S Sapling INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS. advanced time and control systems

Similar documents
Installation and Operation Manual. AllSync Plus Wired Clocks

SC125MS. Data Sheet and Instruction Manual. ! Warning! Salem Controls Inc. Stepper Motor Driver. Last Updated 12/14/2004

Minute Impulse Clock Controller I01DN

Zone Clocks. Installation Manual. Version Number 2.0 Current as of July 20, The Sapling Company, Inc. 670 Louis Drive Warminster, PA USA

XR Analog Clock - Manual Setting Model Troubleshooting Guide

Microcare LCD Solar MPPT User Documentation

Installation Instructions: ICON Anti-Condensate Controller

technical bulletin Installation Instructions: Wall-Mount Dewpoint Probe ( )

2 AllSync Wired Clock System

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

ISOCON-6. 24V AC or DC POWERED ISOLATING SIGNAL CONVERTER

Flexitest Switch Assemblies Type FT-19R and FT-19RX Supersedes DB March 2008

Notebook Circuits With Metering. 22 February July 2009

Experiment B6 Thermal Properties of Materials Procedure

Richter Optica. Instructions for Model: S850 Stereo Zoom Microscope

Heat Meter WR 200-D. 2 temperature inputs for Pt100 in four-wire circuit. Exact calculation of the heat parameters according IAPWS-IF97

UA-SS FAQS UA-SS FAQS

THE MASTER 2 SET UP AND OPERATION MANUAL TABLE OF CONTENTS

To Set Time: Turn the set knob on back of the clock movement in either direction.

PHOENIX CONTACT - 04/2016. Features

Acceleration/Velocity/Displacement VIBRATION METER

Assembly and Operation Manual. April 2016

2.3. Rockers. Contents

SECTION 1 - WHAT IS A BTU METER? BTU's = Flow x ΔT Any ISTEC BTU Meter System consists of the following main components:

Circular Motion and Centripetal Force

Model: WT-3181PL Instruction Manual DC: Indoor/Outdoor Atomic Wall Clock. Get Started

BASIC ELECTRICITY STUDY COURSE

Direct-operated 2/2-way solenoid valves Type EV210B

www. ElectricalPartManuals. com Flexitest Switch Assemblies Type FT-19R and FT-19RX INTL APPLICATION

Explanation: The factory restart returns the atomic clock to an out-of-the-box state and often resolves an issue.

NR2 Thermal Overload Relay

Nixie Clock Manuela Desktop. User Manual

NR2 Thermal Overload Relay. 4. Technical Data. 1. General. 2. Type Designation. 3. Features. Item Series No. I/In Operating time Tp Test condition

PARTS CATALOGUE / TECHNICAL GUIDE Cal. 4F32A, 8F32A Cal. 8F33A, 8F35A

ph electrode Instruction Manual For use with the RAH-210 & RPH-250

Electric Fields. Goals. Introduction

Field Pro Operation and Installation Manual

BETA Protecting. Low-Voltage Fuse Systems. LV HRC fuse links. 3/36 Siemens ET B1 2008

Direct-operated 2/2-way compact solenoid valves Type EV210A

Acceleration, Velocity, Separate probe VIBRATION METER Model : VB-8202

A Rain Sensitive House Window Closes Automatically When Raining

Project. Project Location. Catalog #

Lab 6: Capacitors and Resistor-Capacitor Circuits Phy208 Spr 2008 Name Section

CONTENTS. Batteries. La Crosse Technology, Ltd Page 1

MODEL: R7K4FML3. Remote I/O R7K4F Series. POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.)

POINTS OF CAUTION BEFORE USE...

TeSys enclosed starters 2

24 volts (0.25 amps current-limited)

PHY222 - Lab 7 RC Circuits: Charge Changing in Time Observing the way capacitors in RC circuits charge and discharge.

Safety Precautions WARNING If critical situations that could lead to user s death or serious injury is assumed by mishandling of the product.

