Insulation Resistance and Polarization of Rotating Machines

Similar documents
On-site Non-destructive Dielectric Response Diagnosis of Rotating Machines

Diagnosis of Electrical Performance and Aging Behavior of Transformer Dielectrics

OBSERVATION OF DIELECTRIC PARAMETERS AT GENERATOR STATOR WINDINGS UNDER CHANGING ENVIRONMENTAL CONDITIONS

An Introduction to Insulation Resistance Testing

Evaluation of Capacitance in Motor Circuit Analysis Findings. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

A Perspective on On-line Partial Discharge Testing of Stator Windings. Greg Stone Iris Power Qualitrol

Parameter Influences on HVDC Transformer Insulation and Its Link to Conduction Processes

Comparative Study on Conductivity Using Polarization and Depolarization Current (PDC) Test

HIGH ENERGY DENSITY CAPACITOR CHARACTERIZATION

No Item Code Description Series Reference. Thickness. M B min (mm) T (mm) code. See Thickness Specification Reference Table below

SolderSleeve Devices Specification For Commercial Wire Splices. Table of Contents

World Academy of Science, Engineering and Technology

MULTILAYER CERAMIC CAPACITORS Open-Mode Series (50V to 630V) 0805 to 1812 Sizes X7R Dielectric Halogen Free & RoHS Compliance

Excerpt from the Proceedings of the COMSOL Conference 2010 Paris

METALLIZED POLYPROPYLENE AC FILTERING CAPACITORS

Open-mode Design Capacitors

Comparing Various Moisture Determination Methods for Power Transformers MAIK KOCH*, MICHAEL KRÜGER, STEFAN TENBOHLEN

Prosperity Dielectrics Co., Ltd. 1 ACS-1045 Rev15

Eddy Current Heating in Large Salient Pole Generators

ALUMINUM ELECTROLYTIC CAPACITORS Capacitor Life

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading

Product Data Sheet PD-0037-B

Introduction to AC Circuits (Capacitors and Inductors)

Research on Transformer Condition-based Maintenance System using the Method of Fuzzy Comprehensive Evaluation

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

Modeling of Polarization in Oil-Paper Insulation Using Recovery Voltage Measurements

Jinzhou Power Supply Company, Liaoning Electric Power Company Limited, State Grid, China

Damping resistor design consideration

Physics 248, Spring 2009 Lab 7: Capacitors and RC-Decay

IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 25, NO. 1, MARCH Eric David, Member, IEEE, and Laurent Lamarre. oσu(t)

Recommended Hole Pattern: [mm]

Temperature and Field Dependence of Field Grading Tubes for Medium Voltage XLPE Cable Joints

Grading capacitors for circuit breakers

CHECKING OF POLARIZED AND DEPOLARIZED CURRENTS FOR THE ELECTRICAL EQUIPMENTS, IN ORDER TO DETERMINATE THE STATE OF INSULATION AND ITS HUMIDITY CONTENT

MATLAB SIMULINK Based DQ Modeling and Dynamic Characteristics of Three Phase Self Excited Induction Generator

High Voltage Capacitors Designed to Avoid Catastrophic Failure Modes

CIGRE SC A2 & D1 JOINT COLLOQUIUM 2011, KYOTO JAPAN. Water Saturation Limits and Moisture Equilibrium Curves of Alternative Insulation Systems

Modern Electrical Diagnostics for Metal Oxide Surge Arresters

1. INTRODUCTION 2. FEATURES 3. APPLICATIONS 4.HOW TO ORDER

Product Data Sheet PD-0053-A

Surface Mount Multilayer Ceramic Chip Capacitor Solutions for High Voltage Applications

CERAMIC CHIP CAPACITORS

Surface Mount Multilayer Ceramic Capacitors for Pulse Current Applications

STATIC GAS MONITOR Type SGM/DEW Revision A of 20 aprile 2016

BUSHING AND HV CURRENT TRANSFORMER ON-LINE MONITORING USING M4000 ANALYZER. Victor Sokolov and Vladimir Prikhodko ZTZ-Service Co, Ukraine

