Assessment of the interception efficiency of CVM-based lightning protection systems

Similar documents
Proposed revisions to IEEE Standard 998 (1996) Guide for Direct Lightning Stroke Shielding of Substations

with Implications for Air Terminals

Application of Lightning Location System Data for Designing the External Lightning Protection System

APL 2017 The 10 th Asia Pacific International Conference on Lightning May 16-19, 2017, Krabi Resort, Krabi, Thailand

Available online at ScienceDirect. Reynaldo Zoro*

A Long Term Study on the Performance of Early Streamer Emission Air Terminals in a High Keraunic Region

66kV & 220kV Substation Protection From Lightning by Fixed Angle, Rolling Sphere and Early Streamer Method

EFFECTIVENESS OF WORLDWIDE EXISTING ESE LIGHTNING PROTECTION SYSTEMS MANUFACTURED IN EUROPE

THE EARLY STREAMER EMISSION PRINCIPLE DOES NOT WORK UNDER NATURAL LIGHTNING!!

DIRECT STROKE LIGHTNING PROTECTION DESIGN

Lightning Protection Of Wind Turbines. EWEC 2010 Warsaw Poland By Vidyadhar Peesapati

This case study also provides recommendations for future lightning protection design for existing (brownfield) substation.

DETERMINATION OF THE DIELECTRIC STRENGTH OF LPS COMPONENTS BY APPLICATION OF THE CONSTANT-AREA-CRITERION

Evaluation of the risk of failure due to switching overvoltages of a phase to phase insulation

A Roadmap for Evaluation of Lightning Elimination Technologies

Lightning Effect on Scaled Protected and Un-Protected Building Structures and the Air Terminal Bypasses

This is the submitted version of a paper published in Journal of Electrostatics. Citation for the original published paper (version of record):

Field Sensitive Air Terminal (F-SAT) Simply the Best Lightning Rod

Observation of Cloud-to-Ground Lightning Channels with High-Speed Video Camera

NECESSARY SEPARATION DISTANCES FOR LIGHTNING PROTECTION SYSTEMS - IEC REVISITED

Electric Field Stress Calculation on High Voltage Insulator

Part 5: Total stations

The leader propagation velocity in long air gaps

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Electrical, Electronic and Computer Engineering ENEL4HB - High Voltage 2

Influence of Grounding Material s Property on the Impulse Grounding Resistance of Grounding Grids

Modeling of Transmission Line and Substation for Insulation Coordination Studies

Study of Time Correlation Between Lightning Data Recorded by LLS and Relay Protection

Lightning Flashover Rates of Overhead Distribution Lines Applying EMTP and IEEE Std.1410

Correlation between Lightning Impacts and Outages of Transmission Lines. H-D. BETZ Nowcast GmbH Munich Germany

Analysis of surge arresters failures in the installation of broadcasting transmitter

Lightning Protection Of Wind Turbines

O Plus Dry Bushing 69 kv system, 350 kv BIL, 3000 A. Table of contents

ISO INTERNATIONAL STANDARD. Thermal insulation for building equipment and industrial installations Calculation rules

DESIGN GUIDE FOR GLASS FIBER REINFORCED PLASTIC (GFRP) WIND TURBINE BLADES.

Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO Second edition

C4-304 STATISTICS OF LIGHTNING OCCURRENCE AND LIGHTNING CURRENT S PARAMETERS OBTAINED THROUGH LIGHTNING LOCATION SYSTEMS

ISO INTERNATIONAL STANDARD

ME3620. Theory of Engineering Experimentation. Spring Chapter IV. Decision Making for a Single Sample. Chapter IV

ISO INTERNATIONAL STANDARD. Plastics Determination of thermal conductivity and thermal diffusivity Part 3: Temperature wave analysis method

INTRODUCING THE HALO PDCE LIGHTNING SUPPRESSOR. by EMP Solutions, Inc.

