UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. Interconnection for Wind Energy ) Docket No. RM

Similar documents
Pursuant to Section 205 of the Federal Power Act ( FPA ) 1 and the Commission s

The North American Electric Reliability Corporation hereby submits Informational Filing of the North American Electric Reliability Corporation.

Reliability of Bulk Power Systems (cont d)

Transcontinental Gas Pipe Line Corporation Compliance Filing in Docket No. RP05-369

Module 6 : Preventive, Emergency and Restorative Control. Lecture 27 : Normal and Alert State in a Power System. Objectives

Section 5. TADS Data Reporting Instruction Manual DRAFT Section 5 and Associated Appendices With Proposed Event Type Numbers

El Paso Natural Gas Company, L.L.C.; Semi-Annual Activity Report Washington Ranch Storage Facility Docket Nos. RP72-6, et al.

Derogation Criteria for the Requirements for Generators Network Code

System Impact Assessment Addendum #2 Greenfield & St. Clair Energy Centres

June 26, Federal. Commissioners: Re: CP Pursuant to. the. Pursuant to. ordering

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Report on El Paso Electric Company Weather-Related Issues in February 2011

Role of Synchronized Measurements In Operation of Smart Grids

August 12, Docket OSHA ; Comments on Review of Process Safety Management (PSM) Standard Hydrochloric and Hydrofluoric Acids

El Paso Natural Gas Company, L.L.C.; Semi-Annual Activity Report Washington Ranch Storage Facility Docket Nos. RP72-6, et al., CP79-224, and CP15-516

DE PUBLIC SERVICE COMPANY OF NEW HAMPSHIRE

Power System Security. S. Chakrabarti

Chapter 2. Planning Criteria. Turaj Amraee. Fall 2012 K.N.Toosi University of Technology

1. Introduction. Keywords Transient Stability Analysis, Power System, Swing Equation, Three-Phase Fault, Fault Clearing Time

4/26/94 Revised 12/26/96 5/9/99 7/30/01 WSCC UNSCHEDULED FLOW MITIGATION PLAN

UNITED STATES DISTRICT COURT DISTRICT OF ARIZONA ) ) ) ) ) ) ) )

GENERATOR INTERCONNECTION APPLICATION

Colorado PUC E-Filings System

Transient Stability Assessment of Synchronous Generator in Power System with High-Penetration Photovoltaics (Part 2)

Subject: Availability of New and Revised Public Housing Agency (PHA) Five-Year and Annual Plan Templates and Other Forms

Cascading Outages in Power Systems. Rui Yao

Integrating Wind Resources Into the Transmission Grid

Expedited Filing Draft August 22, 2017

Transmission and Dispatching Operations Manual

Exhibit IV-1: Initiation of Zoning Map Amendments Case Report HEARING DATE: MAY 3, 2012

Power System Seminar Presentation Wind Forecasting and Dispatch 7 th July, Wind Power Forecasting tools and methodologies

Stochastic Unit Commitment with Topology Control Recourse for Renewables Integration

Renewables and the Smart Grid. Trip Doggett President & CEO Electric Reliability Council of Texas

Power Grid Vulnerability to Geographically Correlated Failures - Analysis and Control Implications

Power System Stability and Control. Dr. B. Kalyan Kumar, Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai, India

SUBPART MULTIYEAR CONTRACTING (Revised December 19, 2006)

Outage Coordination and Business Practices

February Industry Communique

Report on Phase 2: System Performance Evaluation. Prepared for:

CITY OF STURGIS 1984 REVISED ORDINANCES TITLE 35-1

Technical Requirements. Version No. 1.0 Effective Date 10/1/2008

Transmission and Dispatching Operations Manual

International Workshop on Wind Energy Development Cairo, Egypt. ERCOT Wind Experience

Vegetation Related Transmission Outage Report

11.1 Power System Stability Overview

I INCH- POUND j MIL-STD-1399(NAVY SECTION 302A 29 February 1988 SUPERSEDING DOD-STD-1399(NAVY) SECTION March 1972 (See 6.3) MILITARY STANDARD

COMMUNITY DEVELOPMENT DEPARTMENT POLICY & PROCEDURE

Risk Analysis for Assessment of Vegetation Impact on Outages in Electric Power Systems. T. DOKIC, P.-C. CHEN, M. KEZUNOVIC Texas A&M University USA

Reference: US Department of Energy.