BEFORE USE... POINTS OF CAUTION COMPONENT IDENTIFICATION INSTRUCTION MANUAL MODEL R7K4DH-1-DAC32D R7K4DH-1-DAC32D

Operating instructions Magnetic-inductive flow sensor SM6004 SM7004 SM / / 2014

VIBRATION METER Acceleration & Velocity Model : VB-8201HA

Circuit Analysis and Ohm s Law

ISOCON-3 MAINS POWERED ISOLATING SIGNAL CONVERTER

Number of poles 1-pole 2-pole Minimum Enclosure Contact G2R-1A-E G2R-1-E

Kingspan Smart-Lite Kite Luminaire

HT600 Dat e Code: 2 - HT MW Purchase Date: PLEASE RETAIN THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE. All Rights Reserved

A clock designed in close consultation with people living with Dementia.

Non-Contact Safety Systems CMS

Non-Acoustical Inputs

Static Electricity. Electric Field. the net accumulation of electric charges on an object

Commercial Generator Parts Catalog. PROTEC Series

Digital Multi-Day Max/ Min/Current Air and Soil Temperatures Protocol

VELA. Getting started with the VELA Versatile Laboratory Aid. Paul Vernon

h/e Apparatus h/e Apparatus Accessory Kit

LAB 3: Capacitors & RC Circuits

CBR-PB3-ATM ProBridge. User Manual

Potential and Kinetic Energy

Set up and Operation Manual

E2T0 DVP

14 ULTRATOMIC WALL CLOCK

W 30 Photoelectric proximity switches: Clear signals even with low remission

Figure 1: Capacitor circuit

T1 and E1 Feature Cards

PHYS320 ilab (O) Experiment 2 Instructions Conservation of Energy: The Electrical Equivalent of Heat

Installation guide 862 MIT / MIR

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

Secured Series Front End Reader Installation Instructions Proximity Reader (ProxPro, ProxPro w/keypad, MiniPro, Thinline II)

Electric Field Mapping

THE LOSMANDY G-11 MOUNT

EL8000M3 Mach 3 Hot Sheet

Weather Station P03/3-Modbus-GPS for Modbus

MAIN PCB R10, 12k R31. 2) Now with the capacitors. C12,C7 C20 C6. 1N4148 D3, D5, D6 Zener 4v7 D1, D D4, D7 ferrites F1+, F2- 4) Transistors

OPERATION MANUAL. Acceleration, Velocity RMS measurement, Metric & Imperial unit PEN VIBRATION METER Model : PVB-820

Solenoid valves 2/2-way direct-operated type EV210A

Experiment objectives: measure the ratio of Planck s constant to the electron charge h/e using the photoelectric effect.

ELECTRICITY Electric Fence Experiment.

AlphaLab Gaussmeter Model VGM -- Instructions

THF / 1SCC330001M THF 1S1 C

Designing a Thermostat Worksheet

The RC Circuit INTRODUCTION. Part 1: Capacitor Discharging Through a Resistor. Part 2: The Series RC Circuit and the Oscilloscope

AIR CONDITIONER (SPLIT TYPE) SERVICE MANUAL

An Ultra Low Resistance Continuity Checker

Panel Mount, Single Phase 120 and 240 Volt Fixed Shaft (click blue text for more details)

Quartz Crystal Nanobalance (QCN)

AccuAligning TM Polar Scope for SmartEQ TM Portable German Equatorial GOTO Mount. Installation and User Manual. Product #3130

RC Circuit (Power amplifier, Voltage Sensor)

Rain Collector (# 7852 & 7852M)

MODE button MAX/MIN button CHANNEL button / C/ F / RCC button SNOOZE / LIGHT button Battery compartment A/C in-jack 3. 4.

Transcription:

INSTALLATION MANUAL FOR FIELD SELECTABLE ANALOG CLOCKS SAA SERIES SPECIFICATIONS Time base: 60 Hz (3-wire system) Quartz (2-wire system) Power input: 85 135 VAC / 60 Hz 7 28 VAC / 60 Hz Current consumption: 15 ma @110 VAC 20 ma @ 24 VAC Correction: 10 ma (current consumption) Display: 12 hour format. Hour, minute and second hands Color: Standard Black (custom colors available) Clock Size: 12 diameter, 1.3 depth. 16 diameter, 1.6 depth Case: Shallow profile, smooth surface metal case Crystal: Shatter-proof, side molded polycarbonate crystal in 12 and 16 Compliance: UL, cul listed and FCC approved T://Field Selectable Analog-SAA Series Page 1