THE APPROACH TO THE ANALYSIS OF ELECTRICAL FIELD DISTRIBUTION IN THE SETUP OF PAPER INSULATED ELECTRODES IN OIL

Experiment 2 Electric Field Mapping

THE INITIATION OF LIGHTNING STRIKES. THE PROTECTION PROVIDED BY LIGHT- NING RODS EQUIPPED WITH DOWN

, times the dielectric constant of the material, k d. . With these definitions, Eq. 1 can be written as:

PHYS 2211L - Principles of Physics Laboratory I

Part 14: Water quality Sampling. Guidance on quality assurance and quality control of environmental water sampling and handling

Introduction to Uncertainty and Treatment of Data

Lightning performance of EHV and UHV overhead transmission Lines in China southern power grid

Electrodynamic Forces Affecting Lightning Protection System Components and Structures

Total Lightning Protection for Floating Roof Petroleum Storage Tanks

Time-varying failure rate for system reliability analysis in large-scale railway risk assessment simulation

Modern Electrical Diagnostics for Metal Oxide Surge Arresters

LIGHTNING PHYSICS AND LIGHTNING PROTECTION: STATE OF ART 2013 Prof. Carlo Mazzetti di Pietralata

VALIDATION OF AN INTEGRATED METHODOLOGY FOR DESIGN OF GROUNDING SYSTEMS THROUGH FIELD MEASUREMENTS


INTERNATIONAL STANDARD

Robustness and Distribution Assumptions

GLD360 AIRPORT LIGHTNING WARNINGS

Quantifying Weather Risk Analysis

Lightning Parameters for Engineering Applications: Recent Updates and Outlook

Analysis of Very Fast Transients in EHV Gas Insulated Substations

Coulomb Balance. Figure 1: The Coulomb Balance apparatus.

SPC Fire Weather Forecast Criteria

PHYS 1111L - Introductory Physics Laboratory I

O Plus Dry Bushing 25 kv system, 150 kv BIL, 3000 A

Unique Vaisala Global Lightning Dataset GLD360 TM

Electric Field Mapping

MONTE CARLO SIMULATION RISK ANALYSIS AND ITS APPLICATION IN MODELLING THE INCLEMENT WEATHER FOR PROGRAMMING CIVIL ENGINEERING PROJECTS

A combinatorial technique for weighbridge verification

Estimation and Confidence Intervals for Parameters of a Cumulative Damage Model

Boundary element modelling of the metalic post protection zone

A Preliminary Analysis on the Statistics of about One-Year Air Gap Measurement for a Semi-submersible in South China Sea

Determination of the Lightning Current from its Thermal Effects

Random Number Generation. CS1538: Introduction to simulations

The Vaisala AUTOSONDE AS41 OPERATIONAL EFFICIENCY AND RELIABILITY TO A TOTALLY NEW LEVEL.

Copyright 2015 Elsevier S.A.

SPECIFICATION SS 51/9 400KV COUPLING CAPACITORS FOR POWER LINE CARRIER SYSTEM

Lab 6. RC Circuits. Switch R 5 V. ower upply. Voltmete. Capacitor. Goals. Introduction

ISO Measurement of radioactivity in the environment Air: radon-222 Part 5: Continuous measurement method of the activity concentration

Name Date Time to Complete

Method of Measuring Machinery Sound Within an Equipment Space

Lab 9. Rotational Dynamics

MATERIAL AND EQUIPMENT STANDARD FOR. INHIBITOR FOR HYDROCHLORIC ACID AND HCl+HF DESCALING AND PICKLING SOLUTION FOR OIL AND GAS WELLS ORIGINAL EDITION

22.S902 IAP 2015 (DIY Geiger Counters), Lab 1

Experiment 2 Random Error and Basic Statistics

Computer 3. Lifetime Measurement

KCC White Paper: The 100 Year Hurricane. Could it happen this year? Are insurers prepared? KAREN CLARK & COMPANY. June 2014

Protocol for the design, conducts and interpretation of collaborative studies (Resolution Oeno 6/2000)

2. Gauss Law [1] Equipment: This is a theoretical lab so your equipment is pencil, paper, and textbook.

STANDARD PROCEDURE: NWSP R2 (15) Polyacrylate Superabsorbent Powders Determination of the Particle Size Distribution by Sieve Fractionation

ISO 354 INTERNATIONAL STANDARD. Acoustics Measurement of sound absorption in a reverberation room