Optimal Placement & sizing of Distributed Generator (DG)

Department of Transportation. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

PUB NLH 185 Island Interconnected System Supply Issues and Power Outages Page 1 of 9

C L I E N T A LERT. Ha r m o n i z i n g Ha z a rd Co m m u n i c a t i o n : OSHA Pr o p o s e s t o. I. Ba c k g r o u n d

Cascading Failures in Power Grids - Analysis and Algorithms

Peterborough Distribution Inc Ashburnham Drive, PO Box 4125, Station Main Peterborough ON K9J 6Z5

THIRD GENERATION SYSTEM PROTECTION SCHEME PROJECT FOR ZEYA HYDRO POWER PLANT

NUCLEAR REGULATORY COMMISSION. 10 CFR Chapter 1 [NRC ] Clarification on Endorsement of Nuclear Energy Institute Guidance in Designing

BVES Annual Reliability Public Presentation 2016 Performance

1. CALL TO ORDER 2. ROLL CALL 3. PLEDGE OF ALLEGIANCE 4. ORAL COMMUNICATIONS (NON-ACTION ITEM) 5. APPROVAL OF AGENDA 6. EWA SEJPA INTEGRATION PROPOSAL

STANDING COMMITTEE ON GEOGRAPHICAL INDICATIONS QUESTIONNAIRE TO NATIONAL GROUPS

EE 451 Power System Stability

ANALYSIS OF SUBSYNCHRONOUS RESONANCE EFFECT IN SERIES COMPENSATED LINE WITH BOOSTER TRANSFORMER

The following procedures describe how application managers will review chemical additives during the permit application review phase.

Commissioning and Testing of AVR and PSS

REVISED UPDATED PREPARED DIRECT SAFETY ENHANCEMENT COST ALLOCATION TESTIMONY OF GARY LENART SAN DIEGO GAS & ELECTRIC COMPANY AND

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT

Transient Stability Analysis of Single Machine Infinite Bus System by Numerical Methods

2018 Annual Review of Availability Assessment Hours

Acknowledgment of Aramco Asia. Supplier Code of Conduct

Weekly Operational Constraints Update

A COMPUTER PROGRAM FOR SHORT CIRCUIT ANALYSIS OF ELECTRIC POWER SYSTEMS

SSC-JE EE POWER SYSTEMS: GENERATION, TRANSMISSION & DISTRIBUTION SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL

Geomagnetic Disturbance Operating Plan

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter *

POWER SYSTEM STABILITY AND CONTROL

National Register of Historic Places Registration Form

CECOER. Renewable Energy Control Center. How technologies have boosted remote operations. Agder Energi-konferansen

Influence of Grounding Material s Property on the Impulse Grounding Resistance of Grounding Grids

Hydra Fault Current Limiting HTS Cable to be Installed in the Consolidated Edison Grid

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 2, MAY Definition and Classification of Power System Stability

POLICY ISSUE (INFORMATION)

OTTER POINT ADVISORY PLANNING COMMISSION. Notice of Meeting on Tuesday, June 5, 2018 at 7 p.m.

POWER FLOWS. Successful power system operation under normal balanced three-phase. steady-state conditions requires the following:

Adaptive under frequency load shedding using synchrophasor measurement

F F FAULT CURRENT Prospective. 1. Introduction. 2. Types of fault conditions

Unit certificate for solar inverters

Research Article A Novel Algorithm for Power Flow Transferring Identification Based on WAMS

NUCLEAR REGULATORY COMMISSION. 10 CFR Parts 50, 52, 54, and 100. [Docket Nos. PRM ; NRC ]

TORNADO VS HURRICANE WHICH IS MORE DETRIMENTAL TO THE SAFETY OF US NUCLEAR POWER PLANTS

6. The August 14 Blackout Compared With Previous Major North American Outages

Sustainable Groundwater Management Act: Initial Notification of a Proposed Basin Boundary Modification

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA PACIFICORP. Direct Testimony of Heidemarie C. Caswell

Planetary Protection The COSPAR Perspective

Standard Practice for Calculating Formulation Physical Constants of Paints and Coatings 1

Research on the Effect of Substation Main Wiring on the Power System Reliability Yuxin Zhao 1, a, Tao Liu 2,b and Yanxin Shi 3,c