TABLE OF CONTENTS DIGITAL COMMUNICATION 2-WIRE SYSTEM Digital Communication 2-Wire System... Page 3 System Wiring Diagram 2-Wire System... Pages 4, 5 and 6 Frequently Asked Questions 2-Wire System... Page 7 Troubleshooting 2-Wire System... Page 8 DIGITAL COMMUNICATION 3-WIRE SYSTEM Digital Communication 3-Wire System... Page 9 System Wiring Diagram 3-Wire System... Pages 10 and 11 Frequently Asked Questions 3-Wire System... Page 12 Troubleshooting 3-Wire System... Page 13 SYNCHRONOUS WIRE SYSTEMS Synchronous 59 Minute Correction... Page 14 Synchronous 58 Minute Correction... Page 15 Synchronous Wire Time and Rauland Correction... Page 16 System Wiring Diagram Sync-Wire System... Pages 17 and 18 Frequently Asked Questions Sync Wire Systems... Page 19 Troubleshooting Sync-Wire Systems... Page 20 Installation Instructions All Systems... Pages 21 and 22 T://Field Selectable Analog-SAA Series Page 2

SAA SERIES WIRING INFORMATION Digital Communication 2-Wire System DESCRIPTION The Sapling 2-Wire Digital Communication system provides immediate correction for time changes. It allows the user to mix Sapling s SAA analog clocks and digital clocks on the same two wires. The Digital Communication system runs on 24 volt power. In order to generate the necessary voltage, a Sapling converter box (part # SCB-000-000-1) is required, or if using an SMC series master clock, the optional 24 volt power supply (part # SMC-000-010- 1) must be installed. For System Wiring Diagram, see pages 4, 5 and 6. For answers to Frequently Asked Questions, see page 7. For Troubleshooting Answers, see page 8. For Installation Instructions, see pages 21 and 22. T://Field Selectable Analog-SAA Series Page 3

2-WIRE DIGITAL COMMUNICATION SYSTEM WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 4

2-WIRE DIGITAL COMMUNICATION SYSTEM WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 5

2-WIRE DIGITAL COMMUNICATION SYSTEM WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 6

2-WIRE DIGITAL COMMUNICA TION SYSTEM Frequently Asked Questions 1. Do I need to power up all the clocks at the same time? No, you do not have to power up all the clocks at the same time. Clocks that are connected at the time of system power up will begin running and receiving correction signals from the master clock. Clocks that are added to the system after the initial power up should be set to 12:00 (see question #2 below). 2. I m adding a new clock into a working system, do I have to set the entire system back to 12:00? No. Set only the new additional clock to 12:00. This clock will reset itself automatically upon receiving a reset signal from the Master Clock. DO NOT SET THE ADDITIONAL CLOCK TO THE SYSTEM TIME. Set it to 12:00 prior to installation. 3. The clock has been powered and running and I would like to reset the clock back to 12:00. How do I do this? In order to correctly set the clock to 12:00, you MUST first set the second hand by pressing the button on the side of the movement until the second hand reaches 12:00. You must reset the second hand even if the second hand is already set on 12:00. Afterwards set the hour and minute hands to 12:00 using the hour and minute set knob. 4. Do I need to reset the clocks to 12:00 after a power failure? No. All the system clocks will automatically adjust themselves to the correct time upon receiving a correction signal from the master clock after a power failure. 5. What happens after powering up the clocks? After the clocks accept the communication signal from the master clock, each individual clock will determine the fastest way to adjust to the correct time. The clock may run faster to catch up to the system time, or it may stop running and wait, and then begin operating again once the system time matches the displayed time on the clock. If jumper # 4 is in the ON position (a jumper is connected to both pins) and the clock does not receive a correction signal from the master clock for 300 consecutive seconds, the clock will signal this loss of communication by moving the second hand once every two seconds in two second increments. To disable this feature, simply remove the pin from jumper #4, thereby setting it to an OFF position. T://Field Selectable Analog-SAA Series Page 7