ISO INTERNATIONAL STANDARD

Report on the U.S. NLDN System-wide Upgrade. Vaisala's U.S. National Lightning Detection Network

ISO INTERNATIONAL STANDARD

Switch + R. ower upply. Voltmete. Capacitor. Goals. Introduction

Enquiry. Demonstration of Uniformity of Dosage Units using Large Sample Sizes. Proposal for a new general chapter in the European Pharmacopoeia

EPRI Lightning Protection Design Workstation

POWER UNDERSTANDING MEASUREMENT UNCERTAINTY IN DP FLOW DEVICES

Test method to assess the suitability of materials and surfaces to avoid problems from static electricity by measurement of capacitance loading

Transcription:

Assessment of the interception efficiency of CVM-based lightning protection systems Julien Brousseau 1 and Harold S. Haller, PhD 2 1 Manager of Application Engineering Europe/Asia, ERICO 2 Director, Case Statistical Consulting Center, Case Western Reserve University 2014 1 Abstract The purpose of this paper is to summarize the findings of an unprecedented field study for the assessment of interception efficiency of lightning protection systems (LPS) based on the Collection Volume Method (CVM). Between 2010 and 2012, buildings protected by optimized air terminals placed according to the CVM lightning protection methodology were surveyed in Kuala Lumpur, Malaysia by an independent technical authority, namely, TÜV-Hessen. At each installation, TÜV-Hessen surveyed the buildings and documented evidence of lightning damage (bypasses) and recorded the readings of instruments showing the number of captured lightning events. At the end of the third round of inspections, 33 events had been collected over a combined 37 years of exposure. This agrees closely with the expected number of events determined by the Eriksson attractive radius model ([D Alessandro and Gumley 2001]). Furthermore, the results are in agreement with a field study carried out earlier in Hong Kong, which confirmed the relevance of the Eriksson model ([Petrov and D Alessandro 2002]). Finally, the average interception efficiency of the lightning protection systems was measured against the predicted average interception efficiency on which the optimized terminal placement had been based. The average interception efficiency was found to be in very close agreement with the predicted efficiency. This confirms the result of a previous field study in Kuala Lumpur, the results of which were published in a peer-reviewed journal paper ([D Alessandro and Petrov 2006]). 2 Foreword It is important to note that lightning is a stochastic natural event and there are no lightning models that are 100% accurate. Similarly, there are no known lightning protection systems that are 100% efficient. For this reason, field testing methods as reported in this paper are particularly relevant. Furthermore, it is important to note that the reader should pay particular attention to the documents listed in the bibliography. The results detailed in this paper rely heavily on the prior work in the field of lightning protection. 3 Introduction 3.1 Scope The efficiency of a lightning protection system depends on the placement of lightning rods on the structure to be protected. These lightning rods can be placed according to various models. There are various models currently used in the field of lightning protection, all of which are based on the physical properties of lightning and many years of observation. It is important that these models be scientifically verified in-situ in order to assess their effectiveness with respect to the standardized lightning protection level (LPL). One such standard for lightning protection is presented in the IEC 62305 series of standards. This paper pertains to the documentation of a field trial to continue the verification of the CVM model. Publications of prior field validations include a study in Hong Kong [Petrov and D Alessandro 2002] and 1