MULTILAYER CERAMIC CAPACITORS Capacitor Arrays Series (10V to 100V) 4 x 0402, 4 x 0603 Sizes NP0, X7R & Y5V Dielectrics Halogen Free & RoHS Compliance

CHAPTER 2 OVERVOLTAGE DUE TO SELF-EXCITATION AND INRUSH CURRENT DUE TO CAPACITOR SWITCHING

CGS ALUMINUM ELECTROLYTIC CAPACITORS

OR Explain thermal breakdown in solid dielectrics. How this mechanism is

MULTILAYER CERAMIC CAPACITORS

Safety Certificated Capacitors X2/Y3

APPLICATION NOTES FOR MULTILAYER CERAMIC CAPACITORS

Recommended Land Pattern: [mm]

MULTILAYER CERAMIC CAPACITORS High Q / Low ESR Series (HH) 0201 to 0805 Sizes NP0 Dielectric Halogen Free & RoHS Compliance

The Impact of Metallized Electrodes on High Energy Density Pulse Power Capacitors

MULTILAYER CERAMIC CAPACITORS General Purpose Series (10V to 100V) 0402 to 1812 Sizes NP0, X7R & Y5V Dielectrics RoHS Compliance

Pretest ELEA1831 Module 11 Units 1& 2 Inductance & Capacitance

RESULTS OF ON-GRID OPERATION OF SUPERCONDUCTOR DYNAMIC SYNCHRONOUS CONDENSER

Surface Mount Multilayer Ceramic Chip Capacitors with Integrated Resistor for High Pulse Current Applications

WCAP-AS5H Aluminum Electrolytic Capacitors

MKV AC Capacitors Damping B High dielectric strength High peak-current capability Especially suitable for snubber circuits

MULTILAYER CERAMIC CAPACITORS High Q / Low ESR Series (HH) 0402, 0603 & 0805 Sizes NP0 Dielectric RoHS Compliance

MULTILAYER CERAMIC CAPACITORS Middle & High Voltage Series (200V to 4kV) 0402 to 1812 Sizes NP0, X7R & Y5V Dielectrics Halogen Free & RoHS compliance

PLASTIC FILM CHIP CAPACITOR TYPE ECHU1(C) Operating temperature range

Low Inductance Ceramic Capacitor (LICC)

EFFECT OF ATMOSPHERIC CONDITIONS ON CABLE TERMINATION TO SWITCHGEAR

Characteristics and Definitions Used for Film Capacitors

1000 to pf (E3 series) Dielectric material K2000 K5000 K14000 Rated DC voltage 100 V 100 V 63 V Tolerance on capacitance ±10% 20/+50% 20/+80%

MLCC APPLICATION GUIDE

WCAP-FTXX Film Capacitors

Conductivity Meter For Liquids LCM-8716 Manual

PLASTIC FILM CHIP CAPACITOR TYPE ECHU(X)

PARTIAL DISCHARGE TESTING: A PROGRESS REPORT

TECHNICAL INFORMATION

Features Instant light (less than 100ns) Lead free reflow soldering RoHS compliant Cool beam, safe to the touch

*Contents in this sheet are subject to change without prior notice.

MULTILAYER CERAMIC CAPACITORS Microwave Series (RF) to 1111 Sizes (6.3V to 1500V) NP0 Dielectric Halogen Free & RoHS Compliance

Analyzing the Effect of Ambient Temperature and Loads Power Factor on Electric Generator Power Rating

Capacitance. A capacitor consists of two conductors that are close but not touching. A capacitor has the ability to store electric charge.

Modeling of Transmission Line and Substation for Insulation Coordination Studies

PMLCAP. Polymer Multi Layer Capacitor Specification Sheet RUBYCON CORPORATION PML DIVISION. PMLCAP ST series RPR Rubycon PART No. Drawing No.