2-WIRE DIGITAL COMMUNICATION SYSTEM TROUBLESHOOTING: 1. The clock is not running, what do I do? a) Make sure your installation includes a converter box (SCB-000-000-1) or a SMC Series Master Clock with the 50 watt power supply (SMC-000-010-1). b) Measure the voltage between the power (black) wire and the neutral (white) wire. The voltage should measure 10-36 volts rms. c) Make sure the ground wire is not touching other wires. d) Make sure the dip switches are set in the correct pattern for the 2-wire system. Jumper pins #1 and #2 should be connected. Pin #3 is not connected, and Pin #4 is optional. If you fail to follow the instructions in (b), the fuses can be blown. 2. The clock is not receiving a reset signal from the Master Clock, what do I do? a) Make sure that the yellow reset wire is securely connected to the black power wire. The voltage between the yellow reset wire and the white neutral wire must measure between 10-36 volts rms. b) Make sure that the wires coming from the master clock and power supply are in the right polarity. If the polarity is reversed, the clock will run at normal speed, but will receive a correction signal. 3. There is data noise bleeding into the intercom line, what do I do? Reduce the transmission rate from the master clock to once a minute. T://Field Selectable Analog-SAA Series Page 8

SAA SERIES WIRING INFORMATION Digital Communication 3-Wire System DESCRIPTION The Digital Communication system provides immediate correction for time changes. The Digital Communication system runs on 110 VAC or 24 VAC and can use Sapling 2000 or 3000 series master clocks that require 24 volt power supply (part # SMC-000-010-1). For System Wiring Diagram, see pages 10 and 11. For answers to Frequently Asked Questions, see page 12. For Troubleshooting Answers, see page 13. For Installation Instructions, see pages 21 and 22. T://Field Selectable Analog-SAA Series Page 9

3-WIRE DIGITAL COMMUNICATION SYSTEM 110 VOLT WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 10

3-WIRE DIGITAL COMMUNICATION SYSTEM 24 VOLT WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 11

3-WIRE DIGITAL COMMUNICATION SYSTEM Frequently Asked Questions 1. Do I need to power up all the clocks at the same time? No, you do not have to power up all the clocks at the same time. Clocks that are connected at the time of system power up will begin running and receiving correction signals from the master clock. Clocks that are added to the system after the initial power up should be set to 12:00 (see question #2 below). 2. I m adding a new clock into a working system, do I have to set the entire system back to 12:00? No. Set only the new additional clock to 12:00. This clock will reset itself automatically upon receiving a reset signal from the Master Clock. DO NOT SET THE ADDITIONAL CLOCK TO THE SYSTEM TIME. Set it to 12:00 prior to installation. 3. The clock has been powered and running and I would like to reset the clock back to 12:00. How do I do this? In order to correctly set the clock to 12:00, you MUST first set the second hand by pressing the button on the side of the movement until the second hand reaches 12:00. You must reset the second hand even if the second hand is already set on 12:00. Afterwards set the hour and minute hands to 12:00 using the hour and minute set knob. 4. Do I need to reset the clocks to 12:00 after a power failure? No. All the system clocks will automatically adjust themselves to the correct time upon receiving a correction signal from the master clock after a power failure. 5. What happens after powering up the clocks? After the clocks accept the communication signal from the master clock, each individual clock will determine the fastest way to adjust to the correct time. The clock may run faster to catch up to the system time, or it may stop running and wait, and then begin operating again once the system time matches the displayed time on the clock. If jumper # 4 is in the ON position (a jumper is connected to both pins) and the clock does not receive a correction signal from the master clock for 30 consecutive seconds, the clock will signal this loss of communication by moving the second hand once every two seconds in two second increments. To disable this feature, simply remove the pin from jumper #4, thereby setting it to an OFF position. T://Field Selectable Analog-SAA Series Page 12

3-WIRE DIGITAL COMMUNICA TION SYSTEM Troubleshooting: 1. The clock is not running, what do I do? a) Measure the voltage between the power (black) wire and the neutral (white) wire. The voltage should measure 85-135 volts in the 110 volt model or 7-28 volts in the 24 volt model. b) Make sure the transformer is an isolated transformer if using a 24 volt model. c) Make sure the ground wire is not touching other wires. If you fail to follow the instructions in b and c listed above, the fuses can be blown. d) Make sure the dip switches are set in the correct pattern for the 3-wire system. Jumper pins #1, #2 and #3 should be connected. Pin #4 is optional. 2. The clock is not receiving a reset signal from the Master Clock, what do I do? a) Make sure there is a 50 watt power supply (SMC-000-010-1) installed in SMC Series Master Clock. b) Make sure that the voltage between the yellow reset wire and the white neutral wire varies between 0 volts 24 volts. c) Make sure that the wires coming from the master clock and power supply are in the right polarity. If the polarity is reversed, the clock will run at normal speed, but will not receive a correction signal. 3. There is data noise bleeding into the intercom line, what do I do? Reduce the transmission rate from the master clock to once a minute T://Field Selectable Analog-SAA Series Page 13