a study in Kuala Lumpur [D Alessandro and Petrov 2006]. While such unique field studies have been conducted for this model and published in scientific journals, it was determined that a continuation of the Kuala Lumpur field study would be beneficial to further validate the CVM model. In order to properly execute a continuation of the prior studies, collaboration was established with an independent technical agency with expertise in safety assessment. The independent firm had the responsibility of collecting lightning data as detailed in section 4. The scope of this paper is to analyze the collected data using the main steps of the statistical method shown in [D Alessandro and Petrov 2006] in order to determine the interception efficiency of CVM-based lightning protection systems. 3.2 CVM-based lightning protection system The lightning protection systems surveyed during this study are known as ERICO System 3000 lightning protection systems. A typical System 3000 LPS is comprised of an optimized air terminal that is grounded using an ERICORE insulated downconductor. A lightning event counter was included in each LPS to count the current impulses from lightning collected by the air terminal. The systems were installed according to the ERICO Installation, Operation and Maintenance manual [1]. For each site, the air terminals were placed according to the Collection Volume Method, which is extensively described in [D Alessandro and Gumley 2001] and [D Alessandro 2003]. More recently, the CVM has been cited in the 2012 edition of the IEEE Guide for Direct Lightning Stroke Shielding of Substations, [IEEE998-2012]. As explained in[d Alessandro and Gumley 2001], the CVM is based on the Eriksson attractive radius model. According to [IEC 62305-1:2010], lightning current is a parameter used to calculate the radius of protection in a lightning protection system. Each level of lightning protection is based on a minimum lightning current value. A proprietary software package, LPSD 3.0, offers a method to implement 3D models of structures and the placement of air terminals using the CVM. This software was used in this study to model each lightning protection design and determine the location of the optimized air terminals according to a specified level of protection. Figure 1 shows an LPSD 3.0 screenshot of the plan view of a building protected by an optimized air terminal according to the CVM. This building has been surveyed in this study. The blue color area represents the area of coverage of the optimized air terminal while the green area shows the competing features of the building. The output image shows that the design meets the specified protection level when the blue area (i.e. the area of coverage of the optimized air terminal) fully encloses the green area (i.e. the competing features of the structure). Figure 1: Placement of an optimized air terminal in LPSD 3.0 according to the CVM 2

3.3 Review of past field studies The two real-world field studies referenced in this report, namely [Petrov and D Alessandro 2002] and [D Alessandro and Petrov 2006], were published in the Proceedings of the Royal Society of London A. The studies were conducted in Hong Kong and Kuala Lumpur respectively. Both of these areas are known for their high keraunic levels and are therefore excellent locations for long-term field studies of lightning protection systems. 3.3.1 Petrov & D Alessandro (2002): Hong Kong In this 2002 study, various models of lightning interception were analyzed against real lightning strike data collected in Hong Kong. The field data spanned a period of 8 years and was taken from 161 structures ranging in height from 10 m to 370 m. These structures were protected with lightning air terminals that had been positioned in the optimal roof locations using an improved electrogeometric model, namely the Collection Volume Method (CVM). One of the goals of this research was to determine the validity of Eriksson s attractive radius model. In doing so, the effectiveness of the CVM was assessed. From Table 1 in[petrov and D Alessandro 2002], the mean value of the total expected number of strikes for the attractive radius models considered was 111 while the total observed number of flashes was 103. Therefore, approximately 92% (103 divided by 111) of all flashes are estimated to have been intercepted by the lightning protection systems. This value is consistent with the typical design interception efficiency expected from traditional lightning protection systems based on the Rolling Sphere Method (RSM) or similar methods. In summary, the Hong Kong study demonstrated the validity of the attractive radius models, upon which the CVM is based, in showing the striking distance is a function of the height of the structure. Also, using the overall statistics, an interception probability of around 90% was estimated. 3.3.2 D Alessandro & Petrov (2006): Malaysia The 2006 study included the analysis of 13 years of lightning strike and bypass data for buildings in the Klang Valley/Kuala Lumpur region, one of the most active lightning regions of the world. The data sample was comprised of 86 structures with a mean height of 57 m and mean exposure time of 6.9 years. These structures were subjected to a combined 384 flashes over a total combined observation time of 592 years. Each building was equipped with a lightning protection system. Since an LPS with 100% efficiency does not exist, the major aim of this study was to determine the proportion of strikes captured by the LPS out of the total number of incident strikes. This quantitative study was remarkable in the sense that such an analysis had not been published since the origins of lightning science more than 250 years ago. After the application of a wide range of statistical tests on the data, it was found that the percentage of strikes captured was about 87%. This is in agreement with three leading theoretical models of lightning interception. Using a known median current of 33 ka for Malaysia, the theoretical interception attainable from the Eriksson and Petrov models was 86% and 83% respectively. Hence, both are in excellent agreement with the observed protection level of 87.5%. 4 Data Collection Review 4.1 TÜV-Hessen third-party inspections The data collection in this study was carried out in the Klang Valley region of Malaysia over the period 2010-2012. For each building surveyed during each round of yearly inspections, the TÜV-Hessen inspector published an inspection report containing the following information: Name of the building Date and time of inspection Numbers of the corresponding pictures taken of each LPS installation and of the eventual bypasses on each building Information about the building (roof and wall material) 3

