERSAL ON CAPACITOR LIFE

12 Chapter Driven RLC Circuits

Transcription:

Simple mproved Equations for Arc Flash Hazard Analysis Dr. obert Wilkins Electrical Engineering Consultant, Heswall, UK, bob@overdee.demon.co.uk Keywords: Arc flash analysis, arcing current, incident energy ntroduction The EEE standard 584 for performing arc-flash hazard calculations [] is based on a large number of tests in a steel box, intended to represent typical equipment. The arrangement is illustrated schematically in Fig.. Arcing was initiated by fine trigger fuse wires across the electrode tips to produce an arcing fireball, and the energy density at a distance d was measured using copper disc calorimeters. Formulae were derived from which the arcing current and incident energy can be estimated. n [] a 3-phase time-domain model of this arc Fig. Arc flash in an open box flash event was described, which enabled the study of transient effects, the sequential operation of current-limiting fuses in the line, interaction between phases, point-on-wave effects and so on. However the time domain model is complex and is more suitable for research than everyday application. n this paper a simplified model is described which eliminates anomalies found with the EEE584 method, and which gives a better overall correlation with test results. Vac 3-phase power system d 0 d g location of worker (or calorimeter in laboratory test). The EEE 584 method The arc flash calculations proposed in EEE 584 require two stages: (a) calculation of arcing current, so that the operating time (t ) of protective devices such as fuses or circuit breakers can be found. (b) calculation of incident heat energy density at a distance d after a time t. This is then used to determine the required level of personal protective equipment (PPE). The variation of incident energy with distance is represented by the use of "distance exponents", which depend on the type of equipment. - -

The equations given in EEE 584 were developed by using a least squares method, to obtain a good statistical fit to the test data, but the grouping of variables was not based on physical phenomena, and can produce anomalous predictions, such as: calculated arcing current being greater than the bolted-fault current calculated arcing current increasing as the electrode gap increases calculated incident energy density being reduced when the electrodes are enclosed in a box sudden jumps/discontinuities in the predictions as variables are changed These anomalies have been discussed in detail in [] and elsewhere. A simplified version is presented here, which is based on the same concepts as in [] but which is suitable for general use. t eliminates the anomalies listed above, since it is based on physical models, and gives a better overall correlation with test results than the EEE 584 equations. Although the EEE 584 standard has been updated since its original publication, and additional testing work has been carried out recently, at the time of writing there has been no change to the basic method of analysis, which is to use a purely statistical fit to the data. Basic ideas (a) Calculation of arcing current For the calculation of arcing current, the basic idea is that behaviour of the electrical power system is well known and can be modelled accurately. The main unknown is the arc characteristic. f the arc is represented as a resistor and its interaction with the source circuit is calculated, the resulting arcing current must always be lower than the boltedfault current. These effects can be represented by the equivalent circuit shown in Fig., which was originally used by Fisher [3]. The three-phase arcing fault is modelled as a set of three Y-connected arcs. Arc current and voltage are represented as r.m.s. values, and the use of phasor calculations implicitly assumes that their waveshapes are sinusoidal, (which they are not). However, the problem of non-sinusoidal waveshapes can only be solved by the use of something like the timedomain method. For the simplified version, the effect of harmonics (principally in the voltage wave) is absorbed into the coefficients generated when fitting the models to the test data. Vph = 0.577V LL jx arc arc Varc Fig. Single-phase model of a 3-phase arcing fault - -

(b) Calculation of incident energy density For the calculation of incident energy density, the basic idea is that the effect of a box enclosure has a focussing effect. adiated energy strikes the back and sides of the box and is then reflected out towards the calorimeters. This gives a higher incident energy density than would be obtained in the open. These comments are only valid for the radiated components of heat flux. f the electrode arrangement were changed so that plasma jets drive the plasma cloud in the direction of the calorimeters, an additional heating term would need to be included. Data set used The data used for this work were taken from the Test esults Database appended to the EEE 584 document, augmented by 37 tests done in 004 []. The total number of useable sets of test data was 347. A reduced set of data was also used, formed by replacing the data for replicated series of tests by a single, suitably "averaged" result. The reduced set gave results close to those obtained for the whole set. Equation for Varc The key to the whole process is to find a suitable value for the r.m.s. arc voltage. This then enables the arcing current, power, and energy delivered to be calculated, using the circuit of Fig.. Analysis of the data (details given in Appendix A-) gave the following equation for the r.m.s. arc voltage. V () 0.457 0.476 0.466.757 g VLL where g V LL = r.m.s. arc current, A = electrode gap, mm = line-line source voltage, V The dependence of V on arc current and gap is similar to that reported previously for single and three-phase tests in several laboratories world-wide []. The dependence on V LL is less easy to explain, and has been discussed in []. However, it enables the equation () to be used over the whole range of voltage, from 08 to 3,800V. Equation () applies for open tests. For tests in a box, the formula must be multiplied by 0.8. The lower arc voltage for tests in a box is probably due to the fact that in the EEE 584 test arrangement, the arcs are driven downwards and hit the bottom of the box, restricting their length. For tests in the open, the arcs are free to elongate, giving a higher voltage. As an alternative, the arc resistance can be used in calculations. From () it is given by: () 0.8543 0.476 0.466.757 g VLL - 3 -

