BNA Series PLENUM FAN with Backward Wheels
BNA Series BNA Series Plenum Fans Backward wheels Kruger Plenum Fans are designed for air handling applications where the fan operates unhoused within a plenum. This results in saving of the space normally occupied by fan housing, transitions and diffusers. The fan wheel pressurizes the entire surrounding air plenum. This allows air ducts to be directly connected to the air handling unit enclosure from any direction. The compact size of the plenum fan makes it an excellent selection for retrofit and replacement application and for variable air volume systems. Type / Operating Limit Each fan type has its maximum operating speed and power due to its mechanical design. The BNA series is designed to meet the requirement of class I, II and III limit as defined in AMCA standard 99-208-9. The BNA series is available in Direct Driven and Belt Driven, Type D, T or U as shown below: Type D This type is supplied with motor support. It is a compact, space saving design with motor directly connected to wheel. As there is no belts or pulley, the maintenance is minimal. This construction is mainly designed/ used for cleanroom, with or without VFD, as there is no belt residue which may contaminate the airstreams. Fan Size : 15 to 100 Volume : 0 to,000 m /h Total Pressure : up to 000 Pa Type T Compact design of reduced shaft length with a bearing located at the inlet. It requires separate base for motor mounting. Fan Size : 15 to 100 Volume : 0 to,000 m /h Total Pressure : up to 000 Pa Drawing and dimension of type T are available upon request. Type U No bearings at fan inlet to affect performance. Requires separate base for motor mounting. Fan Size : 15 to 100 Volume : 0 to,000 m /h Total Pressure : up to 000 Pa Drawing and dimension of type U are available upon request. Wheel TECHNICAL SPECIFICATION The wheel of BNA series has backward curved blades manufactured in cold rolled sheet steel with polyester powder coating finish. Shaft Shafts are manufactured from C5 carbon steel using an automatic process for positioning and cutting of the keyways. All dimensional tolerances of the shaft are fully checked to ensure a precision fit. All shafts are coated with an anti-corrosion varnish after assembly.
BNA Series Bearings Bearings used are either deep groove ball bearings with an adapter sleeve, or spherical roller bearings sealed at both sides for different duty application. Bearings are lubricated for life and maintenance-free. If relubrication is necessary, it is recommended to use lithium base grease suitable for all temperatures within the operational limits. Balancing Quality All wheels are statically and dynamically balanced to ISO1 and AMCA 20 G2.5 standard. All fans after assembly are trim-balanced to ISO1 and AMCA 20 - G2.5 standard. Clean room application fans with balancing grade of G1.0 are available upon request. ACCESSORIES Inlet Guards Inlet guards may be a requirement stated in some industrial safety regulations. These are available on request. Motor Selection The power curve shown on each performance curve represents the absorbed power at the shaft of the fan measured in kw. To determine the power of the motor to be installed, a correction factor should be applied to compensate for the transmission losses. For conversion to horsepower (HP), use multiplying factor 1.. Correction Factor, % motor power output 0 0 0 20 15 10 8 2 Pole & Pole 2 1.5 1 0.2 0. 0.5 0. 0.75 1.5 2.2.5 7.5 15 22.5 0 5 0 75 150 225 00 50 Motor power output (kw)