General information about the LPS (number of terminals, location of terminals against LPSD 3.0 design report) Condition of the LPS (optimized terminal and downconductor condition, resistance of grounding system) Result of lightning damage due to bypasses investigation on roof and upper part of the walls (including detailed sketch of building roof) Lightning counter reading Following each round of inspections in 2010, 2011 and 2012, a final report was compiled by TÜV- Hessen that contained: Information about the scope of the study, approach followed to carry out the study and TÜV-Hessen inspector credentials General information about the inspection process and inspection document A summary of inspections results in tabular format Final comments by the TÜV-Hessen inspector. Figure 2 shows the cover page of the 2012 final report. Figure 2: Cover page of 2012 TÜV-Hessen report The present study is based on data collected from lightning event counters on the lightning protection systems of 17 buildings. The initial inspection in 2010 was performed on all 17 buildings with 6 of them being part of the previous Kuala Lumpur study. However, data was inaccessible on four of these buildings. Hence 2011 was considered as being year zero for these four buildings instead of 2010 for the 13 others. The summary of the TÜV-Hessen 2010 final report indicated that the approach taken and results were satisfactory and that inspections could be continued in 2011. In 2011, after one year of exposure, these 17 buildings were re-inspected. In order to collect more data more rapidly, 16 other buildings were added to the study, increasing the size of the building sample to 33. A full year zero inspection was carried out on 12 of the 16 newly added buildings. One newly added site was considered by the inspector to be at year 1 due to the fact that the counter had been installed six months earlier and had already recorded lightning flashes. This assumption is conservative from a statistical standpoint. Four other sites were not inspected in 2012 for one or more of the following reasons: 4

Grounding electrode not accessible for inspection Roof not accessible Downconductor routing not per manufacturer s instructions Discrepancy between the system design and the actual installation. The summary of the TÜV-Hessen 2011 final report indicated that the LPS were in very good conditions and the inspections could be repeated the following year on the 29 remaining sites. In 2012, inspections were performed the final time in the same manner as the previous years and a final report was generated by TÜV-Hessen for all 29 sites. Out of these 29 sites, 28 site visits were completed because one site had a change in building management preventing the inspection from being completed. 4.2 Strikes, Flashes and Lightning Counters As explained in the [IEC 62305-1:2010] standard, a lightning flash is an electrical discharge of atmospheric origin between cloud and earth consisting of one or more strokes. According to this same standard, a single flash typically has between 3 and 4 strokes with each stroke having a different current waveform. The waveforms may be similar to that of an impulse (typical of first strokes and subsequent strokes) or to that of a continuous current (typical of a long stroke). Annex A of [IEC 62305-1:2010] introduces more details regarding the parameters and current waveforms of lightning flashes. A lightning counter such as the one installed on the LPS surveyed during this study counts multiple strokes for each single flash as long as the amplitude of a single stroke exceeds the minimum sensitivity of the counter and that the response time of the counter is less than the interval time between subsequent strokes. In other words, the counter may not increment if the magnitude of the current stroke is small or if multiple strokes occur so rapidly that the counter cannot respond quickly enough. In [D Alessandro and Petrov 2006], the authors have addressed this counting issue by using the results of earlier publications [D Alessandro and Darveniza 2001] in which a set of Monte Carlo simulations had been performed to determine the strike to flash ratio or counting factor. Due to the fact that the same type of counter has been used in this study, the same counting factor (2.5) has been used. The factor was only applied to counter readings where, from year to year, the reading had been increased by more than 1. When the counter reading was increased by only one on a year to year basis the counting factor was not applied. This does not mean that the lightning flash did not have subsequent strokes but that most likely the subsequent strokes were not detected by the counter. 4.3 Review of TÜV-Hessen collected dataset An in-depth study of the data collected by TUV was undertaken using the individual inspection reports for each building as well as numerous photos. Based on the analysis, it was determined that five sites out of the 29 would be eliminated from the study due to issues of invalid or erroneous data collection. For three out of the five sites, a zero percent efficiency was calculated. This data was rejected because it conflicted with the expected number of strikes and the historical data from previous study. At another site, the lightning event counter went missing after the 2011 inspection. Bypasses, or evidence of lightning damage on a building, were identified at three sites. This is not surprising, considering that no lightning protection system offers 100% efficiency. On two of the three sites, one instance of damage to the building was identified by TUV. On the other building three bypasses were identified by TUV, all of them appearing within a one year span. The data suggest that this is a result of a single stroke having multiple attachment points to the structure. A careful reading of [D Alessandro and Petrov 2006] and [Kong et Al. 2009] indicates that multiple-ground terminations strokes (MGTS) are a very common occurrence. Taking this into account and considering the number of expected strike on the structure, it was found that the three single bypasses should be counted as one single bypass. 4.4 Final Dataset In general, a valid statistical analysis requires at least 20 data points. However, it is impractical to collect statistically relevant data from a single structure because an exposure period of 30 years or more would be required. For this reason, and considering the stochastic nature of lightning, a successful field 5