Proper Security Criteria Determination in a Power System with High Penetration of Renewable Resources

Information Document Calculation of Pool Price and Transmission Constraint Rebalancing Costs During a Constraint Event ID # R

NUCLEAR REGULATORY COMMISSION. [Docket No ; NRC ] Strata Energy, Inc.; Ross Uranium In Situ Recovery Facility; Source and

Laboratory Certification Workshop

Minnesota Public Utilities Commission Staff Briefing Papers

Transcription:

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION Interconnection for Wind Energy ) Docket No. RM05-4-000 REQUEST FOR REHEARING OF THE NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL The North American Electric Reliability Council ( NERC ) submits this request for rehearing of the final rule issued by the Federal Energy Regulatory Commission on June 2, 2005 in the above-referenced proceeding. 1 Order No. 661 made significant progress in standardizing and facilitating the interconnection of large wind generators to the transmission grid. However, certain of the requirements the Commission prescribed in the final rule present an unacceptable risk to the reliability of the bulk electric system and should be changed. I. SPECIFICATIONS OF ERROR 1. The Commission erred in adopting the specifications of Figure 1 as the low voltage ride through ( LVRT ) capability required of wind generators. 2. The Commission erred in shifting to transmission providers the burden of justifying the need for certain good utility practices. 2 In support of these specifications of error, NERC states as follows: II. BACKGROUND On January 24, 2005, the Commission issued a Notice of Proposed Rulemaking ( NOPR ) in the above-referenced docket. 3 The NOPR was issued in response to a 1 Interconnection for Wind Energy, 111 FERC 61,353 (2005) ( Order No. 661 ). 2 The Commission recently concluded that the term good utility practice includes compliance with NERC s new Reliability Standards. 3 Interconnection for Wind Energy, 110 FERC 61,036 (2005). 1

petition submitted by the American Wind Energy Association ( AWEA ) and proposed to require Transmission Providers to adopt certain technical requirements for interconnection service provided to wind generation facilities. The NOPR proposed that the technical requirements applicable to wind generation plants differ in certain respects from those applicable to traditional synchronous generating plants. On March 2, 2005, NERC submitted comments in response to the NOPR. In particular, NERC commented upon the NOPR s proposals regarding the LVRT standard that would be applicable to wind generating plants, the NOPR s proposals regarding Supervisory Control and Data Acquisition ( SCADA ) capability, and power factor design criteria. Order No. 661 did not fully accept NERC s comments regarding these issues. Over NERC s objections, the Commission adopted Figure 1, Minimum Required Wind Plant Response to Emergency Low Voltages, as the LVRT standard. In addition, Order No. 661 shifts to Transmission Providers the burden of justifying common practices in the industry regarding LVRT capability, SCADA capability, and power factors. III. ARGUMENT A. The Commission erred in adopting the specifications of Figure 1 as the low voltage ride-through capability required of wind generators. Section A.i. of Appendix G adopted by Order No. 661 defines the LVRT capabilities required of wind generators in its Figure 1, Minimum Required Wind Plant Response to Emergency Low Voltages. NERC believes that adoption of Figure 1 will reduce the reliability of the electric grid. Figure 1 is not appropriate for wind generator plants connected to the electric system at transmission voltage levels. NERC requests the Commission to reconsider its actions in Order No. 661, and instead require wind plants to 2

meet NERC and regional reliability council reliability standards. NERC strongly believes that anything short of full compliance with its standards could adversely affect grid reliability. NERC therefore respectfully requests that the Commission reverse those aspects of Order No. 661 that would weaken compliance with the NERC reliability standards. Should the Commission choose not to take NERC s approach, the Commission should adopt the LVRT capabilities described in this request for rehearing that would require a wind generator to withstand a normally cleared single line to ground or three phase fault on a transmission line connected to the wind plant switchyard or substation. 1. The Effect of a Transmission Line Fault Near the Point of Interconnection NERC Reliability Standard TPL-002-0, System Performance Following Loss of a Single BES (Bulk Electric System) Element, requires the planning authority and the transmission planner to ensure that the bulk electric system will remain stable with thermal and voltage limits within applicable ratings, and with no loss of demand or curtailed firm transfers, for a normally cleared fault on a single element (an interval of several cycles). If a fault occurs on a transmission line near a wind plant, the voltage measured at that point could drop instantaneously to zero for the short interval required to clear the fault. This low voltage condition would persist until the fault was cleared by the system of protective relays and circuit breakers, separating the faulted line from the electric grid. This clearing time is typically four to eight cycles, or 0.067 to 0.133 seconds. 3