Calculation of arcing current The power system is characterised by three variables, the source voltage V LL, the bolted-fault current BF and the ratio X/. From these the source resistance and inductive reactance X can be found. The arcing current is then given by (see Fig.): (3) V PH ( ) X = BF calculate using () N calculate EW using (3) error = ( NEW - OLD ) / BF if (error > e-6) then OLD NEW = go to endif done... OLD Unfortunately, is a function of and so (3) cannot be solved explicitly for. However (3) can be solved very easily using the iterative method first described by Fisher [3]. Starting with an arcing current equal to the bolted-fault current, is found from (), and substituted in (3) to get a new value of. This is repeated until the iterative process converges. The process is simple to program on a calculator, spreadsheet, or in other software, and it converges quickly and reliably. t can be represented by the pseudo-code fragment shown above. Fig.3 shows a comparison of the arcing current calculated by this method with the test values. The r value is slightly lower than was obtained using the time-domain model, but higher than the EEE 584 model, for which r was 0.969. ncident energy density equation (open tests) After the r.m.s. arcing current has been found, the total arc energy can be calculated from W 3V t (4) Fig.3 Comparison of calculated arcing current with test values where t is the duration of arcing. f the heat transfer to (r = 0.984) the calorimeters is by radiation only, it should be strongly dependent on the spherical energy density E S where is the fraction of the arc energy which is emitted as radiant heat and a, measured, ka 00 0 0. 0. 0 00 a, calculated, ka E S (5) W 4 d - 4 -

When radiant heat is the dominant heat transfer mechanism, tests confirm that the "distance exponent" for open tests is close to. However, a distance exponent of will only be exact for a point source of heat or if d is very large in comparison with the size of the radiating object. Furthermore, the fraction will be affected by the electrode gap g and other factors. Correlating the maximum measured energy density values (9 tests) gave the following best-fit to the open test data: E (6) MAX 4.9 E.0655 S g 0.56 V 0.5697 LL Emax (test) cal/cm 00 0 0. 0.0 0.0 0. 0 00 Emax (model) cal/cm Fig.4 Comparison of calculated incident energy density with test values (open tests only) Fig.4 shows the correlation between the predictions of equation (6) and the test measurements. For this plot r = 0.947, almost the same as was obtained with the time-domain model []. ncident energy density equation (box tests) The basic assumption is that the same dependencies as found in equation (6) for the open tests can be used, but with the spherical energy density component E S increased to a value E that accounts for the additional reflected heat radiation. n [] the single and multiple reflections from the back and sides of the box were computed explicitly, but this is a very complicated process, and for the present work a simplified version was used. t was assumed that E (7) k a W d where k and a are box parameters. E MAX is then calculated by modifying (6) to E (8) MAX 4.9 E.0655 g 0.56 V 0.5697 LL Use of equation (7) is an alternative to the use of distance exponents. The rationale for this is as follows. For a large radiating object the distance exponent is only at very large distances. Nearer to the source the local exponent falls. t tends towards zero as the object is reached (plane wave). This characteristic is built in to the form of (7). - 5 -

Equation (7) is exactly the form of the reflection factor from a disk of radius a to a point at some distance d [4]. We are effectively representing the (arcs+box) as a single heat source with a characteristic dimension a. For a point source a=0 and in this case (7) must degenerate to the spherical formula, so the lowest possible value of k is (/4) = 0.07957. The optimum values of k and a (i.e. which gave the least-squares best fit to the test data) were determined for each of the three equipment classes specified in EEE 584. (These are related to the dimensions of the box). The results are shown in the table below. width height depth Area of inner surface, (mm ) EFF a Open - - - - - 0 0.07957 Panelboard 305 356 9 3608 339.0 00 0.7 LV switchgear 508 508 508 9030 640.9 400 0.3 MV switchgear 43 76 76 377486 096 950 0.46 k 0.5 000 k (optimum) 0.4 0.3 0. 0. a (optimum), mm 500 0 0 500 000 500 eff, mm Fig.5 Dependence of k on equipment size 0 0 500 000 500 eff, mm Fig.6 Dependence of a on equipment size EFF is the radius of a disk which has the same area as the inner surface of the box. t was found that the optimum values of k and a correlate strongly with the box dimensions. This is illustrated in Figs 5 and 6. Using Figs. 5 and 6 it is possible to estimate the values of k and a for box sizes other than those specified in the standard. - 6 -

