Coil in Coil Components for the High Voltage Superconducting Resistive Current Limiter CULT 110

Similar documents
Status and outlook on superconducting fault current limiter development in Europe

System Technology and Test of CURL 10, a 10 kv, 10 MVA Resistive High-Tc Superconducting Fault Current Limiter

2 nd Generation High-Temperature Superconducting Wires for Fault Current Limiter Applications

High-temperature superconducting magnet for use in Saturated core FCL

Superconducting Fault Current Limiters

Fault Current Limiters

KIT-ENERGY CENTRE. KIT The research University in the Helmholtz Association

Combined HTS Cable and Fault Current Limiter Project in Germany

Keywords: Superconducting Fault Current Limiter (SFCL), Resistive Type SFCL, MATLAB/SIMULINK. Introductions A rapid growth in the power generation

Superconductivity for Electric Systems DOE 2006 Wire Development Workshop

Cryogenic and Electrical Test Results of a 30 M HTS Power Cable

Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch

Design of a laminated-steel magnetic core for use in a HT-SMES

Development of 2 MVA Class Superconducting Fault Current Limiting Transformer (SFCLT) with YBCO Coated Conductors

3D Finite Element Simulations of Strip Lines in a YBCO/Au Fault Current Limiter

High Temperature Superconducting Fault Current Limiters as Enabling Technology in Electrical Grids with Increased Distributed Generation Penetration

Study on recovery performance of high T c superconducting tapes for resistive type superconducting fault current limiter applications

The development of a Roebel cable based 1 MVA HTS transformer

Inductance and Current Distribution Analysis of a Prototype HTS Cable

Transient Stability Improvement of a Multi- Machine Power System by Using Superconducting Fault Current Limiters

Self Field Measurements by Hall Sensors on the SeCRETS Long Sample CICCs in SULTAN

Gesellschaft für Schwerionenforschung mbh (GSI), Planckstrasse 1, D Darmstadt, Germany

Simulating Superconductors in AC Environment: Two Complementary COMSOL Models

Experiences with Superconducting Cable & Fault Current Limiter in a German City Center Mark Stemmle

Central Solenoid Winding Pack Design

Finite element modeling of a superconducting fault current limiter

To be published in the Proceedings of ICEC-22, Seoul Korea, July 2008 MICE Note 232 1

Feasibility of HTS DC Cables on Board a Ship

Influence of the voltage taps position on the self-field DC and AC transport characterization of HTS superconducting tapes

An Optimised High Current Impulse Source

Protecting a Full-Scale Nb3Sn Magnet with CLIQ, the New Coupling-Loss Induced Quench System

EQUIVALENT CIRCUIT MODEL FOR HIGH TEMPERATURE SUPERCONDUCTORS

Investigation of AC Loss in HTS Cross-Conductor Cables for Electrical Power Transmission

Superconducting Cables

Field-Circuit Coupling Applied to Inductive Fault Current Limiters

IEEE (2012) 22 (2). ISSN

Superconducting Fault Current Limiter in DC Systems with MLI Fed to IM

Short-circuit protection to a fault: Superconducting fault current limiters

Honghai Song. Yawei Wang, Kent Holland, Ken Schrock, Saravan Chandrasekaran FRIB/MSU & SJTU June 2015, SJTU Xuhui Campus

Russian Development Program on HTS Power Cables

TRANSFORMERS. Pascal Tixador. Grenoble INP - Institut Néel / G2Elab. Introduction

Grid Issues and Challenges Addressed by High Temperature Superconductor (HTS) Technology

Evaluation of the Current Sharing Temperature of the ITER Toroidal Field Model Coil

Current Lead Optimization for Cryogenic Operation at Intermediate Temperatures. L. Bromberg, P.C. Michael, J.V. Minervini and C.

Simulation study on operating chara. Author(s) Shirai, Y; Taguchi, M; Shiotsu, M; IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2003), 13(2): 18

Superconducting Fault Current Limiters

General Physics (PHYC 252) Exam 4

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

Opus: University of Bath Online Publication Store

Design and Application of Superconducting Fault Current Limiter in A Multi-terminal HVDC System

Physica C 468 (2008) Contents lists available at ScienceDirect. Physica C. journal homepage:

Experimental Investigation of High-Temperature Superconducting Magnet for Maglev

Conductor Requirements for Superconducting Fault Current Limiters

A Cryogenic Magnetostrictive Actuator using a Persistent High Temperature Superconducting Magnet, Part 1: Concept and Design

Innovative fabrication method of superconducting magnets using high T c superconductors with joints

Experimental analysis of the magnetic flux characteristics of saturated core fault current limiters

Phys102 Final-163 Zero Version Coordinator: Saleem Rao Tuesday, August 22, 2017 Page: 1. = m/s

IEEE Transactions on Applied Superconductivity. Copyright IEEE.