Number of sites 24 Mean height of buildings, h mean 71m Total exposure time t total 37 years Average exposure time t average 1.54 years Sum of individual number of flashes F observed 30.4 Sum of individual number of bypasses B observed 3 Sum of individual number of events N observed 33.4 Average number of events per year A observed 0.9 Table 1: Summary of data collected by TÜV-Hessen used for statistical analysis experiment must collect data from many structures. As shown in[d Alessandro and Petrov 2006], even the analysis of sub-groupings of data is inappropriate. Hence, to make a comparison of the observed interception efficiency with the desired or estimated value, we need to use the entire data set. In this study, many buildings are considered. Therefore, statistically relevant data was collected over a 3 year period. So, in both studies, all of the strike data were combined to allow the analysis to be made with statistical validity. The inherent statistical assumption in this approach is that all the data from the buildings belong to the same population and that no buildings have features which differentiate them significantly from the rest of the buildings. It was shown in [Petrov and D Alessandro 2002] and [D Alessandro and Petrov 2006] that these uncertainties are less than the fluctuations observed in normal lightning processes. Table 1 shows a summary of the data collected by TÜV-Hessen following the review process explained in the previous two sections. The presented efficiency analysis is based on these results. 5 Analysis of the collected data 5.1 Analysis of the lightning strike distribution In order to further analyze the collected data in terms of comparison with the Eriksson attractive radius model or in terms of lightning protection interception efficiency, it is necessary to check whether the frequency of our collected data matches a Poisson distribution. In [D Alessandro and Petrov 2006], it was demonstrated that, using the Kolmogorov-Smirnov test, lightning flashes are randomly occuring rare events matching a Poisson distribution model. Applying this distribution model to our data means that: Lightning flashes occurring in non-overlapping intervals of time are independent. The probability of the number of lightning flashes in a given interval of time depends on the length of the time interval. The probability of a single lightning flash in an infinitesimal interval is some value, λ. The probability of more than a single lightning flash in an infinitesimal interval is zero. With these postulates, consider now the number of lightning flashes in a year in a location. Let X be a random variable representing the number of lightning flashes in a year in a location. The random variable, X, can take on values in following the set: Ω = 0, 1, 2,... (1) The probability distribution for X has the following form for k a member of the set Ω: m mk P rob(x = k m) = e k! The constant m in this equation, also called point estimator, is the expected number of flashes in a year, which is a parameter that can be determined experimentally by doing field inspections and verified against a theoretical model. We know from table 1 that the average number of events per year, A observed is our point estimator and takes on the value 0.9. (2) 6

