Industrial Generator Set Accessories

Similar documents
Industrial Generator Set Accessories

CIRCO. Sound-attenuating transfer unit QUICK FACTS

Experimental determination of far field sound power due to panel and vent radiation of a portable diesel generator

Turbines and turbine sets Measurement of emitted airborne noise Engineering/survey method

A Global Index of Acoustic Assessment of Machines Results of Experimental and Simulation Tests

VK2 volume flow controller Overview

ISEmax CAM40/CAS40. Technical Information

Assessment & Specifications for Noise Controls

Power Resistor for Mounting onto a Heatsink Thick Film Technology

RPM Adjustable Speed Adjustable Force Noiseless - As Low As 68dB Continuous Duty

nufacturing Company, L.P San Felipe, Suite

PREDICTION OF FAN SOUND POWER

GRC. Circular egg crate grille for transfer/extract air and wall/ceiling mounting QUICK FACTS

ISO INTERNATIONAL STANDARD

Hanson Overhead Garage Door Company proudly presents: Residential 400 Series

Comparison of Noise Test Codes when Applied to air Compressors

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x OUTLET x M6 x 20

ALUMINIUM CENTRIFUGAL FANS x M6 x x M6 x 16

Made in Italy HOSE REELS CATALOGUE TECHNOLOGY FOR FLUIDYNAMICS. No. E14/A1

Calio-Therm NC Type Series Booklet

CNA-CNB. Centrifugal fans

Krantz Components. Twist outlet DD-N... for ceiling installation. Air distribution systems

PATENT PENDING. Easy Gripper product range. #94060 Easy Gripper #94095 Easy Gripper Compact Accessories. Improve SAFETY and efficiency

Serie B2.1. Flanged ductile iron ball valve. made in. Application fields. Shut-off valves E U R O P E. 18

ISO 3741 INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD. Test code for machine tools Part 5: Determination of the noise emission

DBS315 1-phase SIDE CHANNEL BLOWERS

PARTS MANUAL 2 INCH CHIPPER/SHREDDER. SC cc SUBARU

FVBSS fixed volume bottle

Power Resistor for Mounting onto a Heatsink Thick Film Technology

FAN ENGINEERING. Fan Sound & Sound Ratings


AC axial fan. Limited partnership Headquarters Mulfingen Amtsgericht (court of registration) Stuttgart HRA

6 INCH W X 5-3/4 INCH D X 8-3/8 INCH H

ECMA Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

NOP, NOT and NOX. Adaptable, flexible supply air diffusers with ultra low height for free installation. climecon.fi 07.16

REPAIR PARTS. DX17VS Outdoor Inverter. This manual is to be used by qualified technicians only.

CONSOLIDATED GRANULAR MEDIA FOR SOUND INSULATION: PERFORMANCE EVALUATION THROUGH DIFFERENT METHODS

CDD/CDR. Circular ceiling diffuser for supply air QUICK FACTS

ALUMINIUM CENTRIFUGAL FANS. 4 x M6 x 16

Circular duct grille

ALUMINIUM CENTRIFUGAL FANS M20 4 x M5 x 10 INLET. 4 x M5 x 12

A 954 C HD. Technical Description Hydraulic Excavator. Machine for Industrial Applications

Siv-inn School. Complete air-supply solution for school premises. Ensures excellent air supply Cleanable Reinforced front Ideal for renovation work

Sound-Absorbing and Insulating Enclosures for Ultrasonic Range

Protective Coatings: Non-lead orange paint RAL red (optional) non-lead paint Hot dipped galvanized conforming to ASTM A-153.

What s that Noise? Duct System Design Guide. Visit $69.00 value!

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Noise from Oil & Gas Facilities Acoustics 101 and Best Practices for Noise Control. Rob Stevens, HGC Engineering

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Measurement of Acoustic Properties of light weight concrete SL-Deck

I nllk 08018/18 I nllk I nllk 08036/36 I nllk I I nllk 08058/58 I

unit 4 acoustics & ultrasonics

SOCCER FIELDS LEVELS FOR UEFA COMPETITIONS ELITE LEVEL A LEVELS : A-B-C-D

nufacturing Company, L.P San Felipe, Suite

Circular duct grille. Dimensions. Description. Maintenance The grille should be removed to gain access to the duct.