PHYS 241 EXAM #1 October 5, 2006

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian Institute of Technology, Kharagpur

Electric Double Layer Capacitors Product Specification. To. : DATE : SPECIFICATION WRITTEN CHECKED APPROVED

3mm Photodiode PD204-6B

MULTILAYER CERAMIC CAPACITORS Low Inductance Series 0612 Size, 50V X7R Dielectric Halogen Free & RoHS Compliance

PLASTIC FILM CAPACITORS

FILM DIELECTRICS USED IN FILM CAPACITOR PRODUCTS

Reliability of Flexible Termination Ceramic Capacitors in Temperature-Humidity-Bias Conditions. Michael H. Azarian, Ph.D

Metallized polyester film capacitors MKT 470

Chapter 13. Capacitors

FEATURES STANDARD CONFIGURATION

Multilayer Ceramic Capacitors High Capacitance Series

TEST CERTIFICATES OR REPORTS ISSUED BY VEIKI-VNL LTD.

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 3, JULY Tapan K. Saha, Senior Member, IEEE, and Prithwiraj Purkait, Member, IEEE

Effect of Temperature on Condition Assessment of Oil-Paper Insulation using Polarization- Depolarization Current

Double Layer Capacitors. PN: NEX_ series & NED_ series

Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors

T. K. Saha and P. Purkait School of Information Technology and Electrical Engineering University of Queensland St. Lucia, Qld Australia

MULTILAYER CERAMIC CAPACITORS Low Profile Series 0402 to 1210 Sizes X7R, X5R & Y5V Dielectrics Halogen Free & RoHS Compliance

Transcription:

2011 Electrical Insulation Conference, Annapolis, Maryland, 5 to 8 June 2011 Insulation Resistance and Polarization of Rotating Machines S.A. Bhumiwat Independent High Voltage Diagnostics Consultant P.O. Box 18-062 Glen Innes Auckland 1743, New Zealand supatra@kea-consultant.com Abstract This contribution explains insulation resistance and polarization of rotating machines through measurement results of Polarization Depolarization Current (PDC), or charging and discharging current, of machines having different types and conditions of insulation aging. It demonstrates why the Polarization Index (P.I.) cannot be used individually to judge insulation dryness and why the product of insulation resistance and capacitance is a better measure of insulation quality than the insulation resistance alone. But it is the combination of PDC, Capacitance ratio and Dielectric Dissipation Factor () which provides a decisive key in the diagnosis of global problems in machine insulation. Keywords- insulation; polarization; depolarization; resistance; capacitance; absorption; conduction; dissipation factor I. INTRODUCTION A. Conduction and Polarization Problems in any electrical insulation are produced by the mechanisms of conduction or polarization or both. Table 1 shows classification of problems in machine insulation based on its basic properties. For decades, problems caused by conduction and polarization have been detected in combination through the measurement of insulation resistance [1]. Since this is the measurement during the charging of insulation by a constant direct voltage, the current consists of the steady-state conduction current (caused by conduction) and absorption current (due to polarization) which decays exponentially to zero at longer time. At initial time when the absorption current is high and dominant, the conduction current is hardly noticed. At longer time when absorption current decays to minimum, the steady-state conduction current then becomes obvious. In spite of the name, Insulation Resistance, which should have constant value and refer to problem caused by conduction only, it includes the time-dependent Insulation Polarization or Dielectric Absorption which refers to problem caused by polarization. Many efforts were reported (e.g. in [2],[3]) for the determination of absorption current from the values of Insulation Resistance in order to identify problems caused by conduction and polarization but none has been an easy task. B. One-minute reading and Polarization Index (P.I.) Carbon dust in old brush type machines and/or water can cause the charging current to be steady as early as one minute. So the one-minute reading of Insulation Resistance has been TABLE I. CLASSIFICATION OF PROBLEMS IN MACHINE INSULATION Polarization By-products of Partial Discharges Aging molecules at interfaces Arcing by-products Oxidation by-products Products of spilled lubricating oil & dust Chemical dust including salts Corrosive products Thermal aging products Moisture in adsorbed or molecular state successfully used by maintenance people since the old days in the detection of conduction problems. To make it more handy, Polarization Index (P.I.), a ratio of the reading at ten minutes to the reading at one minute, was introduced as an indicator of conduction level. When P.I. =1.0, the problem caused by conduction is severe and needs action. Cleaning and drying decrease conduction current thus cause charging current to be steady at longer than one minute which means P.I. is higher. But whether P.I. can be used individually to judge insulation dryness will be answered later through a case study. Recommended minimum values of Insulation Resistance and P.I. of rotating machines are in [4]. Do higher values ensure that your machine has no risk of failure during operation? C. Product of Insulation Resistance (R) and Capacitance (C) For any insulation system, the product of insulation resistance and its capacitance is the time constant of capacitor self-discharge. The larger this time constant or the longer the capacitor self-discharge time, the better the insulation quality [5]. Therefore insulation resistance of any machine can be compared only with its sister units having the same design and same capacitance. It can be compared with its own previous records. Resistance of ground insulation cannot be compared with resistance of phase-to-phase insulation due to its much difference in capacitance. These will be demonstrated later in the case studies. D. Polarization Depolarization Current (PDC) Analysis All results of Insulation Resistance and other dielectric responses in this contribution are from commercially available PDC-Analyser 1 based on [6] which measures both polarization (or charging) current and depolarization (or discharging) in 1 PDC-Analyser from ALFF Engineering, Switzerland Conduction Surface humidity Free water or droplet Surface contaminants Tracking Carbon dust Metal dust Debris from fault Leakage path 978-1-4577-0276-1/11/$26.00 2011 IEEE 249