BNA Series Performance The tentative performance data shown on each diagram are obtained from test and measurement conducted in accordance to AMCA Standard 210 Fig 12 installation type B (free inlet and ducted outlet condition). The performance is achieved under test conditions of radial discharge, smooth air flows with the aid of proper transitions from plenum outlet to duct, and in a plenum which meets the recommended minimum distance for plenum fans installation. An outlet duct of appropriate size, which gives a reasonable outlet velocity to overcome losses, has also been employed. Rating is referred to the standard air density with the total pressure as a function of the air volume, using logarithmic scales. It is essential that, the same installation type and test standards are used at all times, when comparing fan performances. Noise The noise level shown on each diagram refer to the sound power "Aweighted" and the data on the inlet side has been measured in accordance with AMCA Standard 00. The noise levels of the fans are determined as follows: Sound power level - ("A" scale): Lw (A) as catalogue Octave band spectrum: Lw = Lw(A) + Lw rel. db [refer to Kruger for more details] Sound pressure level: a) free field Lp(A) = Lw(A) - (20log 10 d) -11 b) room conditions Lp(A) = Lw(A) - (20log 10 d) -7 where d = distance from fan (m) SELECTION GUIDELINES To assure optimum performance and be able to use plenum effect pressure loss indicated in the next section, the following guidelines should be adhered to in plenum fan selection. Minimum Distance Recommended minimum distances for correct plenum fan installation. D = Impeller Diameter E>D R>10D A>1.D
BNA Series Plenum Radial Duct Discharge Axial Duct Discharge PLA = K* x Pd Discharge Direction Plenum Effect Loss Fan performance is developed from test conditions of radial discharge. The pressure loss associated with the duct take off, from the plenum, at a different location must be added to the static pressure required of the fan. The correction factor, K*, for pressure loss for axial discharge can be obtained below. Working Example: Required air volume Q, 8m /s and static pressure P s, 1Pa with Discharge duct A=1m², For Axial Duct Discharge:- Outlet Velocity, V = Q/A = 8/1 = 8 m/s Pressure Loss Coefficient, K* 10 8 2 0 0 2 8 10 12 1 1 18 20 Fan Outlet Velocity (m/s) From chart, at outlet velocity, 8m/s, pressure loss coefficient, K* = 1.. Pressure loss = K* x Dynamic Pressure, P d = K* x (V/1.)² = 1. x (8/1.)² = 5 Pa Actual Required static pressure P s = 1+5 = 155 Pa Required Plenum fan selection is to be done with the duty below: Q = 8 m /s and Static Pressure P s = 155 Pa 5
BNA Series Example of Selection Air Volume Q = 98 m /h Outlet Velocity V = 9.88 m/s Dynamic Pressure Total Pressure Pd = 58 Pa Pt =1 Pa 1. Fan Speed N = 17 rpm Absorbed Power W =. kw 17 Total Efficiency ŋ = % 8 Sound Power Level Lw(A) = 8 db(a) 1.9 98 9.88 58
Pt [Pa] 0 000 000 kw 2 1. 5 BNA 15 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 2.5 5 10 M.RPM = 1.22 kg/m 0 8 5 0 5 8 N [rpm] 0 00 00 1 0.8 0. 0.5 0. 0. 0.2 85 95 0 700 00 0 50 20 2 75 1750 70 Lw (A) [db(a)] 100 150.2...5..8 1 2 5 Q [m/s] 0 000 0 00 0 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 55 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 12 M.RPM 20 700 700 = 1.22 kg/m 0 8 57 0 5 7 8 10 000 5 N [rpm] 2 0 1. 1.2 1 0.8 0. 0.5 0. 95 700 50 000 700 50 00 0. 20 00 0.2 5 85 2 2 1750 70 75 Lw (A) [db(a)] 100 150 100.2...5..8 1 2 5 8 Q [m/s] 0 000 0 00 0 0000 Q [m/h] 2 5 8 10 20 0 0 50 0 5 10 50 0 V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
BNA 00 Pt [Pa] 0 kw Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW.5 7 15 M.RPM 2 00 = 1.22 kg/m 9 7 57 2 58 1 000 10 12 000 8 5 N [rpm] 2 0 1. 1.2 1 0.8 105 0 50 00 00 00 0. 0.5 0. 0. 95 000 20 2 2 5 85 1750 70 100 150 75 100 Lw (A) [db(a)] 1150...5..8 1 2 5 8 10 Q [m/s] 0 000 0 00 0 0000 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
BNA 50 Pt [Pa] 0 kw Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 10 18 M.RPM 2 20 00 = 1.22 kg/m 9 50 0 5 59 5 28 000 000 5 8 10 12 1 N [rpm] 2 0 1. 1.2 1 0.8 00 50 00 00 0. 0.5 0. 0. 70 95 20 20 2 85 1750 100 150 75 100 Lw (A) [db(a)] 1150...5..8 1 2 5 8 10 Q [m/s] 0 000 0 00 0 0000 00 Q [m/h] 2 5 8 10 20 0 0 50 0 V [m/s] 5 10 50 0 0 Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