Sales: Malux Finland Oy, P.O.Box 69, FI Porvoo, Phone , Fax ,

ISO INTERNATIONAL STANDARD

BNA Series. PLENUM FAN with Backward Wheels

Introduction to Acoustics. Phil Joseph

Single Phase Motors Technical Datasheets

air and solenoid air operated 5/2-5/3 ISO 5599/01 - Size 2

ALC. ALBATROSS Supply air terminal for large airflows

XBC300 Gen2. Fully-automated debonder and Cleaner

Uncertainties associated with the use of a sound level meter

CDD/CDR. Single cone ceiling diffusers for supply air. Quick facts. Quick guide CDD/CDR A I R F L O W - S O U N D L E V E L

Doc. Number: N 724. ISO/CD Pneumatic fluid power Test method for measuring acoustic emission pressure level of exhaust silencers

Method of Testing of Sound Absorption Properties of Materials Intended for Ultrasonic Noise Protection

Technical Data Sheet DPT & DPIT-4005 SERIES DIFFERENTIAL PRESSURE TRANSDUCERS. Features. Description

LD-LP-LL-LC Rope Safety Switches with reset for emergency stop

ISO INTERNATIONAL STANDARD

POWER PUSHER Snowplow

F O R C E S I L E N T

CHAPTER 5 SOUND LEVEL MEASUREMENT ON POWER TRANSFORMERS

EX-EMERGENCY LIGHT FITTINGS

KSV. Slot diffusers. Ordering code. Description. Linear diffusers 1 / 16

Applications. Remote Weather Station with Telephone Communications. Tripod Tower Weather Station with 4-20 ma Outputs

Field IT 50T Series Transmitters

Pneumatic fluid power Test methods for measuring acoustic emission pressure levels of exhaust silencers

Some considerations on noise monitoring for air handling equipments

GTH. Rectangular double deflection grille QUICK FACTS

PTF30 Series. Features. Ordering information. G 6 N N F8 (0 to 5 kgf/cm 2 ) PTF30

Sound Power Measurement of Domestic Boilers

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

FORMWORK SAVINGS ADAPTABILITY LIGHT WEIGHT ECONOMICAL ALUMINIUM SLAB FORMWORK. BV Cert

4.3. Ex-Pendant light fittings AB 50 / SPG 1N / AB 51 / EVI 200 / EVI 500 / EV35 LED. (Zone 1, 2, 21, 22)

ISEmax CAS40D. Technical Information

Krantz. Variable twist outlet with guide ring DD-VL... jet straightener DD-VG... Air distribution systems

Cell Rupture Nanoparticles Emulsions Liposomes

Self-Testing Prevectron 2 Millenium Lightning Conductor Set-up and Installation Manual

Basics of Sound and Noise. David Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering

SWIFT Ceiling. Square ceiling air diffuser for supply air QUICK FACTS

4.2. Ex-Ceiling light fittings AB 80 / AB 05 LED / AB 05 / AB 12 NAV 70. (Zone 1, 2, 21, 22)

Product Data. Brüel & Kjær B. Sound Power Source Type Introduction

G-FIRE FLANGE ADAPTERS

equator COMBINATION OVENS

Answer - SAQ 1. The intensity, I, is given by: Back

Overload Relays. SIRIUS 3RU1 Thermal Overload Relays. 3RU11 for standard applications. 5/46 Siemens LV 1 AO 2011

B6VMAX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

Transcription:

Industrial Generator Set Accessories Sound Enclosures KD/KM/KV Models General Information Measuring Sound Level The unit of measurement for sound level is the decibel (db) that is calculated using the sound pressure (LpA) relative to a reference pressure. Lp (db) = 10 log (P1 2 /P0 2 ) P1 = sound pressure of the sound wave (expressed in Pascals). P0 = reference pressure (p o =20x10 -- 6 Pa) Figure 1 provides a comparison of sound pressure (LpA) levels and typical sources. Sound Pressure (LpA) Level, db(a) Examples 140 Pain threshold Figure 1 120 Boiler room Engine test stand Pneumatic drill/hammer 100 Diesel engine on test stand at full load at a distance of 1 m (3.3 ft.) 80 Insideasmallcarat80kph(50mph) 70 Road noise 60 Landscaped office 50 Normal conversation 40 Quiet countryside 30 Whisper 20 Recording studio 10 Dead room 0 Audibility threshold in young adults for frequencies of 1000--4000 Hz Sound Pressure (LpA) Level Examples Sound Pressure (LpA) and Sound Power (LwA) Directive 2000/14/EC was drawn up to limit the sound power of equipment used outdoors. This directive can be used as a gauge for limiting sound power in many applications and is of particular relevance to generator sets. Sound power is determined using a measurement of the sound level of the set operating at 3/4 of its rated power. The sound power limit authorized by the directive depends on the equipment s power and is classified as shown in Figure 2. Generator Set at Rated Power, kw (kva) * January, 2002 (Step 1), LwA January, 2006 (Step 2), LwA 0.5--2 (0.6--2.5) 97 95 2.5--3 (3.1--3.8) 98 96 3.2--10 (4--12.5) 99 97 11--31 (14--39) 98 96 32--316 (40--395) 99 97 317--399 (396--499) 100 98 > 400 (> 500) No limit No limit * Rated Power Figure 2 Authorized Sound Power (LwA) Limit Role of Sound Power By limiting the sound power and not the pressure, it is possible to establish noise pollution comparisons between, for example, a portable generator set and a soundproofed unit. At equal sound power, irrespective of the generator set s size, the sound energy produced remains the same, and two generator sets of different sizes will produce exactly the same level of environmental noise pollution for an identical LwA value. However, the larger the generator set, the larger its soundemitting surface and, consequently, the higher the 10 log(s) value. In this case, to keep the LwA value within the permitted limits, the LpA (sound level) must be reduced, requiring improved soundproofing. G6-90 1/08b Page 1

Sound power is calculated using the sound pressure measured by a sound level meter. The latter value is also known as sound level. The sound power (LwA) and sound pressure (LpA) values are expressed in db(a) or decibel (A weighted). See Figure 3. These two variations are exactly proportional and the sound power (LwA) value is, therefore, constant irrespective of the distance and the shape of the area used for measuring. The standard allows a measurement to be taken using six microphones in a hemisphere whose radius depends upon the size of the generator set (4, 10, or 16 m [13, 33, or 52 ft.]) or in an equal distance of 1 m (3.3 ft.) from the generator set using a number of microphones, which depends on the size of the generator set. We use both methods, depending on the context (size of generator set, time saved in measuring, or need to multiply measuring points, etc.). Aim of Directive 2000/14 EC LwA = LpA + 10 log(s) R This directive was adopted by the European Parliament and Council on May 8, 2000, in order to harmonize the legislation of member states. It relates to noise emissions from equipment used outdoors; generator sets were listed among more than fifty types of product. Microphone LwA = sound power LpA = sound pressure S = area of the measurement hemisphere (area S relative to a reference area of length m 2 ) The greater the distance R, the smaller the LpA value The greater the distance R, the greater the S value Figure 3 Sound Power and Sound Pressure Calculations The effect is similar to that of a light bulb where its power is always the same irrespective of the distance, but the light bulb s illuminating capacity diminishes, like the sound pressure, as the distance increases. See Figure 4. LwA LpA Model Enclosure db db(a) @ 1 m (3.3 ft.) db(a) @ 7 m (23 ft.) KD130 Yes 96 77.6 67.6 The aim of the directive is to encourage a healthy home environment and to improve the well-being of the population by reducing noise emissions. The directive has four central aims: D Harmonization of noise emission standards D Harmonization of conformity assessment procedures D Harmonization of labeling relating to sound levels D Collection of data relating to noise emission The directive also aims to ensure that manufacturers respect imposed and declared sound levels. The manufacturer is committed to reducing outdoor noise levels and, in accordance with this directive, carries out regular sound checks on standard product ranges. The manufacturer has invested in the necessary resources: D Approved sound level measuring area D Data acquisition for measurement As stated in Figure 2, the regulations were supplemented on January 1, 2006, when the limit for all generator sets was reduced to 2 db(a). The full range of enclosures for the new generation now conform to the new requirement. Figure 4 Sound Pressure vs. Distance G6-90 1/08b Page 2