Fault Current Limiter Based on Coated Conductor

Experience in manufacturing a large HTS magnet for a SMES

High Temperature Superconductors for Future Fusion Magnet Systems Status, Prospects and Challenges

High-Performance 2G HTS Wire for an Efficient and Reliable Electricity Supply

Symposium VV: Future Directions in HTS

Simple Calibration Free Method to Measure AC Magnetic Moment and Losses

T h e rm i s t o r s

MODELING AND MODIFICATION FOR DISTRIBUTION TRANSFORMER (250 KVA, 11/0.416 KV) TO REDUCE THE TOTAL LOSSES

Penetration dynamics of a magnetic field pulse into high-t c superconductors

Analysis of smart grid with superconducting fault current limiters

Transient analysis of the behaviour of grounding systems consisted by driven rods

Risk mitigation in the development of a Roebel cable based 1 MVA HTS transformer

Railway Research. Study of Superconducting Fault Current Limiter Device in a AC Railway System. 1. Introduction. International Journal of

EPRI Technology Watch 2010 Superconducting Cables Fault Current Limiters

Fault Calculation Methods

Nexans Activities and Plans on HTS Materials. High-Performance Bi2212 Tape and Bulk Conductors for Magnet Technology.

THE NUMERICAL MODEL OF 2G YBCO SUPERCONDUCTING TAPE IN THE WINDINGS OF THE TRANSFORMER

Status and Progress of a Fault Current Limiting HTS Cable To Be Installed In The Consolidated Edison Grid

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

High-Performance Y-based Superconducting Wire and Their Applications

COPPER FOR BUSBARS CHAPTER 4: SHORT-CIRCUIT EFFECTS

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

Optimal Design of PM Axial Field Motor Based on PM Radial Field Motor Data

JOINTS FOR SUPERCONDUCTING MAGNETS

EuCARD-2 Enhanced European Coordination for Accelerator Research & Development. Journal Publication

Effects of the field dependent J/sub c/ on the vertical levitation force between a superconductor and a magnet

Modeling of Power System Components During Electromagnetic Transients

Negative magnetic relaxation in superconductors. E.P.Krasnoperov

ADMISSION TEST INDUSTRIAL AUTOMATION ENGINEERING

Critical Current Properties of HTS Twisted Stacked-Tape Cable in Subcooled- and Pressurized-Liquid Nitrogen

Effect of Discontinuities and Penetrations on the Shielding Efficacy of High Temperature Superconducting Magnetic Shields

Chapter 6: Efficiency and Heating. 9/18/2003 Electromechanical Dynamics 1

What is a short circuit?

Latest Status of High Temperature Superconducting Cable Projects

A parameter- free method to extract the superconductor s J c (B,θ) field- dependence from in- field current- voltage characteristics of HTS tapes

PHY 1214 General Physics II

Homework # Physics 2 for Students of Mechanical Engineering. Part A

Lecture 2: Training, fine filaments & cables

BUSBAR AND JOINTS STABILITY AND PROTECTION

SELF-FIELD AC POWER DISSIPATION IN HIGH-T C SUPERCONDUCTING TAPES AND A PROTOTYPE CABLE

ROEVER COLLEGE OF ENGINEERING & TECHNOLOGY ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ELECTRICAL MACHINES I

This section develops numerically and analytically the geometric optimisation of

Transcription:

Coil in Coil Components for the High Voltage Superconducting Resistive Current Limiter CULT 11 Steffen Elschner (2), Mark Stemmle (3), Frank Breuer (1), Heribert Walter (1), Christian Frohne (3), Mathias Noe (4) and Joachim Bock (1) (1) Nexans SuperConductors GmbH, D 5351 Huerth, Germany (2) Hochschule Mannheim, D 68163 Mannheim, Germany (3) Nexans Deutschland Industries GmbH & Co. KG, D 3179 Hannover, Germany (4) Forschungszentrum Karlsruhe GmbH, D 7621 Karlsruhe, Germany E-Mail: mark.stemmle@nexans.com Abstract - The project CULT 11 funded by German government (BMBF/VDI) is presently the largest current limiter project in Europe. It aims at the development of a one-phase resistive limiter for the 11 kv level and is based on melt cast processed BSCCO 2212 bulk superconductor. The innovative electrical protection concept uses a normal conducting coil arranged around the superconducting bulk coil and connected in parallel. This coil serves as an electrical bypass and simultaneously, under fault conditions, generates a magnetic field for quench homogenisation. Since no continuously connected shunt is needed, an increased voltage can be applied during faults. Manuscript received December 14, 27; accepted Jan 11, 28. Reference No. ST24, Category 6. Based on paper submitted to Proceedings of EUCAS 27; published in JPCS 98 (28), paper # 1239 I. INTRODUCTION Fault current limiters are at present one of the most attractive applications of hightemperature superconductors in electric power systems [1]. Especially resistive concepts [2-5] seem to have excellent chances for economical and technical viability. This was shown, up to the 1 kv/1 MVA rating, e.g., within the successful German current limiter project CURL 1 [3], which utilized melt cast processed (MCP) BSCCO 2212 as the superconductor. On the basis of CURL 1 achievements, the German government (BMBF/VDI) funded the new project CULT 11 which started in 25. It aims at the construction of a 1-phase superconducting resistive fault current limiter demonstrator for the 11 kv grid. The consortium gathers together partners with all the necessary skills for such a complex project. The German utility RWE defined a set of specifications and is committed to test in the future a full-scale 3- Page - 1 - of - 9

phase prototype in grid operation, after the successful development of a single phase demonstrator. Forschungszentrum Karlsruhe (ITP) is responsible for the high voltage design, Leibniz University Hannover supports the project partners with simulations, Nexans Deutschland Industries establishes the cryogenic concept and Nexans SuperConductors develops the components and assembles the whole system. The technical specifications to be met by the 1-phase-demonstrator are based on the requirements for the 3-phase prototype intended to be installed in a grid coupling [6] between two RWE 11 kv grids. Main technical challenges are the rated current I r = 185 A and the limitation time t lim = 6 ms. The prospective short circuit current of 31.5 ka (peak current 8 ka) must be limited to 6 ka with the first peak not exceeding 4 ka. An important task of all resistive fault current limiter projects is a reliable protection concept against the dangers of hot spots. The concept used successfully within CURL 1 [3], a normal-conducting bypass soldered continuously on the superconductor, is not transferable to the high-voltage level. Due to the heating of the shunt, the voltage in the limitation case must not exceed 1 V/cm leading to prohibitively long lengths. Therefore, a novel protection concept has been proposed [4,7], which is based on the strong magnetic field dependence of critical current density. Indeed, at 77 K the critical current density decreases by one order of magnitude in a field as small as.1 T [7]. The new concept consists of a normal-conducting coil arranged around the bulk superconductor and connected in parallel (Figure 1). If a short circuit occurs, a voltage along the superconductor appears due to flux flow and/or the formation of hot spots. This voltage drives a current through the normal conducting coil. The resulting field then brings the still superconducting parts of the sample to a fast and homogeneous quench. Fig 1. Coil-in-coil component. The superconducting coil machined out of a tube (inner) is introduced into the normal-conducting trigger coil (outer) and connected in parallel. Page - 2 - of - 9

This contribution describes the design rules for suitable components, i.e. the superconducting coils and normal-conducting trigger coils. We show by simulation and experiment, that the proposed protection mechanism works reliably. II. SUPERCONDUCTING COILS Initially, the new protection mechanism was proposed for tube-shaped superconductors with normal-conducting trigger coils [4, 7]. However this concept has quite large losses under normal operating conditions: With a rated current of 185 A, an effective tube length of 3 cm and an assumed resistance of 1 μω per component (copper plus 2 contacts), normal conducting losses of about 3 kw per phase at 77 K are expected. These losses can be reduced considerably if we use coils machined out of superconducting tubes. For the set tube diameter, the superconducting length of each coil significantly exceeds the length of the tube. Consequently, a lesser number of components is required in the string (m < m). However, to attain the required current rating (the superconductor cross-section), several such strings must be connected in parallel to form an array. The number k of parallel strings increases with decreasing coil pitch, in our case k 1. As the product of superconducting length and total cross-section must be constant, the volume of superconducting material and consequently the total number of components remains roughly unchanged when compared with the tube-in-coil design, m = km. The current in each component is reduced by the factor k and thus the total losses in the contacts decrease by a factor k². Figure 2 depicts schematically both the old tube in-coil design (a), and the new coil-in coil-design (b). A further advantage of the coil-in-coil design is that the trigger field and self field have the same direction and their values add up directly, whereas in the tubein-coil design both fields are perpendicular to each other. a) b) Fig 2. Arrangement of components for tube in-coil design (a) and coilin coil-design (b), schematic. The total number of needed components remains roughly the same, see text. Page - 3 - of - 9