BNA Pt [Pa] 0 kw Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 5 11 22 M.RPM 1950 2550 = 1.22 kg/m 0 50 1 1 0 000 000 8 11 1 20 5 N [rpm] 0 2 1. 1.2 1 20 00 00 0.8 0. 0.5 0. 70 95 2550 2 1950 1750 100 85 150 75 100 1150 1050 Lw (A) [db(a)]...5..8 1 2 5 8 10 20 Q [m/s] 000 0 00 0 0000 00 Q [m/h] 2 5 8 10 20 0 0 50 0 V [m/s] 5 10 50 0 0 Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 000 kw 10 8 5 1 BNA 50 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 1 2 M.RPM 10 20 = 1.22 kg/m 1 52 2 7 2 7 1 1 20 2 N [rpm] 0 2 1. 20 20 1.2 1 00 00 0.8 0. 0.5 0. 95 10 1750 100 150 70 85 100 1150 1050 75 Lw (A) [db(a)] 950 870..5..8 1 2 5 8 10 20 Q [m/s] 000 0 00 0 0000 00 2 5 8 10 20 0 0 50 0 5 10 50 0 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 0 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 7 1 2 M.RPM 1 2 = 1.22 kg/m 8 57 9 5 1 000 12 1 20 25 N [rpm] 5 8 7 2 0 2 1. 1.2 1 95 1750 00 00 0.8 0. 0.5 85 1 150 100 1150 1050 950 5 75 870 0 70 Lw (A) [db(a)] 720 50.5..8 1 2 5 8 10 20 Q [m/s] 000 0 00 0 0000 00 Q [m/h] 2 5 8 10 20 0 0 50 0 V [m/s] 5 10 50 0 Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 710 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 9 20 0 M.RPM 150 10 2250 = 1.22 kg/m 8 57 9 55 0 000 20 1 12 8 910 25 0 5 N [rpm] 0 2 1. 5 95 2250 10 1750 100 00 1.2 1 0.8 150 150 00 0. 5 85 1150 1050 950 870 70 75 0 720 50 Lw (A) [db(a)].8 1 2 5 8 10 20 0 Q [m/s] 000 0 00 0 0000 00 000 Q [m/h] 2 5 8 10 20 0 0 50 0 V [m/s] 5 10 50 0 Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
BNA 0 Pt [Pa] 0 kw Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 11 25 50 M.RPM 1 100 = 1.22 kg/m 50 59 5 70 7 58 000 000 20 25 0 0 N [rpm] 15 10 0 8 5 105 1750 100 150 2 95 150 00 1. 1.2 1 1 1050 00 0.8 85 950 870 5 0 720 75 50 00 70 550 Lw (A) [db(a)] 1 2 5 8 10 20 0 Q [m/s] 0 00 0 0000 00 000 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 0 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 1 0 0 M.RPM 1050 100 1750 = 1.22 kg/m 50 59 5 70 7 57 000 0 0 50 10 8 1 12 20 N [rpm] 1750 0 5 105 100 100 100 00 00 2 1. 1.2 1 5 85 95 1150 1050 950 870 0 720 50 70 75 5 Lw (A) [db(a)] 520 2 5 8 10 20 0 0 Q [m/s] 0 00 0 0000 00 000 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 0 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 1 0 M.RPM 950 1250 100 = 1.22 kg/m 51 0 71 8 59 000 0 0 25 50 0 70 N [rpm] 20 1 0 12 10 8 5 105 100 150 150 1250 1150 95 1050 00 00 2 1. 1.2 1 85 950 870 0 720 50 00 75 550 70 50 Lw (A) [db(a)] 2 5 8 10 20 0 0 50 0 Q [m/s] 00 0 0000 00 000 00 Q [m/h] 2 5 8 10 20 0 0 50 0 5 10 50 0 V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 000 kw 1 20 0 0 50 BNA 1120 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 1 50 M.RPM 850 1150 150 = 1.22 kg/m 50 0 5 70 7 57 1 0 70 N [rpm] 0 12 10 8 150 100 00 2 5 95 105 1150 1050 950 850 0 00 1. 720 50 70 85 00 550 50 75 00 Lw (A) [db(a)] 2 5 8 10 20 0 0 50 0 Q [m/s] 00 0 0000 00 000 00 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 1250 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 25 55 110 M.RPM 7 0 100 = 1.22 kg/m 51 1 7 72 9 58 0 000 50 0 N [rpm] 0 20 0 15 12 10 100 1150 00 00 1. 2 8 5 95 105 0 950 870 7 720 50 5 85 50 50 70 75 Lw (A) [db(a)] 00 50 2 5 8 10 20 0 0 50 0 Q [m/s] 00 0 0000 00 000 00 00000 Q [m/h] 2 5 8 10 20 0 0 50 0 5 10 50 0 V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
Pt [Pa] 0 000 kw BNA 100 Op Limit Cl. I Cl. II Cl. III Type D T U D T U D T U M.kW 5 70 150 M.RPM 8 1 = 1.22 kg/m 52 1 7 7 70 0 000 0 50 120 N [rpm] 0 0 20 1 0 1 12 10 105 950 8 00 8 5 95 0 720 0 5 00 2 85 50 50 00 75 50 70 Lw (A) [db(a)] 00 5 8 10 20 0 0 50 0 Q [m/s] 00 0 0000 00 000 00 00000 2 5 8 10 20 0 0 50 0 5 10 50 0 Q [m/h] V [m/s] Pd [Pa] Performance shown is for Installation type B free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating kw does not include drive losses. The A weighted sound ratings shown have been calculated per AMCA standard 01. Values shown are for inlet Lwi(A) sound power levels for installation type B free inlet, ducted outlet. Ratings do not include the effect of duct end corr ections.