2. Applicable NERC Reliability Standards NERC Reliability Standard TPL-002-0, System Performance Following Loss of a Single BES [Bulk Electric System] Element, classifies this type of normally cleared fault as a Category B, or single contingency event. TPL-002-0 anticipates that the grid would react to this type of fault with the loss of only one element (the faulted transmission line), and that post contingency, the system should be stable and both thermal and voltage limits should be within their applicable ratings. There would be no loss of demand or curtailed firm power transfers, and there would be no cascading outages. 3. Risk to Reliability Figure 1 of the Appendix G, Interconnection Requirements for a Wind Generating Plant, adopted in Order No. 661 would allow the wind generator plant to disconnect from the electric grid at the instant the voltage at the point of interconnection dropped below 0.15 p.u., which would be prior to the normal clearing time of the fault by the transmission line protective devices. The loss of a single grid element (the faulted transmission line) will now be compounded by the loss to the grid of the real power generation represented by the wind plant, as well as any reactive power support provided by the plant. This effect of creating a double contingency event (loss of the transmission line and the wind power plant) is a violation of Reliability Standard TPL-002-0. Furthermore, because the point of interconnection, as defined by the Commission, is based on contractual ownership arrangements, it may be distant from the wind plant. In situations involving a distant point of interconnection, the wind plant may trip for voltages higher than 0.15 p.u. at the high side of the wind generator step-up transformer. To avoid such situations, the LVRT capability should be measured at the 4

high voltage terminal of the wind plant step-up transformer, regardless of where the contractual point of interconnection is located. The loss of multiple elements of the electric system escalates a Category B single contingency event to the consequences of a Category C or a Category D multiple contingency event. These Category C and Category D events are described in NERC Reliability Standard TPL-003-0, System Performance Following Loss of Two or More BES Elements, or TPL-004-0, System Performance Following Extreme BES Events, respectively. The multiple elements involved in this situation are the faulted transmission line and the wind generation connected to the wind plant switchyard or substation. The impacts to the system of a Category C or Category D contingency are more severe than those permitted for Category B events. Implementation of Figure 1 in Appendix G for wind generating plants will have the effect of reducing the reliability of the electric grid. What would normally be a Category B event will now have the consequences similar to a Category C or a Category D event, with the potential of adverse impacts to the electric grid. High penetration levels of wind generator resources also may increase the severity of the adverse impacts to the grid. NERC believes that significant amounts of wind generation can reliably be added to the bulk electric system as long as all parties involved in the planning and operation of these wind plants (generator owners, generator operators, transmission owners, transmission planners and transmission operators) adhere to established reliability standards. 5

4. Proposed Alternative to Figure 1 NERC stated in its March 2, 2005 comments in this docket that the standards for the reliable planning and operation of bulk electric system facilities should be contained in the standards set by NERC and the regional reliability councils, not the Commission s regulations. NERC s comments encouraged the Commission to require wind plants to meet the requirements of NERC and regional council reliability standards. NERC still believes that NERC and the regional reliability councils are the appropriate organizations to establish reliability requirements for the electric grid. The Commission should, therefore, grant rehearing of Order No. 661 and make clear that wind generating plants must meet all applicable standards established by NERC and the regional reliability councils. If, however, the Commission chooses to establish specific reliability standards in its regulations, 4 NERC believes that Figure 1, Minimum Required Wind Plant Response to Emergency Low Voltage, must be modified to require that a wind generator connected to the grid be able to survive a normally cleared single line to ground or three phase fault on a transmission line connected to the plant switchyard or substation. This can be accomplished by modification of Figure 1 to require the wind plant to stay interconnected with the grid if the voltage at the high side of the wind generator step-up transformer is reduced to zero at time 0.0 for a period of up to 0.167 seconds (ten cycles). After 0.167 seconds, but before 0.625 seconds, the wind plant must remain interconnected as long as the voltage is at or above 0.15 p.u., as currently proposed by Figure 1. These 4 NERC recognizes that the Order No. 661 indicates that the Commission will consider a future standard developed by NERC, but that, in the meantime, a Commission-established standard is necessary. Nonetheless, the Commission must grant rehearing of Order No. 661 as described herein in order to ensure that the standard adopted by the Commission does not harm system reliability. 6