5.2 Attractive Radius Calculations The number of expected strikes to the structures or events, N d, also called number of dangerous events in [IEC 62305-2:2010], is determined using the Eriksson attractive radius equation, A d, which was extensively documented in [Petrov and D Alessandro 2002] using a field validation method and is also included in [IEEE998-2012]. This concept is applied to revisit the number of dangerous events equation from Annex A of [IEC 62305-2:2010]. The number of strikes to a structure, N d, is determined by the following set of equations: N d = N g A d C d 10 6 (3) A d = π 0 R 2 a(i, h)f(i)di (4) R a = 0.84I 0.74 p h 0.6 (5) N g is the average ground flash density and will be determined in section 5.3 while R a is the attractive radius equation according to the Erikson model for a median peak current value, I p of 33kA as explained in [Yahaya and Zain 2000] and for a maximum building height h. C d is the location factor of the structure based on Table A.1 of [IEC 62305-2:2010] which has been reproduced in table 2. This location factor was determined by carefully looking at the pictures sent by TÜV-Hessen and picking the closest conservative value. Relative Location C d Structure surrounded by higher objects 0.25 Structure surrounded by objects of the same height or smaller 0.5 Isolated structure: no other objects in the vicinity 1 Isolated structure on a hilltop or a knoll 2 Table 2: Structure location factor, C d 5.3 Lightning Activity in the Klang Valley during the 2010-2012 period The average ground flash density N g has been estimated based on official data obtained from the research division of the Malaysian national utility Tenaga Nasional Berhad (TNB). TNB Research Sdn Bhd operates the lightning detection network across Malaysia and the results shown in table 3 were obtained for the period ranging from 2010 to 2012, which is the period covered in this study. Area N g in flashes/km 2 /year KL Sentral 20 to 28 Shah Alam, Selangor 24 to 32 Subang Jaya, Selangor 28 to 32 Putrajaya 20 to 24 Table 3: Average ground flash density for various locations around the Klang Valley area 5.4 Result of the comparison between the number of expected strikes and the collected data The sum of the number of expected strikes to the structures was calculated to be respectively 27.44 events and 35.89 events over 37 individual years depending on whether the low side or the high side of the average ground flash density N g from table 3 was being used. The average of number of expected strikes across all sites was calculated to be 0.74 and 0.97 for both sides of the N g range. It is these numbers, m low and m high, already mentionned in 5.1, that can be used for a null hypothesis testing H null of the data collected on the field as follow: H null : m low = 0.74 and m high = 0.97 (6) H non null : m low 0.74 and m high 0.97 (7) 7

Figure 3: Kolmogorov-Smirnov criterion test As mentioned in table 1, the individual number of events N observed is 33.4. Considering a 95% confidence interval for testing this hypothesis, the lower and upper limits of our confidence interval become respectively 22.1 and 44.7. In that same table, the average number of events per year A observed is 0.9. This value serves as our point estimator which itself has a 95% confidence interval ranging from 0.6 to 1.2. Because this confidence interval includes both 0.74 and 0.97, the null hypothesis is accepted and the Eriksson model further validated while the quality and rigorousness of the work carried out by TÜV-Hessen is also demonstrated. The statistical analysis can be enhanced by carrying-out a Kolmogorov-Smirnov criterion test as in [D Alessandro and Petrov 2006]. The sample cumulative distribution function (CDF) based on the sum of the counter flashes and bypasses measured by TÜV-Hessen, F n(x), is compared with the CDF of a Poisson random variable with parameter 0.74 flashes per year, F0.74(X). Figure 3 illustrates these two CFDs. The Kolmogorov-Smirnov statistic, F 0.74 (X), measures the maximum distance between these two CDFs as the number of flashes, X, ranges from 0 to infinity as shown in the equation below: D = max F n (X) F 0.74 (X) (8) The value of D for this test is 0.225, which is less than the 5% critical value, 0.23. Thus, the hypothesis that the total number of flashes is a Poisson random variable with parameter 0.74 flashes per year, is accepted, when the level of significance is 0.05. 6 Comparison between the theoretical and actual lightning protection system interception efficiency Following the positive results of the null hypothesis testing, it is now possible to assess whether the actual interception efficiency, E observed of the CVM-based lightning protection systems surveyed by TÜV-Hessen corresponds to the theoretical efficiency E theoretical. Of the 24 buildings comprising the final data set, 2 are protected by a lightning protection system with efficiency 97%, 20 with a lightning protection system with efficiency 91%, and 2 with a lightning protection system with efficiency 84%. This yields an average theoretical efficiency E theoretical of 90.92%. On the other hand, E observed is determined by equation 9. That is, the actual interception efficiency, E observed, of the CVM-based lightning protection systems surveyed by TÜV-Hessen is 91.02% which is in very close agreement with the E theoretical the theoretical lightning protection efficiency. The error between E observed and E theoretical is minor and understandable. As a side comment, it should be noted that if the 2.5 counting factor from section 4.2 had been applied accross all sites regardless of whether the registered number of strikes was 1 or more, as done in [D Alessandro and Petrov 2006], the observed efficiency would have been 90.32%. E observed = F observed N observed (9) 8