BNA D BNA 15 ~ 710 D F L A n x Øq C B K P J E Øu x Model A B C D E F K n x q u J L P Frame Size Weight 15 50 515 225 55 10 29 x 9 12 BNA 0 ~ 100 D 55 555 25 9 50 20 8 x 9 12 00 50 595 25 7 7 8 x 12 12 50 5 5 2 8 50 81 8 x 12 12 0 715 15 50 5 28 8 x 12 12 50 700 785 50 0 50 8 x 12 12 0 7 875 95 7 70 51 8 x 12 12 710 8 9 5 750 80 52 8 x 12 12 9 9 71 5 57 7 71 527 50 57 57 00 97 112 58 17 51 5 87 58 112 12 18 51 58 112 8 81 78 12 10 75 708 595 112 85 898 785 12 10 71 7 All Dimensions 112 in mm. 98 82 12 10 8 8 75 112 12 10 92 10 1 879 912 799 112 12 109 1082 99 10 1 All Dimensions in mm.
BNA D BNA 0 ~ 100 D F L A n x Øq C B K P J E Øu x Model A B C D E F K n x q u J L P Frame Size Weight 0 0 1 87 950 1 12 x 12 12 BNA 0 ~ 100 D 0 1120 1220 50 9 1070 78 12 x 12 12 0 120 10 20 102 11 7 12 x 12 12 1120 1 1515 95 11 125 82 1 x 1 12 1250 1550 1700 775 10 175 911 1 x 1 12 100 1700 1850 850 1 125 102 18 x 1 12 9 97 8 11 11 105 115 1178 105 125 1278 115 12 129 118 1 19 128 17 107 127 17 1507 17 15 11 11 10 1 1 158 117 1 17 177 159 112 12 10 1 12 10 1 225 10 1 225 250 10 1 225 250 1 225 250 2 1 225 250 2 All Dimensions in mm. All Dimensions in mm.
Operational Limits - "BNA" 15 55 00 50 50 0 710 0 0 0 1120 1250 100 Maximum Absorbed Power Cl.I kw 2.5.5 5 7 9 11 1 1 1 25 5 Cl.II kw 5 7 10 11 1 1 20 25 0 0 50 55 70 Cl.III kw 10 12 15 18 22 2 2 0 50 0 110 150 Maximum Fan Speed Cl.I rpm 20 2 2 1950 10 1 150 1 1050 950 850 7 Cl.II rpm 700 00 20 2550 10 100 100 1250 1150 0 8 Cl.III rpm 700 00 20 2 2250 1750 100 150 100 1 Operating temperature Range / Min. -20 o C Cl.I-Cl.II-Cl.III Max. o C
Comparison Between Plug Fan and Plenum Fan Plug Fan A fan with centrifugal impeller, which may or may not have a housing, discharge air to a plenum or fan enclosure. Generally designed to have the motor and drive separated from the impeller and enclosure. Installation Type for Plug Fan: A free inlet, free outlet C free inlet, ducted outlet Plenum Fan A fan with centrifugal impeller not contained in a housing, discharging air to a plenum. Generally designed with motor and drive contained in the plenum area. Installation Type for Plenum Fan: A free inlet, free outlet C free inlet, ducted outlet RADIAL DISCHARGE AXIAL DISCHARGE AIR INLET Page 1 of
APPLICATION Plug Fan - Most commonly used within a chamber for ovens, dryers, kilns or cold room in which air volume and temperature distribution throughout the enclosure is vital to the final results. Omni-directional circulation Uni-directional circulation Counter-directional circulation Advantages - minimize cost and space requirement - building the fan into the oven reduces width or height - Expensive external ductwork, penthouses, insulation and fan and motor mounting bases is eliminated. - Fan components such as bearings, drives and motors, which require attention due to the temperature, are located outside the oven and are easily serviced for continuity of production. Page 2 of