order to identify conduction and polarization in electrical insulation. The depolarization current represents absorption current since conduction current does not exist when external power source is switched off for discharging. This on-site instrument is able to measure current as low as one Pico- Ampere (10-12 A) with high precision which allows ground insulation of rotating machines to be tested at the voltage as low as 50V. In addition to the time-domain PDC measurement results, the instrument also provides the frequency-domain evaluation results of Capacitance (C) and Dielectric Dissipation Factor (). Details of PDC diagnosis of machine insulation including test connection, factors affecting the measurement, interpretation and in-service criteria are in [7]. In that reference, the author proposed three diagnostic parameters from the Analyzer for interpretation of dielectric response results which are PDC shape, and (the ratio of C at corresponding frequency to C at 50 Hz). While PDC shape identifies the type of problem, tells how severe the problem is and indicates how much insulating materials have been deteriorated by polarization. When is unity, there is no deterioration in the insulating materials. Reference [7] does not include insulation resistance in the interpretation since it provides the same information as polarization current. For each case study in this contribution, a plot of insulation resistance versus time is accompanied by the PDC so readers who are familiar with the plot of insulation resistance and P.I. results can better understand the characteristics of each aging type. A plot of RC versus time is also presented. RC is obtained by multiplying the 50-Hz capacitance value (given by the PDC- Analyser) to the insulation resistance. The value of RC at 60 s is presented in Table II together with capacitance, P.I. and insulation resistance at 15, 60 and 600 s. In addition, the results of & are included in each case study together with the suggested limits (proposed in [7] and [9]) for safe operation of ground insulation () and phase-to-phase insulation (). II. PROBLEMS IDENTIFIED BY DIELECTRIC RESPONSES A. No Problem The dielectric response results of phase-to-phase () and ground insulation () of a new generator stator (not yet in service) in good condition are presented in fig. 1 for reference. When the insulation system is good and dry, the polarization current () and the depolarization current (I depol.) are nearly equal for about one-tenth of the charging time such as in fig. 1a. Both currents are straight in log-log scale, following inverse power law. The magnitude of PDC depends mostly on the capacitance and insulation condition. For any machine, always has much higher PDC magnitude than at the same test voltage and temperature no matter how good/bad the insulation is because always has much larger capacitance than. Since insulation resistance is the result of a constant test voltage divided by, the insulation resistance of is always higher than, as shown in fig. 1b. It does not mean has better insulation quality than. The shape of insulation resistance for a good and dry machine is also straight in log-log scale but increases with time. So the ratio of insulation resistance between 1 and 10 minutes is more than 1. In another word, P.I. shows a good result. 1.E+13 Suggested limit for, (f) Suggested limit for, PDC at 100V, 20 o C Suggested limits for at 20 o C, (g) Suggested limits for at 20 o C, Figure 1. Dielectric response results of phase-to-phase () and ground insulation () of the good new machine in case IIA: PDC at 100V Insulation Resistance Time constant, RC of of (f) of and (g) of With the result of insulation resistance alone, someone can incorrectly interpret that has better insulation condition than. Therefore, the time constant, RC, as introduced on the previous page is the better measure of insulation quality. The RC-plot in fig. 1c shows that has inferior quality to L- G. Actually the RC-plot of in fig. 1c can be a typical RCplot for a machine having very good ground insulation. Mostly, the phase-to-phase insulation of a new machine has inferior quality to the ground insulation. This can be confirmed by comparing of in fig. 1d with in fig. 1f. The slight increase of at very low frequencies of means slight deterioration of insulating materials due to polarization. Moisture in adsorbed state as described later in case IIB is the cause. While problems caused by polarization increase, problems caused by conduction do not. lower than suggested limit in fig. 1e and fig. 1g means acceptable condition. Both conduction and polarization increase the frequency-dependent. B. Problem with Moisture This is the case of moisture in the adsorbed state (Polarization) without surface humidity, free water or other conductive contaminants (Conduction). It is the case which P.I. cannot be used individually to judge insulation dryness. The dielectric response results in this case study are in fig. 2. 250