Noise reduction has always been a priority for the manufacturer. Consequently, the manufacturer has for some time possessed the measuring tools needed for checking the soundproofing of our generator sets. Nevertheless, in the interest of improvement and enhanced performance, the manufacturer has recently invested in cutting-edge techniques. Traditional Methods Traditional methods of measuring sound pressure using a sound level meter or several microphones connected to a data acquisition unit are sufficient for measuring the sound level of machines and relaying data on global sound pressure and sound spectra at the various measuring points. The manufacturer still uses these traditional methods to check the sound power of all models covered by directive 2000/14/EC. To perform these checks, the manufacturer has portable sound level meters and a data acquisition connection to six microphones. Accessory Noise Reduction Research Enclosure Features However, these measurements give only a general picture. They are not capable of determining the precise position or intensity of sound sources. The free field method of sound measurement can detect a sound level but cannot be used to determine the sound sources. Sound Intensity Measurement The manufacturer has been using the new technique of sound intensity measurement. This highly advanced method has a distinct advantage over traditional methods in that it is able to precisely identify sources of noise. It can be used to create a map of the sound emitted from the various components or surfaces of machines. This precision analysis enables exact identification of all sound emissions in db(a) and also on a frequency band. Consequently, noise sources can be more effectively identified and generator set soundproofing optimized. The results of sound intensity measurement can also be corroborated using vibration measurements at various points on the generator set or by model analysis that we are now able to do using 3D CAD technology. M126 -M129 KM Models, All KD Models up to KD110/KD100U M226 -M230 KD120U/KD130 and Larger All KV Models Aluminum hinges lined with epoxy powder paint F F Plastic (polyamide) hinges (qty. 6) F F Locks with seal F F Bichromate galvanized bolting F F Stainless steel rivets F F Polyurethane sound insulating foam lined with protective film F X Polyurethane sound insulating foam lined with hydrocarbon sealing film X F Foam fire classification type automotive (self-extinguishing foam) F F Rock wool with glass film X X Emergency stop button on outside of enclosure F F Operator access via side access panel with true keyed lock, number of access panels Three Four Command/control unit porthole F F Control unit door F F Exhaust silencer integrated in enclosure F F F Standard Figure 5 X Not Available Enclosure Accessories G6-90 1/08b Page 3

Enclosure Handling One of the factors determining the quality of an enclosure designed to incorporate all the necessary lifting and is the ease with which it can be fitted. The standard handling points to respond to this requirement. See enclosures in the manufacturer range have been Figure 6 and Figure 7. Accessory M126 -M129 KM Models All KD Models up to KD110/KD100U M226 KD120U -KD200U KD130 -KD220 KV200U/KV220 M227 -M230 KD250U -KD400U KD275 -KD440 All KV Models except KV200U/KV220 Integral brackets for forklifts F X F Removable brackets or pads for forklifts X F X Handling the generator set using a forklift either lengthwise or sideways F F F Eye for pulling and/or mounting F F F Single central lifting eye F F X Side lifting eyes X X F Base panel for fluid recovery F f X F Standard X Not Available f Optional Figure 6 Lift and Handling Points 1 2 3 4 8 5 7 6 1. Control unit viewing porthole 2. Central lifting ring (enclosures M126--M129 and M226) Note: Enclosures M227--M230 have side lifting eyes. 3. Radiator filler access 4. Air outlet via top only; facilitates installation inside buildings through addition of a shroud 5. Engine access door 6. Base panel for fluid recovery (enclosures M126--M129) 7. Brackets for fork lifts 8. Remote emergency stop button Figure 7 Enclosure Features G6-90 1/08b Page 4