Plenum Fan - Mainly use for pressurized plenum in build-up system in air-handling industry. - The unhoused design of the plenum fan makes it ideal for retrofit projects where space is limited. PLENUM FILTER COIL Pressurized Plenum Advantages - compact in size and outlet discharge can be of any direction. - suitable for clean room application, no chips produced from rubbing belts - goods for multiple ducts take off at the discharge Kruger Product Fan Type Model Wheel Type Size Air Volume (m/h) Static Pressure (Pa) Arrangement PLUG FAN PLENUM FAN APA BPA ANA BNA Airfoil Backward Curved Airfoil Backward Curved 15 to 100 m/h to,000 m/h Approx. up to 000 Pa Direct Driven or Belt Driven Page of
FAN STRUCTURE Plug Fan APA - BPA Direct Driven Belt Driven Type-1 Type-2 Plenum Fan ANA - BNA Direct Driven Belt Driven Type-1 Type-2 Page of
BNA D BNA 15 ~ 710 D F A n x Øo ØD C B K G J H E Øu x s Model Frame Size A B C D E F G H J K L n x o u x s 15 55 15 59 92 71 181 8 517 50 225 55 10 29 2 20 50 59 x 9 1x18 2 5 579 275 578 11 15 8 51 71 181 508 51 50 25 9 50 20 287 20 50 5 8 x 9 1x18 2 570 0 275 02 5 71 181 55 58 20 557 5 2 597 0 50 570 25 7 7 1 275 29 2 8 x 12 1x18 112 292 79 12 72 72 759 20 591 2 2 1 5 20 2 8 50 8 8 275 9 8 x 12 1x18 112 292 71 12 72 70 79 19 8 71 2 78 711 0 15 50 5 28 95 25 710 7 8 x 12 1x18 112 282 727 70 12 2 7 80 19 7 709 2 71 All 79 Dimensions in mm. 700 750 50 0 50 25 78 781 8 x 12 1x18 112 282 75 798 12 2 85 878 19 72 759 2 7 799 770 820 85 7 720 519 8 25 798 81 8 x 12 1 x 18 112 282 815 88 12 2 895 928 21 812 85 25 8 877 112 850 25 750 7 52 59 22 81 89 8 x 12 17 x 22 12 2 91 97 10 72 1071 110 BNA 0 ~ 100 D 00 50 50 0 710 All Dimensions in mm.
BNA D BNA 0 ~ 100 D F L A n x Øo ØD C B K G J H E Øu x s Model Frame Size A B C D E F G H J K L n x o u x s 0 0 0 1120 1250 100 112 282 915 98 12 2 995 1028 100 70 87 8 1 58 10 92 1125 1158 12 x 12 17 x 22 1 550 118 121 12 2 1057 10 10 92 1187 1220 1 100 110 515 9 9 78 5 550 125 1278 12 x 12 17 x 22 10 105 18 225 51 1 179 10 92 1255 1288 1 550 11 1 110 120 570 102 10 7 71 10 17 10 12 x 12 17 x 22 225 51 11 17 250 71 19 1527 10 77 151 18 1 55 109 12 12 115 5 11 1225 82 9 595 19 1502 1 x 1 17 x 22 225 1510 15 250 71 15 12 1 525 178 1511 585 158 1571 225 120 1570 710 10 15 911 878 2 1579 112 1 x 1 17 x 22 250 70 159 192 2 827 17 181 1 525 109 12 585 19 1702 All Dimensions in mm. 225 100 1750 0 1 1525 102 9 2 1710 17 18 x 1 17 x 22 250 70 17 182 2 827 1911 19 All Dimensions in mm. BNA 0 ~ 100 D