The superconducting coils of CULT 11 are based on MCP BSCCO 2212 tubes with an outer diameter of 5 mm, the same as used in CURL 1. Superconducting ceramic tubes can be cut to mono- (see Figure 1) or bifilar coils by milling or sawing [8]. For CULT 11 a monofilar design is preferred instead of the bifilar coils used in CURL 1, because of high voltage issues. Indeed, in the case of lightning surges a high voltage wave front propagates along the conductor and in the case of bifilar coils huge voltages may appear between the first turns of the coil. The wall thickness of the coils has to be chosen as small as possible in order to minimise the AC losses. Also, due to self-field effects, the critical current density decreases with increasing wall thickness. However, mechanical stability has to be ensured and the total number of components has to be limited. Trade-off suggests the wall thickness of 2 mm. The needed total superconducting cross section A SC is given by the specified operating current I r and the assumption that the AC maxima of the rated current must just remain below the critical current of the component. With jc (77 K) = 145 A/ cm² we obtain a total cross section of: ASC = Ir 2/ jc = 1.8cm² (1) With k = 1 components connected in parallel, a wall thickness of 2 mm and a cutting width of 1.5 mm a pitch of 1.5 mm results. The minimum superconducting length is defined by the temperature T max acceptable during a short circuit. The corresponding maximum electric field E max is evaluated in an adiabatic approximation: E ρ 2 max SC lim Tmax t = C ( T) dt (2) TLN where ρ SC is the mean resistivity in the relevant temperature range and C SC (T) the well-known temperature-dependent specific heat per volume. With T max = 3 K we obtain E max = 32 V/m. Assuming a double line-to-ground fault (i.e. the worst case), the minimum required superconducting length is 231 m. With an active tube-length of 26 mm and a winding pitch of 1.5 mm, a superconducting length of 36 cm per component results. This leads to the total number of 65 components per phase. SC III.TRIGGER COIL DESIGN The geometry of the parallel coil is of crucial importance. The radius of the coil r has to be as small as possible in order to minimise the inductance and the time constant τ = L/R ~ r. For similar reason the coil has to be as short as possible, but with the superconducting windings positioned entirely in the homogeneous field region. Three parameters then remain to be chosen independently: The material, i.e., the specific resistance ρ Tr (T), the number of windings N Tr and the cross section A Tr of the conductor. However, there are three physical arguments which restrict the possible coil configurations: Page - 4 - of - 9

(1) Current limitation The sum of both currents, through the shunt coil I shunt and through the superconductor I SC, must remain below the specified limited current I k. The I SC is calculated from the geometry of the superconductor and its resistivity ρ SC (T), the impedance Z of the trigger coil is obtained with the usual approximations for a long coil: 2 2 2 2 ω µ N πr 2 2 2 ρ 2 ( ) Tr πr N Z = R + ωl = Tr + Tr ATr ltr A numerical evaluation including the phase shift and the coupling between both inductances then allows one to calculate the maximum possible cross section A Tr as function of the number of turns N Tr. (2) Heating of the coil The heating of the trigger coil during quench must be limited. It is essentially given by the resistivity of the material ρ Tr (T). If a temperature increase Δ T is accepted, the condition tlim TLN + ΔT P() t dt CTr ( T) dt (4) TLN must remain fulfilled. Here, P(t) is the electric power dissipated within the trigger coil, C Tr (T) the temperature dependent heat capacity of the coil and T LN the temperature of the coolant. In a rough approximation (4) simply defines the minimum length of the conductor and thus the minimum number of windings. A closer examination shows that this minimum number slightly depends on the cross section A Tr, because of the inductive part in (3). (3) Geometric limitations A single layer coil is strongly preferred because of high voltage issues. Also, due to large electromechanical forces in the limiting case, for mechanical stability reasons the coil spiral is preferably cut from a metal tube. The cutting procedure defines the upper limit for thickness. Obviously, with increasing number of turns the possible cross section decreases. For each conceivable material, a numerical study including the temperature dependences of ρ Tr and C Tr, visualises these three conditions by three lines in the A Tr versus N Tr diagram shown in Figure 3. These lines limit an area in the (A Tr, N Tr ) space which reflects possible configurations in accord with specifications and physical restrictions. Figure 3 shows the (A Tr, N Tr ) plots for copper (Figure 3a) and stainless steel (Figure 3b). Two additional physical arguments are helpful: The trigger field has to be large and has to increase as rapidly as possible. For a qualitative consideration of both requirements, we assume a step-type increase U Step of voltage ( hot spot ) (3) Page - 5 - of - 9