SAA SERIES WIRING INFORMATION Synchronous Wire 59 Min Correction DESCRIPTION SAA 59 MINUTE CORRECTION 110 VAC/24 VAC 60 Hz is used to run the clock normally. Applying an 8 second reset signal from 57 minutes and 54 seconds will cause an hourly correction. Applying a 14 second reset signal from 5:57:54 will cause a daily correction. For System Wiring Diagram, see pages 17 and 18. For answers to Frequently Asked Questions, see page 19. For Troubleshooting Answers, see page 20. For Installation Instructions, see pages 21 and 22. T://Field Selectable Analog-SAA Series Page 14

SAA SERIES WIRING INFORMATION Synchronous Wire 58 Min Correction DESCRIPTION SAA 58 MINUTE CORRECTION 110 VAC/24 VAC 60 Hz is used to run the clock normally. Applying a 55 second reset signal from 58 minutes and 05 seconds will cause an hourly correction. Applying a 55 second reset signal when hours equal 05 or 17 and minutes equal 03, 07, 11 15, 19,23 31, 35, 43 and 47 and seconds equals 05 will cause a daily correction. For System Wiring Diagram, see pages 17 and 18. For answers to Frequently Asked Questions, see page 19. For Troubleshooting Answers, see page 20. For Installation Instructions, see pages 21 and 22. T://Field Selectable Analog-SAA Series Page 15

SAA SERIES WIRING INFORMATION Synchronous Wire, National Time and Rauland Correction DESCRIPTION SAA NATIONAL TIME AND RAULAND CORRECTION 110 VAC/24 Vac 60 Hz is used to run the clock normally. Applying a 25 second reset signal when minutes equal 00 and seconds equal 00 will cause an hourly correction. Applying a 24 minute reset signal when hours equal 06 or 18 and minutes equal 00 and second equals 25 will cause a daily correction. For System Wiring Diagram, see pages 17 and 18. For answers to Frequently Asked Questions, see page 19. For Troubleshooting Answers, see page 20. For Installation Instructions, see pages 21 and 22. T://Field Selectable Analog-SAA Series Page 16

SYNC-WIRE SYSTEM 110 VOLT WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 17

SYNC-WIRE SYSTEM 24 VOLT WIRING INFORMATION T://Field Selectable Analog-SAA Series Page 18

SYNC-WIRE SYSTEM Frequently Asked Questions 1. Do I need to power up all the clocks at the same time? No, you do not have to power up all the clocks at the same time. Clocks that are connected at the time of system power up will begin running and receiving correction signals from the master clock. Clocks that are added to the system after the initial power up should be set to 12:00 (see question #2 below). 2. I m adding a new clock into a working system, do I have to set the entire system back to 12:00? No. Set only the new additional clock to 12:00. This clock will reset itself automatically upon receiving a reset signal from the Master Clock. DO NOT SET THE ADDITIONAL CLOCK TO THE SYSTEM TIME. Set it to 12:00 prior to installation. 3. The clock has been powered and running and I would like to reset the clock back to 12:00. How do I do this? In order to correctly set the clock to 12:00, you MUST first set the second hand by pressing the button on the side of the movement until the second hand reaches 12:00. You must reset the second hand even if the second hand is already set on 12:00. Afterwards set the hour and minute hands to 12:00 using the hour and minute set knob. 4. Do I need to reset the clocks to 12:00 after a power failure? No. All the system clocks will automatically adjust themselves to the correct time upon receiving a correction signal from the master clock after a power failure. 5. What happens after powering up the clocks? After powering up the system, the clocks will run at a normal speed for up to one hour. After the clocks accept the communication signal from the master clock, each individual clock will determine the fastest way to adjust to the correct time. The clock may run faster to catch up to the system time, or it may stop running and wait, and then begin operating again once the system time matches the displayed time on the clock. After receiving a correction pulse, the clock will enter a correction mode and will run at a faster rate. It will calculate the time required to reach the correct system time and will add it automatically in the adjustment. For example, the time of the clock shows 5:40:00, when the clock receives a daily correction signal to reset the clock to 5:58.08. The clock will run at a faster rate until the clock reaches 6:01.00. This includes the correct time plus the time it takes the clock to make the adjustment. T://Field Selectable Analog-SAA Series Page 19