PDC at 100V, 19 o C 10,000 1.E+13 19 o C (f) Suggested limit for, Suggested limit for, at 19 o C, Suggested limit for (g) at 19 o C, Suggested limit for Figure 2. Dielectric response results of phase-to-phase () and ground insulation () of the machine having problem of mositure in in case IIB: PDC at 100V Insulation Resistance Time constant, RC C ratio of of (f) of and (g) of A new generator stator in this case study was wet during storage before installation. The drying was done on site and the PDC analysis was applied to verify insulation dryness. The shape of PDC measurement results as presented in fig. 2a looks like a good and dry machine in case IIA (quite straight in loglog scale, following inverse power law). It is also difficult to judge from its evaluation results of insulation resistance in fig. 2b alone that only ground insulation () is acceptable but not phase-to-phase insulation (), unless there is a sister unit to compare or there is a previous test record. The insulation resistance of in fig. 2b is even higher than. The P.I. of (as shown in Table II) is 5.74, which is high like dry insulation. But it is not true. Moisture in adsorbed state is the case that insulation resistance and P.I. are not sensitive to. The Suggested limit 1.E-0 4 Suggested limits for 1.E-04 1.E-03 1.E-02 1.E-01 1.E+00 Figure 3. Dielectric response results of phase-to-phase () insulation of the machine in case IIC, before and after cleaning and drying: PDC at 50V Insulation Resistance Time constant, RC of and of RC plot in fig. 2c gives a hint that is low and inferior to L- G. But the decisive answer of unacceptable but acceptable comes from the PDC evaluation results of and (fig. 2d - fig. 2g) which include the suggested limits for safe operation ( and have different limits). Unlike surface humidity or free water which are conduction problems and do not influence the absorption current, moisture in the adsorbed state increases absorption current without changing the PDC shape. It also increases and. C ratio is very sensitive to this moisture problem. C. Problem with conductive contaminants and mositure Fig. 3 presents the dielectric response results at 32 o C of phase-to-phase insulation of an old machine before and after drying & cleaning. The in fig. 3d and the in fig. 3e reveal the successful drying by circulating short-circuited current which could decrease large amount of moisture in the adsorbed state thus decrease substantially, and the magnitude of absorption current in fig. 3a (decrease both TABLE II. CLASSIFICATION OF PROBLEMS IN MACHINE INSULATION Reference Fig. 1 Fig. 2 Fig. 3 Fig. 4 Fig. 5 Insulation analyzed () () V-W W-U Winding temperature ( o C) 20 20 14 14 32 32 18 30 30 Capacitance (pf) 951 107,860 770 213,400 2,422 2,113 301,175 295 1,328 R at 15 s (GΩ) 199 9.56 49 2.54 3.18 11.8 1.32 84.9 90.6 R at 60 s (GΩ) 401 27.2 172 7.41 5.36 19.8 3.10 144 135 R at 600 s (GΩ) 1,460 157 988 55 8.23 39.0 25.9 234 219 PI (between 15 and 60s) 2.02 2.85 3.51 2.92 1.69 1.68 2.35 1.70 1.49 PI (between 60 and 600 s) 3.64 5.77 5.74 7.42 1.54 1.97 8.35 1.63 1.62 RC at 60 s (s) 381 2,934 132 1,581 13 42 934 42 179 251