Generator Set Model KM5.5M Enclosure 7 m (23 ft.), 60 Hz M126 -M129 Enclosure Specifications 7 m (23 ft.), 50 Hz Length, Width, Height, Area, m 2 (ft 2 ) Enclosure Wt., kg (lb.) KM7.5 60.1 KM9M 60.4 KM11U KM11UM 62.5 KM11.5 60.4 M126 KM11.5HM 70.8 1750 (69) 715 (28) 1230 (48) 1.25 (13.4) 148 (326) KM12M 60.7 KM15H 70.8 KM16 60.7 KM16U KM16UM 64.0 KM17M M127 61.0 2080 (82) 960 (38) 1415 (56) 2.00 (21.6) 230 (507) KM20H M126 68.4 1750 (69) 715 (28) 1230 (48) 1.25 (13.4) 148 (326) KM20U 65.4 KM20UM 67.0 KM22 61.0 KM27H 62.0 KM30U 67.4 230 (507) KM30UM 63.3 2.00 (21.6) KM33 73.0 KM40UM KM40U 69.2 KM44 M127 61.1 2080 (82) 960 (38) 1415 (56) KD20U 67.6 KD22 65.0 220 (485) KD24M 68.0 KD30U KD30UM 73.0 KD33 68.0 1.88 (20.5) 230 (507) KD40U KD40UM 72.0 KD44 65.0 220 (485) KD60U 66.0 KD66 M128 66.0 2300 (91) 1080 (43) 2.48 (27.2) 400 (881) KD70U 420 (926) 67.0 KD70UM M129 2554 (101) 1170 (46) 2.99 (32.3) 400 (881) KD77 66.0 1680 (66) KD80U M128 73.1 2300 (91) 1080 (43) 2.48 (27.2) 420 (926) KD88 70.0 KD100U 70.0 M129 KD110 67.0 2554 (101) 1170 (46) 2.99 (32.3) 3) 400 (881) G6-90 1/08b Page 5

KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-565-3381, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com Kohler Power Systems EMEA Headquarters 3 rue de Brennus 93200 Saint Denis, France Phone (33) 1 49 178300, Fax (33) 1 49 178301 Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455 Generator Set Model Enclosure 7 m (23 ft.), 60 Hz M226 -M230 Enclosure Specifications 7 m (23 ft.), 50 Hz Length, Width, Height, Area, m 2 (ft 2 ) Enclosure Wt., kg (lb.) KD120U 70.1 KD130 67.6 590 (1301) KD150U 68.9 KD165 68.8 M226 KD175U 68.9 3508 (138) 1200 (47) 1830 (72) 4.21 (45.0) 600 (1323) KD200 69.0 KD200U 70.1 KD220 68.6 610 (1345) KD250U 72.5 990 (2183) KD275 69.5 M227 4004 (158) 1380 (54) 2145 (84) 5.5353 (59.3) KD275U 71.3 950 (2094) KD300 69.5 990 (2183) KD350U 71.0 1120 (2469) KD400 66.5 M228 4475 (176) 1410 (56) 2430 (96) 6.31 (68.4) KD400U 71.0 1130 (2491) KD440 66.6 KV200U 71.7 M226 KV220 68.5 3508 (138) 1200 (47) 1830 (72) 4.21 (45.0) 640 (1411) KV250U NA M227 KV275 67.8 4004 (158) 1380 (54) 2145 (84) 5.5353 (59.3) 930 (2050) KV300U 69.9 KV330 67.0 1130 (2491) KV350U 73.0 1124 (2478) KV375 M228 67.0 4475 (176) 1410 (56) 2430 (96) 6.31 (68.4) 1130 (2491) KV400U 73.0 1072 (2363) KV410 1120 (2469) 70.00 KV440 1072 (2363) KV450U 73.8 KV500 68.0 M229 KV500U 75.0 1560 (61) 2435 (96) 7.85 (83.9) 1250 (2755) KV550 68.0 5031 (198) KV550U 75.4 1530 (3373) KV630 M230 71.5 1690 (67) 2662 (105) 8.50 (92.1) 1520 (3351) KV700 75.2 1530 (3373) NA Not available at this time. DISTRIBUTED BY: Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability. 2006, 2007, 2008 by Kohler Co. All rights reserved. G6-90 1/08b Page 6