modifications will provide for the wind plant to remain interconnected during a normally cleared fault and will reduce the risk to the reliability of the electric system to an acceptable level. NERC understands that the intent of Figure 1 is to have a reasonable requirement for system reliability and also meet the physical capabilities of existing wind generation technology. But wind technology is advancing rapidly. If Figure 1 is included in the Commission s order, it is likely to be static over time and may limit technological development. For example, Hydro-Quebec s grid code 5 for wind plant interconnections requires that the dynamic behavior of wind plants provides the same level of performance as traditional generating facilities to insure system reliability. Hydro-Quebec believes that wind turbine generators can meet its LVRT requirement, which is similar to what NERC proposes (that a wind plant remain interconnected for a normally cleared transmission fault). In fact, a major wind turbine manufacturer will supply wind turbines to Hydro-Quebec for eight projects totaling over 1000 MW during the 2006 through 2012 period. B. The Commission erred in shifting to transmission providers the burden of justifying the need for certain good utility practices. The NOPR would have required that large wind plants seeking to interconnect to the grid (1) to demonstrate LVRT capability; 6 (2) to possess SCADA capability to transmit data and receive instructions from the Transmission Provider; and (3) to maintain a power factor within the range of 0.95 leading to 0.95 lagging, measured at the 5 See Hydro-Quebec Grid Code for Wind Farm Interconnection, S. Bernard, D. Beaulieu, G. Trudel, IEEE 0-7803-9156-X/05. Paper presented at IEEE Power Engineering Society 2005 General Meeting, San Francisco, California, June 12-16, 2005. 6 To demonstrate LVRT capability, the wind generator must show that the plant can remain on line during voltage disturbances up to specified time periods and associated voltage levels. 7

high voltage side of the substation transformers. 7 In Order No. 661, the Commission, without adequate explanation or justification, shifted the burden to transmission providers to justify the need for these commonly accepted features of good utility practice in each particular system impact study. The Commission also said that wind generators could challenge a transmission provider s finding that such requirements were necessary. Shifting the burden to transmission providers of justifying on a case-by-case basis what most regard as common elements of good utility practice is unwise. The approach contained in the final rule could deter transmission providers from following and implementing good utility practice. Inviting wind generators to challenge a transmission provider s decision that such requirements are necessary only compounds the problem. Finally, the Commission s decision in the final rule to use a case-by-case approach may have the unintended consequence of spawning a patchwork of varying requirements. NERC urges the Commission to grant rehearing and return to the approach set out in the NOPR. IV. CONCLUSION Based on the foregoing, NERC respectfully requests that, on rehearing, the Commission remove Figure 1 from Appendix G and instead require wind generators to meet standards established by NERC and the regional reliability councils. If the Commission continues to believe it must specify low voltage ride-through requirements in its regulations, NERC urges the Commission to revise those requirements as described above to reduce the risk to the reliability of the electric system. NERC also requests that the Commission return to requiring wind generators to conform to certain good utility 7 A transmission provider may waive this requirement if it is unnecessary in particular circumstances. 8

practices, unless the requirement is waived in particular circumstances, as the Commission proposed in its NOPR in this proceeding. Respectfully submitted, NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL By /s/ Debra Ann Palmer Its Attorneys SCHIFF HARDIN LLP 1101 Connecticut Avenue, NW Suite 600 Washington, DC 20036-4390 (202) 778-6400 (202) 778-6460 facsimile dpalmer@schiffhardin.com David N. Cook Vice President and General Counsel North American Electric Reliability Council 116-390 Village Boulevard Princeton, NJ 08540-5731 (609) 452-8060 (609) 452-9559 facsimile david.cook@nerc.net July 5, 2005 9

CERTIFICATE OF SERVICE I hereby certify that I have served a copy of the foregoing document upon all parties listed on the official service list compiled by the Secretary in this proceeding. Dated at Washington, DC, this 5 th day of July, 2005. Attorney for NORTH AMERICAN ELECTRIC RELIABILITY COUNCIL DC\ 7011586.1 /s/ Debra Ann Palmer SCHIFF HARDIN LLP 1101 Connecticut Avenue, NW Suite 600 Washington, DC 20036-4390 (202) 778-6400 10