cross section (mm 2 ).5.4.3.2.1 max db/dt 3 33 36 39 42 45 number of turns (a) max B limitation heating geometry cross section (mm 2 ) 8 7 6 5 4 3 2 1 max db/dt 3 5 7 9 11 13 number of turns (b) max B limitation heating geometry Fig 3. Winding/cross-section diagrams for copper (a) and stainless steel (b). Only trigger coils within the surface delimited by the three lines and by the N Tr -axis are allowed according to physical restrictions (see text). and consider the response of the current: I(t) = I (1 exp( t / τ)) with I = U Step / R and τ = L / R. The initial rate of field increase is then db N ( ) Tr di NTr I NTr UStep UStep t = = µ = µ = µ = ( 5) dt l dt l τ l L NTr π r² This rate increases with decreasing N Tr, independently of A Tr, whereas the equilibrium field B µ NTr U Step µ NTr UStep A Tr µ UStep ATr = = = l R l ρ (77 K) N 2 π r l ρ (77 K) 2π r Tr Tr Tr (6) increases with increasing A Tr, independently of N Tr. Consequently, for the target coil N Tr must be as small as possible, and A Tr as large as possible (qualitatively depicted by the arrows in Figure 3). In the case of copper shown in Figure 3(a), these rules lead to a straightforward design, i.e., the coil has to be chosen corresponding to the left crossing point in Figure 3(a) marked by the full dot. However for other materials such as brass or stainless steel, the latter shown in Figure 3(b), the decision is less evident because the line defined by limitation strongly increases with N Tr and a compromise between both requirements (5) and (6) has to be found. Page - 6 - of - 9

VI. NUMERICAL SIMULATION The final optimisation of the target coil with respect to quench homogenisation, in particular the choice of the material and, where required, the exact position on the line given by current limitation, e.g., as in Figure 3(b), can be done by experiment or simulation. To this purpose a numerical tool was developed within MATLAB. The electric properties of both coils, including their cross-correlation, follow directly from their geometry. The U(I)-characteristics of the superconductor were measured as functions of field and temperature [7] and parameterised with simple analytic expressions. The temperature-dependent specific heat and resistivity are well known. Heat conduction was neglected, since within the short limitation time of 6 ms the process is adiabatic. The central point of the model is the introduction of a well-defined hot spot. A simple way to do this is to assume a reduction of cross section (bubble, small crack), in our case by 3 %. The length of the hot spot (e.g. 1 mm) is not critical for the simulations if it is negligible compared to the total length of the superconductor. A similar simulation model has already been described in detail [6]. The simulation depicted in Figure 4 dramatically demonstrates the beneficial effect of the magnetic field. The copper coil of Figure 3(a) (full dot) was chosen for this simulation. The prospective fault current was only 6 times the rated current, a range particularly dangerous with respect to quench inhomogeneity. Prospective and limited current are depicted, as well as the temperatures of the hot spot and of the remaining of the superconductor. Figure 4(a) shows the results of the simulation described above, Figure 4(b) shows the same results, but with the influence of the magnetic field switched numerically to zero, i.e., the coil acts only current (ka) i prosp i CL T SC T HS 1.8 35 1.8 1.5 1.2.9.6.3 -.3 -.6 -.9 325 3 275 25 225 2 175 15 125 temperature (K) i prosp i CL T SC T HS 35 325 3 275-1.2 1-1.2 1-1.5 75-1.5 75-1.8 5-1.8 5 1 2 3 4 5 6 7 8 9 1 1 2 3 4 5 6 7 8 9 1 time (ms) time (ms) current (ka) 1.5 1.2.9.6.3 -.3 -.6 -.9 25 225 2 175 15 125 temperature (K) (a) (b) Fig 4. Simulated limitation behaviour of a superconducting component with a weak segment (hot spot). Prospective fault current (i prosp, dashed line) and limited current (i CL, full line) are depicted as well as the temperature of the superconductor (T SC, dash-dots) and of the weak segment (T HS, dots); (a) with magnetic field acting, (b) without magnetic field (see text) Page - 7 - of - 9