BNA UI BNA 15 ~ 710 UI F L A n x Øo t ØD C B t1 z Ød-g w K G J H E Øu x s Model A B C D E F G H J K L n x o t t1 w z d u x s 15 50 225 55 10 29 2 27 582 75 x 9 8 7 0 28 25 1x18 55 50 25 9 50 20 287 00 2 725 8 x 9 8 7 0 0 1x18 00 50 570 25 7 7 1 20 79 772 8 x 12 8 7 0 0 1x18 50 5 20 2 8 50 81 8 0 7 8 8 x 12 10 8 50 8 5 1x18 0 15 50 5 18 85 0 811 91 8 x 12 10 8 50 8 5 1x18 50 700 750 50 0 50 78 87 9 8 x 12 12 8 70 0 1x18 0 770 820 85 7 720 512 8 00 99 102 8 x 12 12 8 70 0 1x18 710 850 25 750 7 52 59 20 107 1170 8 x 12 1 9 8.5 5 17x22 All Dimensions in mm. BNA 0 ~ 100 UI F A n x Øo t ØD C B t1 z Ød-g w L G J H E Øu x s Model A B C D E F G H J K L n x o t t1 w z d u x s 0 1020 70 87 8 1 58 0 108 120 12 x 12 1 9 8.5 5 17x22 0 100 1110 515 9 9 78 5 1195 18 12 x 12 18 11 59 55 17x22 0 110 1220 570 102 10 7 71 510 128 12 12 x 12 18 11 59 55 17x22 1120 12 115 5 11 1225 82 9 572 158 101 1 x 1 18 11 110 0 17x22 1250 120 1570 710 10 15 878 2 1597 1770 1 x 1 20 12 110 9 5 17x22 100 100 1750 0 1 1525 108 9 717 181 198 18 x 1 22 1 110 7.5 70 17x22 All Dimensions in mm.
BNA TI BNA 15 ~ 100 TI M L F A t z Ød-g B w C t1 Øu x s K J H J G G E G Model A B C E F G H J K L M t t1 w z d u x s 15 50 50 225 25 21 20 115 9 5 0 7 8 7 0 28 25 1x18 55 25 27 27 20 11 78 5 7 8 7 0 0 1x18 00 50 50 25 27 27 20 1 85 5 1 7 8 7 0 0 1x18 50 5 5 2 2 08 20 10 9 5 517 7 10 8 50 8 5 1x18 0 0 15 28 5 20 181 102 5 55 7 10 8 50 8 5 1x18 50 700 700 50 2 8 25 201 11 58 2 8 12 8 70 0 1x18 0 770 770 85 2 25 22 10 58 7 8 12 8 70 0 1x18 710 850 850 25 79 25 27 11 58 72 8 1 9 70 8.5 5 17x22 0 70 0 5 25 275 15 58 7 8 1 9 70 8.5 5 17x22 0 100 100 515 1 595 25 05 170 58 89 8 1 10 59 55 17x22 0 110 110 570 1 25 9 187 58 97 8 1 10 59 55 17x22 1120 12 12 5 95 78 82 211 10 98 18 11 0 17x22 1250 120 120 710 5 7.5 12 2 70.5 11 108 18 11 110 9 5 17x22 100 100 100 0 52 9 7.5 77 2 70.5 128 108 20 12 110 7.5 70 17x22 All Dimensions in mm.
BNA TII BNA 15 ~ 100 TII M L F A t z Ød-g B w C t1 K J H J G G E G Øu x s Model A B C E F G H J K L M t t1 w z d u x s 15 50 50 225 25 21 20 115 9 5 10 7 8 7 0 28 25 1x18 55 25 27 27 20 11 78 5 5 7 8 7 0 0 1x18 00 50 50 25 27 27 20 1 85 5 8 7 8 7 0 0 1x18 50 5 5 2 2 08 20 10 9 5 59 7 10 8 50 8 5 1x18 0 0 15 28 5 20 181 102 5 57 7 10 8 50 8 5 1x18 50 700 700 50 2 8 25 201 11 58 0 8 12 8 70 0 1x18 0 770 770 85 2 25 22 10 58 8 12 8 70 0 1x18 710 850 850 25 79 5 27 11 8 750 10 1 9 5.5 50 17x22 0 70 0 5 25 275 15 58 8 1 9 5.5 50 17x22 0 100 100 515 1 595 25 05 170 58 87 8 18 11 0 17x22 0 110 110 570 1 25 9 187 58 92 8 18 11 0 17x22 1120 12 12 5 95 78 82 211 10 98 18 11 110 9 5 17x22 1250 120 120 710 5 7.5 12 2 70.5 1152 108 20 12 110 7.5 70 17x22 100 100 100 0 52 9 7.5 77 2 70.5 1298 108 22 1 110 85 17x22 All Dimensions in mm.