Synchronous-Wire Analog Clocks / SAS Series Troubleshooting: 1. The clock is not running, what do I do? a) Measure the voltage between the power (black) wire and the neutral (white) wire. The voltage should measure 85-135 volts in the 110 volt model or 7-28 volts n the 24 volt model. b) Make sure the transformer is an isolated transformer if using a 24 volt model. c) Make sure the ground wire is not touching other wires. If you fail to follow the instructions in b and c listed above, the fuses can be blown. d) Make sure the dip switches are set in the correct pattern for the sync-wire correction signal you are using. For 58-minute correction, only jumper pin #1 should be connected. For National Time/Rauland correction, only jumper pin #2 should be connected. For 59- minute correction, none of the jumper pins should be connected. 2. The clock is not receiving a reset signal from the Master Clock, what do I do? a) Make sure during reset that the neutral (white) wire and the reset (yellow) wire are receiving the proper voltage (24 or 110 voltage). b) Make sure that when not applying a reset signal, the voltage between the reset (yellow) wire and the neutral (white) wire is zero ( both AC & DC). Also, makes sure the clock is disconnected from the master clock while taking this measurement. Some Master Clocks (other brands than Sapling) have some leakage through the relay circuit that doesn t allow the voltage to drop to zero. In this case, an external bypass relay is necessary to insure that the voltage during non-reset time is zero. Please contact Sapling for more information. T://Field Selectable Analog-SAA Series Page 20

SAA SERIES INSTALLATION INSTRUCTIONS WALL MOUNT 12 CLOCK 16 CLOCK H = 8.75 H = 10.81 INSTRUCTIONS 1. IMPORTANT: If using a low voltage system (24 volt) make sure that the transformer is an isolated transformer. 2. IMPORTANT: Clock must be set to 12:00 prior to installation. 3. Connect the wiring as shown on the wiring diagram. 4. Mount the back plate to a single gang box using the 2 machine screws #6-32 included in the kit for 12 clock and 16 clock. 16 requires the screw to connect to the ground wire. 5. Mount the plastic anchor into the back plate, through the large hole towards the top of the plate. 6. Insert the sheet metal screw (#10) into the plastic anchor. Screw should protrude approximately 1 for 12 clock. Screw should go in all the way for the 16 clock. 7. Plug the connector into the movement. 8. Insert the ground tab into the clock (12 clock). 9. Hang clock on the protruding screw (12 clock). 10. Put screw #8-32 through hole on top of clock into hole at the top of the plate. T://Field Selectable Analog-SAA Series Page 21

DOUBLE MOUNTED CLOCK INSTRUCTIONS 1. IMPORTANT: If using a low voltage system (24 volt) make sure that the transformer is an isolated transformer. 2. IMPORTANT: Clock must be set to 12:00 prior to installation. 3. Screw hanger/mounting rod (included in the kit) into the mounting plate (also included in the kit). 4. Insert wires through hanger/mounting rod. 5. Install mounting plate using 2 #6-32 screws into double gang box. 16 requires the screw to connect to the ground wire. 6. Remove one clock face (open the 4 screws around the clock). 7. Insert clock housing onto hanger/mounting rod. 8. Insert the support bracket onto the hanger/mounting rod. 9. Screw the 2 nuts included in kit onto hanger/mounting rod and secure clock housing to wall. 10. Connect the wiring as shown on the wiring diagrams. 11. Plug connectors into the movement. 12. Insert ground tab into the case (12 clock). 13. IMPORTANT: Make sure the second clock is also set to 12:00 prior to installation. 14. Repeat numbers 10 and 11 for second clock. 15. Mount second clock to case and replace screws previously removed. T://Field Selectable Analog-SAA Series Page 22