10,000 PDC at 50V, 18 o C 10,000 10,000 V-W, 30 o C W-U, 30 o C W-U, V-W, V-W, W-U, V-W, 30 o C W-U, 30 o C Suggested limit for, 1.E-0 4 Suggested limits for at 18 o C 1.E-0 4 Figure 4. Dielectric response results of ground insulation of the machine in case IID which was overheated due to high load and poor ventilation: PDC at 50V Insulation Resistance Time constant, RC of and of and ). Insulation resistance in fig. 3b as well as in Table II therefore show a considerable increase. But there is no increase of P.I. between 15 and 60 s (see Table II) since conduction current has not yet influenced (or insulation resistance) in the first 60 s. While removing conductive contaminants causes the separation of and to appear at longer time as in fig. 3a, it also causes the insulation resistance to be steady at longer time as in fig. 3b. In addition, P.I. between 60 and 600 s increases from 1.54 to 1.97 (see Table II). P.I. is a good diagnostic tool for the problem with conductive contaminants. In spite of much improvement of, the RC-plot in fig. 3c shows slight improvement because the value of 50-Hz capacitance also decreases with the decrease of moisture (see Table II). RC in this case especially before refurbishment is the lowest among all the cases presented here. D. Thermal problem Fig. 4 presents the dielectric response results at 18 o C of ground insulation of a machine which was overheated due to high load and insufficient cooling. The similar shape of and in fig. 4a refers to absorption current which is dominant and has one prominent crook. Insulation resistance and RC versus time are presented to show the characteristics for this type of aging. The resistance curve in fig. 4b is steep and P.I. (between 60 and 600 s) in Table II shows the value of 8.35 which is very high. Experienced from many cases, P.I. (between 60 and 600 s) higher than 7.0 reveals thermal aging or overheating. This is another case to confirm that the high P.I. does not always mean good insulation. (Note: The ground insulation of a new machine in case II B was thermally aged during drying. P.I. is 7.42 and the bending or prominent crook of PDC shape can be noticed in fig. 2a.) Suggested limit for V-W W-U 1.E-0 4 V-W at 30 o C W-U at 30 o C Suggested limit for 1.E-04 1.E-03 1.E-02 1.E-01 1.E+00 Figure 5. Dielectric response results of phase-to-phase V-W and W-U of the motor stator in case IIE with abrasion of insulation: PDC at 500V Insulation Resistance Time constant, RC of and of, in additio to a photo of abraded phase-to-phase insulation The RC-plot in fig. 4c looks like those having good insulation except it is not in a straight line. The in fig. 4d shows deterioration of insulating materials but still acceptable. The -plot in fig. 4e is also within suggested limit for. The ventilation of the machine room was improved and the insulation condition has become stable. E. Combination of polarization problems Deterioration products due to heat, vibration and partial discharges which caused serious abrasion of insulation between two phases in the same stator slot (phase-to-phase slot packer) increase absorption current at initial time within 10 seconds, as shown in fig. 5a. The insulation between phase V and phase W (V-W) shows higher current (or lower insulation resistance) than the insulation between phase W and phase U (W-U) in the first 10 seconds. that, of V-W and W-U have quite similar amplitude or similar shape. This means insulation resistance after 10 seconds of both pairs are also very similar, as shown in fig. 5b and Table II, in spite of more serious condition of V-W than W-U. The P.I. of V-W and W-U are also quite similar (see Table II). So this is an example that higher value of 1-min insulation resistance than IEEE Std. 43 recommendation does not always mean safe for opeartion. The very abraded insulation of V-W can be clearly seen from the much lower capacitance value of V-W (only 295 pf) compared to W-U (1,328 pf) as shown in Table II, which leads to much lower time constant, RC of V-W compared to W-U in fig. 5c, much higher and unacceptable (fig. 5d) and (fig. 5e). It is actually the very high and unusual shape of which characterizes the very deteriorated insulation of V-W. This large motor was stripped a few months after the PDC tests and rewound. The deteriorated phase-to-phase slot packers are shown in the photo of fig. 5. The middle one is the very abraded V-W. 252