as an electrical bypass. The influence of the magnetic field on quench homogenisation is obvious. The transition of the bulk happens one half wave earlier, and the temperature of the hot spot is strongly reduced. This results in a reduction of the temperature difference between hot spot and the remaining of the bulk (from more than 15K to about 3 K) and clearly contributes to protection of the component. Indeed, the minimisation of hot spot temperature is the objective of the simulation with different coils. For each material (copper, brass, stainless steel, aluminium) the coil was optimised with respect to its position in the (A Tr, N Tr ) diagram. Subsequently, the corresponding coils were compared. The copper coil of cross-section and number of turns marked by the full dot in Figure 3(a) gave rise to the lowest temperature of the hot spot and will therefore be used in the CULT 11 demonstrator. V. SHORT CIRCUIT EXPERIMENTS Short circuit tests with the tube-in-coil geometry were already successful [7]. In the following, first limitation experiments with coil-in-coil geometry are presented. Unfortunately, in these experiments still a suboptimal stainless steel coil was used. Its performance with respect to quench homogenisation is expected to be somewhat weaker compared to the copper coil (full dot in Figure 3(a). Also, the lengths of the superconducting coil and of the bypass coil are scaled down by a factor of 2/3 due to experimental restrictions. This assembly was tested in 67 short circuits each lasting 6 ms. Between and after these experiments no degradation of the superconductor was observed. In the short circuit experiment shown in Figure 5 the prospective peak current of 1.2 ka (full load) is limited to less than 3.7 ka within the first half wave and further to 1.1 ka rms at the specified limit. The voltage during limitation corresponds to the design field of 3.2 V rms /cm. VI. CONCLUSION In order to reduce the normal losses of the system the component design of CULT 11 has been improved considerably by extending the self-triggered magnetic homogenisation concept to a coil-in-coil geometry. Numerical simulation and first experiments clearly show that the concept is viable and that the protection mechanism works. This has been also confirmed with partial loads and in parallel operation, however not yet with the desired reproducibility. The next steps are the use of optimum trigger coils and a pre-prototype test with several components connected in parallel and in series. ACKNOWLEDGEMENTS The authors want to thank A. Kudymow, S. Bemert and R. Dommerque for valuable contributions, and the BMBF/VDI for support by Grant 13N8868. Page - 8 - of - 9

REFERENCES [1] M. Noe and M. Steurer, Supercond. Sci. Technol., 2, R15 (27) [2] M. Chen, W. Paul, M. Lakner, L. Donzel, M. Hoidis, P. Unternaehrer, R. Weder, M. Mendik, Physica C, 372 376, 1657.(22) [3] J. Bock, F. Breuer, H. Walter, S. Elschner, M. Kleimaier, R. Kreutz, M. Noe, IEEE Trans. Appl. Supercond., 15, 1955 (25). [4] X. Yuan, K. Tekletsadik, L. Kovalsky, J. Bock, F. Breuer, S. Elschner, IEEE Transact. Appl. Supercond., 15, 1982 (25). [5] A. Usoskin, H.C. Freyhardt, A. Issaev, J. Knoke, J. Dzick, M. Collet, P. Kirchesch, J. Lehtonen, IEEE Transact. Appl. Supercond., 13, 1972 (23). [6] M. Stemmle, C. Neumann, F. Merschel, U. Schwing, K.H. Weck, M. Noe, F. Breuer and S. Elschner, IEEE Transact Appl. Supercond., 17, 2347 (27). [7] S. Elschner, F. Breuer, H. Walter, M. Stemmle, J. Bock, IEEE Transact. Appl. Supercond., 17, 1772 (27). [8] S. Elschner, F. Breuer, M. Noe, T. Rettelbach, H. Walter, J. Bock, IEEE Trans. Appl. Supercond., 13, 198 (23). Page - 9 - of - 9