Fig.7 shows a comparison of the measured incident energy density with the predictions, for the whole data set (347 tests). Equations (5) and (6) were used for the open tests, while (7) and (8) were used for the box tests, with the appropriate k and a.n this case the r value is significantly higher than is obtained with the EEE 584 model, for which r is 0.763. Emax (test) cal /cm 00 0 0. Current-limiting fuses The simplified method given here can only be used for fuses if the bolted fault current is below the threshold of current limitation. For higher fault currents the current-limiting action gives a dramatic reduction in incident energy, as illustrated in Fig.8. The bend in the characteristic corresponds roughly to the 0.0s point on the fuse's time-current characteristic. For 0.0 0.0 0.0.00 0.00 00.00 Emax (model) cal/cm Fig.7 Comparison of calculated incident energy density with test values (all tests, r = 0.860) higher fault currents the arc flash energy density is well below the critical value for a nd-degree burn (. cal/cm ). Conclusion The proposed simplified method gives results that are based on real physical models, and which overcomes the anomalies built in to the current EEE 584 equations. Use of the arc voltage equation () ensures that the arcing current is always lower than the boltedfault current and that it decreases as the electrode gap increases. Use of equation (8) ensures that the incident energy density increases when an arcing fault is enclosed in a box. The method also gives better overall correlations with test data than the equations in EEE 584, especially for the incident energy density values. 00 0 0, 0 00 bolted-fault current, ka Fig.8 Typical arc-flash characteristic for a 600A current-limiting fuse - 7 -

eferences EEE Guide for Performing Arc-Flash Hazard Calculations. EEE Standard 584, EEE, September 00. Wilkins,., Allison, M. and Lang, M. "mproved method for arc flash hazard analysis", 004 EEE & CPS Technical Conference, Clearwater Beach, Florida, May -6, 004. Fisher, L.E. "esistance of low-voltage arcs". EEE Transactions on ndustry and General Applications, vol GA-6, No 6, Nov-Dec 970, pp 607-66. Ozisik, M.N. "Heat Transfer", McGraw-Hill, 985. Appendix - Method used for calculating Varc V in equation () is the effective (r.m.s.) phase-neutral arc voltage. Measured values of arc voltages are not available for many of the tests in the data set. Furthermore, when they are available they are line-to-line values. (The phase-neutral value cannot be measured directly as the neutral point is somewhere in the middle of the arc plasma!) n addition, accurate measurement of the arc voltage is difficult because of the erratic nature of the waveform. For these reasons an implied value of r.m.s. arc voltage was used for the development of the arc voltage equation. This is the method used by Fisher [3]. V can be derived from the r.m.s. arc current (which is easy to measure accurately). f is known, it is simple to calculate the r.m.s. arc voltage which will produce this value of circuit current, for the circuit of Fig.. The calculation is as follows. ( V PH / ) X then V However, this method gives numerically inaccurate results if the arcing current is very close to the bolted-fault current. Data sets were only used for the calculation if the arcing current was less than 95% of the bolted-fault current. This gave 43 sets, which were used in a multiple regression fit to give equation (), for which r = 0.907. - 8 -

Conference: Organized by: 0 th nternational Conference on Electric Fuses and their Applications Dresden University of Technology Postfach 00 90 0076 Dresden, Germany Copyright This work is copyrighted in its entirety. Any usage in violation of the narrow boundaries of copyright law without the prior approval of the organizer is prohibited and is punishable by law. This applies especially to copies in any form (photocopy, microfilms or any other practices) translations, as well as storing and processing with electronic media. The organizing committee of the conference and organizer are not responsible for the opinion expressed in the papers published in this Program and Abstracts. The contents of the paper express entirely the views of the authors. All copying, reprint or reproduction requests should be addressed to the Dresden University of Technology. All rights reserved. Copyright: Dresden University of Technology. Frankfurt am Main, Germany September, 05