7 Conclusion Results consistent with [Petrov and D Alessandro 2002] and [D Alessandro and Petrov 2006] have been demonstrated. This further validates the Collection Volume Method (CVM) and Erikson s attractive radius model on which the CVM is based. As expected, no lightning protection system offers 100% protection, but the observed interception efficiency of lightning protection systems with components placed according to the CVM is in accordance with the theoretical efficiency. It is important to note that the theoretical efficiency of each site is based on a minimal peak current for each protection level, which is equivalent to the parameters listed [IEC 62305-1:2010]. It has been observed that the difference between the theoretical and observed efficiency is less than 0.5%. For comparison, the difference between observed and theoretical values in the initial study is 1.5% [D Alessandro and Petrov 2006]. This variation can be explained by the stochastic nature of lightning or alternatively by the fact that, in this study, lightning protection systems utilizing a newer generation of air terminals were surveyed. These terminals have a blunt tip and optimized dome shape resulting from a careful study of the extensive research of [Moore et Al. 2003] and [D Alessandro et Al. 2003]. It has also been shown that the Erikson attractive radius concept can be applied when using risk assessment calculations per IEC 62305-2, as the null hypothesis testing has demonstrated that the number of events predicted by the theoretical model is in line with the field data collected. References [1] ERICO, ERITECH SYSTEM 3000 Installation, Operation and Maintenance Manual, 2009. [Petrov and D Alessandro 2002] Petrov N. & D Alessandro F., Assessment of protection system positioning and models using observations of lightning strikes to structures, Proc. R. Soc. Lond. A 458, 723-742, 2002 [D Alessandro and Petrov 2006] Petrov N. & D Alessandro F., Field study on the interception efficiency of lightning protection systems and comparison with models, Proc. R. Soc. Lond. A 462, 1365-1386, 2006 [D Alessandro and Gumley 2001] D Alessandro, F. & Gumley, J. R., A collection volume method for the placement of air terminals for the protection of structures against lightning, J. Electrostat. 50, 279-302, 2001 [D Alessandro 2003] D Alessandro, F., The use of field intensification factors in calculations for lightning protection of structures J. Electrostat. 58, 17-43, 2003 [IEEE998-2012] IEEE Power and Energy Society, IEEE998-2012-IEEE Guide for Direct Lightning Stroke Shielding of Substations, 2012 [IEC 62305-1:2010] IEC, Protection against lightning Part 1: General principles, Ed 2.0, 2010 [IEC 62305-2:2010] IEC, Protection against lightning Part 2: Risk Assessment, Ed 2.0, 2010 [Kong et Al. 2009] X.Z. Kong, X.S. Qie, Y. Zhao & T. Zhang, Characteristics of negative lightning flashes presenting multiple-ground terminations on a millisecond-scale, J. Atmospheric Research 91, 381-386, 2009. [Yahaya and Zain 2000] Yahaya, M. P. & Zain, S. A. F. S., Characteristics of cloud-to-ground lightning in Malaysia, Conf. Lightning Protection & Earthing Systems, Kuala Lumpur 1-15, 2000. [Moore et Al. 2003] C.B. Moore, G.D. Aulich, & W. Rison, The case for using blunt-tipped lightning rods as strike receptors, J. Appl. Meteorology 42, 984-993, 2003. [D Alessandro et Al. 2003] F. DAlessandro, C. J. Kossmann, A. S. Gaivoronsky & A. G. Ovsyannikov, Experimental Study of Lightning Rods Using Long Sparks in Air, IEEE Transac. on Dielectrics and Electrical Insulation Vol. 11 No. 4, 638-649, 2003. [D Alessandro and Darveniza 2001] D Alessandro, F. & Darveniza, M., Field validation of an air terminal model, Proc. Sixth Int. Symp. on Lightening Protection, Santos, Brazil pp. 234239, 2001., 9