III. CONCLUSION Like polarization current or charging current, insulation resistance detects problems caused by conduction and polarization of rotating machines in combination. Its value depends not only the insulation condition but also the capacitance. So it can be compared only with its sister units having same design or same capacitance. Insulation resistance of phase-to-phase insulation cannot be compared with ground insulation due to its much difference in capacitance. Without any fingerprint, the time constant or product RC provides better measure of insulation quality than the insulation resistance alone. This is demonstrated in most of the case studies particularly the case of abraded insulation in fig. 5 or case II E. P.I. (between one and ten minutes) is sensitive to problems caused by conductive contaminants (carbon dust, surface humidity or free water) but not problems caused by polarization. P.I. cannot be used individually to judge insulation dryness since moisture in the adsorbed state (fig. 2 or case II B) decreases insulation resistance without changing PDC shape so P.I. can still be high in case of moisture if no conductive contaminants are included. When P.I. is higher than 7, thermal aging can be suspected. In all case studies shown, and together with PDC shape provide the most efficient and decisive indicator in the assessment of global problems in machine insulation. The accuracy of PDC in the first 10 seconds is very important. ACKNOWLEDGMENT Many thanks to my clients from whose machines the data presented here were collected. REFERENCES [1] J. S. Askey, J. S. Johnson, Insulation resistance and dielectric absorption characteristics of large A-C stator windngs, AIEE Transactions on Electrical Engineering, vol. 64, June 1945, p. 347-351. [2] W. McDermid, Dielectric absorption characteristics of generator stator insulation, in 2000 IEEE International Symposium on Electrical Insulation, Anaheim, USA, April 2-5, 2000, p. 516-519. [3] B. Milano, E. Eastment, B. Weeks, New insights and complications in determining generator stator insulation absorption current exponents and constants from Polarization Index, in 2009 IEEE Electrical Insulation Conference, Montreal, QC, Canada, May 31- June 3, 2009, pp. 13-4, p. 254-258. [4] IEEE Standard 43 Recommended practice for testing Insulation Resistance of electric machinery. [5] B. Tareev, Physics of Dielectric Materials. Mir Publishers, Moscow. [6] J. Alff, V. Der Houhanessian, W. S. Zaengl and A.J. Kachler, "A novel, compact instrument for the measurement and evaluation of relaxation currents conceived for on-site diagnosis of electrical power apparatus," in 2000 IEEE International Symposium on Electrical Insulation, Anaheim, USA, April 2-5, 2000, p. 161-167. [7] S. A. Bhumiwat, On-site non-destructive dielectric response diagnosis of rotating machines, IEEE Transaction on Dielectrics and Electrical Insulation, vol. 17, no. 5, October 2010, p. 1453-1460. [8] S. Bhumiwat, Application of polarisation depolarisation current (PDC) technique on fault and trouble analysis of stator insulation, in CIGRE SC A1 & D1 Joint Colloquium, Gyeongju, Korea, October 24, 2007, p. 79-87 [can be downloaded from www.kea-consultant.com]. [9] S. Bhumiwat, Practical experiences on condition assessment of stator insulation using Polarisation / Depolarisation Current technique, in CIGRE 2008 Session, Paris, August 24-29, 2008, pp. D1-210. [10] S. Bhumiwat, Field experience in insulation diagnosis of industrial high voltage motors using dielectric response technique, in Electrical Insulation Conference, Montreal, Canada, May 30 June 3, 2009, pp. 21-2, p. 454-457. 253